You are on page 1of 1

Relay Setting Curves for Recloser Coordination

10,000.00
ACR1

ACR2

ACR3

1,000.00 ACR4

ACR5

100.00

10.00
Time (s)

1.00

0.10

0.01

0.00
10 100 1,000 10,000 100,000
Current (A)

Setting ACR1 ACR2 ACR3 ACR4 ACR5


Load Current (A) 300.00 200.00 150.00 100.00 60.00
TMS (s) 0.10 0.10 0.10 0.10 0.10
Curve type IEC-VI IEC-SI IEC-SI IEC-SI IEC-SI
Inst-mult 3.0 3.0 2.5 2.0 2.0
DT (s) 0.20 0.15 0.10 0.05 0.02
High Current lockout 10 8 8 8 8

Prepared by: Kem Ratana

You might also like