Professional Documents
Culture Documents
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Design for Equipment Anchorage to Bottom Concrete Based on 2018 IBC & 2019 CBC Chapter A
where Occurs
eB = 0.5 ft, (0.15 m) FH
W
H
KWIK BOLT-TZ DIAMETER f= 3/4 in, (19 mm), Per ICC ESR-1917 FV
ANCHOR DEPTH hef = 4 3/4 in, (121 mm), Per ICC ESR-1917
EDGE DISTANCE c = 12 in, (305 mm) h ef
1.3h ef
DESIGN LOADS
FH = F p = W0 (KH) MAX{ 0.3SDSIpW , MIN[ 0.4apSDSIp(1+2z/h)/Rp W , 1.6SDSIpW ] } , (ASCE 7-10, Sec. 13.3.1)
= 1.5 (1.3) MAX{ 0.43W , MIN[ 0.81W , 2.30W ]} where SDS = 0.96 (ASCE 7-10 Sec 11.4.4)
= 1.58 W , (SD) = 25.29 kips Ip = 1.5 (ASCE Sec. 13.1.3)
= 1.13 W , (ASD) = 18.07 kips ap = 1 (ASCE Tab. 13.6-1)
Rp = 1.5 (ASCE Tab. 13.6-1)
F V = KV W = 0.25 W , (SD) = 3.99 kips, up & down z= 20 ft
0.18 W , (ASD) = 2.85 kips, up & down h= 36 ft
W0 = 1.5 (ASCE 7-10 Supp. 1 Tab. 13.6-1)
KV = KH 0.2 SDS / 1.4 = 0.18 (vertical seismic factor) KH = 1.3 (This option only for local
jurisdiction amendments to the code.)
MAXIMUM OVERTURNING MOMENT AT ANCHOR EDGE
MOT = Fp H +(0.9W - Fv ) eB = 78.04 ft-kips
MRES = (0.9W - Fv ) (0.5B) = 28.87 ft-kips < MOT ,therefore design tension anchors.
CHECK COMBINED LOADING CAPACITY (ACI 318-19 17 & ICC ESR-1917 Sec. 4.2.2)
(Pu,s / fPn,t) + (Vu,s / fVn,t) = 1.141 < 1.20 [SATISFACTORY]
(Ps / Pt) + (Vs / Vt) = 1.070 < 1.20 [SATISFACTORY]
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Design for Equipment Anchorage to Bottom Concrete & Mounting on Metal Wall Based on 2018 IBC & 2019 CBC Chapter A
INPUT DATA & DESIGN SUMMARY Connector by MFR
EQUIPMENT WEIGHT W = 1.9 kips, (8 kN)
CM
KWIK BOLT-TZ DIAMETER f= 1/2 in, (13 mm), Per ICC ESR-1917
FH
where Occurs
ANCHOR DEPTH hef = 2 in, (51 mm), Per ICC ESR-1917 W E
EDGE DISTANCE c = 48 in, (1219 mm)
FV H
ANCHORAGE LENGTH L = 3 ft, (0.91 m)
BOLTS ALONG L EDGE NL = 2 per line
ANCHOR SPACING SL = L / (NL - 1) = 36 in, (914 mm)
ANCHORAGE WIDTH B = 3 ft, (0.91 m) 1.3h ef h ef
BOLTS ALONG B EDGE NB = 2 per line (Min. Conc. Thk)
ANCHOR SPACING SB = B / (NB - 1) = 36 in, (914 mm) ELEVATION
L
ANALYSIS
TENSION & SHEAR CAPACITY (SD - 2019 CBC 1905A,and ASD - ICC ESR-1917, 4.2) PLAN
fPn,t = 1750.5 lbs, 2019 CBC 1905A & ACI 318-19 17 Pt = 1167 lbs, Tallowable,ASD
fVn,t = 3134.6 lbs, 2019 CBC 1905A & ACI 318-19 17 Vt = 2239 lbs, Vallowable,ASD
BOLT-TZ SPACING & EDGE REQUIREMENTS (ICC ESR-1917, Table 3 or 4)
Scr = 4 1/8 in, (Critical Spacing for Kedge-space based on ACI 318-19 17)
Smin = 2 3/4 in
DESIGN LOADS
FH = F p = W 0 (KH) MAX{ 0.3SDSIpW , MIN[ 0.4apSDSIp(1+2z/h)/Rp W , 1.6SDSIpW ] } , (ASCE 7-10, Sec. 13.3.1)
= 1.5 (1.3) MAX{ 0.43W , MIN[ 0.81W , 2.30W ]} where SDS = 0.96 (ASCE 7-10 Sec 11.4.4)
= 1.58 W , (SD) = 3.00 kips Ip = 1.5 (ASCE Sec. 13.1.3)
= 1.13 W , (ASD) = 2.15 kips ap = 1 (ASCE Tab. 13.6-1)
Rp = 1.5 (ASCE Tab. 13.6-1)
FV = KV W = 0.25 W , (SD) = 0.47 kips, up & down z= 20 ft
0.18 W , (ASD) = 0.34 kips, up & down h= 36 ft
W0 = 1.5 (ASCE 7-10 Supp. 1 Tab. 13.6-1)
KV = KH 0.2 SDS / 1.4 = 0.18 (vertical seismic factor) KH = 1.3 (This option only for local
jurisdiction amendments to the code.)
OVERTURNING MOMENT AT ANCHOR EDGE AT PARALLEL WALL DIRECTION
MOT = Fp H +(0.9W - Fv ) eB = 7.78 ft-kips
MRES = (0.9W - Fv ) (0.5B) = 2.06 ft-kips < MOT ,therefore design tension anchors.
CHECK BOLT-TZ COMBINED LOADING CAPACITY (ACI 318-19 17 & ICC ESR-1917 Sec. 4.2.2)
(Pu,s / fPn,t) + (Vu,s / fVn,t) = 1.057 < 1.20 [SATISFACTORY]
(Ps / Pt) + (Vs / Vt) = 0.991 < 1.20 [SATISFACTORY]
PLAN
ANALYSIS
DESIGN LOADS
F H = Fp = (KH) MAX{ 0.3SDSIpW , MIN[ 0.4apSDSIp(1+2z/h)/Rp W , 1.6SDSIpW ] } , (ASCE 7-10, Sec. 13.3.1)
= 1.3 MAX{ 0.43W , MIN[ 0.81W , 2.30W ]} where SDS = 0.96 (ASCE 7-10 Sec 11.4.4)
= 1.05 W , (SD) Ip = 1.5 (ASCE Sec. 13.1.3)
= 0.75 W , (ASD) = 0.98 kips ap = 1 (ASCE Tab. 13.6-1)
Rp = 1.5 (ASCE Tab. 13.6-1)
FV = K V W = 0.18 W , (ASD) = 0.23 kips, up & down z= 20 ft
h= 36 ft
KV = KH 0.2 SDS / 1.4 = 0.18 (vertical seismic factor) KH = 1.3 (This option only for local
jurisdiction amendments to the code.)
OVERTURNING MOMENT AT BOTTOM HORIZONTAL SCREWS
MOT = Fp H +(W + FV ) L = 4.94 ft-kips