Generator
Protection
With the SEL-400G
Rogerio Scharlach
Principal Engineer
© SEL 2019
SEL Confidential
Presenter Notes
SEL Confidential
1
Advanced protection and control
for large generators driven by:
HYDRAULIC TURBINES
STEAM TURBINES
COMBUSTION GAS TURBINES
SEL Confidential
The SEL-400G relay offers unsurpassed protection, integration, and control features for generators of
all types and sizes including hydro, pumped-storage hydro, large steam turbines, and combustion gas
turbines (CGTs).
Presenter Notes
SEL Confidential
2
SEL-400G
Advanced
Generator
Relay
SEL Confidential
The SEL-400G relay provides a suite of elements for the comprehensive protection and monitoring of
generators of all types and sizes. In total, the relay consists of 24 analog channels, divided into two
groups of analog inputs. The first group consists of 18 channels for phase current inputs and the
second group consists of 6 channels for two three-phase voltage inputs. One of the three-phase current
inputs can be configured as three single-phase current inputs and one of the three-phase voltage inputs
can be configured as three single-phase voltage inputs. The relay can also be equipped with high-speed
transducer I/O, which can be used for condition monitoring and other applications.
Presenter Notes
SEL Confidential
3
SEL-400G Terminal Connections
SEL Confidential
Presenter Notes
SEL Confidential
4
18 Current Channels
SEL Confidential
Presenter Notes
SEL Confidential
5
6 Voltage Inputs
SEL Confidential
Presenter Notes
SEL Confidential
6
High-Current High-Speed, Independent and
Outputs High-Current Outputs Common Inputs
SEL Confidential
Presenter Notes
SEL Confidential
7
New INT9 Interface Board
SEL Confidential
Presenter Notes
SEL Confidential
8
Ethernet Card
SEL Confidential
Presenter Notes
SEL Confidential
9
Serial Ports
IRIG-B Input
SEL Confidential
Presenter Notes
SEL Confidential
10
Two Independent Frequency Zones Provide
Simultaneous Frequency Tracking
GSU
60 Hz
10
9 Hz
8
7
6
5
4
3
2
1
0
60 Hz
SEL Confidential
The SEL-400G features extended range frequency tracking of 5–120 Hz. Generators may, at times,
operate at frequencies significantly different than nominal. The SEL-400G wide-range frequency
tracking algorithm ensures that all protection functions are secure and dependable regardless of the
system frequency. The SEL-400G also independently tracks the generator and system frequencies.
Presenter Notes
SEL Confidential
11
Independent Differential Protection Zones
Allow Separate Generator and GSU Protection
GSU
87 Zone 2
87 Zone 1
SEL Confidential
The SEL-400G includes two differential zones, each of which can include an in-zone transformer and
can accept as many as six sets of CT inputs to protect both the generator and generator step-up (GSU)
transformer without the need for an additional transformer differential relay. Each current terminal can
be included into either or both differential zones. Increasing the number of inputs to the differential
zone removes the need to parallel CTs when including various circuits connecting to the zone. This, in
turn, makes it much more practical to provide overcurrent, breaker failure, and inadvertent
energization protection for multiple breakers.
Presenter Notes
SEL Confidential
12
SEL Confidential
The SEL-400G internally corrects the phase transpositions introduced by the reversing switch. The
logic ensures that the phasing of the differential element is correct and that the phase rotation is
correct. This allows a pumped storage hydro unit to be protected with a single SEL-400G without the
need to externally switch the CT or PT secondary wiring.
Presenter Notes
SEL Confidential
13
GSU
Built-In Autosynchronizer
SEL Confidential
The built-in autosynchronizer can synchronize up to three breakers, one at a time, and offers three
pulse control options
• PPW
• PPF
• Fixed
It supports biased operation for frequency and voltage control. Control actions and governor and AVR
responses are available on event or disturbance reports.
Presenter Notes
SEL Confidential
14
100% Stator Ground Element
SEL-2664S
Coverage
64G1
64G2
64G3
64S
Z2 or V2 0% 50% 100% Z
64 64 64 64 64
S1 S2 G1 G2 G3
SEL Confidential
• Third-harmonic differential.
• Third-harmonic ratio.
• Acceleration path
• Integration timer
Presenter Notes
SEL Confidential
15
Dependable Directional Q
Power Element Unbiased
Characteristic
• Includes 4 elements
• Can be assigned to dedicated CT
PM
• Has biased option P
Sensitive directional power elements in the SEL-400G provide anti-motoring and/or low forward
power tripping. As many as four elements are provided for detecting real (watts) or reactive (VARs)
directional power flows, with independent time delays and sensitivities. Directly trip the generator
under loss-of-prime mover conditions to prevent prime movers from motoring or use low forward
power indication as a tripping interlock when an orderly shutdown is required.
The SEL-400G includes a biased characteristic. This provides extra dependability for a motoring event
where motoring power is very low and reactive power is high. Under these circumstances, small angle
errors associated with the instrument transformers can have a more significant impact on the power
calculation.
The directional power element can be assigned to a dedicated CT. It also incorporates an integrating
timer.
Presenter Notes
SEL Confidential
16
SEL GRID Configurator
SEL Confidential
The SEL-400G will be the first product to ship with SEL GRID Configurator software.
Presenter Notes
SEL Confidential
17
INT9 Analog Board
Q2 2020 Release
SEL Confidential
2 analog outputs
• 16-bit resolution
6 analog inputs
• 16-bit resolution
• Sampled at 8 kHz
8 digital inputs
7 digital outputs
•
Presenter Notes
2 Aurora-proof high current interrupting output contacts
SEL Confidential
18
Stator Field Current Differential
Stator
Rotor
Shunt
SEL Confidential
The SEL-400G measures the second-harmonic component of the field current. The field component is
translated to a 60 Hz phasor using the pre-fault stator voltage and current. This quantity is then used
along with the negative-sequence current in the stator to derive differential and restraint quantities and
applied to a conventional percentage-restraint operating characteristic. This element can detect faults
not otherwise detectable by the phase differential and ground fault elements.
Presenter Notes
SEL Confidential
19
Aurora Proof Contacts
GSU
SEL Confidential
Aurora refers to the possibility of a malicious attack on the power system where a generator is
damaged because of rapid, uncontrolled switching of the generator breaker. An accepted mitigation
method is the insertion of timer logic into the breaker control circuit that requires that the breaker
remain opened for a minimum duration before allowing it to close again. The SEL-400G implements
this logic within the INT9 I/O board circuitry, and the logic is enabled by using a jumper on the board.
Since the solution is implemented in hardware, it cannot be bypassed by remotely accessing the relay.
Presenter Notes
SEL Confidential
20
Pumped-
Storage
Logic 87T
87G
M G
Pumped Storage
T *
Switching from generator to pump mode impacts elements that use sequence components. This can be
addressed by dynamically changing the phase rotation setting. A second impact occurs if the
differential zone includes the reversing switch. In the past, this was addressed by switching of the CT
secondary wiring. The SEL-400G solution addresses both problems using a very intuitive approach.
The user identifies any CTs and PTs that are downstream from the reversing switch. The relay then
rolls the phasing internally to correct the phase change introduced in the primary circuit.
Presenter Notes
SEL Confidential
21
Steam Turbine
Generator
SEL-2664S Fiber
SEL-2600
Serial
SEL-2664
VB X Z W S Y1 T U VA VC
SEL-400G
SEL Confidential
Presenter Notes
SEL Confidential
22
Combustion Gas Turbine Generator
LCI Start Auxiliary Transformer
SEL-2664S Fiber
SEL-2600
52 52
Serial
SEL-2664
VA,
VB X Z T W VC Y1 U
SEL-400G
SEL Confidential
Presenter Notes
SEL Confidential
23
Hydro Generator
Brake
SHAFT
VA,
VB X W U S T VC
SEL-400G
SEL Confidential
Presenter Notes
SEL Confidential
24
The Message Advanced protection, monitoring, and
communication features are critical
Protect
substantial
Limit Return
investment
generator service
Detect in generating
damage faster
faults earlier facilities
SEL Confidential
The advanced protection, monitoring, and communication features in the new SEL-400G are a critical
part of protecting the substantial investment required in a generating facility. Detect faults earlier,
limiting damage to the generator, and return to service faster.
Presenter Notes
SEL Confidential
25
Win Engineers in 30 Seconds
SEL Confidential
Presenter Notes
SEL Confidential
26
Advanced generator, bus, transformer
and auxiliary system protection for
hydro, thermal, and pumped storage
Presenter Notes
SEL Confidential
27
I/O, automation, and communication features
allow for easy integration with plant systems
Presenter Notes
SEL Confidential
28
Grid Configurator is SEL’s new tool
for configuration of protection,
control, and metering systems
Presenter Notes
SEL Confidential
29
Win Management in 30 Seconds
SEL Confidential
Presenter Notes
SEL Confidential
30
Advanced protection, monitoring, and
communication features are critical part
of protecting substantial investment
Presenter Notes
SEL Confidential
31
SEL-400G can detect faults earlier, limiting generator
damage and allowing you to return service faster
Presenter Notes
SEL Confidential
32
Flexible controls and communication
allow for integration, operator
visibility, and asset management
Presenter Notes
SEL Confidential
33
SEL-400G Price Breakdown
Standard $10,000
+ Autosynchronizer +$2,000
Ethernet +$550–$720
I/O Boards (up to 3) +$525–$1,050
IEC 61850 +$400
Connectorizer +$275
Conformal Coating +$250
SEL Confidential
Presenter Notes
SEL Confidential
34
Competitor Prices
$18k**
$9.3–17k*
$12.5k
G60
7UM85 REG670
SEL Confidential
*Depending
on features; largest cost is function points
Presenter Notes
SEL Confidential
35
Questions?
SEL Confidential
Presenter Notes
SEL Confidential
36
Competitive Landscape
GE
ABB
REG670
Multilin
Siemens
7UM85
Beckwith
M-3425A
SEL-400G
G60
Current /
Voltage Inputs 24 / 12 16 / 8 32 / 23 32 / 23 18 / 6
Integrated
Synchronizer
No No Yes No Yes
Anti-motoring No No No No Yes
Wide
Frequency 9–95 Hz Not 10–80 Hz 10–80 Hz 5–120 Hz
Range specified
SEL Confidential
Review the full competitive analysis spreadsheet available in the SEL-400G sales kit.
Presenter Notes
SEL Confidential
37
Transverse Differential Protection
Universal
Differential 87 Zone
Lateral 87
87 Zone Transverse 87
87 Zone
87 Zone
SEL Confidential
• Dual zones
• Up to 6 restraint currents
• In-zone transformer
– Fast (sample-based)
Presenter Notes
SEL Confidential
38
Current Unbalance Element
SEL Confidential
2 2
𝑛+𝑖 𝑛−𝑖
𝐼2EQ = 𝐼22 + 𝐼 + 𝐼 , 𝑛 = 2 … 15
2 𝑛_2 2 𝑛_1
𝑛
Negative-sequence current heats the rotor at a higher rate than positive-sequence current. The
negative-sequence definite-time element provides alarm for early stages of an unbalanced condition.
The inverse-time overcurrent element provides tripping for sustained unbalance conditions to prevent
machine damage. The inverse-time negative-sequence element provides industry standard I22 • t
protection curves. The element accounts for heating due to the harmonic components as high as the
15th. In accordance with IEEE C50.12 and IEEE C50.13, each component is scaled by a weighting
factor based on its sequence (positive or negative) and its harmonic order.
Presenter Notes
SEL Confidential
39
Capability-Based LOF (40P)
Q
Zone 1 Analogous to 40 Z1
Z4 (GCC)
Independent supervision Z1
and timing for each zone
SEL Confidential
Use this function to more effectively coordinate with the generator capability curve (GCC), steady
state stability limit (SSSL), and underexcitation limiter (UEL). The element can dynamically shift with
voltage to maintain coordination with the UEL. It can also dynamically expand and contract following
an analog measurement such as hydrogen pressure. This element provides an alarm for operation
outside the GCC. It also provides a trip for an underexcitation event. It can alarm or trip for an SSSL
event.
Presenter Notes
SEL Confidential
40
Current-Based Thermal Element
1 x 103
• Implements 3
independent models
• Conforms to
SEL Confidential
The SEL-400G thermal element provides thermal overload protection based on the thermal model
described in IEC 60255-149. The model can be biased by ambient temperature if the RTD option is
used. The relay operates a thermal model with a trip value defined by the relay settings and a present
heat estimate that varies with time and changing generator current.
Presenter Notes
SEL Confidential
41
Shaft Overcurrent Element
From PPT 3104. A mix of slides 8 and 11.
Oil Film
Bearing Housing
Bearing
Insulation
Can be configured
Shaft to respond to
Shaft CT
fundamental, RMS,
Rotor
or harmonics
Guide Bearing
Turbine
Spiral
Case
SEL Confidential
Presenter Notes
SEL Confidential
42
Disturbance Report
• Up to 300-second • Sampled at 20 ms
records • Captures
• Stored in nonvolatile ▪ Power swings
memory
▪ Synchronizing events
• Contains
▪ Slowly evolving
▪ 20 analog quantities protection operations
▪ 800 Relay Word bits
SEL Confidential
The SEL-400G triggers disturbance reports with record lengths of as long as 300 seconds (5 minutes).
As many as five records can be stored. Each record can have 20 analog and 800 digital quantities at a
sampling rate of 20 ms. The disturbance report can be configured to include filtered quantities
(fundamental, RMS, harmonics, etc.), frequency, power, protection operating signals, and transducer
inputs. Digitals include protection Relay Word bits, contact inputs, and remote digitals received over a
communications channel. Use the disturbance recorder to capture power swings, synchronizing events,
and slowly evolving protection operations.
Presenter Notes
SEL Confidential
43
Applications Using INT9 Board
SEL Confidential
The ability to monitor additional signals allows the SEL-400G to provide more comprehensive
protection and facilitates the development of novel protection algorithms. The relay includes six high-
fidelity transducer inputs supporting the standard ranges of ±20 ma, 4–20 ma, ±10 V, or 0–10 V.
These inputs are sampled at 8 kHz with a resolution of 16 bits.
• Vibration monitoring
Presenter Notes
SEL Confidential
44
Applications Using INT9 Board
SEL Confidential
Presenter Notes
SEL Confidential
45