CLIENT : Dr. REDDY'S LABORATORIES, HYDERABAD.

PROJECT : CLUSTER - 2 DATE: 07.01.16


EXHAUST SUMMARY SHEET REVISION : R3 (02.03.16)
MINIMUM MAXIMUM SELECTED SELECTED
FUME HOOD SNORKEL / CABINET / CANOPY HOOD BLOWER BLOWER BLOWER MOTOR REMARKS
CAPACITY CAPACITY CAPACITY CAPACITY
UNIT NO. ROOM NO. ROOM DESCRIPTION EQUIPMENT NAME
MINIMUM TOTAL MAXIMUM TOTAL TOTAL
EXHAUST CFM
QTY EXHAUST CFM MINIMUM EXHAUST CFM MAXIMUM QTY EXHAUST CFM CFM CFM IN Kw
/ HOOD
/ HOOD EXHAUST / HOOD EXHAUST CFM CFM

ANALYTICAL CHEMISTRY LAB Spot Extractor --- --- --- --- --- 4 60 240
INTRUMENT LAB - 1 Spot Extractor --- --- --- --- --- 1 60 60
INTRUMENT LAB - 2 Spot Extractor --- --- --- --- --- 1 60 60
STORAGE AREA Cabinet --- --- --- --- --- 2 30 60
1200 WIDE Fume
KF SAMPLE & MOBILE 1 360 360 360 360 --- --- ---
Hood
PREPARATON
Spot Extractor --- --- --- --- --- 2 60 120
WASH AREA Canopy Hood --- --- --- --- --- 1 350 350

Spot Extractor --- --- --- --- --- 3 60 180


Cabinet --- --- --- --- --- 2 30 60
1800 WIDE Fume
10 155 1550 495 4950 --- --- ---
CHEMISTRY LAB Hood
Canopy Hood --- --- --- --- --- 1 350 350
Room General
--- --- 240 --- 85 --- --- ---
Exhaust
CONNECTED TO AHU-1
SCB-1 2150 5395 1480 3630 6875 6875 18.50
& AHU - 3
Spot Extractor --- --- --- --- --- 2 60 120
Cabinet --- --- --- --- --- 2 30 60
1800 WIDE Fume
4 155 620 495 1980 --- --- ---
Hood
2400 WIDE Fume
POTENT GENOTOXIC IMPURITIES 1 190 190 655 655 --- --- ---
Hood
LAB
Canopy Hood --- --- --- --- --- 1 350 350

Isolator --- --- --- --- --- 3 100 300


Room General
--- --- 240 --- 85 --- --- ---
Exhaust
CHANGE ROOM Room Exhaust --- --- --- --- --- --- --- 6

Spot Extractor --- --- --- --- --- 1 60 60


INTRUMENT LAB - 3
Room Exhaust --- --- --- --- --- --- --- 427

Isolator --- --- --- --- --- 1 100 100


ISOLATOR ROOM
Room Exhaust --- --- --- --- --- --- --- 236

SCB-2 1050 2720 1659 2709 4379 4379 11.00 CONNECTED TO AHU-2