CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Composite Beam/Collector Design, without Metal Deck, Based on AISC 360-10/16 & ACI 318-19
ANALYSIS
DETERMINE CAMBER/SHORING ON NON-COMPOSITE
w= 2.497 kips / ft, floor system self weight, to W21X44, on non-composite
D = 5wL4 / 384 EI = 1.86 in, deflection of W21X44
< L / 180 = 2.00 in [Satisfactory]
Camber = 0.75 D = 1.40 in
CHECK FLEXURAL & AXIAL CAPACITY (AISC 360 I3, ACI 318-19 21 & 22)
Note:
1. Between compression & tension controlled is
Transition, which the f should be by linear
interpolation. (ACI 318-19 Tab. 21.2.2 & Fig. R10.4.2.1)
2. ACI 318-19 changed f (Fig.R21.2.2b) and keeps
be (22.2.2.4.1) and ecu (Fig. R21.2.2a) the same.
But AISC 360/341-16 has different f (0.9 only) and
be (1.0 or 0.7).
2
2 e f C' f y ty , for compression controlled
500 o , ty , t
0.003 , for tension controlled
Ec Es ty
f Pn
(k)
'
E c 57 f C , E s 29000ksi , e 0.7 , cu 0.003
0
0 200 400 600 800
b = MIN (L / 4 , B) = 90 in, (AISC 360 I3.1a)
f= 0.9 , (AISC 360 I3)
Mn @ Pu/ f = 597.5 ft-kips
f Mn = 675.4 ft-kips
-
f Mn (ft-k) Solid Black Line - Tension Controlled > Mu + 0.5CcPu = 484.2 ft-kips
Solid Red Line - Transition [Satisfactory]
Dash Line - Compression Controlled
E
n 6.76 , (ACI 318-19 19.2.2.1) A d Ix Sx Zx
Ec
13 20.7 843 81.6 95.4
Actr = b t0 / n = 56.5 in2
(cont'd)
Actr t 20
I tr I x A y b 0.5 d Actr 0.5t 0 d yb
2 2
2573 in2
12
I tr
S tr 126 in3, referred to steel bottom.
yb
I tr
St 577 in3, referred to concrete top.
d t 0 yb