Professional Documents
Culture Documents
BY
12 MAY 2017
1 of 116
TABLE OF CONTENTS
2. SWITCHBOARD
3. ALTERNATOR UNIT
4. ELECTRIC MOTORS
5. POWER CABLES
2 of 116
1. TYPICAL ELECTRICAL DISTRIBUTION SYSTEM IN PALM OIL MILLS
BAY
Linking Power Generators and Main Switchboard. Commonly used are PVC/PVC Single Core
Copper Conductors laid in cable trench. Selection due to flexibility.
3 of 116
Comprising Main Generator Boards, Main Distribution Boards, Power Factor Correction
Board, and Synchronizing Panel
Connecting Main Switchboards and Motor Control Centers / Sub-Boards. Commonly used are
4 Core Armored Cable laid in cable trench and on cable tray.
(e) Sub-Switchboards
Comprise Motor Control Centers and Sub-Boards. Starter Boards are located here.
These are attachment of panels to control power intake from power generators and distribute
the same to load centers through the MDB under control conditions.
(a) 1 No. draw-out 3 Pole ACB c/w under voltage release and auxiliary contacts
5 of 116
(a) 30 A
(c) 100 A
(d) 225 A
(e) 400 A
(f) 600 A
Overloads can be adjusted
(g) 800 A
(h) 1000 A
(i) 1250 A
(b) Digital type Power Factor Regulator is normally available in steps of 6 and 12.
(c) Measurement Current Transformer should be installed at location where the total power
demand flows through. This is to ensure total correction of all inductive reactive load to
the desired power factor.
- C/K setting (The time response setting to switch on capacitor bank at 70% of their
reactive power)
6 of 116
- Switching sequence of capacitor banks
(e) Example :
Equality in Voltage
Equality in Frequency
(d) Paralleling of power generator sets other than the above conditions can cause serious
damage to generators, switchgears and meters due to reverse power thus causing
motoring in one of the power generators.
7 of 116
1.2.6 LIST OF COMMON ELECTRICAL MATERIALS USED IN PALM OIL MILLS
8 of 116
24 Hour run Counter 220V 48mmsq 5 ½ Digit GAE
25 Time Switch 240V NC, NO OMRON
26 Power Factor Regulator Electronic12-Step type NOKIAN
3-phase 380V Dry Type c/w
27 Capacitor Bank ABB
Housing
Metering (Class CM) & Protection
28 Current Transformer CIC / SEG
(Class 10P10)
Rain-Proof TBL 12FC 1.5A 250V
29 Ball Float Switch KASUGA
Level Relay c/w Stainless Ball
Float
Suspended Electric Hoist Push- Water Proof 5A 250V 4 Way Type
30 SHANHO
Button (for Capstan) SRE82 Push-button
31 Spring Balancer (for Capstan) 1.2 – 2kg Model 602 SHANHO
PLN
71 Transmission Poles 9m & 11m Steel Tubular Poles
Approved
10 of 116
PLN
72 Distribution Poles 7.5m Steel Tubular Pole
Approved
PLN
73 Pole for Compound Light 7.5m Steel Tubular Pole
Approved
11 of 116
1.3 MOTOR CONTROL CENTERS (MCC)
1. MCCs provide electrical power to electric motors and Lighting Distribution Boards
2. A MCC comprise:-
b) Magnetic Contactor(s)
12 of 116
1.4 ELECTRICAL DRAWINGS OF SWITCHBOARDS
13 of 116
14 of 116
15 of 116
16 of 116
17 of 116
18 of 116
19 of 116
2. ALTERNATOR UNIT
2.1 DIFFERENT REPRESENTATIVE VIEWS
20 of 116
BLOCK DIAGRAM OF AN ALTERNATOR
21 of 116
2.2 PRINCIPLES OF OPERATIONS
These 2 input signals are processed by the AVR. The resultant signal (DC
power) is then feed into the main exciter stator
As the exciter rotor rotates around the exciter stator a 3-phase AC power is
produced in the exciter rotor which are rectified (DC power) and then feed into
main rotor
Similarly 3-phase AC power is produced at main stator when main rotor rotates
over the main stator windings
22 of 116
5. When lamps are totally dark and synchronoscope almost 12 o’clock, Switch on
ACB for Set No.2
6. Adjust governor switch (kW) and voltage trimmer (Kvar) of Set No.2 to take
desired load
P1 = VOLTAGE DROOP
P2 = VOLTAGE OUTPUT
P3 = STABILITY
23 of 116
MAJOR CONNECTIONS
24 of 116
25 of 116
RELATION BETWEEN OUTPUT VOLTAGE, SPEED & FIELD CURRENT
f = Frequency (c/s)
= Flux (webers)
T = No. of turns/phase
P = No. of poles
N = Speed (rpm)
= Absolute Permeability
A = Area of Coil
Vs = 4.44 f T (1)
But f = PN (2)
120
= µIT . A (5)
L
PN IT
Vs = 4.44 ( )( A) T
120 L
Vs = KNI
It implies that Output Voltage is proportional to a) Speed and b) Current output from
Main Rotor
26 of 116
2.3 TYPES OF PROTECTION RELAYS
Overcurrent
Earth Fault
Reverse Power
Insulation Resistance
Over-Excitation
Over-Temperature
Phase Sequence/Breaking
27 of 116
OVERCURRENT RELAY
Magnetic Type EARTH FAULT RELAY
MechanicalType
28 of 116
REVERSE POWER RELAY
Mechanical Type
29 of 116
2.3.2 SYY 155 (Under/Over Voltage Relay)
Any Combination
L1 L2 L3 N
L2 L3 L1
L3 L1 L2
6
5 7
4 8
3 9
2 10
1 11
SYY 155
Connected to three phases and neutral the SYY 155 meter sinusoidal voltages.
The phase sequence is arbitrary. The relay stays ON as long as all three phase-
neutral voltages are between an upper and lower limit. The two limit are
separately adjusted. If one or more of the phase-neutral voltages rises above the
upper limit or drops below the lower limit, the relay releases (OFF). The relay
operates again, when all three phase-neutral voltages are inside the set limits.
The hysteresis on operate is 2%.
30 of 116
2.3.2.3 Operation Diagram
AC or DC supply voltage.
Example 1 Example 2
Basic coupling Inversion
Black
Black
6 6
5 7 5 7
4 8 4 8
3 9 3 9
2 10 2 10
1 11 31 of 116 1 11
ST 115 ST 115
Example 3
Slave coupler
6 6
5 7 5 7
4 8 4 8
3 9 3 9
2 10 2 10
1 11 1 11
ST 115 ST 115
Master Slave
2.3.3.2 Operation Diagram
In conjunction with a remote sensor, type ETR, this S-system can be used to
control temperature of heaters of refrigerators. In the latter case inverted relay
function should be employed as a precaution.
The variable hysteresis makes control by this S-system extra flexible. The
supply voltage must continuously be connected to the S-system.
The temperature in oC at which the relay shall operate or release is set on the top
potentiometer.
The hysteresis in oC. I.e. the difference of temperature required for a change in
position of the relay, is set on the bottom potentiometer. If the S-system is used
32 of 116
to control a refrigerator, pins 8 and 9 (example 2) are to be interconnected.
However, in the case of controlling a heater, these pins should not be connected
(example 1).
Example 1 Example 2
L1 L2 L3 L1 L2 L3 N
6 6
5 7 5 7
4 8 4 8
3 9 3 9
2 10 2 10
1 11 1 11
SM 170 SM 170
33 of 116
2.3.4.2 Mode of Operation
The relay measures on its own 3-phased supply voltage and operates, when all
phases are present and the phase sequence is correct.
Example 1
The relay releases in case of corruption of one of the phases, provided that the
voltage regenerated by electric motors on the interrupted phase does not exceed
50% of the nominal voltage.
Example 2
34 of 116
2.4 CALIBRATION OF PROTECTION RELAYS
~
Protection
Current Injector Relay
Variac
Is = 0 – 5A
Iv Secondary Circuit
CT2 Ip
L
Nv CT1
Link
Bus Bars
Primary Circuit
N
No of turn of CT2 Ip = High Current
Iv Nv Ip Np Np = 1
Iv Nv
Ip = = Iv Nv Np = 1 (Eqn. 1)
Np
Ip
Is = (step down) (Eqn. 3)
CT1Ratio
Calculations
Let Iv =5A
2000
Ip =5 (From Eqn 2)
5
= 2000 A
2000
and Is = 5A (From Eqn 3)
2000
=5A
35 of 116
2.4.2 SECONDARY INJECTION TEST
36 of 116
2.4.3 OVER-CURRENT PROTECTION
Setting Values
Calculations
Pr imary Amps
Secondary Amps =
CT Ratio
1478
To Carry : 5 4.62 A
1600
1770
To trip in one minute : 5 5.53 A
1600
2217
To trip in one second : 5 6.92 A
1600
37 of 116
2.4.4 EARTH FAULT RELAY
CT Ratio : 1600/5A
Setting : 10% (147.8A)
Trip Time : Within 1 second
Other Brands
a) CROMPTON
b) MIKRO
i) Setting in %
Turn % knob to 7
CT Ratio = 1600/5A
7
= 1478 A
100
= 103.46 A
38 of 116
Pr imary Amps
Secondary Amps =
CT Ratio
103.46
= 5A
1600
= 0.32 A
CT Ratio = 1600/5A
7
= 1478 A
100
= 103.46 A
Pr imary Amps
Secondary Amps =
CT Ratio
103.46
= 5A
1600
= 0.32 A
Power = 3 V I P.F
= 3 415 0.32 1
= 230 Watts
Resitive Load = 1
39 of 116
2.5 POWER FACTOR CORRECTION
Definitions :
(a) The phase different between the Voltage and Current Vectors.
KW Active Power
(b) P.F = Cos =
KVA Apparent Power
KW
=
3 V I
(a) Reduce rated active power (Kw) of electric machinery due to large increase of
current thus temperature rise.
(b) Large voltage drop along power line (IR drop) and thus low receiving end voltage.
(c) Higher ratings of switch gear and cables required thus higher capital investment.
40 of 116
2.5.4 POWER FACTOR IMPROVEMENT
(b) Synchronous Motor (By varying D.C. field to control Power Factor of motor)
(c) Phase Advancer (a special equipment to modify the magnetising current of motor)
P3 = 1.732 VL x IL x P.F
XL
V Motor Winding
V
Vector
Diagram
IL
(Lagging)
V
IL Lagging by o
2
41 of 116
2.5.6 CAPACITIVE CIRCUIT
IC
V XC Capacitor
IC (Leading)
Vector Diagram
V
90o
Power = VI Cos
= VI x 0
= 0 Watt
IC Leading V by
o V
Phase Diagram
2
/2
42 of 116
2.5.7 POWER TRIANGLES
V
I Cos
V
I Sin
I
Multiply By ‘V’
VI Cos
V
VI Sin
VI
KW
V
KVA r Power Triangle
KVA
KW = KVA2 KVAr 2
43 of 116
2.5.8 REACTIVE POWER (KVAR) BY CAPACITOR
I1 V
AC
Cos
V
MOTOR
I1
I2 I1
V
V IC AC Cos 2
Cos 1
MOTOR
IC I2
IC
IC
Capacitor I1
Banks
KW
Cos 2
KVAr2
Cos 1
KVA2
KVAr1
KVA1
KVArC
Cos 2
The power plant of an Oil Mill supplies a combined load of 850 at 0.7 power factor
lagging. The normal ratings of these generating set are 3-phase 415 V 50 Hz.
44 of 116
Calculate :
(a) The reactive power (KVAr) required to improve power factor to 0.9 lagging.
(b) What is the capacitance per phase of the capacitor banks is delta-connected in 6-
steps.
Solution
Voltage = 415 V
Before Correction
KVAr1 = KW Tan 1
= 850 x 1.02
= 867 KVAr
After Correction
KVAr2 = KW Tan 2
= 850 x 0.48
= 408 KVAr
= KVAr1 – KVAr2
= 867 – 408
= 459 KVAr
45 of 116
(b) If capacitor banks are connected in 6-step
459
KVAr per step =
6
76.5
KVAr/step/capacitor =
3
25.5 1000
Current in each capacitor IC = 61.44 A
415
V 1
Ic , where Xc
Xc 2 fc
Ic 2 fcv
Ic 61.44
c 471.25F
2 fv 2 50 415
46 of 116
2.5.10 POWER FACTOR REGULATOR
LED
LIGHTS
BELUK
c/ Cos
0. k 0. 0.90 0.85
0. 3 2 0.
7 0.95
1 1
0.07 1 0.80
5
aut
cap ind - man
+
47 of 116
2.5.11 C/K SETTING TABLES
For mains voltage Rating per Stage of Reactive VA Control System in KVAr
380 VAC
Current Transformer 5 6.67 8.33 10 12.5 15 16.7 20 25 30 33.3 40 50 60 100
30/5 0.83 1.07
50/5 0.50 0.65 0.83 1.00
75/5 0.33 0.43 0.55 0.67 0.83 1.00 1.11
100/5 0.25 0.32 0.42 0.50 0.63 0.75 0.84 1.00
150/5 0.17 0.22 0.28 0.33 0.42 0.50 0.56 0.67 0.83 1.00
200/5 0.13 0.16 0.21 0.25 0.31 0.38 0.42 0.50 0.63 0.75 0.83 1.00
300/5 0.08 0.11 0.14 0.17 0.21 0.29 0.28 0.33 0.42 0.50 0.56 0.67 0.83 1.00
400/5 0.02 0.08 0.10 0.13 0.16 0.19 0.21 0.25 0.31 0.38 0.42 0.50 0.63 0.75
600/5 0.06 0.07 0.08 0.10 0.13 0.14 0.17 0.21 0.25 0.28 0.33 0.42 0.50 0.83
800/5 0.05 0.06 0.08 0.09 0.10 0.13 0.16 0.19 0.21 0.25 0.31 0.38 0.63
1000/5 0.05 0.06 0.08 0.08 0.10 0.13 0.15 0.17 0.20 0.25 0.30 0.50
1500/5 0.05 0.06 0.07 0.08 0.10 0.11 0.13 0.17 0.20 0.33
2000/5 0.05 0.06 0.08 0.08 0.10 0.13 0.15 0.25
3000/5 0.05 0.06 0.07 0.08 0.10 0.17
4000/5 0.05 0.06 0.08 0.13
37 15 0.84 73 0.95 65
45 20 0.85 88 0.97 76
55 20 0.85 107 0.95 95
75 30 0.85 145 0.96 127
90 40 0.85 172 0.97 151
110 40 0.85 210 0.95 187
132 60 0.85 252 0.97 220
7.5 5 0.78 17.5 0.96 14
11 5 0.78 25 0.91 20.9
Synchronous 750 r.p.m
48 of 116
45 20 0.84 90 0.96 78
55 20 0.84 110 0.94 96
75 30 0.85 145 0.96 127
7.5 5 0.74 18 0.93 14.2
11 5 0.73 26 0.86 22.1
15 10 0.73 36 0.93 28.1
22 20 0.73 52 0.98 39
30 20 0.73 69 0.93 54
37 20 0.77 80 0.93 66
45 30 0.78 96 0.97 78
55 30 0.78 116 0.95 96
75 40 0.80 154 0.96 128
11 5 0.89 21.5 0.99 19.2
15 5 0.89 29 0.97 26.6
18.5 5 0.89 35 0.96 33
Synchronous 3000 r.p.m
22 10 0.89 42 0.99 38
30 10 0.91 56 0.98 52
37 10 0.91 68 0.97 63
45 15 0.90 84 0.98 77
55 15 0.90 103 0.97 94
75 15 0.90 135 0.95 130
90 20 0.91 163 0.97 153
110 20 0.91 200 0.96 189
7.5 5 0.85 15.5 0.99 13.2
11 5 0.85 22.5 0.97 19.6
15 5 0.86 30 0.95 26.9
18.5 10 0.85 37 0.98 32
22 10 0.86 43 0.98 38
Synchronous 1500 r.p.m
30 15 0.87 58 0.99 50
37 15 0.88 70 0.98 62
45 20 0.86 86 0.98 76
55 20 0.86 105 0.96 93
75 20 0.88 140 0.95 128
90 30 0.88 167 0.97 150
110 40 0.88 202 0.97 183
132 40 0.88 245 0.96 222
49 of 116
2.6 SPECIFICATIONS FOR SERVICING, MAINTENANCE, OVERHAUL AND REPAIRS
OF ALTERNATOR
Air Circulation
Daily perform visual inspection that the air inlet and outlet grilles are not partially
blocked by any foreign materials.
Regreasing use: Lithium Standard NLGI 3 (Factory Lubrication : Shell ALvania G3)
b) Qty of Grease 50 gm 70 gm 35 gm
Temperature rise in the bearings should not exceed 50 Deg C above ambient
temperature.
Electrical Servicing
Mechanical Servicing
Fitted With Air Filters : Clean filter elements regularly; once a week
: USD __________________________
51 of 116
4. Business Address : ______________________ ________________________
______________________ ________________________
______________________ ________________________
______________________ ________________________
Cost
Rp USD
1. Service at Site
2. Transportation
3. Service at Workshop
52 of 116
3.4 Conduct insulation and voltage drop tests.
Record readings.
4. Replacement Cost
MS
4.1 Supply and replace DE and NDE bearings.
54 of 116
2.6.3 REWINDING OF ALTERNATOR UNIT
: USD _______________
55 of 116
2.6.3.2 SCOPE OF WORKS
56 of 116
10. CRANAGE AND TRANSPORTATION
Provide cranage, transportation and labour to :
a) Move alternator unit from Palm Oil Mill’s Engine Room
to Electrical Workshop
b) Return alternator unit from Electrical Workshop to Palm
Oil Mill’s Engine Room
11. INSURANCE
Purchase all-risk insurance coverage for alternator unit from
date of removal to date of return
TOTAL OF TENDER PRICE Rp USD
57 of 116
2.7 ALTERNATOR’S FAILURE : CASE STUDY
a. No-Load Conditions
58 of 116
500/4 66.0 2.8 57.0 2.4
500/5 82.0 3.4 77.0 3.2
59 of 116
2.7.4 Winding Resistances (Typical Values)
AVR
MAIN OUTPUT
DIODES
ROTOR
FIELD
SHAFT
60 of 116
2.7.6 Reminder ( Relationship Between Output Voltage and Excitation Amps / Voltage)
f = Frequency (c/s)
= Flux (webers)
T = No. of turns/phase
P = No. of poles
N = Speed (rpm)
= Absolute Permeability
A = Area of Coil
Vs = 4.44 f T (1)
PN
But f = (2)
120
IT
and B = (4)
L
IT
= A (5)
L
PN IT
Vs = 4.44 A T
120 L
Vs = KNI
61 of 116
2.8 POWER CORRECTION COEFFICIENTS FOR ALTERNATORS
i) Standard ratings for generator are given for the following site condition :
b. Altitude : Up to 1000 m
For special conditions of operation, the standard ratings given should be multiplied by one or
more of the following coefficient (k).
Where more than one special condition is involved, the total multiplication factor is the
product of the individual coefficient.
1.1
Rating 1.0
Factor
0.9
0.8
20 30 40 50 60 oC
Ambient
Temperature
62 of 116
iii) Altitude (above 1000 m)
1.0
Rating
Factor 0.9
0.8
0.7
1000 2000 3000 4000
63 of 116
3. ELECTRIC MOTORS AND STARTERS
64 of 116
3.1.1 INTERACTION OF CONDUCTOR FLUX AND FIELD FLUX
Notes :
a) Apply current into conductor. Magnetic flux is produced. Use cork screw rule to
define direction of flux.
b) The inter-action of the field flux and the conductor flux produced a force
ThuMb : Motion
65 of 116
3.1.2 INTER-ACTION BETWEEN STATOR FLUX AND ROTOR FLUX
b) This alternating flux from the stator cut the rotor bars as such current is generated at
the rotor bars
c) The current generated at the rotor bars in turn produced another set of flux.
d) Because of the inter-actions between the stator flux and rotor flux, a force is
produced
Operation at constant load during a given time, less than that required to reach
thermal equilibrium, followed by a rest and de-energized period of sufficient
66 of 116
duration to re-establish equality of temperature with the coolant. The recommended
values for short time duty are 10, 30, 60 and 90 minutes.
In this duty the stopping of the motor is obtained either by natural deceleration after
disconnection of the electricity supply or by means of braking such as a mechanical
brake which does not cause additional heating of the windings.
67 of 116
8) Continuous Operation Duty With Related Load/Speed Changes (Duty Type S8)
Unless otherwise specified, the duration of the duty cycles shall be 10 minutes.
The recommended values of cyclic duration factors are 15%, 25%, 40% and 60%.
9) Designation
The duty type is normally designated by the abbreviations S1, S2, etc, the
abbreviation is followed by an indication of the duration of the duty. For duty types
S3 and S6 the abbreviations are followed by the cyclic duration factor.
Examples : S2 60 min
S3 25%
S6 40%
a) The motors are designed to operate satisfactorily for a voltage variation of 5% and
a frequency variation of 3%. However at extreme limits of voltage and frequency,
the performance figures will be different from those mentioned in name plate.
b) Table below describe the effects of variation of voltage and frequency on the
characteristics of the motors.
68 of 116
3.2.3 THE EFFECTS OF VARIATION OF VOLTAGE AND FREQUENCY ON
INDUCTION MOTOR
Torque *
Starting and Increase 21% Decrease 19% Decrease 10% Increase 11%
maximum running
Speed **
Synchronous ... No change No change Increase 5% Decrease 5%
Full Load ... Increase 1% Decrease 1.5% Increase 5% Decrease 5%
Per cent slip ... Decrease 17% Increase 23% Little change Little change
Efficiency :
Full Load ... Increase 0.5 to 1% Decrease 2% Slight increase Slight decrease
¾ Load ... Little change Little change do do
½ Load ... Decrease 1 to 2% Increase 1 to 2% do do
Power factor :
Full load ... Decrease 3% Increase 1% do do
¾ Load ... Decrease 4% Increase 2 to 3% do do
½ Load ... Decrease 5 to 6% Increase 4 to 5% do do
Current :
Starting ... Increase 10 to 12% Decrease 10 to 12% Decrease 5 to 6% Increase 5 to 6%
Full Load ... Decrease 7% Increase 11% Slight decrease Slight increase
Temperatur rise ... Decrease 3 to 4o C Increase 6 to 7o C Do Do
Maximum overload Increase 21% Decrease 19% Do Do
capacity
Magnetic noise ... Slight increase Slight decrease Do Do
* The starting and maximum running torque of A.C. induction motors will vary as the square of the
voltage
** The speed of A.C. induction motors will vary directly with the frequency
INMACO motors are manufactured with class B insulation as standard. Class F and class
H motors are also offered against orders. The insulating materials used for various
classes of insulation are briefly described below :
69 of 116
1) Class E
The maximum operating temperature is 120o C. The insulating materials used are
mostly synthetics like Polyester films with trade names like Melinex, Mylar, etc.
Combination of Polyester film with other materials like terylene, presspahn, etc., are
also used. The copper wires are insulated with Polyester or Polyvinyl Acetate (PVA)
enamels.
This class of insulation is still commonly used by most motor manufacturers for
standard small motors.
2) Class B
The maximum operating temperature is 130o C. The insulating materials used are
varnished Fiberglass tapes and cloth, terylene compounds, fiberglass sleevings, mica
and mica-glass combination, etc.
3) Class F
The maximum operating temperature is 155o C. The insulating materials used are
Nylon compound, with trade names like Nomex, combination of films using Nomex,
silicon varnished glass tapes, glass-resin composite strips, etc.
4) Class H
The maximum operating temperature is 180o C. The insulating materials used are
Nylon compounds, Nomex combinations, silicon varnished glass tapes and sleeving,
etc.
All insulating materials used in the manufacture of electrical motors perform one or
more of the following functions :
70 of 116
4. To withstand the heat which is present at their point of use during operation of the
motor. It is essential that the insulating properties of the materials used remain
unaffected at the operating temperatures
Listed below are four principal areas where a potential difference occurs and where,
therefore, insulation must be applied.
1) Enclosures for motors are designated by the letters ’IP’ followed by two numerals as
explained below :
a) The first numeral designates the degree of protection to persons against contact with live
or moving parts of the motor and to motors against entry of solid foreign bodies.
71 of 116
b) The second numeral designates the degree of protection to the motor against harmful
entry of water
c) A letter may appear after the 2 numerals which could be S (indicating that the motor was
rested while stationery) or M (indicating that the motor was tested while in operation)
2) Protection to persons against contact with motor parts and to motor against solid bodies
First
Short designation Degree of protection definition
Numeral
No special protection of persons against accident
Non-protected or inadvertent contact with love or moving parts.
0
machine No protection of machine against ingress of solid
foreign bodies.
Protection against accidental or inadvertent
contact with live or moving parts inside the
Machine protected enclosure by a large surface of the human body,
1 against solid bodies for example, a hand, but no protection against
greater than 50 mm deliberate access to such parts.
Protection against ingress of large solid foreign
bodies (diameter greater than 50 mm)
Protection against contact by finger with love or
Machine protected
moving parts inside the enclosure. Protection
2 against solid bodies
against ingress of small solid foreign bodies
greater than 12 mm)
(diameter greater than 12 mm)
Protection against contact with live or moving
parts inside the enclosure by tools, wires, or such
objects of thickness greater than 1 mm.
Machine protected Protection against against ingress of small solid
4 against solid bodies foreign bodies (diameter greater than 1 mm)
greater than 1 mm excluding the ventilation openings (intake and
discharge) of external fans and the drain holes of
enclosed machines, which may have degree 2
protection
Complete protection against contact with live or
moving parts inside the enclosure.
Machine protected Protection against harmful deposits of dust. The
5
against dust * ingress of dust is not totally prevented, but dust
cannot enter in an amount sufficient interfere with
satisfactory operation of machine
* The degree of protection against dust defined by this standard is a general one. When the
nature of the dust (dimensions of particles, their nature, for instance fibrous particles) is
72 of 116
specified, test conditions should be determined by agreement between the manufacturer
and the user.
For first characteristic numeral 2, 4, and 5 with machines cooled by means of an external
fan, the fan shall be so protected as to prevent contact of the blades or spokes of the fan
with the standard test finger. However, at the outlet of the fan the test finger is not inserted
past the 50 mm diameter guard.
NOTE : a machine is weather protected when its design reduces the ingress of rain, snow and
air bone particles under specified conditions to an amount consistent with correct operation.
This degree of protection is designated by the letter W (placed between IP and the numerals).
73 of 116
3.4.1 MAKING ENQUIRIES FOR MOTOR
ii. Make
v. Rated Amps
x. Type of Mounting
• Direct-On-Line (DOL)
• Star-Delta (SD or - )
• Auto-Transformer (AT)
74 of 116
3.5.2 Selection of Starters
b) 7.5 – 30 hp : SD starter
75 of 116
Primary Resistance a) Possibility of adjusting a) Small reduction in starting
starting current current
b) No break in line supply b) Require resistor
during starting
Auto-Transformer a) Good torque Require a costly auto-
transformer
b) Possibility of adjusting
starting values
Soft Starter a) Torque can be adjusted a) Expensive
b) Starting current can be b) Electrical Assistance require
adjusted and limited training.
c) Immediate stop can be
avoided
d) Avoid water hammering at
pipeline
Rotor Resistance e) Very good torque a) Slip ring motor more
expensive
f) Low starting current
b) Requires additional resistor
g) Possibility of adjusting
bank
starting current
h) No break in line supply
76 of 116
Operation
77 of 116
PRIMARY RESISTANCE STARTER
L1 L2 L3
Q1 TP ISOLATOR
F1 FUSE
KM11
KM1
u1 v1 w
R 1 RESISTANCE
u2 v2 w
2
F2 THERMAL
OVERLOAD
M
3~
Operation
Manual Closing of Q1 (Main Switch)
Closing of KM11 – Motor Energised and Run
Timer energised and counting
Closing of KM1 – Shorting of Resistances
Direct Connection of Motor to Line 3
78 of 116
Power Circuit Operation
79 of 116
80 of 116
L1 N
240 V 50 Hz SUPPLY
C/F
MOTOR TRIP
1
O/L R 5
4
C
C-1 MOTOR RUN
INTERLOCK RELAY
R
2 3 4
REMOVE LINK WHEN USING
REMOTE START/STOP PUSH
BUTTTON
Control Circuit
Type C (Direct-on-Line)
L1 N
240 V 50 Hz SUPPLY
C/F
MOTOR TRIP
1
O/L TDR-1 D
4 R 5 6 7
C S
P
LC- SP-1
8 L
1
C
LC-2
5
2 3 4 TDR
81 of 116
L1 N
240 V 50 Hz SUPPLY
C/F
MOTOR TRIP
1
O/L TDR2- TDR1- LC-1
R 1 5 4 1 6 7 TSC
TSC 8 LC-2 9 L
4 C
SC
5 TDR
2 3 9 1
REMOVE LINK WHEN USING
REMOTE START/STOP PUSH TDR
2
BUTTTON TDR1-
2
1 1 LC
0 0
LC-3
HRM
MOTOR RUN
1
Control Circuit 0
R
Type D (Auto-Transformer)
82 of 116
L1 N
240 V 50 Hz SUPPLY
MOTOR TRIP
C/F
HRM
1
O/L 4 R 5 SC
SC-1 FR-1
5 TDR1
TDR1-1
6 A
2 3 4 R
REMOVE LINK WHEN USING TDR2
REMOTE START/STOP PUSH
BUTTTON TDR2-1
5 7 FR
R INTERLOCK RELAY
Control Circuit
Type A (Rotor Resistance)
83 of 116
9 5.5 7.5 11.0 SD 30 2 x 2.5
10 7.5 10 4.0 SD 30 2 x 2.5
11 11.0 15 20.0 SD 40 2 x 6.0
12 15.0 20 26.5 SD 40 2 x 10
13 18.5 25 35.0 SD 60 2 x 16
14 22.0 30 41.3 SD 60 2 x 16
15 30.0 40 52.4 AT 60 1 x 25
16 37.0 50 70.0 AT 80 1 x 35
17 45.0 60 82.0 AT 100 1 x 50
18 55.0 75 100.0 AT 125 1 x 50
19 75.0 100 135.0 AT 150 1 x 75
20 93.0 125 165.0 AT 200 1 x 95
84 of 116
4. POWER CABLES
Types Denotions
i) PVC Cables PVC or PVC/PVC
ii) PVC Insulated Armoured PVC/SWA/PVC
iii) Hard Drawn Stranded Aluminium Conductor HD AL
iv) Mineral Insulated Cable MICC
v) PVC Insulated Flexible Cords PVC FC
i) The Conductor
iii) For Mechanical : Lead Alloy, Galvanised Steel Wire, Steel Rod, Aluminum Sheath
c) Voltage Range
i) 250/440 volts
v) 6350/11000 volts
85 of 116
vi) Other higher ranges
d) No. Of Core
i) One Core
4.2 APPLICATIONS
a) PVC Cables
1. Lighting Point
2. Power Point
3. Motor Point
5. Internal Cabling for Main Switchboard and Sub-Switchboard (Motor Control Centre)
iii. To link main switchboard or sub-switchboard with other starter panels outside the main
processing building
Similar Application as PVC Insulated Armoured Cable except it is not commonly used for
motor point wiring.
86 of 116
Paper insulated cable has higher Ampere rating than Armoured cable but more expensive.
MICC cable can withstand ambient temperature of 150oC. Insulation material use is
Magnesium Oxide a Fire-proof material.
v. Electronic Equipment
Mainly used for overhead distribution power line. For instance, chanelling electric power
from power house to workers quarters.
i. 3/.132 inch
g) Method of Installation
87 of 116
iv. Installed inside conduits
h) Points to Note
i. Cable Trenches
Cables laid direct in the ground shall be buried to a depth of 30 inches. 3 inch deep clean
sand shall be provided at the bottom and at the top of the cable. Good quality house
bricks shall then be laid length-wise along the route.
At road crossing, the cable shall be protected with ducting eg G.I. pipe
iv. Conduits
All conduits shall be galvanized screwed steel type. Saddles shall be provided every 4
feet. Inspection elbows shall be provided at bend. Tee boxes shall be provided at branch-
off. All conduits shall be painted orange.
4.3 IDENTIFICATIONS
Phase A – Red
Phase B – Yellow
Phase C – Blue
Neutral – Black
88 of 116
c) D.C. Wiring and bus-bars are coloured as follows :
When current flows through a conductor, voltage is dropped along the conductor due to
resistance (DC power) or impedance (AC Power). The drop in voltage is in terms of
millivolts/amps/metres.
89 of 116
Single Core Cables
4.6 Three core cable, single wire armoured and PVC oversheathed
2. PVC insulation
3. Taped bedding
5. PVC oversheath
90 of 116
4.7 Four core cable, single wire armoured and PVC oversheathed
2. PVC insulation
3. Extruded bedding
5. PVC oversheath
The conductor consists of four sector shaped solid aluminum conductors laid up together and
bound. Extruded PVC insulation is applied over the conductor followed by a PVC oversheath. A
similar armoured version is also available.
2. Conductor binder
91 of 116
3. Extruded PVC insulation
Conductors of shaped, solid aluminium are insulated with PVC. The cores are laid up and bound
with PVC tapes, followed by a single layer of aluminium strips and and overall PVC sheath.
2. PVC insulation
3. Taped bedding
5. PVC oversheath
92 of 116
4.10 Construction of Aluminum Stranded Conductor
7 Strands 19 Strands
37 Strands 61 Strands
93 of 116
4.11 CURRENT RATINGS
(COPPER)
Single-circuit current ratings and associated volt drops for single-core p.v.c. Insulated
cables, non-armoured, with or without sheath (copper conductors)
Conductor Bunched and Enclosed in conducts or Clipped direct to a surface or on a cable tray,
trunking bunched and unenclosed
2 cables, single phase 3 or 4 cables three- 2 cables, single phase 3 or 4 cables three-
Nominal a.c., or d.c. phase a.c a.c., or d.c. phase a.c
No. and
cross- Current Volt drop Current Volt drop Current Volt drop Current Volt drop
dis (m) of
sectional rating per rating per rating per rating per
wires
area ampere ampere ampere ampere
per metre per metre per metre per metre
mm2 A mV A mV A mV A mV
1.0 1/1.13 11 40 9 35 13 40 12 35
1.5 1/1.38 13 27 11 23 16 27 15 23
2.5 1/1.78 18 16 16 114 23 16 20 14
95 of 116
25 7/2.14 73 1.6 66 1.4 89 1.6 80 1.4
35 18/1.53 90 1.2 80 1.0 109 1.2 98 1.0
(COPPER)
Single-circuit current ratings and associated volt drops for single-core p.v.c. Insulated cables,
non-armoured, with or without sheath (B.S. 6004 or B.S. 6346) (Copper Conductors)
Nominal Bunched and enclosed in conduit or Clipped direct to a surface or on a cable Con-
Defined conditions
cross trunking tray, bunched and unenclosed duc-
sectional tor
area of Flat or vertical (2 cables,
2 cables, single-phase 3 or 4 cables, 2 cables, single phase 3 or 4 cables, (3 cables,
conductor single-phase a.c., or d.c., or 3 or
a.c. or d.c three-phase a.c. a.c., or d.c. three-phase a.c. three phase)
4 cables three-phase)
Cur- Volt drop per Cur- Volt Cur- Volt drop per Cur-rent Volt Cur- Volt drop per ampere Cur- Volt
rent ampere per rent drop rent ampere per rating drop rent per metre rent drop
rating metre rating per rating metre per rating ra- per
ampere ampere ting ampere
per per Single Three- per
a.c d.c a.c d.c d.c
metre metre -phase phase metre
mm2 A mV A mV A mV A mV A mV mV mV A mV mm2
50 145 0.97 0.91 125 0.84 175 0.93 0.91 160 0.82 195 0.95 0.91 0.85 170 0.80 50
70 185 0.71 0.63 160 0.62 220 0.65 0.63 200 0.59 240 0.68 0.63 0.62 210 0.59 70
95 230 0.56 0.45 195 0.48 270 0.48 0.45 240 0.45 300 0.52 0.45 0.49 260 0.42 95
120 260 0.48 0.36 220 0.42 310 0.40 0.36 280 0.38 350 0.44 0.36 0.43 300 0.34 120
150 - - - - - 355 0.34 0.29 320 0.34 410 0.39 0.29 0.39 350 0.29 150
185 - - - - - 405 0.29 0.24 365 0.30 470 0.35 0.24 0.36 400 0.25 185
240 - - - - - 480 0.24 0.18 430 0.27 560 0.36 0.18 0.38 480 0.22 240
300 - - - - - 560 0.22 0.14 500 0.25 660 0.33 0.14 0.35 570 0.19 300
400 - - - - - 680 0.20 0.12 610 0.24 800 0.30 0.12 0.33 680 0.17 400
500 - - - - - 800 0.15 0.086 710 0.23 910 0.28 0.066 0.31 770 0.16 500
600 - - - - - 910 0.17 0.068 820 0.22 1040 0.26 0.068 0.30 880 0.15 600
96 of 116
e) P.V.C., non-armoured twin and multicore (1.0 mm2 to 35 mm2)
(COPPER)
Single-circuit current ratings and associated volt drops for twin and multicore p.v.c.
Insulated and sheathed cables, non-armoured (B.S. 6004 **) (Copper Conductors)
mm2 A mV A mV A mV A mV A mV A mV mm2
1.0 1/1.13 11 40 9 35 12 40 10 35 - - - - 1.0
1.5 1/1.38 13 27 12 23 15 27 13 23 - - - - 1.5
2.5 1/1.78 18 16 16 14 21 18 18 14 - - - - 2.5
Flat
4 7/0.85 24 10 22 8.8 27 10 24 8.8 - - - - cables
only
6 7/1.04 30 6.8 27 5.9 35 6.8 30 5.9 - - - - 4
10 7/1.35 40 4.0 37 3.5 48 4.0 41 3.5 - - - - 6
97 of 116
f) P.V.C., non-armoured twin and multicore (50 mm2 to 300 mm2)
(COPPER)
Single-circuit current ratings and associated volt drops for twin and multicore p.v.c. -
Insulated and sheathed cables, non-armoured (B.S. 6004 ) (Copper Conductors)
mm2 A mV mV A mV A mV mV A mV mm2
50 140 0.94 0.93 125 0.81 170 0.94 0.93 145 0.81 50
70 175 0.66 0.64 155 0.57 215 0.66 0.64 190 0.57 70
95 215 0.49 0.46 190 0.42 260 0.49 0.46 230 0.42 95
120 250 0.40 0.37 215 0.34 300 0.40 0.37 265 0.34 120
150 285 0.33 0.30 250 0.29 340 0.33 0.30 300 0.29 150
185 325 0.28 0.24 280 0.24 385 0.28 0.24 340 0.24 185
240 385 0.24 0.19 335 0.20 450 0.24 0.19 400 0.20 240
300 445 0.21 0.15 390 0.18 520 0.21 0.15 460 0.18 300
98 of 116
g) P.V.C., armoured (1.5 mm2 to 35 mm2)
(COPPER)
Single-circuit current ratings and associated volt drops for twin and multicore armoured
p.v.c. - Insulated cables (B.S. 6346) (Copper Conductors)
mm2 A mV A mV A mV A mV mm2
1.5 14 28 13 24 - - - - 1.5
2.5 20 17 17 15 - - - - 2.5
4 26 11 22 9.1 - - - - 4
99 of 116
h) P.V.C., armoured (50 mm2 to 400 mm2)
(COPPER)
Single-circuit current ratings and associated volt drops for twin and multicore armoured
p.v.c. – Insulated cables (B.S. 6346) (Copper Conductors)
mm2 A mV mV A mV A mV mV A mV mm2
50 150 0.92 0.92 125 0.81 180 0.92 0.92 155 0.81 50
70 180 0.65 0.64 155 0.57 220 0.65 0.64 190 0.57 70
95 225 0.48 0.46 190 0.42 270 0.48 0.46 230 0.42 95
120 260 0.40 0.36 220 0.34 310 0.40 0.36 270 0.34 120
150 290 0.32 0.25 250 0.29 355 0.32 0.25 310 0.29 150
185 340 0.29 0.23 290 0.24 410 0.29 0.23 350 0.24 185
240 400 0.25 0.18 350 0.20 485 0.25 0.18 420 0.20 240
300 460 0.23 0.14 400 0.18 550 0.23 0.14 475 0.18 300
400 520 0.22 0.11 460 0.17 620 0.22 0.11 550 0.17 400
100 of 116
i) Bare circular copper conductors (risers)
Single-circuit current ratings and associated volt drops for bare or lightly-covered solid
copper conductors of circular cross section
mm mm2 A mV A mV mV A mV mV
j) Flexible Cords
Current ratings and associated volt drops and masses supportable, for flexible cords insulated
with p.v.c.
(B.S. 6500)
Nominal cross No. and diameter Current rating d.c. Volt drop per ampere per metre Maximum mass
sectional area of (mm) of wires or single-phase a.c., d.c. or single- Three-phase supportable by twin
conductor forming conductor or three-phase a.c. phase a.c. a.c. flexible cord
mm2 A mV mV Kg
0.5 16/.20 3 83 72 2
0.75 24/.20 6 56 48 3
1.0 32/20 10 43 37 5
1.5 30/.25 15 31 26 5
2.5 50/.25 20 18 16 5
4 56/.30 25 11 936 5
28/.15
For p.v.c. parallel-twin non-sheathed cords
42/.15
101 of 116
k) For impregnated paper insulated lead alloy sheathed cables
120 365 335 310 275 390 325 0.35 0.46 0.35
150 410 375 345 315 445 375 0.30 0.42 0.28
185 460 425 385 355 520 430 0.26 0.39 0.24
240 530 490 440 410 620 510 0.22 0.35 0.20
300 600 550 490 460 710 590 0.20 0.32 0.18
400 680 620 550 530 820 680 0.18 0.30 0.17
102 of 116
l) Stranded Aluminium Conductors ( BS 215/1/170)
* This item denotes in round figures the area of a solid hard-drawn copper rod of resistance
approximately equal to that of stranded aluminum conductor.
Example :
0.81
Therefore voltage drop = 100 40 volts
1000
103 of 116
= 3.24 volts
3.24
% of voltage drop = 100%
415
= 0.78%
104 of 116
MULTI CORE CABLE
Di atas 1 0,95 0,90 0,88 0,85 0,81 0,95 0,84 0,80 0,75 0,75
penyangga
kabel tertutup 2 0,90 0,83 0,83 0,83 0,80 0,95 0,80 0,76 0,71 0,69
(sirkulasi 3 0,88 0,83 0,83 0,79 0,78 0,95 078 0,74 0,70 0,68
udara 6 0,86 0,81 0,79 0,77 0,76 0,95 0,76 0,72 0,68 0,66
terhindar)
(Enclosed
cable trench)
Di atas 1 1,00 0,98 0,96 0,93 0,92 0,95 0,84 0,80 0,75 0,73
penyangga 2 1,00 0,95 0,93 0,90 0,89 0,95 0,80 0,76 0,71 0,69
kabel terbuka 3 1,00 0,94 0,92 0,87 0,88 0,95 0,78 0,74 0,70 0,68
6 1,00 0,93 0,90 0,87 0,86 0,95 0,76 0,72 0,68 0,66
105 of 116
MULTI CORE CABLE (lanjutan)
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Dipasang 1,00 0,93 0,90 0,87 0,86 0,95 0,78 0,73 0,68 0,66
pada
konstruksi
besi atau
dinding
106 of 116
SINGLE CORE CABLE
107 of 116
SINGLE CORE (lanjutan)
1 2 3 4 5 6 7 8 9 10
Kabel dipasang satu di atas 0,94 0,91 0,89 Penyusunan kabel
yang lain pada rangka besi yang faktor
atau dinding koreksinya boleh
diabaikan
108 of 116
5. COMMON ELECTRICAL FAULTS IN PALM OIL MILLS
Overload/over-current
Overheat
Short Circuit
Earth Fault
Single Phasing
Reverse Power
Under Voltage
Over Voltage
109 of 116
8. Over-Voltage a) External-lightning a) Damage
electronic
b) Internal-mill machineries
equipment
(start/srop operations)
b) Expedite aging of
electronic
components
9. Earth-leakage a) Poor insulation Endanger operator
b) Presence of moisture
110 of 116
6. SHORTCOMING IN MAINTENANCE, OPERATION AND CARE
OF ELECTRICAL EQUIPMENT AND MACHINE
6.1 MAINTENANCE
1. Alternator
b) Cable terminal box is seldom opened up to inspect for loose connections and heating.
c) Electric heater or carbon lamp is not used to heat up windings to remove moisture when
alternator is not in operation.
d) Blowing of windings is only done at the overhangs. Little attempts are made to remove
dust and dirt in other areas of alternator’s windings.
e) Lubrication of bearings are not properly recorded to maintain standard time for greasing.
f) Diode connections to rotating disc are not checked by torque wrench and as such under
and over tightening occur. Both can lead to failure of rotating diode assemblies.
2. Main Switchboard
a) Arrangement is not made to re-calibrate the overcurrent and earth fault relays
periodically.
b) Defective meters, indicating lights, switched and lighting fittings are commonly found.
This shows lack of maintenance.
c) Cleaning of trench is not done. Water, debris, cockroaches and rats are common sight.
d) Front, side and back covers are not close tightly. Gaps are left behind inviting the entry
of vermin.
e) Defective power and control fuses are not replaced but instead shorted with ‘copper
wire’. This can lead to fire hazard.
f) Main switchboard is seldom being opened up to check for loose connections and
excessive heatings.
111 of 116
g) The top of main switchboard is dirty and couple with rain water through leaking roof has
caused rust to set in. This leads to entry of water inside main switchboard and probably
short-circuit.
a) Externally, most MCPs are messy with peeled paint, oil and dirt.
b) Internally, the control wirings and power cables are not strapped and routed properly.
c) MCPs are usually set upon by water, oil and fibre. Little is done to improve the situation.
d) Screw are usually not complete or totally absent from front and back covers. As such
many covers are seen ajar.
e) Contractors are not opened up for servicing. They are left to operate until failures set in.
f) Power fuses are sometimes replaced not according to connected load but what are
available in stock. This can lead to single phasing.
g) Defective indicating lights and start/stop push buttons are commonly found.
Replacement are normally by cannibalizing from spare starter boards.
4. Electric Motor
a) Motors laden with oil, dirt and fibre are easily sighted. The roots of these problem are
not being attended to.
b) Bearings are not lubricated sufficiently but are left to run till failures. Shafts are at times
affected as well.
c) Missing fan covers are not replaced thus damage to fans have occurred.
d) Failures due to alignment, overheat, overload, short-circuit, water ingression etc are
common. These causes can be controlled with proper maintenance.
e) Missing screws from cable terminal box can be found. This can lead to short-circuit due
to ingreesion.
f) In the past. Wound rotors have failed due to defects of spring tension and carbon brushes
being too short. Scouring and arcing at slip rings are bad signs.
g) Many times after a motor is opened up and re-assembled the coil terminals are not
installed in the right order. This shows poor maintenance technique.
112 of 116
h) The loading on each phase of an electric motor should be periodically checked.
Unbalanced loading is a sign of imminent failure. If the problem is identified in the early
stage, the motor could be saved by just cleaning and revarnishing.
5. Lighting Fitting
a) A large proportion of existing fittings are without bulbs and tubes. These forgotten
fittings are being left alone to ‘rot’.
b) Fittings in use are usually dirty or covered with cob-webs. This points to lack of
maintenance again.
d) Control box has been neglected to such an extend lizards have claimed habitat over it.
Since the choke acts as a current limiter, short-circuit by lizard can cause failure to these
fittings.
e) At times bracket has come loose and fittings are left dangling by the wire. Beside the
danger of falling on someone’s head, it can cause nuisance tripping of ACB due to earth
leakage.
6. Earthing
a) Earthing is one of the most neglected part of the electrical system in our palm oil mill.
Many times difficulty is encounter trying to locate these points and sometimes they are
not found at all.
b) Ironically, earthing is a very important part of any electrical system where providing
protection to electrical installations and operators are concerned.
c) Electrocution or explosion can happen if a fault is not isolated quickly due to defective
earthing. Maintenance of earth leads and earth electrodes must not be neglected but
instead given the same treatment like other important installations.
f) Conceal earthing points are not attended to but are left alone to be forgotten.
113 of 116
g) Clamping of earth leads to earth electrodes is not being checked. Good connection is
important to effective earthing.
h) The reason for not maintaining this earthing system is mainly because of non-availability
of earth tester. Arrangement should be made with wiring contractor to perform the test
once a year.
7. Overhead Lines
a) Rotting poles and heavily sagged lines are just a few signs of poor maintenance.
e) Anti-termite paint is not renew at pole bases thus deterioration of wood poles are
expedited.
f) Connection through line taps between service line and main lines are never checked.
8. Instrumentation/UPS
a) Field equipment like solenoid valves, actuator, regulator and transmitter are usually
cover with oil and dirt.
d) Dust and dirt accumulation inside UPS is not attended to. When these inter-act with
moisture, a conductive path is formed where shoort-circuit and mal-function can happen.
e) Maintenance of UPS batteries is totally lacking. Some mills have already reported
battery failure.
6.2 OPERATIONS
1. Alternator
114 of 116
b) High excitation will be introduced into the alternator operating at below rated speed.
This can lead to failure of windings.
c) Loading is not progressive but are buil up in short duration. Shock loading can lead to
failures.
d) The sharing of load between alternators in parallel are not proportional to their ratings.
This does not comply with manufacturer’s request.
e) Under-speed and over-voltage protection is not periodically checked to confirm these are
in good working condition.
f) Paralleling procedures are not strictly followed by all engine drivers and electrical
workers. The generated voltages are not adjusted to equal magnitude and in phase when
the main air-circuit breaker is closed.
g) Defective synchronoscope has been seen in used for months and no arrangement is made
to replace the defective unit. Only the synchronising lights are taken as guide to
synchronise alternator sets. This metode is highly dangerous.
2. Electric Motor
a) The most common mal-treatment of electric motor is frequent running and stopping in
short durations leading to winding failure. This particularly true for screw-press drive.
b) The setting of thermal overloads relay does not usually match the rated current of the
electric motor. There are adjusted just to prevent frequent trippings and thus stoppages of
machinery but at the expense of the electric motor.
c) Electric motor emitting excessive heat should be identified and checked. Very often no
one pays any attention to these motors.
d) Checks should be done to compare the running and rated amperes to prevent
overloading.
e) When replacing electric motor ensure the correct size and type are used. This is not
always the case and as result the original designs are all upset.
f) When the floors are being cleaned by hosing, the motors are not spared at all. The mill
management does not spared at all. The mill management does not make any effort to
stop such practice but only watch with astonishment.
115 of 116
3. Uninterruptible Power Supply System (UPS)
a) Additional loads are seen to be connected to the UPS without looking into the designed
capacity. Problems have been reported in these mills.
b) Operating procedures are not strictly complied with. Loads are not switch on and off
individually as instructed but the switch at the UPS is used. High surge is generated by
this manner of switching which can cause damage to UPS or electronic equipment.
c) Food and container have been seen placed on top of UPS for warming. The UPS is also
conveniently used as table top to keep files and number tags. These must be stopped
immediately to avoid problems.
6.3 CARE
Generally care of equipment is lacking at mill level. More interest and thought should be given
to equipment by mill personnel. The shortcomings are as following :
a) Spare equipment are not kept in clean, dry and cool place.
c) Most electrical workshop are messy without proper compartment for storing electrical
components. Instead everything is being thrown at one corner, more damage is done.
d) Before handling any equipment care must be taken to ensure they are securely fasten.
e) Loading and unloading of equipment shall be gradual and not being thrown off suddenly.
f) Care must be taken to comply with manufactures instructions on installation, operation and
maintenance.
g) When dismantling any equipment do not throw parts around but instead should be kept in
container or box.
116 of 116