Fault Ride-Through Capability

• To simulate a 3 phase fault for different durations at the transmission system for different fault
impedances (total of three case studies), and to identify the fault ride-through capability of the
solar photovoltaic inverters’ performance upon fault clearance.

• To verify the AC voltage recovery of the Facility under dynamic conditions according to MGC-
CC 6.4.15.2 (a) voltage pattern.
Reactive Power Requirements

• The facility must be capable of generating reactive power at the interconnection point in
accordance with the performance chart or MW or MVAr or voltage capability limits shown in
figures under section CC6.4.2.1 and CC6.4.2.5, where the operating power factor is at least
0.85 lagging to 0.95 leading at PCC.
Reactive Power Requirements (Cont..)
Frequency Response Capability

• To simulate loss of large load in the system to test the LSS active power output reduction
gradient of 40%/Hz.

• To verify that the LSS will be able to maintain or reduce active power output (MW) when
subjected to large frequency variation based on MGC-CC 6.4.2.3