You are on page 1of 1

Automatic Releases for Preaction and Deluge Sprinkler Systems

The function of these releases is to open water valves automatically via FM Approved fire detection devices.
Release control panels FM Approved for deluge and preaction sprinkler systems are compatible with the specified solenoid-operated
valves, have standby power supplies capable of providing the required 90-hour system operation should primary power fail, and fire
detection circuitry capable of operation during open circuit fault condition.

Series 4004R control...


Series 4004R control. Panel Models 4004-9301 (beige enclosure) and -9302 (red enclosure) are each provided with 4 initiating
device circuits (IDC), which must be connected to 4004-9864 Class A Adapter Module to configure for (Class A) Style D wiring. Two
release circuits are provided for sprinkler release. Each releasing appliance circuit must connect to a 2081-9046 coil supervision
modules which in turn is connected to a compatible 24 and 12 V dc actuators or solenoid. For FM Approved combinations of solenoid
and water control valves, refer to the Automatic Water Control Valve listings that follow. Optional Models 4081-9301, -9302, -9303,
and -9304 External Battery Chargers provide the 4004R charging capability for a standby battery bank up to 50 AH in capacity to
supply the required 90 hours of standby power. [See Control Panel Description under LOCAL PROTECTIVE SIGNALING.]

Company Name: Simplex Time Recorder Co


Company Address: 50 Technology Dr, Westminster, Massachusetts 01441-0001, USA
Company Website: http://simplexgrinnell.com
New/Updated Product Listing: No
Listing Country: United States of America
Certification Type: FM Approved
Class of Work: 3010-Fire Alarm Systems

© 2007-2020 FM Approvals. All rights reserved. Page 1 of 1