ONE WAY SLAB

SECOND FLOOR VERTICAL SEC. 1 20MPa<28MPa


(SPAN B-C) ß=0.85
ρmax =0.85(20)(0.85)(3)
Given: 275(7)
fy=275MPa ρmax =0.02252
fc’=20Mpa use ρmax
L=2m
1.2DL=12.2960 KN/m As= ρmax bd
1.6LL=6.4753 KN/m =(0.02252)(1000)(174)
Wu=18.7713 KN/m As=3918.48mm2

*Cantilever
S=1000Ab/As
t= L/10 ( 0.40 + fy/700 )
S=1000(π/4 (12)2) /3918.48
t=( 2000mm/10) (0.40 + 275/700 )
S=28.86mm or 25mm
t=158.57mm or 200mm
Smax= 3t=3(200)= 600mm
Smax= 450mm
d=t-cover-0.5Db
d=200mm-20mm-0.5(12mm)
d=174mm Thus, use 12mm main bars @ 25mm o.c

W l2 As= 0.002bt
Mu=
2 =(0.002)(1000)(200)
=18.7713(22)/2 As=400mm2
Mu=37.5426 KN-m
S=1000/As
Mu=ɸbd2ρfy(1-ρfy/1.7fc’) S=1000(π/4 (10)2) /400
Assume Tension Controlled S=196.35mm or 190mm
37.5426x106=0.9(1000)(174)2ρ(275)[1- Smax= 5t=5(200)= 1000mm
275ρ/1.7(20)] Smax= 450mm
ρ =0.1184
ρmax = 0.85fc’ß1(3) Thus, use 10mm temperature bars @ 190mm o.c
Fy(7)