Reliable sensing system coupled with very latest digital New TTG (Through-The-Glass) keypad technology
technologies — allows quick and easy local configuration without opening
— provides large turn down ratio up to 100:1 the cover, even in explosion proof environments
Functional Specifications
Range and span limits
Sensor Code Upper Range Limit Lower Range Limit (LRL) Minimum span
(URL) Model 266MST Model 266RST Model 266MST Model 266RST
differential absolute differential absolute
A 1 kPa -1 kPa – 0.05 kPa –
10 mbar -10 mbar 0.5 mbar
4 inH2O -4 inH2O 0.2 inH2O
C 6 kPa -6 kPa – 0.2 kPa –
60 mbar -60 mbar 2 mbar
24 inH2O -24 inH2O 0.8 inH2O
F 40 kPa -40 kPa 0 abs 0.4 kPa 2 kPa
400 mbar -400 mbar 4 mbar 20 mbar
160 inH2O -160 inH2O 1.6 inH2O 15 mmHg
L 250 kPa -250 kPa 0 abs 2.5 kPa 12.5 kPa
2500 mbar -2500 mbar 25 mbar 125 mbar
1000 inH2O -1000 inH2O 10 inH2O 93.76 mmHg
N 2000 kPa -2000 kPa 0 abs 20 kPa 100 kPa
20 bar -20 bar 0.2 bar 1 bar
290 psi -290 psi 2.9 psi 14.5 psi
R 10000 kPa -10000 kPa – 100 kPa –
100 bar -100 bar 1 bar
1450 psi -1450 psi 14.5 psi
Second sensor of 266MST differential pressure transmitter Zero suppression and elevation
for absolute pressure measurement Zero and span can be adjusted to any value within the range
Measuring range: 41 MPa, 410 bar, 5945 psi limits detailed in the table as long as:
(2 MPa, 20 bar, 290 psi for sensor code A) — calibrated span ≥ minimum span
Transmitters for absolute pressure model 266RST operate Sensors Fill fluid Static pressure limits
without damage between the following limits: Sensor F to N Silicone oil 0 abs.
and 16 MPa, 160 bar, 2320 psi, or
Sensors Fill fluid Over pressure limits 25 MPa, 250 bar, 3625 psi, or
Sensor F to N Silicone oil 0 abs. 41 MPa, 410 bar, 5945 psi
and 16 MPa, 160 bar, 2320 psi, or
25 MPa, 250 bar, 3625 psi, or Proof pressure
41 MPa, 410 bar, 5945 psi The transmitters can be exposed without leaking to line
pressure:
266MST, up to 1.5 times the nominal pressure simultaneously
on both sides
266RST, up to 1 time the normal pressure
Meet ANSI/ISA–S 82.03 hydrostatic test requirements.
Important 1 85 °C (185 °F) for application below 10 kPa, 100 mbar abs., 1.45 psia down to
3.5 kPa abs., 35 mbar abs., 0.5 psia
For Hazardous Atmosphere applications see the temperature 2 85 °C (185 °F) for application below atmospheric pressure down to
range specified on the certificate / approval relevant to the 40 kPa abs., 400 mbar abs., 5.8 psia
aimed type of protection.
Model 266RST Process temperature limits
Model 266MST – 266RST Ambient temperature limits Silicone oil -40 and 121 °C (-40 and 250 °F)1
LCD integral display -40 and 85 °C (-40 and 185 °F) Viton gaskets -20 and 121 °C (-4 and 250 °F)
Viton gasket -20 and 85 °C (-4 and 185 °F) PTFE gaskets -20 and 85 °C (-4 and 185 °F)
PTFE gaskets -20 and 85 °C (-4 and 185 °F)
1 85 °C (185 °F) for application below 10 kPa, 100 mbar abs, 1.45 psia
LCD display may not be clearly readable below –20 °C (–4 °F)
or above 70 °C (158 °F). Storage
Additional blocks
1 enhanced Resource block
1 custom Pressure with calibration transducer block
1 custom Advanced Diagnostics transducer block including
Plugged Input Line Detection
1 custom Local Display transducer block
Number of VCRs
35
Current consumption
Operating (quiescent): 15 mA
Fault current limiting: 20 mA max.
Output signal
Physical layer in compliance to IEC 1158-2 / EN 61158-2 with
transmission to Manchester II modulation, at 31.25 kbit/s
Output interface
PROFIBUS PA communication according to PROFIBUS DP
50170 part 2 / DIN 19245 part 1-3.
Function blocks
3 analog input
3 transducer
1 physical
Integral display
Wide screen LCD, 128 x 64 pixel,
52.5 x 27.2 mm (2.06 x 1.07 in.) dot matrix. Multilanguage.
Four keys for configuration and management of device.
Easy setup for quick commissioning.
User selectable application-specific visualizations.
Instantaneous flow indication.
Display may also indicate static pressure, sensor temperature
and diagnostic messages and provides configuration facilities.
Electrical connections
Two 1/2-14 NPT or M20 x 1.5 threaded conduit entries, direct
on housing.
Special communication connector (on request)
— HART: straight or angle Harting Han 8D connector and one
plug
— FOUNDATION Fieldbus, PROFIBUS PA: M12 x 1 or 7/8 in.
Terminal block
HART version: three terminals for signal / external meter wiring
up to 2.5 mm2 (14 AWG), also connection points for test and
communication purposes
Fieldbus versions: two terminals for signal wiring (bus
connection) up to 2.5 mm2 (14 AWG)
Grounding
Internal and external 6 mm2 (10 AWG) ground termination
points are provided.
Change from two to one column
7
10
145 (5.70)
179 (7.02)
210 (8.28)
3
60 (2.36) with plug
41.3 (1.63)
72 (2.83) with d/v valve 8
4
9
65 (2.53)
12 (0.47)
(*)
5
142 (5.59) 90 (3.54) 33 (1.30)
M10019
Note
Process connection, gasket groove and gaskets are in accordance with IEC 61518. Bolting threads for fixing adapter or other
devices (i.e. manifold etc.) on process flange is 7/16 - 20 UNF.
29 (1.14)
91 (3.58) 18 (0.71) 56 (2.21) 53 (2.09) 18 (0.71)
179 (7.02)
210 (8.28)
60 (2.36) with plug
72 (2.83) with d/v valve
12 (0.47)
72 (2.83)
89 (3.48)
45 (1.77) 33 (1.30)
210 (8.28)
45 (1.77) 33 (1.30)
(*) 72 (2.83)
210 (8.28)
60 (2.36) with plug
72 (2.83) with d/v valve
12 (0.47)
118 (4.63)
45 (1.77) 33 (1.30)
70 (2.75)
49 (1.93)
25 (0.98)
70 (2.75) 44 (1.71)
142 (5.59)
89 (3.48)
M10022
M+
60 10
2
2 40 80
0
20 10
% 0
0
Kent-Taylo r
+
+
+
4
- 691HT
-
F1 F2 F3 F4
PV
TRI M
A B C D E F G H I
1 2 3
J K L M N O P Q R
4 5 6
S T U
@ %
7
V W X
8
& /
Y Z #
9
+
3
0 -
M10023
HART hand-held communicator may be connected at any wiring termination point in the loop, providing the minimum resistance
is 250 Ω. If this is less than 250 Ω, additional resistance should be added to allow communications.
Fieldbus Versions
2 DATA + GROUND
3 SHIELD DATA –
4 GROUND SHIELD
M10024
Ordering information
Basic ordering information model 266MST Differential Pressure Transmitter
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information and specify one or more codes for each transmitter if additional options are required.
XX XX XX
Accuracy
Base accuracy 0.025 % (Note 3) D1
Vent and Drain Valve Material / Position
AISI 316L SST (1.4404) On process axis NACE V1
AISI 316L SST (1.4404) On flanges side top NACE V2
AISI 316L SST (1.4404) On flanges side bottom NACE V3
Hastelloy C-276 On process axis NACE V4
Hastelloy C-276 On flanges side top NACE V5
Hastelloy C-276 On flanges side bottom NACE V6
Monel 400 On process axis NACE V7
Monel 400 On flanges side top NACE V8
Monel 400 On flanges side bottom NACE V9
Explosion Protection Certification
ATEX Group II Category 1 GD - Intrinsic Safety Ex ia E1
ATEX Group II Category 1/2 GD - Flameproof Ex d E2
ATEX Group II Category 3 GD - Type of protection "N" Ex nL design compliance E3
FM approval (Canada, CSA) Class I, II, Div. 1, 2, Group A to F (XP, IS, NI) (Only available with 1/2-14 NPT or M20 electrical connections) E4
FM approval (USA) Class I, II, Div. 1, 2, Group A to F (XP, IS, Nl) (Only available with 1/2-14 NPT or M20 electrical connections) E6
FM approvals (USA and Canada) Intrinsic Safety EA
FM approvals (USA and Canada) Explosion Proof EB
FM approvals (USA and Canada) Non Incendive EC
Combined ATEX, FM and CSA (Only available with 1/2-14 NPT or M20 electrical connections) EN
Combined ATEX - Intrinsic Safety, Flameproof and Type „N“ EW
IEC Approval Group II Category 1 GD - Intrinsic Safety Ex ia E8
IEC Approval Group II Category 1/2 GD - Flameproof Ex d E9
IEC Approval Group II Category 3 GD - Type of protection "N" Ex nL design compliance ER
XX XX XX
Drain or Vent Valve Material / Position
AISI 316L ss On process axis NACE V1
AISI 316L ss On flanges side top NACE V2
AISI 316L ss On flanges side bottom NACE V3
Hazardous area certifications
ATEX Intrinsic Safety II 1 G and II 1/2 G Ex ia IIC T6; II 1 D Ex iaD 20 T 95° C and II 1/2D Ex iaD 21 T95° C E1
ATEX Explosion Proof Group II Category 1/2 G Ex d IIC T6 and Group II Category 1/2 D Ex tD A21 IP67 T85° C E2
ATEX Type „N“ Group II Category 3 G Ex nL IIC T6 and Group II Category 3 D Ex tD A22 IP67 T85° C E3
ATEX Intrinsic Safety Ex ia, Explosion Proof Ex d, Type "N" Ex nL EW
Combined ATEX, FM approval (USA) and FM approval (Canada) EN
FM approval (Canada) E4
FM approval (USA) E6
FM approvals (USA and Canada) Intrinsic Safety EA
FM approvals (USA and Canada) Explosion Proof EB
FM approvals (USA and Canada) Non Incendive EC
IEC Intrinsic Safety II 1 G and II 1/2 G Ex ia IIC T6; II 1 D Ex iaD 20 T 95° C and II 1/2D Ex iaD 21 T95° C E8
IEC Explosion Proof Group II Category 1/2 G Ex d IIC T6 and Group II Category 1/2 D Ex tD A21 IP67 T85° C E9
IEC Group II Category 3 G Ex nL IIC T6 and Group II Category 3 D Ex tD A22 IP67 T85° C ER
Other hazardous area certifications
GOST (Russia) Ex ia W1
GOST (Russia) Ex d W2
GOST (Kazakhstan) Ex ia W3
GOST (Kazakhstan) Ex d W4
Inmetro (Brazil) Ex ia W5
Inmetro (Brazil) Ex d W6
Inmetro (Brazil) Ex nL W7