Professional Documents
Culture Documents
Industrial Waste Water Treatment System Post Maintenance Checks
Industrial Waste Water Treatment System Post Maintenance Checks
Document
Number
---UNCONTROLLED---
HPSL/TEL/O/OM/GNL---
WHEN PRINTED
PREPARED CHECKED APPROVED
REV. DATE MODIFICATIONS
BY BY BY
ALL RIGHT PERTAINING TO THE REPRODUCTION, TRANSFORMATION AND USE OF THIS DOCUMENT. IN ANY
FORM OR MANNER REMAIN THE EXCLUSIVE PROPERTY OF HPSL
1. References
POSTMAINTENANCE CHECKS FOR INDUSTRIAL WASTE WATER TREATMENT SYSTEM
HPSL/TEL/O/OM/GNL---
2. SCOPE
The scope of this document is to take up the industrial waste water treatment system in service
after major maintenance works, in order to avoid any potential obstruction in the system
while heading towards operation. Following subsystem has also been taken into account in
order to make industrial waste water treatment system available completely
Post Maintenance Checks For Waste Water System
Post Maintenance Checks For Storage Pond
Post Maintenance Checks For pH Regulator Tank
Post Maintenance Checks For Reaction Tank
Post Maintenance Checks For Inclined Plate Clarifier
Post Maintenance Checks For Final Neutralization Pond
ADDITIONAL
STEP ACTIONS REMARKS
INFORMATION
INDUSTRIAL WASTE WATER TREATMENT SYSTEM
Post Maintenance Checks For Waste Water System
Industrial waste water auxiliary treatment system pre- Chemical System is ready
1.
start check should be carried out to Start
Check Root’s Blower-A Suction Fan is Intact Root Blower-A Kept in
2. Service
10GNC11AA*** And its Mesh is Clean
Open Root Blower-A Suction Damper isolating Valve
3.
10GNC11AA***
Check Root Blower-A Discharge Line Expansion Bellow
4.
is Intact
Check Root Blower-A Discharge Line Safety Valve is
5. Intact 10GNC11***** and Open its root Valve
10GNC11AA***
Check Root Blower-A Discharge pressure Indicator is
6. Intact 10GNC11CP101 and Open its root Valve
10GNC11AA101
Open Root Blower-A Discharge Isolating Valve
7.
10GNC11AA001
Check Root Blower-B Suction Fan is Intact
8. Root Blower-B is in Standby
10GNC12AA*** And its Mash is Clean
Close Root Blower-B Suction Damper isolating Valve
9.
10GNC12AA***
Check Root Blower-B Discharge Line Expansion Bellow
10.
is Intact
Check Root Blower-B Discharge Line Relief Valve is
11. Intact 10GNC12***** and Open its root Valve
10GNC12AA***
1
POSTMAINTENANCE CHECKS FOR INDUSTRIAL WASTE WATER TREATMENT SYSTEM
HPSL/TEL/O/OM/GNL---
2
POSTMAINTENANCE CHECKS FOR INDUSTRIAL WASTE WATER TREATMENT SYSTEM
HPSL/TEL/O/OM/GNL---
3
POSTMAINTENANCE CHECKS FOR INDUSTRIAL WASTE WATER TREATMENT SYSTEM
HPSL/TEL/O/OM/GNL---
4
POSTMAINTENANCE CHECKS FOR INDUSTRIAL WASTE WATER TREATMENT SYSTEM
HPSL/TEL/O/OM/GNL---
Valve 10GNS11AA501
Open Clarified Sludge pump-1 Discharge Isolating Valve
7.
10GNS11AA002
Close Clarified Sludge pump-1 Discharge Line Drain
8.
Isolating Valve 10GNS11AA401
Check CLARIFIED SLUDGE PUMP-1 10GNS11AP001
A. Motor And Pump are Coupled and Coupling guard Electrical Supply is
in place.
9. Available on XXX
B. Motor Fan cover in place.
Board
C. Motor Ground strip in place.
D. Motor Base plate Bolts are In place
Open Clarified Sludge pump-2 Suction Isolating Valve
10.
10GNS12AA001
Check Clarified Sludge pump-2 Discharge Pressure
11. Indicator is Intact 10GNS12CP501 and Open its root
Valve 10GNS12AA501
Open Clarified Sludge pump-2 Discharge Isolating Valve
12.
10GNS12AA002
Close Clarified Sludge pump-2 Discharge Line Drain
13.
Isolating Valve 10GNS12AA401
Check CLARIFIED SLUDGE PUMP-2 10GNS12AP001
A. Motor And Pump are Coupled and Coupling guard Electrical Supply is
in place.
14. Available on XXX
B. Motor Fan cover in place.
Board
C. Motor Ground strip in place.
D. Motor Base plate Bolts are In place
Check Clarified Sludge pumps Discharge Line Common
15. Pressure Indicator is Intact 10GNS10CP101 and Open
its root isolating valve 10GNS10AA101
Post Maintenance Checks For Final Neutralization Pond
Close Final Neutralizer Pond Inlet from Storage Pond
1. Inlet isolating Valve 10GNL20AA002
Open Final Neutralizer Pond Inlet from Inclined Plate
2. Clarifier Inlet isolating Valve 10GND40AA001
Check Final Neutralizer Pond Mixer 10GND50AM001
A. Motor are Coupled and Coupling guard in place. Electrical Supply is
3. B. Motor Fan cover in place. Available on XXX
C. Motor Ground strip in place. Board
D. Motor Base plate Bolts are In place
Check Final Neutralizer Pond pH Meter Is Intact
4. 10GND50CQ101
Check Final Neutralizer Pond Level Transmitter is intact
5. 10GND50CQ101 and Open its root Valve
10GND50AA101
6. Check Clarified Water Pond Pump-1 Discharge Pressure
5
POSTMAINTENANCE CHECKS FOR INDUSTRIAL WASTE WATER TREATMENT SYSTEM
HPSL/TEL/O/OM/GNL---
AUTHORIZED BY:
NAME & SIGN DATE
PERFORMED BY:
NAME & SIGN DATE
6
POSTMAINTENANCE CHECKS FOR INDUSTRIAL WASTE WATER TREATMENT SYSTEM
HPSL/TEL/O/OM/GNL---
COMPLETED BY: