Model FB-2120X Series

Manual Alarm Call (MAC) Stations


Suitable for use in Explosion-Proof Areas
Single or Dual Action

Overview Operation
The FireBus Model FB-2120X Series are high-quality, The Model FB-2120X is operated by pulling the bar
die-cast metal manual alarm stations, UL Listed and ap- marked “PULL” on the front of the station as far down
proved for use in hazardous “explosion-proof” locations. as it will go. At that point, the station will lock in place
These models contain enhanced component features and is easily visible from up to 50 feet. The activation
that allow them to operate reliably within the uniquely bar is reset by opening the station with the key provided,
difficult environments found in petrochemical, refining placing the bar in the normal upright position and then
and offshore applications. The FB-2120X Series are relocking the station.
approved for use in Class I, Division I, Groups B, C and
D; Class II, Division I, Groups E, F and G and Class III. With the dual action configuration, the bar marked
The station enclosure is approved for indoor and outdoor “PUSH” rotates inward allowing the “PULL” bar to be
use, NEMA 4X applications and is Marine rated. grasped and operated by a single hand.

All models in the series have been designed specifically Features


for compliance with all applicable ADA requirements
(Americans with Disabilities Act; 28 CFR Part 36). These • Special Hazard Protection
FireBus manual stations can be operated with a single
hand without tight grasping, pinching or twisting of the • Marine and NEMA 4X Ratings
wrist. The force required to operate the station has been
tested by Underwriter’s Labs for compliance with the 5 • Single or Dual Action
lbf pull force. When properly installed, these models will
protrude less than 4 inches into halls, corridors, etc. no • DPDT Alarm Contacts
matter the height at which it is installed.
• Terminal Connections
The Model FB-2120X Series are available in single action
or dual action configurations. Station alarm contacts are • Key Lock Reset
DPDT, rated 10 amps @ 125 VAC and 1 amp @ 30 VDC.
The alarm contacts are gold plated for corrosion resis- • Custom Color Option
tance. Each station is configured with terminal connec-
tions and a key reset. • ADA Compliant

For unique hazard protection, both models are available • Meets International Standards (NRF-210 etc.)
in a variety of custom colors. Custom colors provide
distinct station identification for use in equipment • UL Listed
shutdown, medical aid, fire suppression actuation and
similar applications. The FB-2120X Series may also be • Standard colors of Red, White or Violet
configured with stainless steel components that provide
enhanced protection when used in extreme corrosive • Multiple language and message choices.
environments.
Explosion Proof Manual Alarm Operating voltage: Dimensions: Communication protocol*:
Call (MAC) Stations 17–28 VDC 4.75” (120.6 mm) High FireBus-AP™ 5–9V peak
Model FB-2120X to peak (with optional
Supply wiring: 3 1/4” (82.5 mm) Wide
FB-AP input module.
Two-wire supply, polarity 3 7/8” (98.4 mm) Deep
Area Classification Ratings: EMI/RFI compatibility*:
insensitive Weight:
Class I, Division 1, CE marked, A copy of
Alarm Contacts (DPDT) Rating: 4.8 lbs (2.17 kg) the relevant declaration
Groups B, C and D 1 amp at 30 VDC Color: is available on request.
Class II, Division 1, 10 amps at 125 VAC
Groups E, F and G Standard colors:
Terminal Connects:
Environment Classification: Red, White or Violet
Up to 14 AWG
NEMA 4X (weather- Custom Color Options:
proof), Marine Rated Conduit Fittings: Blue, Yellow or Green
Temperature range: 2 Other colors available at extra
Max. continuous operat- Conduit Fitting Size: cost, contact factory.
ing 150°F (66°C) 3/4” – 14 NPT Custom Label Options:
Min. continuous operat- A variety of labels are
ing -40°F (-40° C) available in English,
Storage -40°F to +176°F Spanish, Portuguese &
(–40°C to +80°C) French. For custom text
or other languages con-
Humidity: sult factory.
90% Relative Humidity at
100° F (37.7° C)

* Utilizing FB-AP Series® 7254-FBD-5830 Mini Priority Switch Monitor, or, 7254-FBD-5831 Mini Switch Monitor

** Unused conduit entry must be sealed with a 3/4 NPT pipe plug. All joints must be sealed using pipe thread seal-
ing compound or Teflon tape in accordance with the requirements for the particular installation. Pipe plug and joint
sealant are not provided.

Note: All stations are supplied with 1 break-rod, 1B key and installation instructions. Spare rods available---
2002-FBD-0001=12 pack of scored plastic (acrylic) break-rods.

Ordering information: Language Kits:


2121-FBD-2001 Single Action Explosion Proof MAC - Red 210N Series labels where “N” specifies language: 1 = Eng-
2121-FBD-2002 Single Action Explosion Proof MAC - Violet lish, 2 = Spanish, 3 = Portuguses, 4 = French. Substitute the
2121-FBD-2003 Single Action Explosion Proof MAC - White number for the required language in the part numbers below to
2121-FBD-2004 Single Action Explosion Proof MAC - Custom specify appropriate label kit.

2122-FBD-2001 Dual Action Explosion Proof MAC - Red 210N-FBD-0001 Label Kit - Fire
2122-FBD-2002 Dual Action Explosion Proof MAC - Violet 210N-FBD-0002 Label Kit - CO2 Release
2122-FBD-2003 Dual Action Explosion Proof MAC - White 210N-FBD-0003 Label Kit - FM-200 Release
2122-FBD-2004 Dual Action Explosion Proof MAC - Custom 210N-FBD-0004 Label Kit - Abandon Platform
210N-FBD-0005 Label Kit - Abandon Installation
210N-FBD-0006 Label Kit - Man Overboard

Example: 2102-FBD-001 = Label Kit - Fire, in Spanish

Copyright ©2018 FireBus, LLC Note: The information in this data sheet is given in good faith and consid-
www.FireBus.net ered accurate at the time of printing, however, the company reserves the
right to change specifications of products at any time without prior notice.

07FCS009-C18