You are on page 1of 31

CL730S1

Three-phase Split Wired Keypad Prepayment Meter

Technical Manual
Catalogue
1. Use Instruction...............................................................................................................3
1.1 Overview...................................................................................................................3
1.2 Technical Parameters..............................................................................................4
1.3 Meter Operating Principle Block Diagram................................................................7
2. Physical Design.............................................................................................................9
2.1 Meter Construction Diagram....................................................................................9
2.2 Meter Dimension Diagram.....................................................................................10
2.3 Meter Wiring Diagram............................................................................................11
2.4 Meter Protective Class...........................................................................................11
2.5 Resistance to Heat and Fire..................................................................................11
3. Metering Function........................................................................................................12
3.1 Active Energy Metering..........................................................................................12
3.2 Active Direction Definition......................................................................................12
3.3 Max Demand (MD) Calculation..............................................................................12
4. Function Explanation...................................................................................................13
4.1 Metering Function...................................................................................................13
4.2 Load Control Function...........................................................................................13
4.3 Available Days to Use............................................................................................13
4.4 Overdraft Consumption Function...........................................................................13
4.5 Event Log...............................................................................................................13
4.6 Friendly Time Function..........................................................................................15
4.7 Meter LCD Data Display........................................................................................15
4.8 Prepayment Function.............................................................................................16
4.9 IR Communication Function..................................................................................17
4.10 Prompts................................................................................................................18
4.11 Data Item Display Function..................................................................................18
4.12 Indicator Status....................................................................................................23
4.13 Vending System Operation Instruction................................................................23
5. Meter Installation Instruction........................................................................................24
5.1 Cautions on Operation...........................................................................................24
5.2 Tools and Materials Required................................................................................24
5.3 Installation Dimension Figure................................................................................24
5.4 Cautions on Installation.........................................................................................25
6. Transport and Storage.................................................................................................26
7. Warranty......................................................................................................................26
8. Troubleshooting...........................................................................................................26
9. Service.........................................................................................................................26

-I-
Forward
General Safety Rules

CL730S1 Three-phase Split Wired Keypad Prepayment Meter owns advantages of simple
measurement, simple installation and simple operation. But to avoid personal injury and
other products related to the meter, it is suggested that this manual should be carefully
read, which is better for usage before being installed, detected, operated and used.
While the designing and producing of CL730S1 Three-phase Split Wired Keypad
Prepayment Meter, its solidity and reliability and users’ safety and convenience have
been already fully considered. Thus common faulty operations can be endured. If the
meter is reasonably and safely installed and used according to the guideline, its lifespan
will be extended. This product could only be used within its provisions; Our company has
no responsibility for the damage and personal injury caused by faulty operations,
operation and the usage beyond the specific range.

Safety Information

In each chapter of this manual, different letter symbols and graphic symbols which are
adopted to express the danger according to different levels of danger will be
explained. Please pay attention!

Caution!

This sign is to remind of possible danger, which will possibly cause some severe hurt and
damage to people and the equipment.

Attention!

This sign is to remind of possible unexpected situation, which might result in personal
injury, equipment damage and data error.

Safety Rules

1) Pay attention to this product’s rated voltage and maximum current.


2) Pay attention to this product’s measured load capacity.
3) Correct and reliable installation and connection.
4) Pay attention to effective cross-sectional area of wire connection.
5) Do not touch bare wire or use bare wire to connect.
6) Please don’t use this product in explosive environment.
7) Keep the product’s surface clean.
8) Pay attention to meter’s seal management.

1
9) Don’t immerse the meter in water and any chemical substance and don’t use any
chemical substance to clean the meter.
10) Displays are all examples in this manual, which may have some difference from the
real data in meters.
11) Since it is life-threatening to touch live components, the power must be cut off before
installation and replacement.
12) Please obey local safety rules; Installation and replacing of meter only could be done
by qualified person with specified technology.
13) When installing meter, pay attention to meter’s safety; Appearance damaged or fell
downed meters are not allowed to install.
14) Washing the meter by water is not allowed.
15) The Clou Standard applies to production and test in Clou Electronics, not the
standard for client test or acceptance. Only IEC standards apply to the client
inspection and acceptance.

COPYRIGHT NOTICE:

Sustainable product improvement is a policy of our company. Therefore, the company


reserves rights to change product operational details and specification. Contents of this
manual may be changed without special notification. Without permission in writing from
our company, any part of the manual cannot be reproduced or spreaded in any form or by
any means for any purpose by any individuals or other companies

2
1. Use Instruction
1.1 Overview
1.1.1. Construction Profile

Three-phase Split Keypad Prepayment Meter


1.1.2. Major application
CL730S1 Three-phase Split Wired Keypad Prepayment Meter takes digital medium as
information exchange media. It is an active electric energy meter in which users load in pre-
purchased electricity amount, and it takes electricity amount as its billing. It also has numeric
keypad interface, can realize the functions of active power measuring and prepayment control.
MCU and UIU communicate via current loop. MCU includes measurement unit, real-time clock
unit, load switch, IR communication and RS485 communication functions and other auxiliary
equipments, while the UIU includes numeric keypad interface and display.
1.1.3. Additional Functions

1) Reverse consumption measured as forward consumption.


2) Demand calculating.
3) Realizing users’ load detecting and controlling.

1.1.4. Main Functions


4) When available credit is 0, the meter can send out power off signal to control load for auto
switching off, and it shall auto restore the power supply after the new purchased power
amount is loaded.
5) Function of auto detection.
6) Function of recording event of cover open, phase off and power off etc.(see 4.5 Event
Log)

1.1.5. Main Features


1) The meter can realize paying first and using later.
2) CL730S1 Three-phase Split Wired Keypad Prepayment Meter takes electricity as its
electricity billing; Electricity users purchase electricity first, and meter subtracts available
credit. When available credit is 0, meter will send power off signal to control load switch
automatically cut off.
3) CL730S1 Three-phase Split Wired Keypad Prepayment Meter adopts STS algorithm (NRS
009-6-7, NRS 009-6-8 and NRS 009-6-9), which has a set of security management
system and owns a high level security and is completely compatible with the other STS
standard systems.
1.1.6. Normative references
1) IEC62052-11 Electricity metering equipment (A.C)-General requirements tests and test
conditions- Part11: Metering equipment.
2) IEC62053-21 Electricity metering equipment (A.C)-Particular requirements-Part21: Static
meters for active energy (classes 1 and 2).
3) IEC62055-31 Electricity metering -Payment systems-Part31: Particular requirements
Static payment meters for active energy (class 1 and 2).
4) IEC62055-41 Electricity metering-Payment systems-Part 41: Standard transfer
specification (STS) - Application layer protocol for one - way token carrier systems.
5) IEC62055-51 Electricity metering-Payment systems-Part51: Standard transfer
specification (STS)-Physical layer protocol for one-way numeric and magnetic card token
carriers.
1.2Technical Parameters
1.2.1 Meter operating voltage

1) Meter rated voltage Un 3 x 240/415V


2) Operating voltage range 60% Un ~110% Un
3) Limit range of operating voltage:
0Un—1.90Un
Within this range, the meter will not be damaged; it will indicate normally, but it’s not
guaranteed that the accuracy class as well as load control equipment’s normal operation. After
operating voltage turn to normal again,
meter will work normally and its
metering accuracy class will remain
unchanged.
1.2.2 Meter current parameters
1) Imax 100A
2) Meter starting current (0.4%Ib) 20mA
3) Meter metering current range 20mA ~ 100A
4) Common current specification 5(100)A

1.2.3 Meter frequency parameters


1) Rated frequency fn 50Hz
2) Frequency application range 95% fn—105% fn

1.2.4 Self- power consumption of meter


1) Power consumption of voltage
circuit <1.5W 8VA
2) Power consumption of current
circuit <4VA
1.2.5 Meter active metering accuracy
CL730S1 Three-phase Split Wired Keypad Prepayment Meter’s active measurement accuracy
conforms to IEC62053-21 class 1.
CL730S1 Three-phase Split Wired Keypad Prepayment Meter --- Active power class 1
percentage error limit.
Error limit in percentage
Load value PF
IEC62053-21 Clou Standard
1.2.6 Display Mode
0.05Ib^I<0.10 Ib 1 ±1.5 ±0.7
The meter displays numeric.
1) 0.10Ib^I<Imax
Display mode 1 ±1.0
LCD display of wide-temperature±0.5
range 8
2) Character digits for data item display
decimals digits including 6 integers and 2
0.5L ±1.5 ±0.7
3) 0.1Ib^I<
Character 0.2Ib
display dimension ±10.00*5.00mm 2 digits
0.8C ±1.5 ±0.7
4) Character digits for data ID display
0.5L ±1.5 ±0.5
1.2.70.2Ib^I^Imax
Meter Pulse Constant 400imp/kWh
1) Active pulse constant 0.8C 400imp/kvarh
±1.5 ±0.5
2) Reactive pulse constant
1.2.8 Meter Active Check
TableOutput
1 1: Meter active metering accuracy
The meter is equipped with special pulse indicator for testing active energy (LED is on the
nameplate of meter). In order to ensure the accuracy of active measuring test, according
to different current test points, pulse quantity collected from test should be incremented
with the increase of current, and reasonably select pulses between the numbers 1~8.
1.2.9 Meter serial communication interface
Interface 1:
1) Type
Serial bi-direction communication
2) Baud rate
interface 2400bps
3) Application
Meter metering data reading and related data items
4) Pattern
conf. Non-modulated IR communication
Interface 2:
1) Type
Two-wire current loop communication
2) Baud rate
interface 1200bps
3) Application Communication port between MCU and UIU
4) Pattern Current loop communication
Interface 3:
1) Type Serial bi-direction communication interface
2) Baud rate 2400bps
3) Application Measuring data reading and related
data item configuration
4) Pattern RS485 communication
1.2.10 Meter EMC

Requirements
No. Item of Clou Standard
IEC62052-11
Contact 8KV 10KV
Electrostatic
discharge
1 Discharge
Immunity Air 15KV 18KV
discharge
HF 80MHz-2GHz 80MHz-2GHz
2 electromagnetic 30V/m 30V/m
field immunity

3 4KV/100KHz 4.3KV/100KHz
Fast transient burst
Equipment of Equipment of
Radio CISPR 22 class B CISPR 22 class B
4
interference test

Immunity to
conducted 150kHz - 80MHz 150kHz-80MHz
5 disturbances, 10V 10V
induced by radio-
frequency fields
6 Surge immunity 4KV 4.3KV
Table 12: EMC

1.2.11 Meter application environment


No.
Item Requirements of
IEC62052-11 Clou Standard
-25°C~55°C -25°C~70°C
Operation
temperature
range

1 Temperature Limit range of -40°C~70°C -40°C~70°C


operation
-40C-70C -40°C~70°C
Limit range for
storage and
transport
2 Humidity Annual mean <75% <75%
<95% <95%
For 30 days, these
days being spread
in a natural
manner over one
year
Occasionally on <85% 6 <85%
other days
Table 13: Application environment

1.2.12 Meter insulation test

No. Item Requirements of


IEC62052-11 Clou Standard
Insulation class II 6KV 6.5KV
1 Impulse
voltage
4KV (5mA) 4.1KV (5mA)
Between current
AC circuit and the earth
2
voltage (insulation class II)
Between auxiliary 2KV (5mA) 2.5KV (5mA)
terminals
Table 14: Insulation test

1.3Meter Operating Principle Block Diagram


This MCU circuit consists of measurement and control circuit modules centralized with
SOC single chip (with internal measurement module, realtime clock and temperature
testing compensation circuit etc.), memory circuit module composed of memory chip,
current loop communication circuit module, power supply circuit module, cover open
detection module, LCD display, audio reminding user information display module, IR
emission and IR receiving circuit module etc. the current sampling uses measurement
method of CT sampling, while voltage sampling uses dividing resistance network, and
meter adjustment is completed via software.
UIU consists of push button module centralized of SOC single chip, LCD display and
audio indicating user information display module.

7
8
2. Physical Design
2.1 Meter Construction Diagram
* MCU diagram:

1 LCD display 6 Tamper alarm LED 11 Terminal cover

Reactive pulse indication


2 Cover 7 12 Hookerplate
LED
Active pulse indication
3 IR communication port 8 LED

4 Base 9 Slica gel button

5 Low-energy alarm LED 10 Cover sealing screw


* UIU diagram:

12

oo
______o a______*

9
1 LCD display 7 Seal piston

Slica gel button Current loop


2 8 communication port
Current loop
3 Cover 9 communication indication
LED
4 Base 10 Tamper alarm LED

5 Hookerplate 11 Low-energy alarm LED

6 Battery cover

1
0
2.2Meter Dimension
Diagram * MCU dimension

o
CL
CL
Ci
CL

Cc

153

Outline dimension: 270.00mm x 170.00mm x 74.00mm

UIU dimension diagram:

E
xi m (M w
TI m m c IJ It
ooo 8
i

Outline dimension: 150.00mmx85.00mmx34.00mm

diagram:

1
1
2.3Meter Wiring Diagram
All movable terminals of meter locate in the connection terminal cover with secured screws
fitted with user seal to prevent from operations such as unauthorized connection or other
settings, etc.

2.4Meter Protective Class


The test is carried out with the prepayment energy meter in accordance with IEC60529-4. The
test results are shown as follows: IP 54.

2.5 Resistance to Heat and Fire


Resistance to heat and fire class: V0 (all the casing made out of heat-resistant and fire-
retardant material)

1
2
3. Metering Function
CL730S1 Three-phase Split Wired Keypad Prepayment Meter can measure reverse power in
the same way of measuring forward power and the energy can be accumulated in total active
energy and active energy of each settlement month. It can measure total active power and
store the data and calculate the available credit then store the data; meanwhile have them
indicated by LED. The meter measures real-time power by pulse constant and pulse interval.

3.1Active Energy Metering


Active energy: kWh
1) Three-phase energy meter metering phasor diagram in right connection
Active power expressed as:

Reactive power expressed as: iL

Active energy expressed as:


dt

Reactive energy expressed as:

3.2Active Direction Definition

P =P1+P2+P3=Ua4cospa+ Ub/bcos<Pb+ UJccosyc Q =Q1+Q2+Q3 =Ua/asin<Pa+

Ub4sin<Pb+ UJc sin^c


Ep =fPdt=f (Ua/acos%+ Ub4cos<Pb+ Uc/ccosyc)

Eq =/Qdt=/ (Ua/asin^a+ Ub/bsin%+ UJcsinyc) dt

The CL730S1 meter uses the conception of forward power and reverse power from the
customers’ point of view.
1) Customers’ forward power =power suppliers’ sending power.
2) Customers’ reverse power =power suppliers’ received power.
3.3Max Demand (MD) Calculation
1) Active maximum demand unit: kW.
2) Active MD calculation method is slip calculation method.
3) MD calculation cycle is 15min.
4) MD slip window time: 1 minute.

1
3
4. Function Explanation
4.1 Metering Function
1) To meter total active power consumption.
2) Demand is programmable for slip method.
a) Demand calculation cycle is 15min.
b) Demand slip window time: 1 minute.
4.2Load Control Function
1) The meter can be programmed for load control threshold;
2) In the event that current power > user load threshold (the load threshold can be viewed by
inputting 13 on meter and pushing Enter key), the overload alert will be triggered. If alert
status goes for a specified time of 30s by default, meter will cut off user load; and will add
1 to count of overload power off times. if overload trip times goes < 4 times within half an
hour, the meter shall trip for each overload and get relay auto closed in 2min after each
trip; if overload trip times goes ^4 times within half an hour, meter will trip and get relay
auto closed in 30min; When load threshold is 0, this function will be disabled.
3) When meter is powered off constantly for overload, customers can apply for enlarging
capacity and then input the number of enlarging capacity to recover power supply.

4.3Available Days to Use


When available credit in meter can be used for<1.5days, low-energy alert indicator shall blink
in red; when 1.5days < days to use<3days, alert indicator will keep lighting in red; when 3
days< days to use<7days, alert indicator will keep lighting in yellow; when days to use >
7days, alert indicator will keep lighting in green; (available days=available energy/24/A; (A is
demand in last month, if demand in last month is 0, A shall be demand of current month; if
demand in current month is also 0, A shall be load threshold, if load threshold is 0, A shall be
69kW by default; when available energy is greater than 10000kWh, the available days shall be
1000d by default, if the available days calculated is over 1000d, the meter shall display 1000d
by default for available days), view the available days to use by pushing 05 and Enter.

4.4Overdraft Consumption Function


1) User overdraft threshold can be programmed.
2) When overdraft energy is not equal to o, the meter shall start overdraft consumption
function, when energy balance is 0, load switch shall cut off, pushing any key on MCU or
inputting 00 on UIU and pushing Enter will have power supply restored. When overdraft
consumption is used up, load switch shall auto cut off, pushing any key on MCU or
inputting 00 on UIU and pushing Enter will not have relay reclosed, unless recharge.
3) When overdraft threshold is 0, this function shall be disabled.
4.5Event Log
1) Power off event log
In case meter powers off and gets energized again, it will add 1 to the No. of power off times.
Up to 399 times for power off and time records of last 5 power off events.
2) Terminal cover-opening detection and record
When meter terminal cover is opened, meter will send out power off signal to control load
switch auto cut off power supply and meter will add 1 to No. of times for terminal coveropening
and up to 399 terminal cover-opening events and last 5 terminal cover-opening events time
can be recorded. In that case, the power shall power supply cannot be restored even if put the

1
4
meter cover and terminal cover in place, but only inputting special token (not any other token)
by Utility can get the power supply restored in condition of both covers in place. Meter can
detect terminal cover-opening event at power off.
3) Cover-opening detection and record
When meter cover is opened, meter will send out power off signal to control load switch auto
cut off power supply and meter will add 1 to No. of times for cover-opening and up to 399
cover-opening events and last 5 cover-opening events time can be recorded. In that case, the
power shall power supply cannot be restored even if put the meter cover and terminal cover in
place, but only inputting special token (not any other token) by Utility can get the power supply
restored in condition of both covers in place. Meter can detect cover-opening event at power
off.
4) Phase off event log
In case meter detects some phase voltage meets requirement of phase off and the situation
continues for certain time, it will add 1 to the No. of phase off times. Meter will display the
failure phase, if phase A, meter will display L1. Up to 399 times for phase off and time records
of last 5 phase off events.
5) Overload trip event log
When meter overload alarm passes duration specified, meter will send out power off signal to
control load switch auto cut off power supply, meter will add 1 to No. of overload trip times. Up
to 99 overload events and last 5 overload time records can be recorded.
6) Power purchase event log
The meter can record last 10 valid tokens and last 10 power purchase amount record.
7) Over-current event
When meter detects the three phases current get greater than over-current threshold
simultaneously (120A by default, the over-current threshold can be viewed by pushing 106
and Enter key) for 10s, meter will trip; the power supply shall auto get restored in 5min; in this
event, meter will add 1 to event counter, and up to 399 events and last 5 event time stamps
can be recorded.
8) Reverse event
When meter detects reverse consumption keeps for 30s, meter will send out power off signal
to control load switch auto cut off power supply, meanwhile the alert LED will keep lighting in
red. meter will add 1 to No. of times for reverse count and up to 399 reverse events and last 5
reverse events time can be recorded. In that case, the power shall power supply cannot be
restored unless inputting special token (not any other token) by Utility.
9) Voltage sequence reverse
When meter detects voltage sequence reverses (if phase off event present, no voltage
sequence event will be determined) for 60s, alert LED will blink in red, meter will add 1 to
voltage sequence reverse times count, up to 399 voltage sequence reverse events and last 5
voltage sequence reverse time can be recorded.
10) Load unbalance event
When meter detects the max. phase power is greater than the min. phase power by
12.5% (if some phase is 0, no load unbalance event will be determined) for 30s, alert
LED will blink in red, meter will add 1 to load unbalance event counter, and up to 399
events and last 5 event time stamps can be recorded.
Note:
1) To have power supply restored at relay trip shall meet requirement of voltage normal,
wiring correct, meter cover and terminal cover in place and energy balance non-zero.

1
5
2) If meter detects the three phases voltage get too low simultaneously, relay action will be
impacted.
4.6 Friendly Time Function
1) During public holidays and weekends ( public holiday and weekend status word can be
set by software), if available energy decreases to 0, meter will not trip (unless
terminal/meter cover-open event, reverse event or over-current event present);
2) At night (17:00~23:59 by default, settable by software), it is non-power-outage time, if
during night the available energy decreases to 0, meter will not trip (unless terminal/meter
cover-open event, reverse event or over-current event present);

3) In friendly period, meter LCD will display smile icon.


4.7Meter LCD Data Display

Item Introduction

Power purchase token is correct and


Accept accepted and "accept” is displayed.

Power purchase token is wrong and


rejected and "reject” is displayed.

Reject
When "old” is displayed, it means token is
Old expired.

When "used” is displayed, it means the


Used token is a used one.

1
6
Overload consumption—When
consumption load is over the load threshold
specified, “over po” will be displayed and

uuEr Pq the power will be cut off within specified


time.
n i
U 1 Enter 01 and push Enter key, the
consumed amount 100.00kWh and the
kWh corresponding code 01 are displayed.
innnn
• I
a? Enter 02 and push Enter key, MD 2.00kW
kW in current month and MD in current month
inn code 02 are displayed.

i LUU
n i Enter 07 and push Enter key, the energy
U 1 balance 100.00kWh and energy balance
code 07 are displayed.
kWh
innnn
31 Enter 31 and push Enter key, the realtime
kW power 1.00kW and real-time display code
inn 31 are displayed.

i
Table 4 1: LCD Data Display

4.8Prepayment Function
The Power Sales Management System will produce a 20 digits code (generated based on
user’s information and purchase amount). After the user input this code via the meter’s
keypad, meter will decrypt the code. After passing the encryption authentification, current
purchase amount will be written into meter’s memory and added to the available credit and
stored; When abnormal consumption happens, the abnormal consumption amount will be
deducted from the purchase amount and the new available credit will be stored in memory;
When the user is consuming power, the meter will deduct the available credit gradually
according to corresponding conditions. When the power-off condition is met, meter will cut off
power supply and when power supply condition is met, meter will connect to user load
automatically.

4.8.1 Open an account


Opening an account is necessary after the key system of meter is changed and user
information registration is completed. Opening an account can give user a number and

1
7
appointed ID in order to correspond one meter with one user. At the same time, initial
purchasing power, the key and other parameters can also be written into meter.
Meter ID display: Input “65” and then push Enter key, meter will display ID in 11 digits in 2
pages.

4.8.2 Purchase power


When the available credit in meter is insufficient, the customer can visit the power vending
office to purchase electricity. At vending office a 20 digits serial number (TOKEN) will be
produced based on user information and purchase amount.
Power purchase method:
1) Visit the local power vending office.
2) Provide your meter ID to the operator.
3) Inform the operator the amount you want to buy and pay the bill.
4) Obtain a 20-digits token printed on your receipt.

4.8.3 Load power


User will input the 20-digits serial number via meter’s keypad. After passing key
authentification, meter will accept purchase amount and adjust the available credit and
cumulative purchase amount and then save the new available credit in EEPROM. At the same
time power amount loaded this time will also be displayed on LCD.
1) Key in the 20-digits token via keypad.
2) Confirm the numbers on LCD.
3) If token is wrongly input, please use backspace to modify.
4) After inputting all the 20 digits, push Enter to confirm the token input.
5) If token is correctly input, LCD will display “accept” and the power amount purchased.
6) If token is wrongly input, LCD will display “reject”.
4.9IR Communication Function
The meter equips with non-modulated IR optical communication interface and RS485
interface. With the HHU with serial communication port, the meter can realize time
synchronization and read meter data items and other functions.

4.9.1 Time synchronization

The meter can carry out time synchronization via communication interface.

4.9.2 Read meter data item


Via communication interface, it is available to read data items in meter, including current
consumption data, credit balance, meter clock, previous 12 months consumption data, all
kinds of meter data items and log data.

1
8
4.10
8)
1)
4.11
Prompts
13)Err_08:
Err_03:
ACCEPT:
10 o O to
Appointed
Key change
TOKEN
Data Item Display
9) Err_04:
23 45678 9
function found L
error not Li
accepted
Function
Energy overflow Key
VAkWh°CkVarh 15
3
OI J U U U U U U U L
2) REJECT:
0 0 0 0 0 0 020
TOKEN rejected
4.11.1
3) OLD: LCD Display Instruction
TOKEN expired 14
10)
Firstly
4) USED:
Err
do 11
initialization
type error Token data
to LCD after
TOKEN usedpower on, LCD fully displays and automatically enter
the
5) set
_05:
6) Err_01:
MCU:
7) Err_02:
OtO
OK:display mode ofSuccessful
Manufacture
Token type
code error
13
power information after 4 seconds. LCD full screen are as follows:
format erroroperation

11) Err -------------—


Key expired
error K>S>

_06:

12) Err

_07:

1
9
1 Display code 2 Reverse tag 3 Phase A tag
Phase B tag 5 Voltage tag 6 Phase C tag
4
7 Active unit tag 8 Cry face 9 Smile tag (time friendly
tag)

10 Relay state tag 11 Energy bar tag 12 Current tag

13 Display content 14 Reactive unit tag 15 Temperature alarm tag

1 356 711
0010 _
UIU:
U U I LJVAVwh
L2L Li 1
3 2
8 °CWarh 1
I00000000 0
EOOQQ.OQ.Q.Q 9

2
0
1 Display code 2 Voltage tag 3 Phase A tag

4 Current tag 5 Phase B tag 6 Phase C tag

7 Relay state tag 8 Energy bar tag 9 Display content

10 Reactive unit tag 11 Reverse tag 12 Temperature alarm tag

13 Active unit tag

1) Data indication: 6 digit of integer and 2 digits of decimal. Power unit is kWh; Active power
unit is kW.
2) Display code: With 2 digits code to indicate respective data item (please see 4.11.3 Meter
data item code).
4.11.2 Meter data display
Display content includes consumption data, configuration data, and history data and so on.
1) For data item length over 8 digits (e.g. date & time and meter No. etc.), meter will display
in two pages.
2) For credit balance, the data item can be used to indicate the specific value; meanwhile bar
can be displayed on LCD screen.
Credit balance in meter<30kWh, no bar displays;
30kWh<credit balance<60kWh, the first bar displays;

2
1
60kWh<credit balance<90kWh, the first 2 bars display;
90kWh<credit balance<120kWh, the first 3 bars display;

270kWh<credit balance, all 9 bars display.


In a similar way, when the credit balance decreases, the corresponding bar will turn
off.
4.11.3 Meter data item code table
For display code of 2 digits, the corresponding content can be viewed by inputting the
related 2-digit code and pushing Enter key, e.g. for data of item 07, the code and item
data shall be displayed by inputting 07 and pushing Enter key; for display code of 3 digits,
the corresponding content can be viewed by inputting the related 3-digit code and
pushing Enter key on meter, e.g. for data of item 100, the display code A0 and data shall
be displayed by inputting 100 and pushing Enter key; item 100~109 corresponds to code
A0~A9 on meter; 110~119 item corresponds to b0~b9; 120~129 item corresponds to

C0~C9; 130~139 item corresponds to d0~d9; 140~143 em corresponds to E0~E3.


il
Display Data Item Name Display Data Item Name
No. No.
01 Current total consumption 73 Current date
MCU reserved/UIU hardware version
02 MD in current month 74
No.
Occurrence time of MD in MCU reserved/UIU software version
03 current month 75 No.

04 Reserved 76 Last power purchase TOKEN


Last 2nd power purchase TOKEN
05 Available days to use 77

06 Total energy purchased 78 Last 3rd power purchase TOKEN

07 Credit balance 79
Last 4th power purchase TOKEN

08 Reserved 80 Last 5th power purchase TOKEN

Reactive consumption in current Last 6th power purchase TOKEN


09 month 81

10 Total reactive consumption 82 Last 7th power purchase TOKEN

11 Last credit charging time 83 Last 8th power purchase TOKEN

12 Reserved 84 Last 9th power purchase TOKEN

13 Load threshold 85
Last 10th power purchase TOKEN
14 Demand in last month 86 Last energy purchase amount

15 Overdraft energy threshold 87 Last 2nd energy purchase amount


Display Data Item Name Display Data Item Name
No. No.
16 Overload delay outage time 88 Last 3rd energy purchase amount

Last 4th energy purchase amount


17 Transfer time 89

18 90
Consumption in current month Last 5th energy purchase amount

19 Consumption in last month 91


Last 6th energy purchase amount

20 92
Consumption in last 2nd month Last 7th energy purchase amount

21 Consumption in last 3rd month 93 Last 8th energy purchase amount

22 Consumption in last 4th month 94 Last 9th energy purchase amount

23 Consumption in last 5th month 95


Last 10th energy purchase amount
24 Consumption in last 6th month 96 A phase present voltage
25 Consumption in last 7th month 97 B phase present voltage
26 Consumption in last 8th month 98 C phase present voltage

27 Consumption in last 9th month 99 A phase present current

28 Consumption in last 10th month 100 B phase present current

29 Consumption in last 11th month 101 C phase present current

30 Consumption in last 12th month 102 A phase present PF

31 Real-time power 103 B phase present PF


32 Demand calculation method 104 C phase present PF
33 Demand calculation cycle 105 Frequency
34 Slip window time 106 Over-current threshold

35 Key revision No. 107 Over-current times


36 Tariff index 108 Last over-current time

37 Alarm duration 109 Last 2nd over-current time


38 Arrear tag 110 Last 3rd over-current time
39 Reserved 111 Last 4th over-current time
40 Cover open times 112 Last 5th over-current time

41 Last cover open time 113 Reverse times


42 Last 2nd cover open time 114 Last reverse time
43 Last 3rd cover open time 115 Last 2nd reverse time
Display Data Item Name Display Data Item Name
No. No.
44 Last 4th cover open time 116 Last 3rd reverse time

45 Last 5th cover open time 117 Last 4th reverse time
46 Overload power off times 118 Last 5th reverse time
Voltage sequence reverse times
47 Last overload time 119

48 Last 2nd overload time 120 Last voltage sequence reverse time

Last 2nd voltage sequence reverse


49 Last 3rd overload time 121
time
Last 3rd voltage sequence reverse
50 Last 4th overload time 122
time

51 Last 5th overload time 123 Last 4th voltage sequence reverse
time

52 Power off times 124 Last 5th voltage sequence reverse


time
53 Last power off time 125 Load unbalance times
54 Last 2nd power off time 126 Last load unbalance time

55 Last 3rd power off time 127 Last 2nd load unbalance time
56 Last 4th power off time 128 Last 3rd load unbalance time

57 Last 5th power off time 129 Last 4th load unbalance time
58 Phase off times 130 Last 5th load unbalance time
59 Last phase off time 131 Cover-open times
60 Last 2nd phase off time 132 Last cover-open time
61 Last 3rd phase off time 133 Last 2nd cover-open time
62 Last 4th phase off time 134 Last 3rd cover-open time

63 Last 5th phase off time 135 Last 4th cover-open time
64 Current tariff No. 136 Last 5th cover-open time
65 Meter ID No. 137 Consumption in last day
66 Active meter constant 138 Consumption in last 2nd day

67 Hardware version 139 Consumption in last 3rd day


68 Software version 140 Consumption in last 4th day

69 Reactive meter constant 141 Consumption in last 5th day


70 SGC 142 Consumption in last 6th day
0 User mode/1 Factory
71 mode 143 Consumption in last 7th day

72 Current time 00 MCU adjustment tag/UIU display OK

Table 4 2: data item code table


Meter ex-factory display item:
UIU:
S/N Display No. Data Item Name
1 01 Total consumption

2 02 MD in current month
3 07 Available amount
4 31 Realtime power

4.12 Indicator Status


1) MCU indicator status:

Pulse indicator:blue, blinks during consumption.

Alert indicator: ® blinks once a time in red in case of no tamper and meter error present.
© blinks twice a time in red during meter error.
© blinks trice a time in red at tamper.
Low-energy indicator: when days to use^1.5days, low-energy indicator will blink in red
once a time; 1.5days<days to use<3days, alert indicator will keep lighting in red; when 3
days<days to use<7days, alert indicator will keep lighting in yellow; when days to use>
7days, alert indicator will keep lighting in green.
When available energy is 0 or negative quantity, the low-energy
indicator shall blink at frequency 4 times a time.
2) UIU indicator status:
Communication indicator: red, blinks during communication.

Alert indicator: ® blinks once a time in red in case of no tamper and meter error present.

© blinks twice a time in red during meter error.

© blinks trice a time in red at tamper.


Low-energy indicator: when days to use^1.5days, low-energy indicator will blink in red
once a time; when 1.5days<days to use<3days, alert indicator will keep lighting in red;
when 3 days<days to use<7days, alert indicator will keep lighting in yellow; when days
to use>7days, alert indicator will keep lighting in green.
When available energy is 0 or negative quantity, the low-energy
indicator shall blink at frequency 4 times a time.

4.13 Vending System Operation Instruction


Details please refer to "Keypad Prepayment Energy Meter- Technical Manual of Power
Vending System”.
5. Meter Installation Instruction
5.1 Cautions on Operation
The installation and commission operator of energy meter must be technically qualified as
below:
1) Trained with relevant technical training.
2) Be familiar with and comply with safety regulations, strictly comply with specific
regulation of safety.
3) Please see if the required materials and tools are all prepared before starting
operation (see 5.2 "Tools and Materials required”).
5.2Tools and Materials Required
The following tools and materials are necessary for installing the meter:
1) The energy meter preset correctly (already opened an account) and sealed well.
2) Customers’ information chart of energy meter.
3) Screws to fix energy meter.
4) Seal and seal tools provided by the Utility.
5) Slotted screwdriver and cross screwdriver which are used to secure screw.
6) Drilling tools (if it is needed) and multi-meter.

5.3Installation Dimension Figure


MCU module installation dimension figure:

Height 200.00 (210.00 )(220.00) mm

Width 153mm

UIU module installation dimension figure:


o 60
o
in

aa

Installation dimension: 60.00mm*57.5.00mm

5.4Cautions on Installation
1) Before wiring, please carefully check the connection diagram on meter case and
confirm the phase line, and neutral line (ground wire) consistent with connection
diagram. It is better to use copper wire and copper contact to connect to meter.
2) If the cable is old, operator shall cut the end of cable to ensure the new exposed wire
end is about 15mm long to be used to connect; if cable diameter is between 3mm
and 6.5mm, directly connect to inside of terminal and make sure it secured; if cable
diameter is less than 3mm, then it is necessary to use a suitable size copper or
aluminum bushing to clamp cable end so as to avoid loose contact of connection
resulting in terminal burnout.
3) During wire-connection, firstly loosen each screw on each terminal, then insert In-
phase line into end of connection aperture and the in-neutral line into end of
connection aperture, fully tighten screws of terminals. Similarly insert Out-phase line
into end of connection aperture. Tighten screws of terminals fully and make them
secured.
4) Power on energy meter to test the working condition, if energy meter works normally,
record readings of meter. Otherwise, please carefully test condition of installation and
connection and working voltage.
5) Be gentle with the energy meter so as to avoid dropping and collision during whole
installation processes.
6) When installing energy meter, please be careful with operation and power usage
safety so as to avoid accident.
6. Transport and Storage
1) The product shall be transported and stored according to the related rules. No intense
impact to the product is allowable during transportation and unpacking.
2) The product shall be stored in a clean place where the ventilation is good, the ambient
temperature is -25°C—70°C, and the relative humidity is not more than 75%, and
make sure no corrosive gas or harmful material present and the natural ventilation is
good.
3) The product shall be stored on shelf in a warehouse and the stacking height shall not
be more than 8 layers.

7. Warranty
The manufacturer warrants its products against defective parts and workmanship and will
repair or (at its option) replace, free of charge, any meter which is or may become
defective under proper operation with all seals in good condition within the warranty period
specified in contract from date of sales.

8. Troubleshooting
The meter features self-test. If the following information is found on the LCD, or the selftest
information displayed on LCD is abnormal (e.g. character missing or character incomplete
etc.), contact the manufacturer for advice.

FAULT ACTION

When LCD display in full screen, some


symbols occurs lack of stroke, unclear or When LCD display is abnormal, it is needed
energy indicator flashes, but LCD is without to ask meter manufacturer or local agent to
display. change LCD.

1. Check whether wire connection is correct


LCD does not display, and energy pulse or not.
indicator does not flash.
2. Check whether voltage is under
operating range.

LCD display is normal, energy pulse does 1. Check whether wire connection is correct
not flash during power usage. or not.
2.Power usage amount is less than 0.4%Ib.

9. Service
SHENZHEN CLOU ELECTRONICS CO., LTD. guarantees to provide a lifetime service
with the meters and the related devices made in our company. In product distribution
areas, there are offices and or agents accompanying with customer service center
responsible for providing customers with product consultation and maintenance service
etc.