Professional Documents
Culture Documents
Home / Technical Articles / 4 electrical quantities you MUST fully understand to select the right cast-resin
transformer
Low fire load due to design with little insulating material (less than 10 %
of the weight is accounted for by the insulants),
No special fire protection measures required (cast-resin moulding
material is fire-retardant and self-extinguishing once the energy supply has
been cut off),
No risks that would make a fire more serious (e.g. toxicity risk due to
release of poisonous gases in case of a fire),
Measures to protect the ground water (e.g. oil collecting throughs or
traps) are not required,
Continuous overload capacity up to 140-150 % of the rated power due to
built-on, temperature-dependently controlled radial-flow fans,
Utilization of the continuous overload capacity as “hot standby“
redundancy to increase the supply reliability,
No loss of service life when continuous overload capacity is used,
No danger of impermissible switching overvoltages due to resonance
excitation of the windings on switch-on and switch-off with a vacuum
switch.
To select cast-resin transformers, the following electrical quantities must
be determined:
This largely compensates for the internal voltage drops of the transformer when
a load is applied. Distribution transformers can also be adapted to the prevailing
system conditions using taps.
Table 2 – Matching the transformation ratio kTr to the voltage conditions
in a 20/0.4kV network
Table 2 – Matchi
Table 3 – Standard impedance voltages at rated current in the power range of
an example ‘GEAFOL’ cast-resin transformers that is relevant to industrial
applications
SrT in kVA urz in %
250 4 6
315 4 6
400 4 6
500 4 6
630 4 6
800 4 6
1000 4 6
1250 6
1600 6
2000 6
2500 6
Parallel operation of distribution transformers with an impedance voltage at
rated current of urZ = 4 % is largely found in networks with loads that cause
unwanted power system perturbations.
3. Vector group
The vector group indicates how the phases of the two windings of a transformer
are connected and the phase position of their respective voltage vectors. It
consists of letters and a phase angle number.
The upper-case letter of the vector group denotes the type of connection of the
primary winding; the lower-case letter, that of the secondary winding.
Table 4 provides a list of the most common vector groups used in three-phase
transformers.
For reasons concerning the insulation, the star connection is preferred at high
nominal system voltages because the insulation of a star-connected winding
only has to be dimensioned for 1/√3 times the line-to-line voltage.
For high load currents, on the other hand, a delta connection is more
favourable. The delta winding is characterized by the fact that its winding
phases are only subjected to times the phase current. This means that smaller
cross-sectional areas can be used for the winding wires than in a star
connection, which saves costs for materials.
For these reasons, the vector group YNd5 is used for generator
transformers.
Unlike generator transformers, distribution transformers supplying a low-voltage
system have to be star-connected on the secondary side. A brought-out neutral
on the low-voltage side is essential so that the neutral conductor can be
connected to provide the voltage for single-phase loads, which usually require
230 V.
When power is supplied to single-phase loads, however, unbalanced loads
must be expected. For this reason, the necessary delta connection can only be
implemented on the primary side of distribution transformers.
1. Expense for cables and switchboards to distribute the power to the loads,
2. Transformer loads optimized for losses in parallel operation (busbar
interconnection of the transformers),
3. Maximum power demand of the loads that form a technological and
process-related unit (e.g. production or function area),
4. Maximum impulse load caused by individual consumers (e.g. large
asynchronous motors) or consumers operated in groups (e.g. welding
machines),
5. Necessary power reserve to adhere to the (n–1) principle in case of a
transformer fault,
6. Maximum possible short-circuit capacity of the LV operational equipment.
In accordance with the importance of each of these influencing factors,
optimization calculations to determine the most economical rated transformer
power must be performed.
The basis for these calculations is an area to be supplied with power within a
factory with an average load per unit area of P=300-350 VA/m2 , a nominal
system voltage of UnN = 400 V and a permissible short-circuit load of Ik ≤ 100
kA. For a supplied area with these system parameters, the rated power SrT =
800 kVA proved the most cost-efficient solution.
For smaller loads per unit area (< 300 VA/m2) or higher nominal system
voltages (e.g. UnN = 690 V), smaller rated powers SrT and for larger loads per
unit area ( > 350 VA/m2) or lower nominal system voltages (e.g. UnN = 208 V),
larger rated powers SrT are more cost-efficient.
For a power supply adjusted to the load centres, dry-type transformers from the
power range 500 kVA ≤ SrT ≤ 1,250 kVA should preferably be chosen because,
with large transformer units, the power reserve required to handle the (n–1)
fault case increases.
Table 5 is based on this value to provide a power calculation to handle the (n–
1) fault case in parallel operation of cast-resin transformers. Using the power
calculation provided in Table 5, industrial LV power systems can be
dimensioned according to the (n–1) criterion.
Sources:
1. Planning Guide for Power Distribution Plants by Dr.-Ing. Hartmut Kiank
and Dipl.-Ing. Wolfgang Fruth (Siemens)