You are on page 1of 1

Relay Setting Curves for Recloser Coordination

1,000.00
ACR1
ACR2
ACR3
ACR4
ACR5
DT
100.00

10.00
Time (s)

1.00

0.10

0.01
10 100 1,000 10,000 100,000
Current (A)

Setting ACR1 ACR2 ACR3 ACR4 ACR5


Load Current (A) 300.0 270.0 250.0 150.0 120.0
TMS (s) 1.3 0.1 0.1 0.1 0.1
Curve type DT IEEE-VI IEEE-VI IEEE-EI IEEE-EI
Inst-mult 3.0 1.1 1.1 1.3 1.3
DT (s) 0.8 0.6 0.4 0.2 0.1
HCT 5.0 5.0 4.5 5.0 5.0
DT (s) 0.3

inst_setting (A) 900 297 275 195 156


HCT_current (A) 1500 1350 1125 750 600

Prepared by: Kem Ratana