Professional Documents
Culture Documents
PowerFactory
1 August 2016
8/4/2016
Indonesia Clean Energy Development 1
SESSION 1
• Install PF
8/4/2016 2
INSTALL PF
• Create a project
• Basic concepts of DIgSILENT
• Create a 2-bus model
• Run load flow
• Scenario
• Basic function buttons
8/4/2016 4
CREATE A PROJECT
• Objective: Set nominal frequency, project settings, base
MVA, deactivate – activate project
8/4/2016 5
CREATE A PROJECT
PLNExample1
8/4/2016 6
CREATE A PROJECT
8/4/2016 7
BASIC CONCEPTS OF DIgSILENT
• Element types:
– Template with specifications that several elements of the type will
use
– Example: If a grid has five 25 MW generators from the same
manufacturer, we would define one generator type. All give
generators would use this type
• Database
– Everything about the project is saved in a DB
• Visual representation
– Separate from DB. For example, we could have entire network
defined in DB, but cannot see. Visual representation is needed only
to see the network
8/4/2016 8
CREATE A SIMPLE MODEL: EXERCISE 1
• Objective: Draw bus, draw gen, create gen type, draw a transmission
line, create a TL type, draw a transformer global, create transformer
type, draw load, reference generator
8/4/2016 9
CREATE A SIMPLE MODEL
CREATE A BUSBAR
8/4/2016 10
CREATE A SIMPLE MODEL
CREATE A BUSBAR TYPE
• Each bus element has a busbar type with nominal voltage of the bus.
• A busbar type can be used for multiple bus with same specification.
8/4/2016 11
CREATE A SIMPLE MODEL
CREATE A GENERATOR
8/4/2016 12
CREATE A SIMPLE MODEL
CREATE A GENERATOR TYPE
• Basic data used to define the nominal rating parameters
• Detail specifications like Xd, X’, X’’, H and so on can be specified in
RMS-Simulation tab
8/4/2016 13
CREATE A SIMPLE MODEL
CREATE A GENERATOR TYPE
8/4/2016 14
CREATE A SIMPLE MODEL
DISPATCH A GENERATOR
8/4/2016 15
CREATE A SIMPLE MODEL
WHAT IS A REFERENCE GENERATOR?
• In load flow, the generator used to balance the active power and
reactive power is called reference generator.
• It can either supply or absorb active and reactive power into or from
the system.
• Example:
– 3 generators in the grid, one is reference
– For 2 generators, dispatch is specified
– PF computes output of reference generator, based on loads and
losses
8/4/2016 16
CREATE A SIMPLE MODEL
CREATE A TRANSFORMER
8/4/2016 17
CREATE A SIMPLE MODEL
CREATE A TRANSFORMER TYPE
8/4/2016 18
CREATE A SIMPLE MODEL
CREATE A TRANSMISSION LINE
8/4/2016 19
CREATE A SIMPLE MODEL
CREATE A TRANSMISSION LINE TYPE
8/4/2016 20
CREATE A SIMPLE MODEL
CREATE A LOAD
8/4/2016 21
CREATE A SIMPLE MODEL
COMPLETE MODEL
8/4/2016 22
RUN LOAD FLOW
• Objectives:
– Run load flow
– Show result box
– Current, bus voltage,
active power,
reactive power, -ve
& +ve numbers for
gens, -ve & +ve for
other elements)
– Change result box.
– Output calculation
8/4/2016 23
RESULT BOX AND LOAD FLOW REPORT
• Result box on Buses – can display voltage in kV and p.u.
8/4/2016 24
RESULT BOX AND LOAD FLOW REPORT
• Result box on Load and Generator - displays active & reactive power
and current
8/4/2016 25
LOAD FLOW REPORT
• Output -> Output Calculation Analysis
• Different load flows report can be created
8/4/2016 26
ANALYSIS OF LFA RESULTS
8/4/2016 27
SCENARIOS
• Scenarios are used to define different conditions of a grid.
• It could be high/low wind, wet/dry season, high/low load.
• A scenario is created File > Save Operation Scenario As..
8/4/2016 28
ACTIVATE-DEACTIVATE SCENARIOS
• Scenarios are activated and deactivated in two ways:
– File > Activate/Deactivate Operation Scenario
– Right click on the scenario > Activate/Deactivate
8/4/2016 29
BASIC FUNCTION BUTTONS
• Zoom-in
• Switch on-off elements
• Connect-disconnect
• Select multiple elements
• Undo
• Element listing window
8/4/2016 30
SESSION 3
8/4/2016 31
Power/Load Flow Analysis
8/4/2016 32
EXERCISE 2
• Objectives: Create a 3–bus model, create type for all elements,
balance dispatch sheet, run load flow, solve issues observed in load flow,
short-circuit analysis.
• SCPR = 7.88
8/4/2016 IWE 46
ADDITION OF AVRS AND GOVERNORS
• To add AVRs, right click on the gen > Define > Automatic
Voltage Regulator (avr)
• To add Governors, right click on the gen > Define > Governors
and Turbine (gov)
• To list all the Events in any given study case, click on the Edit
Simulation Events
• To plot the results of the transient analysis, RMS variables for each
element must be defined.
• RMS variables can be defined: right click on the element > Define
> Results for RMS/EMT simulation
• Select the required variables from the list.
• In the calculation window, select the elements and their variables in the
Operands section
• Specify the arithmetic formula for the operands in the Formula section
• Click on Verify to check the formula
– Click on the “x-Axis” row > Font, change the font, font size,
precision, etc.
DIgSILENT
1.20
[-]
0.90
0.60
0.30
0.00
-0.30
-0.1000 3.9085 7.9170 11.926 15.934 [s] 19.943
Bus1: Electrical Frequency
Bus2: Electrical Frequency
Bus3: Electrical Frequency
DIgSILENT
1.0025
[-]
0.9900
0.9775
0.9650
0.9525
0.9400
-0.1000 3.9085 7.9170 11.926 15.934 [s] 19.943
Bus1: Electrical Frequency
Bus2: Electrical Frequency
Bus3: Electrical Frequency
• To export,
– Deactivate the project
– File > Export > Data (*.pfd, *.dz)
– Select the project and define the location to save
– Click Execute.
• To import,
– Deactivate the project
– File > Export > Data (*.pfd, *.dz)
– Select the pfd file and click Execute.
• Frequency runaway
DIgSILENT
52.50
[Hz]
50.00
47.50
45.00
42.50
40.00
-0.1000 2.9042 5.9084 8.9125 11.917 [s] 14.921
DIgSILENT
50.10
[Hz]
49.90
49.70
49.50
49.30
49.10
-0.1000 2.9454 5.9908 9.0361 12.082 [s] 15.127
DIgSILENT
50.14
[Hz]
50.04
49.94
49.84
49.74
49.64
-0.1000 3.3848 6.8696 10.354 13.839 [s] 17.324
DIgSILENT
DIgSILENT
1.50 90.00
[p.u.] [MW]
1.20 70.00
50.00
0.90
30.00
0.60
10.00
0.30
-10.00
0.00 -0.0779 0.3112 0.7004 1.0895 1.4787 [s] 1.8679
-0.0779 0.3112 0.7004 1.0895 1.4787 [s] 1.8679 WTG 01: Total Active Power
Thank You
INDONESIA CLEAN ENERGY DEVELOPMENT II
Implemented by Tetra Tech
Menara Jamsostek, North Tower 14th Floor
Jl. Gatot Subroto No.38 | Jakarta12710 INDONESIA
Main: +62 21 5296 4445 | Fax: +62 21 5296 4446
www.iced.or.id