You are on page 1of 4

E N E R GY A U T O M AT I O N

& I N F O R M AT I O N

LMU 5000
Coupling Device

COMPREHENSIVE STAND-ALONE COUPLING


DEVICE FOR PLC TELECOMMUNICATIONS

Using a power line as the transmission medium,


the PLC Telecommunications world requires
particular interfacing functions between
telecommunications equipment (power line carrier
equipment) and high-voltage components such as
the line, line trap circuits and coupling capacitors.

AREVA has designed the LMU 5000 coupling


device specifically for this type of application,
guaranteeing the ultimate quality in terms of
reliability and safety.

Without any additional accessories, the LMU 5000


fulfils the modularity of the various configurations
encountered in the power line technique (phase
earth coupling, phase-phase coupling, inter-circuit
coupling).

THE BEST WAY TO COPE WITH LINE


CHARACTERISTICS

Based on a new design, the LMU 5000 is a part of the 5000 Telecom product
range and offers the following features:

Customer Benefits • Efficient protection against HV power effect and transient voltage picks,
ensuring a high level of safety for staff and excellent protection for the
• High safety levels power line carrier equipment.
• Compliant with all • Designed to provide a fast and efficient commissioning
PLC transmissions • Matching characteristics that cope with all the impedances between a
• Easy to install and PLC equipment and the power line / coupling capacitor circuit.
configure
• Cost effective solution
• Allows a wide range
of applications
• Extended temperature
range

T&D
FEATURES ADDITIONAL FEATURES (OPTIONS)

SIMPLIFIED INSTALLATION PHASE TO PHASE COUPLING DEVICE

The LMU 5000 is designed to operate with many Phase to phase coupling is carried ou by means of one
different sizes of R.F coaxial cables and with all Hybrid transformer.
different sections of copper bar.

ATTENUATION DEVICE
OUTSTANDING PROTECTION LEVEL
An additional (optional) attenuator is available for short
> Coupling capacitor terminal. lines with low R.F attenuation. It provides an efficient
solution against line reflections and resulting
The connection is protected against any
impedance distortions, based on extensive knowledge
unwanted contact (personnel protection).
and detailed analysis capability

> Grounding switch .


This protection device is used during the unit POWER LINE COUPLING SCHEME
adjustment (commissioning) or testing (maintenance).
For safety reasons, the grounding switch is coupled to Figures 1, 2 and 3 show the usual arrangement for
the door control so that whenever the LMU door is LMU 5000 (coupling to the HV Line) by single phase or
opened a preliminary grounding process is initiated.
multi-phase methods

TUNING & MATCHING TAPS


TECHNICAL CHARACTERISTICS
> Tuning-matching method and tool
Tuning is performed by means of taps. The method
RF CHARACTERISTICS
uses pre-settings specified in tables / abacus graphs
referring to the following values:
> General
• Coupling Capacitor
• Frequency range
• Line impedance
25 kHz - 500 kHz
• Frequency band
• Nominal P.E.P (Peak Envelope Power)
400W
• Coupling mode
• Phase to Ground
• Phase to Phase
Fig. 1 Phase-to-Ground Coupling
• Intercircuit
Phase-to-Earth Coupling • Coupling capacitor
2000 pF to 10000 pF
• Intermodulation: IEC 60481 Compliant
Line-trap Coupling
capacitor

LMU
5000
PLC
System

Fig. 2 Phase-to-Phase Coupling Fig. 3 Line-to-Line Coupling

Phase-to-Phase Coupling Line to Line coupling

Line 1

Line-trap Coupling Coupling


Line-trap
capacitor capacitor

LMU LMU
5000 5000 Line 2
PLC
System Line-trap Coupling
capacitor

LMU LMU
5000 5000
PLC
System

2>3
> Matching & Tuning PROTECTION CHARACTERISTICS
• Nominal Impedance
• Line side > Grounding switch
- impedance 50 Ω to 800 Ω • Short-circuit Current: 200A/permanent
- mode unbalanced
Phase to ground
• PLC Side > Primary Arrester
- impedance 50, 75, 125, 150 Ω • D.C. Spark-over voltage 1kV ±20%
- mode balanced
• Impulse Spark-over voltage (1.2/50 µs)
unbalanced
<2kV
• A.C. discharge current (50 Hz, 1s, 10 times)
> Attenuator option ≤ 20A
• Attenuation 6 dB • Impulse discharge current (8/20 µs): 20kA
• Impedance 50, 75, 125, 150 Ω • Nominal current after striking 30A / 1s
100A / 200ms
• Insulation resistance ≤ 1010 Ω
ENVIRONMENTAL CHARACTERISTICS
at 100V

> Climatic characteristics


> Secondary Arrester
• Protection index: IP 55 (EN 60529)
• Operational range temperature: -45 to +70°C • D.C. Spark-over voltage. 600V
• Relative humidity: 95% at 23°C • Impulse Spark-over voltage (1.2/50 µs)
<2kV
• Storage Temp.: -60 to +70°C
• A.C. discharge current (50 Hz, 1s, 10 times)
• Relative humidity: 100%
>10A
• Impulse discharge current (8/20 µs): >5kA
> Withstand & EMC characteristics
• Basic constraints: IEC 60481 > Drain coil (at temperature range)
• Power frequency insulation (primary-secondary)
• Impedance within 40 kHz to 500 kHz
5kV rms
> 5 kΩ
• Impulse voltage Insulation (primary)
• Impedance at the power frequency
10kV
< 13 Ω

MECHANICAL CHARACTERISTICS

> Cables range

Coaxial-PLC side: from 8mm to 18mm

• Coupling Capacitor
• Connection: bolt and metric threading (M8)
• Cable: Insulated Cable or copper bar.
• Section: 16 mm2 to 25 mm2

• Grounding
• Bolt for Cu cable up to 75 mm2
• Connection: bolt and metric threading (M10)
• Cable: Copper naked cable
• Section of cable: 50 mm2 to 95 mm2

Physical

• Box Metal Stainless steel


UNRIVALLED EXPERTISE

• With this 5th generation of Line Matching Units,


designated LMU 5000, AREVA T&D brings to
Power Line Carrier applications a comprehensive
stand-alone coupling device, backed by unrivaled
experience in facilitating configuration and
installation. The result is an outstanding level of
security for your networks.

WORLD CLASS EXPERTISE

• With AREVA's state of the art Telecom offering,


covering products as well as global solutions,
we bring unrivalled expertise to meet your needs
We have 50 years' experience of designing,
manufacturing and supplying a complete range of
telecommunication equipment. Anywhere in the
world, our experts can provide the solution for all
of your telecom requirements, enabling you
to focus on your core business.

MiCOM is a registered trademerk of AREVA. The other names mentioned, registered or not, are the property of their respective companies. - 389191982 RCS PARIS - SONOVISION-ITEP.
THE NEW INTERFACE
LMU 5000 at a glance
• In the constantly evolving world of power line
>> High safety level
technology, LMU 5000 represents a new

EAI-L3-LMU5000-BR-03.04-0275-GB - ©2004 AREVA . AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
>> High protection level generation for securing telecom networks.

>> Cost effectiveness


>> Compactness
>> Easy installation
>> Extended application range

• SOUTH EAST ASIA


Tel.: +65 67 49 07 77 - Fax: +65 68 41 95 55
• PACIFIC
Tel.: +65 67 49 07 77 - Fax: +65 68 46 17 95
• CHINA
Tel.: +86 10 64 10 62 88 - Fax: +86 10 64 10 62 64
• INDIA
Tel.: +91 44 2431 7100 - Fax: +91 44 2434 1297
• NORTH AMERICA
Tel.: +1 (484) 766-8100 - Fax: +1 (484) 766-8650
• CENTRAL AMERICA
Tel.: +52 55 11 01 10 00 - Fax: +52 55 26 24 04 93
• SOUTH AMERICA
Tel.: +52 55 11 3491 7469 - Fax: +55 11 3491 7476
• FRANCE
Tel.: +33 (0)1 40 89 66 00 - Fax: +33 (0)1 40 89 67 19
• BRITISH ISLES
Tel.: +44 (0) 1785 27 41 08 - Fax: +44 (0) 1785 27 45 74
• NORTHERN EUROPE
Tel.: +49 69 66 32 11 51 - Fax: +49 69 66 32 21 54
• CENTRAL EUROPE & WESTERN ASIA
Tel.: +48 22 850 96 96 - Fax: +48 22 654 55 88
• NEAR & MIDDLE EAST
Tel.: +971-6-556 0559 - Fax: +971-6-556 5133
• MEDITERRANEAN, NORTH & WEST AFRICA
Tel.: +33 (0)1 41 49 88 38 - Fax: +33 (0)1 41 49 24 23
Our policy is one of continuous development. Accordingly
• SOUTHERN & EASTERN AFRICA the design of our products may change at any time.
Tel.: +27 11 82 05 111 - Fax: +27 11 82 05 220 Whilst every effort is made to produce up to date literature,
this brochure should only be regarded as a guide and is
intended for information purposes only. Its contents do not
constitute an offer for sale or advise on the application of
T&D Worldwide Contact Centre any product referred to in it. We cannot be held responsible
for any reliance on any decisions taken on its contents
contact.centre@areva-td.com without specific advice.
www.areva-td.com

You might also like