Professional Documents
Culture Documents
196 - MUNDRA2-4NT-lng Spill Detection PDF
196 - MUNDRA2-4NT-lng Spill Detection PDF
MUNDRA2-4NT-9990006-000 W1 12.10.12 14
This document is the property of GSPC LNG Limited. It must not be copied, loaned or transferred nor must the information i t contains be disclosed to any Third Party
without the written consent of GSPC LNG Limited.
1/14
Table of content
MUNDRA2/4NT/9990006/000/W1
2/14
8. Recommendation for Installation of Detectors and Associated Equipment .............. 13
MUNDRA2/4NT/9990006/000/W1
3/14
1. Introduction
The purpose of this document is to provide the philosophy to be fulfilled by the
CONTRACTOR during the execution of the contract for the design of the fire, spill and
gas detection of the Mundra LNG Terminal.
It is the CONTRACTOR responsibility to perform the detail engineering in compliance
with this philosophy and with the safety philosophy and the recommendations resulting
from the QRA to achieve the required functionalities and performances.
This document is to be used together with the other project documents and data as
attached to the FEED report. The philosophy is complemented by the “Fire, Spill and
Gas Detection System specification”.
The terms and definitions used in this specification are in accordance with the terms
and definitions defined for the project.
2. Abbreviations
Abbreviations used in this document are defined in the general specification “Terms,
definitions and Abbreviations”.
The terminology shall conform to ANSI/ISA S 51.1 "Process Instrumentation
Terminology".
MUNDRA2/4NT/9990006/000/W1
4/14
• initiate:
z alarms via the Process Control System (PCS) described in the document
"Process Control System",
3) All field equipment shall be suitable for outdoors service (IP 65 minimum) and shall
withstand the environmental conditions.
4) If a communication bus is provided for data transfer between the FSGDS and the
Process Control System (PCS) used for control and supervision of the LNG
Terminal, this link shall be used to transfer information like alarms, valves positions
and so on, to be displayed in the PCS, but not for shutdown related signals which
shall be hardwired.
6) The system shall be immune from the effects of any RF interference that may occur
at the plant location.
7) The detection system shall be designed in such a way that it can be functionally
tested without interrupting the normal plant activities.
8) The system design shall give a high degree of reliability and flexibility.
The safety design of the system shall include not fail-safe design, self-monitoring of
loops, wire-break detection, etc. It shall meet the latest LNG INDUSTRY applicable
safety standards.
MUNDRA2/4NT/9990006/000/W1
5/14
The Fire, Spill and Gas Detection System shall receive information from miscellaneous
sensors from which it can determine the status and take the necessary actions. A fire
and gas causes and effects matrix shall be prepared during detailed engineer and shall
be submitted for approval to the ENGINEER.
5. Fire Zones
From a fire and gas point of view, the plant shall be divided into zones containing
certain types of equipment and that can be considered as separate geographically one
from another, from a fire and gas point of view.
The plant fire zones are (to be confirmed during detail engineering on basis of QRA):
The term building includes all buildings of the plant, administrative building as well
workshop, laboratory, electrical substation, instrument rooms, etc. These buildings are
generally located outside the hazardous area and shall thus not be equipped with gas
detection system. However, air inlet for HVAC of buildings shall be provided with gas
detector which shall stop HVAC in case of gas presence in the air introduced in the
building.
Buildings shall be also provided with fire alarm system based on smoke detectors,
which shall be interconnected for alarming and reporting with the PCS.
Buildings shall have their dedicated means of annunciating inside problem and outside
problem that can have influence inside.
6. Detector selection
6.1. General
Fire, Spill and Gas Detection System is part of the Safety System, and as such it shall
include Instrument Protection Functions. This means that for these particular functions,
a SIL level shall be required. Nevertheless as these functions generally do not take
actual actions (actions are taken through the operator), the degree of fault tolerance, and
the probability of failure on demand of the set of detectors shall be calculated. In
MUNDRA2/4NT/9990006/000/W1
6/14
general, the associated control system shall have a Safety Integrity Level SIL 3.
Detectors shall be SIL 2.
Detectors shall be in conformity with regulations of the country in which they have to
be installed. In case of lack of such regulation, International Standards shall be
applicable (ISO 7240).
Number and location of detectors shall be determined during detail engineering in
accordance between the CONTRACTOR and the ENGINEER.
Gas leaks into LNG plant does not generally escalate into fire, due to the design of the
plant which reduce the probability of occurrence of electrical or other source of ignition
in the location where gas leak can occur.
Nevertheless, such a situation shall be detected rapidly and the action to avoid
escalation shall be taken promptly.
Generally, the “smart” technology detectors shall be used allowing for calibration
without opening the sensor head in the field, and to automatically remove the sensor
out of the sequence when calibration.
The type and location of detectors is of high importance. It shall be justified in every
case and the final choice shall be approved by both parties, CONTRACTOR and
ENGINEER under the advice of the detector VENDOR.
6.2.2. Selection of Point Gas Detectors
For their numerous advantages, Point Flammable Gas Detectors shall be wherever
usable of the infrared absorption type. These detectors are usable with most of the
hydrocarbon gases but cannot be used for hydrogen for example. The capability of
operating in the type of gas to be detected in the particular project shall be checked
with the FSGDS VENDOR.
6.2.3. Selection of Open Path detectors
Open path gas detectors are based on the properties of hydrocarbon to absorb certain
wavelengths of the IR spectrum and not the others. Thus the ratio between absorbable
at the receptor side and the same ratio at the emitting side is changed in relation with
the thickness and the concentration of a layer of gas crossed by the IR beam.
The installation of such open path detectors shall be carefully studied to cover the
required perimeter, and the height of installation of the sensors shall be chosen
according the land configuration and the type of gas. In all cases, these detectors shall
be installed and mounted in such a way that they shall not be submitted to vibrations or
movements.
This type of detector is suitable for detecting gas accumulations and/or clouds.
The alarm settings for the flammable gas linear detectors shall 2.5 LEL.m for corrective
actions.
MUNDRA2/4NT/9990006/000/W1
7/14
• Smoke detectors,
• Heat detectors.
6.3.2. Optical Fire Detectors
• UV Fire detectors,
These detectors shall be used where flammable products are mainly hydrocarbon, and
where fast detection must be guaranteed. These detectors are based on the flame-flicker
principle. They shall be installed away from sunshine.
6.3.2.2. UV Fire Detectors
UV Fire Detectors are extremely fast in detecting fire, but they are very sensitive to
dust and oil droplets or heavy smoke. They are also sensitive to arc welding light.
6.3.2.3. UV/IR Fire Detectors
UV/IR Fire detectors combine the advantages and disadvantages of both preceding
types. This type of detector checks for the presence of both UV and IR radiation. This
allows reducing the sensitivity and thus number of false alarms, etc. Furthermore, the
distance covered with this type of detector is rather short.
6.3.2.4. Triple IR Fire Detectors
Triple IR Detectors are using three IR frequencies; one at the CO2 formation peak, one
before this peak and one after this peak. The relation between the intensities of IR
radiation at these frequencies is well known in case of fire. The sensor thus checks that
the relation between the measured IR radiation intensities corresponds to the one obtain
in case of fire.
The distance covered with this type of detector is several time the distance covered by
UV/IR type. Furthermore, this distance depends largely on the type of fire to be
detected. The estimation of that distance is very important to allow determining the
number of sensors required and their locations.
MUNDRA2/4NT/9990006/000/W1
8/14
This type of sensor gives good results in every case and shall thus be the preferred one
in all case.
6.3.2.5. CCTV Flame Detectors
CCTV Camera together with suitable software can recognize fire for a wide range of
products. CCTV Flame Detectors have not been yet field proven. Thus the application
of that technology shall be limited to VENDOR who can proof experience and
satisfactory results with that technology and shall be in any case approved by
ENGINEER.
6.3.3. Smoke Detectors
6.3.3.1. General
Smoke detectors are generally used in confined spaces or inside buildings. Two types
of smoke detectors are used:
This detector is based on the effect of smoke particles on light. This type of detector is
more sensitive to smoke with large size particles like cable fires and hydrocarbon fires.
This type of detection can also be used in open path smoke detectors with a range of 30
m.
6.3.3.3. Ionization-Type Smoke Detectors
Ionization-type detectors are considered when optical Smoke detectors are not suitable.
They are typically detecting smaller particles than optical Smoke detectors.
6.3.4. Heat Detectors
Heat detector shall be used where fire can occur and rapidly develop much heat. This
type of detector remains any way slow to detect a fire.
In some specific circumstances, thermo sensitive cable could be used to detect heat
release over a certain linear distance.
Spill channels and impounding basins where cryogenic liquid spills are collected shall
be equipped with spill point detectors at the outlet of the spill channel e.g. at the re-
condenser and at the send-out pumps. Some impoundings shall also be fitted with three
of such detectors in such ways that action can be taken in case of confirmed LNG
spillage (stop impounding water draining, start foam generators, etc.).
MUNDRA2/4NT/9990006/000/W1
9/14
• Cold Sensor strip, which can be used to detect spillage over a certain
linear distance and needs an interface to a gas detection alarm system;
MUNDRA2/4NT/9990006/000/W1
10/14
fiber
cold optic gas
UV thermal point cold H2 path
Areas detector detector detector detector detector gas detector detector
off-
shore
as as
jetty head 6 2 6 option 13 option
Trestle
seawater intake 2
Electrochlorination 2
FW pump diesel engine 2 1
flare platform
nbr per
jetty monitoring building NFPA72 1/ air inlet
nbr per
sea water intake substation NFPA72 1/ air inlet
on-
shore
shore line ESD valves
tank A/shore line impounding 2 2
as as
tank A bottom 2 4 option 6 option
as as
tank A roof platform 4 4 option 8 option
tank A PSV 1/PSV 1/PSV
tank B impounding 2 2
as as
tank B bottom 2 4 option 6 option
as as
tank B roof platform 4 4 option 8 option
tank B PSV 1/PSV 1/PSV
flare KO drum 2 2
drain drum 2 2
compressor desuperheater and suction
drum 2 2 4
BOG compressors and blowers shelter 2 4
MUNDRA2/4NT/9990006/000/W1
11/14
fiber
cold optic gas
UV thermal point cold H2 path
Areas detector detector detector detector detector gas detector detector
BOG compressors and blowers rack 2 4
Absorber 1 4 4
as as
HP pumps rack and shelter 2 12 option 16 option
as as
Vaporizers 5 option 5 option
as as
vaporisers rack 2 5 option 5 option
HP pump: vaporisers impounding 2 2
metering station 2 7
nitrogen generation 2 1:Compressor
air compressors 2 1:Compressor
water storage and pumps
gas turbine 2 3
emergency diesel generator
nbr per
process substation NFPA72 1/air inlet
nbr per
metering building NFPA72 1/air inlet
nbr per
incoming substation NFPA72 1/air inlet
nbr per
control building NFPA72 1/air inlet
nbr per
warehouse and workshop NFPA72 1/air inlet
nbr per
administration building NFPA72 1/air inlet
future
truck loading bays 2 1/bay 2/bay
truck loading impounding 2 2
MUNDRA2/4NT/9990006/000/W1
12/14
7. Layout of Detectors
7.1. Purpose of the Fire, Spill and Gas Detection
7.1.1. Purpose of the Gas Detection System
The role of the Gas Detection System is to detect sufficiently early gas accumulation to
avoid that a gas cloud reaches a point where it could be ignited or at least early enough
to avoid that the quantity accumulated is such that the explosion could result in
important damage to persons and to equipment.
7.1.2. Purpose of the Spill detection
The purpose of the Spill Detection is to anticipate on the cloud formation by detection
of a LNG leak.
7.1.3. Purpose of the Fire Detection System
The role of the Fire detection system is to detect early enough fires to minimise the risk
of damage to personnel and plant.
To determine the layout of the gas detectors, it necessary to perform the following
steps:
• Simulate with a software model the formation of the gas cloud for
different directions and speeds of wind. This type of software is better
used on a 3D model of the area to be studied,
• Determine, for the different studied cases, the optimum type and
location of the gas detectors,
• Also determine how to group the detectors of a given area into voting
group.
This process is rather complicate and can only be properly done by some companies
using the modelling software on 3D model. It is mandatory that the EPC
CONTRACTOR let perform this study by a specialized company chosen in agreement
with ENGINEER. The results of this study shall be approved before installation of gas
detectors.
MUNDRA2/4NT/9990006/000/W1
13/14
The CONTRACTOR shall comply with the SEC recommendations and with the
referred standards.
7.2.2. Fire Detectors
For Fire detectors, the importance is whether the detector can see the fire or not. The
fire detectors location shall be also done through specialized software based on 3D
model but with purpose of checking that the location of the detectors is such that at
least two detectors in an area will see a fire of a given power (50 kW, to be checked
during detail engineering with regard to QRA) anywhere in the given zone.
Building fire detector layout shall comply with related IS and NFPA 72.
• HVAC,
• Analyser house,
• Flanges and all systems using bolt and sealing form process closure, like
valves, relief valves, etc.
• Compressors sealing.
Detectors shall not be placed to close to the potential leak source, because gas cloud
may disperse and be diverted by neighbour’s structure.
Location of gas detector shall take into account the specific gravity of the gas, heavier
than air or not. Particular attention shall be taken in case of LNG spillage, for which the
vapour is heavier than air when it is cold but when it is heat-up, it becomes lighter than
air.
MUNDRA2/4NT/9990006/000/W1
14/14
MUNDRA2/4NT/9990006/000/W1