You are on page 1of 2

®

DSEGenset

DSE8610 ENVIRONMENTAL TESTING STANDARDS

ELECTRO MAGNETIC COMPATIBILITY


SYNCHRONISING AUTO START LOAD SHARE BS EN 61000-6-2
EMC Generic Immunity Standard for the
CONTROL MODULE Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the
Industrial Environment
FEATURES ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment

TEMPERATURE
BS EN 60068
The DSE8610 is an easy to use The event log will record 250 events KEY LOAD SHARE FEATURES: Ab/Ae Cold Test -30oC
Synchronising Auto Start Control to facilitate easy maintenance. An • Peak lopping/sharing (with BS EN 60068-2-2
Bb/Be Dry Heat +70oC
Module suitable for use in a extensive number of fixed and DSExx60)
multi-generator loadshare system, flexible monitoring, metering and • Sequential set start VIBRATION
designed to synchronise up to 32 protection features are included • Manual voltage/frequency BS EN 60068-2-6
Ten sweeps in each of three major axes
generators including electronic and as well as comprehensive adjustment 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
non-electronic engines. communication and system • R.O.C.O.F. and vector shift
expansion options. protection HUMIDITY
BS EN 60068-2-30
The DSE8610 monitors the • Generator load demand Db Damp Heat Cyclic 20/55oC @ 95% RH
generator and indicates operational Using the DSE PC Configuration • Automatic hours run balancing 48 Hours
status and fault conditions, Suite Software allows easy • Mains (Utility) de-coupling BS EN 60068-2-78
Cab Damp Heat Static 40oC @ 93% RH
automatically starting or stopping alteration of the operational • Mains (Utility) de-coupling 48 Hours
the engine on load demand or fault sequences, timers and alarms. With test mode
SHOCK
condition. all communication ports capable of • Dead bus sensing BS EN 60068-2-27
being active at the same time, the • Bus failure detection Three shocks in each of three major axes
System alarms are annunciated on DSE8610 is ideal for a wide variety • Direct governor and AVR control 15gn in 11mS
the LCD screen (multiple language of demanding load share • Volts and frequency matching DEGREES OF PROTECTION
options available), illuminated LED applications. • kW and kV Ar load sharing PROVIDED BY ENCLOSURES
BS EN 60529
and audible sounder. • Dead bus synchronising IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY


OF LOAD SHARE APPLICATIONS
DSE2130 MODEM MODBUS PC
DSE2131
DSE2133
DSE2152 11 6 4
DSE2157
DSE2548 232 485

DSENET ®
RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V
+
ETHERNET

DEUTZ
DSE8610 MSC
ISUZU
PERKINS
CATERPILLAR
MTU
7 55xx ­75xx ­8xxx VOLVO
OTHER
CUMMINS
SCANIA

BUS VOLT FREE GENERATOR SENSING FUEL & START CHARGE ELECTRONIC MAGNETIC
SENSING OUTPUTS OUTPUTS ALTERNATOR ENGINES PICK-UP
CURRENT VOLTS
D­+
+ W/L

1ph 2 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E N

ISSUE 3
®

DSEGenset

DSE8610 SPECIFICATION

SYNCHRONISING AUTO START LOAD SHARE DC SUPPLY


CONTINUOUS VOLTAGE RATING
CONTROL MODULE 8 V to 35 V continuous

CRANKING DROPOUTS
FEATURES Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is achieved
without the need for internal batteries

MAXIMUM OPERATING CURRENT


460 mA at 12 V, 245 mA at 24 V

MAXIMUM STANDBY CURRENT


375 mA at 12 V, 200 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A AC at 250 V AC (Volt free)

AUXILIARY OUTPUTS E,F,G,H,I & J


2 A DC at supply voltage

GENERATOR & BUS


VOLTAGE RANGE
KEY FEATURES KEY BENEFITS 15 V to 333 V AC (L-N)
• Comprehensive synchronising & • CAN, MPU and Frequency speed • Compatible in load share systems
FREQUENCY RANGE
loadsharing capabilities sensing containing DSE5500, DSE7500 and 3.5 Hz to 75 Hz
• Built-in governor and AVR control • Tier 4 CAN engine support DSE8600 series. Contact DSE for
• Base load (kW export) • “Protections disabled” feature further details MAGNETIC PICK-UP
VOLTAGE RANGE
functionality • Front panel editing with PIN • 132 x 64 pixel ratio display for +/- 0.5 V to 70 V
• Mains (utility) de-coupling protection clarity
protection • Fully configurable using DSE • Real-time clock provides accurate FREQUENCY RANGE
10,000 Hz (max)
• Generator power (kW, kV Ar, kV A Configuration Suite PC software event logging
& pf) monitoring via USB • Ethernet communication, provides BUILT-IN GOVERNOR CONTROL
• Overload (kW & kV Ar) protection • 4 Line back-lit LCD text display builit in advanced remote MINIMUM LOAD IMPEDANCE
1000Ω
• Reverse power (kW & kV Ar) • LED and LCD alarm indication monitoring. Fully isolated
protection • Configurable display languages • Can be integrated into building
GAIN VOLTAGE
• Unbalanced load protection • USB connectivity management systems (BMS) and 0 V to 10 V DC
• Independent earth fault protection • Customisable status screens programmable logic control (PLC) Fully isolated
• Advanced integral PLC editor • Five key menu navigation • Increased input and output
OFFSET VOLTAGE
• 11 Configurable inputs • 3 Configurable maintenance expansion capability via DSENet® +/- 10 V DC
• 8 Configurable outputs alarms • Licence-free PC software Fully isolated
• Configurable flexible sensor inputs • Multiple date and time run • IP65 rating (with supplied gasket) BUILT-IN AVR CONTROL
• DSENet® expansion compatibility scheduler offers increased resistance to water MINIMUM LOAD IMPEDANCE
• User configurable RS232, RS485 • Manual fuel pump control ingress 1000Ω
Fully isolated
and Ethernet communications • Fuel usage monitor and low fuel • Advanced Internal PLC editor allows
• Remote SCADA monitoring via level protection user configurable functions to meet GAIN VOLTAGE
0 V to 10 V DC
various DSE software applications • Charge alternator failure specific application requirements. Fully isolated
• MODBUS RTU & TCP support protection
• User configurable MODBUS • Load switching (load shedding EXPANSION DEVICES OFFSET VOLTAGE
• DSE124 CAN/MSC Extender +/- 10 V DC
pages and dummy load control) Fully isolated
• Advanced SMS control and fault • Configurable event log (250) • DSE2130 Input Expansion Module
• DSE2131 Ratio-metric Input Expansion DIMENSIONS
messaging (additional GSM • Backed up real time clock
Module OVERALL
modem required) • DSE2133 RTD & Thermo-couple 240 mm x 181 mm x 42 mm
• Easy access diagnostic pages Expansion Module 9.4” x 6.8” x 1.6”
including modem diagnostic pages • DSE2152 Ratio-metric Output PANEL CUTOUT
• Data logging and trending Expansion Module 220 mm x 160 mm
• DSE2157 Output Expansion Module 8.7” x 6.3”
• DSE2548 LED Expansion Module MAXIMUM PANEL THICKNESS
8 mm
RELATED MATERIALS 0.3”
TITLE PART NO’S OPERATING TEMPERATURE RANGE
DSE8610 Installation Instructions 053-069 -30 oC to +70 oC
DSE8610 Operator Manual 057-115
DSE8600 PC Configuration Suite Manual 057-119 STORAGE TEMPERATURE RANGE
DSE8660 Date Sheet 055-086 -40 oC to +85 oC

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708