RFP-2100 / RFP-2100B
Scalable Analog/Addressable Fire Alarm Control
System
The IFP-2100 (red) and IFP-2100B (black) are intelligent analog/
addressable Fire Alarm Control Panels (FACP). The basic IFP-2100 panel
contains one built in signaling line circuit (SLC), which can support 159
System Sensor® IDP/SK sensors and 159 IDP/SK modules or 127 Hochiki®
SD devices per loop. Additional SLC loops can be added using the model IFP-2100B
6815 SLC expander for IDP/SK devices to increase the overall point capacity
to 2100 or model 5815XL for SD devices to increase the overall point
capacity to a maximum to 2032 points per panel.
IFP-2100 has eight on-board Flexput™ circuits that can be configured for
auxiliary power, notification outputs, or for conventional smoke detector
inputs (Class A or Class B). The FACP also has a Built in dual phone line
digital alarm communicator/transmitter (DACT), IP or optional cellular RFP-2100B
technologies, Form C trouble relay, and two programmable Form C relays.
IFP-2100 has powerful features such as detector sensitivity, day/night
thresholds, drift compensation, pre-trouble maintenance alert, and
calibration trouble alert
F E AT U R E S & B E N E F I T S
• RFP-2100 or • Four line LCD display • Network card allows • JumpStart • Supports up to four
RFP-2100B can be with 40 characters per copper network AutoProgramming® SWIFT wireless
used in a networked line connection with a feature for easy gateways. Each
system where at lease multi-mode or programming gateway can have up
• Available in a red or
one IFP-2100 is in the single-mode fiber to 49 wireless devices
black cabinet • Renewable license on
system connection option
downloading software • Supports Class B
• IFP-2100 or
• Network support for • Built-in dual phone helps inhibit (Style 4) and Class A
RFP-2100 can be
up to 32 Sites line, digital alarm unauthorized (Style 6 or Style 7
surface or flush
communicator/ programming configuration for SLC,
• Built-in support for up mounted
transmitter (DACT), IP and SBUS.
to 159 IDP/SK • Built in USB interface
• Four programmable or optional cellular
detectors and 159 for programming
function keys technologies
IDP/SK modules or
127 SD SLC devices
IFP-2100 / RFP-2100 Technical Specifications
PHYSICAL listing of the IDP, SK, SWIFT or SD devices. For a complete listing of all
Overall Dimensions: 26.4”H x 16.4"W x 4.11”D 3350361: IDP Device Protocol data sheet compliance approvals and
certifications, please visit
Shipping Weight: 33 lbs. 53623: SK Device Protocol data sheet www.farenhyt.com.
Color: Red or Black 350360: SD Device Protocol data sheet
Microsoft, Windows, and
350615 & 350617: SWIFT devices data sheet the Windows Logo are
ENVIRONMENTAL
registered trademarks
Operating Temperature: 32°F to 120°F (0°C to ORDERING INFORMATION or trademarks of
49°C) IFP-2100: Intelligent Fire Alarm Control Panel. Red Microsoft Corporation.
Humidity: 0 to 93% relative humidity (non- Cabinet.
SWIFT® and Honeywell®
condensing) IFP-2100B: Intelligent Fire Alarm Control Panel. are registered trademarks
Black Cabinet. of and Farenhyt™ is a
ELECTRICAL IFP-2100HV: High Voltage (240V) Intelligent Fire trademark of Honeywell
IFP-2100 Primary AC: 120VAC @ 50/60Hz, 4.5A Alarm Control Panel. Red Cabinet International, Inc.
IFP-2100HV AC: 240VAC @ 50/60Hz, 2.8A IFP-2100HVB: High Voltage (240V) Intelligent Fire This document is not
Total Accessory Load: 9A @ 24VDC power-limited Alarm Control Panel. Black Cabinet intended to be used for
Standby Current: 230mA RFP-2100: Remote Fire Alarm Panel without built installation purposes. We
in display. Red Cabinet. try to keep our product
Alarm Current: 415mA
information up-to
Battery Charging Capacity: 17 to 55AH RFP-2100B: Remote Fire Alarm Panel without built date and accurate. We
Battery Size: 18AH max. allowed in control panel in display. Black Cabinet. cannot cover all specific
cabinet. Larger capacity batteries can be housed in RFP-2100HV: High Voltage (240V) Remote Fire applications or anticipate
RBB accessory cabinet. Alarm Panel without built in display. Red Cabinet. all requirements. All
specifications are subject
Six Conductor Wiring: Two voice bus & four SBUS RFP-2100HVB: High Voltage (240V) Remote Fire
to change without notice.
Alarm Panel without built in display. Black Cabinet.
FLEXPUT CIRCUITS For Technical
Eight circuits that can be programmed SBUS ACCESSORIES Support, Please call
RA-2000, RA-1000, RA-1000R, RA-100, 800-446-6444.
individually as:
Notification Circuits: 3A per circuit @ 24VDC, RA-2000GRAY: Remote annunciators
power limited 6815: Signal Line Circuit (SLC) Expander for IDP or
Auxiliary Power Circuits: 3A per circuit @ 24VDC, SK devices
power limited. 5815XL: Signal Line Circuit (SLC) Expander for SD
Initiation Circuit: 100mA per circuit @ 24VDC, devices
power-limited RPS-1000/B: Power Supply. Red or Black Cabinet
5496: NAC Expander
AGENCY LISTINGS AND APPROVALS 5824: Serial/Parallel Module
NFPA 13, NFPA 15, NFPA 16, NFPA 70, & NFPA 5880: LED I/O Module
72: Central Station; Remote Signalling; Local 5865-3 or 5865-4: LED Annunciator
Protective Signalling Systems; Auxiliary Protected
5883: Relay Interface
Premises Unit; & Water Deluge Releasing Service
UL Listing MISCELLANEOUS ACCESSORIES
CSFM 7165-0559:0505 HFSS: Software Suite. Provides programming,
FDNY COA# 6251 upload/download and event reporting
Seismic (CA) (pending) RBB: Remote Battery Box Cabinet. Use for backup
FM approved batteries up to 35AH. Dimensions: 16"W x 10"H x
6"D
APPROVED RELEASING SOLENOIDS SK-SCK: Seismic Compliance Kit
Asco T8210A107 24 VDC 3 A max 0 Hz SK-NIC: Network Interface Card
Asco 8210G207 24 VDC 3 A max 0 Hz SK-FML: Multi Mode Fiber Card
SK-FSL: Single Mode Fiber Card
COMPATIBLE DEVICES
CELL-MOD: Cellular Communicator in Plastic
See the data sheets listed below for a complete Enclosure
CELL-CAB-SK: Cellular Communicator in Metal
Enclosure with lock and key
For more information
Learn more about Honeywell’s Farenhyt Series and
other products available by visiting
www.farenhyt.com>
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 351602| A | 01/18
800-328-0103 © 2018 Honeywell International Inc.
IFP-2100ECS / IFP-2100ECSB
Scalable Analog/Addressable Fire Alarm
Control System
The IFP-2100ECS (red) and IFP-2100ECSB (black) are intelligent analog/
addressable Fire Alarm Control Panels combined with an Emergency
Communication System (ECS). When the ECS features are enabled, they
are integrated with the fire alarm and voice evacuation functions of the
control panel. The IFP-2100ECS panel and accessories provide features to
meet the requirements for Mass Notification Systems as described in UL
2572.
This state of the art fire alarm control panel allows you to choose one of
three SLC protocols per system. The IFP-2100ECS panel contains one
built in signaling line circuit (SLC), which can support 159 System Sensor®
IDP/SK sensors and 159 IDP/SK modules or 127 Hochiki® SD devices per IFP-2100ECSB
loop. Additional SLC loops can be added using the model 6815 SLC
expander for IDP/SK devices or model 5815XL for SD devices to increase COMPATIBILITY
the overall point capacity to a maximum of 2100 points per panel. The IFP-2100ECS is compatible with the following
ECS components:
IFP-2100ECS has the interconnection capability for up to 32 panels. The
system has two modes of operation, multiple panels covering one larger • ECS-50W, ECS-125W, ECS-INT50W or ECS-
building, or multiple independent buildings. A separate network can be DUAL50W Amplifier
used for voice paging across all panels. • ECS-RVM: Remote voice module
The IFP-2100ECS supports a variety of devices, including RA-2000, • ECS-SW24: 24 switch expander (max 2)
RA-1000 or RA-100 remote annunciator, 5824 serial/parallel printer • ECS-NVCM: Network Voice Control Module
interface module (for printing system reports), RPS-1000 power module, (included)
and IDP, SK or SD devices.
• ECS-LOC: Local Operator Console
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 351600 | A | 01/18
800-328-0103 © 2018 Honeywell International Inc.
5815RMK / 5815RMKB Remote Mounting Kit
Product Installation Document
Farenhyt™ is a trademark, Silent Knight® and Honeywell® are registered trademarks of Honeywell International, Inc.
The 5824 also provides the Gateway interface for communicating to other
systems, such as a building control system. The Gateway protocol is a data
stream produced by the FACP that can be used to display system events
on a PC monitor. The protocol allows a building control system to handle 5824
events and to silence or reset the FACP. The Gateway protocol can be used
to interface with CadGraphics, the PC-based graphics annunciator
software (available from Honeywell).
COMPATIBILITY
The 5824 is compatible with the following FACPs:
• IFP-2100 / IFP-2100ECS / RFP-2100
• IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50
• IFP-25
F E AT U R E S & B E N E F I T S
• Allows connection of • Out of paper/system • UL listed with the • Interfaces with the
standard computer trouble annunciated at Okidata Microline 320 CadGraphics
printers fire panel parallel printer PC-based graphics
annunciator software
• Quick and easy to • Parallel and RS-232 • FM approved
install serial output
• Gateway interface can
• DIP switches for • Reports event with be used to display
setting ID codes date/time stamp in system events on a PC
user-friendly report monitor and interface
• Housed in a sturdy,
format. with building control
wall-mountable,
systems
plastic enclosure • UL listed, complies
with NFPA 72 and 101
5824 Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademark
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
For Technical
ENVIRONMENTAL AGENCY LISTINGS AND APPROVALS
Support, Please call
Operating Temperature: 32°F to 120°F (0°C to NFPA 72 and NFPA 101. 800-446-6444.
49°C) UL Listed
Humidity: 0 to 95% non-condensing) CSFM 7165-0559:0502;
MEA: 429-92-E Vol 9
ELECTRICAL FM approved
Operating Voltage: 24VDC
Current: 45mA (alarm and standby)
Max. per system: 2
Wiring Distance: Up to 6,000 feet from control
panel (depending on wiring method)
The 5815XL communicates with the FACP via an RS 485 system bus. A
green LED on the 5815XL board blinks to indicate good communication. If
an addressable device on a 5815XL fails, the loop communicates the
failure to the IFP-1000 and continues to operate normally.
5815XL
INSTALLATION
The 5815XL can be mounted on standoffs located in the IFP-1000,
IFP-1000ECS, IFP-2000/ECS or RPS-1000 cabinet or in the 5815RMK
remote mounting kit. All control panel mounting options allow you to install
two 5815XLs per cabinet.
COMPATIBILITY
The 5815XL is compatible with the following Honeywell Farenhyt series
FACPs:
• IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
F E AT U R E S & B E N E F I T S
• Adds support for up to • Communicates with • House up to two • SLC wiring used • CSFM approved
159 IDP detectors and the FACP via RS 485 5815XLs in the standard wire. Twisted
• MEA
159 IDP modules or system bus IFP-1000 cabinet, pair or shield cable are
127 SD devices to the IFP- 2000/ECS not required • FM approved
• LED indicates good
IFP-2000/ECS cabinet, RPS-1000
communication • UL 864 listed,
system. cabinet, or one
complies with NFPA
5815XL in the
• Adds support for up to 72 and 101
5815RMK remote
99 IDP detectors and
mounting kit •
99 IDP modules or
127 SD devices for the
IFP-1000/ECS
system.
5815XL Technical Specifications
For a complete listing of all
PHYSICAL ORDERING INFORMATION compliance approvals and
5815XL Physical 5815XL: Signaling Line Circuit Expander certifications, please visit
www.farenhyt.com.
Dimensions: 4.2” H (10.7 cm): 4.8” W (12.2 cm)
Shipping Weight: 5.6 oz (159 g) ACCESSORIES Microsoft, Windows, and
RPS-1000: Intelligent Power Module. Cabinet the Windows Logo are
RPS-1000 Physical (Optional Accessory)
holds two 5815XLs. registered trademarks
Height: 26” (66 cm) or trademarks of
5815RMK: Remote Mounting Kit. Cabinet holds Microsoft Corporation.
Width: 16” (40 cm)
two 5815XLs.
Depth: 4.7” (11.8 cm) Honeywell® is a
Shipping Weight: 28.8 lbs (13.1 kg) AGENCY LISTINGS AND APPROVALS registered trademarks
5815RMK Physical (Optional Accessory) of and Farenhyt™ is a
NFPA 13, NFPA 15, NFPA 16, NFPA 70, &
trademark of Honeywell
Height: 10.2” (25.9 cm) NFPA 72: Central Station; Remote Signalling; Local International, Inc.
Width: 10.4” (26.4 cm) Protective Signalling Systems; Auxiliary Protected
Depth: 3” (7.6 cm) Premises Unit; & Water Deluge Releasing Service. This document is not
Suitable for automatic, manual, waterflow, sprinkler intended to be used for
Shipping Weight: 1.2 oz (37g) installation purposes. We
supervisory (DACT non-coded) signalling services.
try to keep our product
ENVIRONMENTAL UL Listed information up-to
Operating Temperature: 32°F to 120°F (0°C to CSFM 7170-0559: 135; date and accurate. We
49°C) MEA 429-92-E Vol. VI cannot cover all specific
applications or anticipate
Humidity: 10 to 93% relative humidity (non- FM Approved all requirements. All
condensing) specifications are subject
to change without notice.
ELECTRICAL
For Technical
Standby & Alarm Current: 80mA max Support, Please call
800-446-6444.
SYSTEM CAPACITY
IFP-1000/ECS FACP supports seven 5815XLs
IFP-2000/ECS or IFP-300/ECS FACP supports 63
5815XLs
5815XL Capacity
• 127 SD addressable devices per loop for IFP-
1000/ECS, IFP-300/ECS & IFP-2000/ECS
• IFP-1000 / IFP-1000ECS
• IFP-75 / IFP-75B
• IFP-50
F E AT U R E S & B E N E F I T S
• 30 programmable LED • Comes with four • Both modules UL 864 • MEA Approved
outputs (15 red and semi-transparent listed; comply with 429-92-E, Vol 9
15 yellow)) labels that can be NFPA 72
• CSFM Approved
typed or printed on
• Up to 8 5865s can be • 4-wire connection to
• FM Approved
used on one panel • DIP switch FACP SBUS
addressable
• Fit into a standard 3-
or 4-gang electrical • Connects to FACP
box SBUS
5865-3 and 5865-4 Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
ENVIRONMENTAL
Operating Temperature: 32°F to 120°F (0°C to
49°C)
Humidity: 10% to 93% relative humidity (non-
condensing)
Compatibility
The 5880 is compatible with the following FACPs:
• IFP-1000 / IFP-1000ECS
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50
IFP-25.
F E AT U R E S & B E N E F I T S
• 40 programmable • No external resistors • FM approved
open collector LED required for the 5880
• CSFM listed
outputs LED driver outputs
• Individually mapped
• Provides 8 supervised • DIP switch
outputs
dry contact inputs for addressable
system or alarm • Inputs for dry contacts
• 4-wire connection to
monitoring functions or a remote silence or
control panel SBUS
reset switch
• Its compact size
• UL 864 listed;
allows mounting • You can use up to
complies with NFPA
inside the annunciator, eight 5880 modules
72
or in an accessory on one control panel
cabinet • MEA 429-92-E, Vol. 9 for maximum
fl exibility
5880 Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademark
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
Compatibility
The 5883 is compatible with the following Farenhyt Series FACPs:
• IFP-1000 / IFP-1000ECS
• IFP-100 / IFP-100ECS
5883
• IFP-75 / IFP-75B
• IFP-50
F E AT U R E S & B E N E F I T S
• 10 general purpose • Controls any dry
Form C relays contact device
• Relays rated at 5.0A @ • Housed in protective
30 VDC or 250 VAC cabinet
resistive
5883 Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
APPLICATIONS
Printed transaction records reduce the man-hours required to install and
maintain a system. A printed record of all system events (alarms, troubles,
etc.) and status changes can be especially valuable in the event of a
disputed incident.
IFPN-PRN7
CONSTRUCTION AND OPERATION
The printer is housed in its own separate enclosure and is suitable for
placement on a desk top, counter, or table.
INSTALLATION
The PRN-7 should be placed in a secure area to prevent theft of the printer
and/or printed records. The PRN-7 must not be located further than 20
ft/6.10 m (actual cable length) from the control panel.
Consult the control panel installation manual for the proper method and
PIN numbers used to complete the electrical connection to the control
panel.
F E AT U R E S & B E N E F I T S
• Provides a hard copy • Uses standard 9” x 11” • Includes a 24-pin
printout of all system tractor-feed fan-fold print head
events and status paper
• Very quiet
changes
• Prints 80 columns of (approximately 52
• Time stamps printed data at 10 characters dBA).
on the record of each per inch
event and status
• Provides printed
change with the
records of system
current time-of-day
configuration and
and date
addressable device
parameters
IFPN-PRN7 Technical Specifications
PRINTER SPECIFICATIONS ORDERING INFORMATION For a complete listing of all
Printer Method: Serial printing with 24-pin matrix PRN-7: 24-pin dot-matrix printer, 110-230 VAC compliance approvals and
certifications, please visit
print head power
www.farenhyt.com.
Printing Speed (copy draft): 333 cps at 10 cpi
Character Density: 10 cpi standard (12, 15, 17.1, AGENCY LISTINGS AND APPROVALS Microsoft, Windows, and
and 20 cpi available via front panel) These listings and approvals apply to the modules the Windows Logo are
specified in this document. In some cases, certain registered trademarks
Graphic Resolution (VxH): Up to 360 x 360 dpi or trademarks of
modules or applications may not be listed by
Ribbon Life (approx.) : 6 million characters (DPQ) Microsoft Corporation.
certain approval agencies, or listing may be in
Acoustic Noise Level : 52 dBA (approx.)
process. Consult factory for latest listing status. Honeywell® is a
Dimensions: 18”(45.8cm)W x 7.9” (20.01cm)H x registered trademarks
• UL Listed: S35611
10.4 (27.8cm)D of and Farenhyt™ is a
Weight: 18.9 pounds (8.6 kg) trademark of Honeywell
International, Inc.
ELECTRICAL This document is not
Power Supply: 110-230 VAC auto ranging, auto intended to be used for
sensing installation purposes. We
try to keep our product
Power Consumption: 40 watts (printing)
information up-to
date and accurate. We
ENVIRONMENTAL cannot cover all specific
Operating Temperature: 50°F to 104°F (10°C to applications or anticipate
40°C) all requirements. All
specifications are subject
Humidity: 10% to 85% relative humidity (non-
to change without notice.
condensing)
For Technical Support,
call 800-446-6444.
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 350271 | F | 02/18
800-328-0103 © 2018 Honeywell International Inc.
IFP-Net-3
GRAPHICAL MONITORING WORKSTATION
IFP-Net is a Microsoft® Windows® based graphic user interface linking
selected fire alarm control panels together to a PC to easily monitor them.
The PC operator would receive real-time information about a system with
details showing right where the event is occurring. For example, if a pull
station was activated a graphic of the floor of that building would zoom in
onto the location of the pull station and provide the operator with specific
instructions on what to do or who to call.
PC REQUIREMENTS
The following are the minimum requirements for a IFP-Net-3 workstation
that is used on a PC provided by the customer.
F E AT U R E S & B E N E F I T S
• Support of IFP-Series • System Administrator- • New and • Powerful search filters • Floor plans can be
devices with definable security Acknowledged Event for custom reporting zoomed in and out to
IFPN-GW-Kit profiles allow for boxes display all of all events any level
installation package extremely flexible off-normal events,
• Screen database with • Devices can be placed
definitions for simultaneously with
• Autonavigation screens for all sites. at any zoom level
operator accounts graphic screens
automatically locates
• Administrator- • Import vector.dfx,
and zooms to the • Configurable windows • Operator log with
definable macros for wmf, .bmp, .jpg or .gif
device related to an provide flexibility to response tracking
device communication
alarm or event based display information as • Full linked multimedia
• History Manager
on the priority of the desired • Definable function (text, audio, video, and
records operator,
event keys, functional bitmaps) to any device,
• Dynamically event, and response
buttons, and all-definable by the
generated sizable key (with time and date
navigational buttons administrator
map stamp) to disk
IFP-NET-3 Technical Specifications
ORDERING INFORMATION For a complete listing of all
IFP-NET-3: Software and key (a key is required on compliance approvals and
certifications, please visit
each PC in system)
www.farenhyt.com.
IFPN-GW-EM-3: Gateway Interface board
IFPN-GW-KIT: Installation packages includes Microsoft, Windows, and
Gateway interface, Cabinet, and 5824 Serial/ the Windows Logo are
registered trademarks
Parallel printer interface
or trademarks of
IFPN-CAB1: Gateway/5824/NION router cabinet Microsoft Corporation.
IFP-4: IFP-NET verion 4 Software KeyBit (Required
Honeywell® is a
for Version 4)
registered trademark
IFP-MM: Adds floatable/Dockable Windows option of and Farenhyt™ is a
(to support dual monitors) to IFP-NET trademark of Honeywell
International, Inc.
• IFP-50
• IFP-75
• IFP-100 / IFP-100ECS
• IFP-1000 / IFP-1000ECS
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 350928 | F | 02/18
800-328-0103 © 2018 Honeywell International Inc.
SK-F485C
Fiber to SBUS Converter
INSTALLATION
The SK-F485C can be mounted using the standoffs on the board in the
cabinet of a compatible FACP. The 5815RMK remote mounting kit can also
be used allowing up to two SK-F485C converter modules in a single
cabinet.
Compatibility
The SK-F485C is compatible with the following FACPs:
• IFP-1000 / IFP-1000ECS
• IFP-100 / IFP-100ECS
• IFP-75 / IFP-75B
• IFP-50
• 5496
• RPS-1000
F E AT U R E S & B E N E F I T S
• Fiber connection • Fiber distance Up to • SK-F485C data
duplex ST connectors 1.0 mile (1.6Km) direction control
for Tx and Rx data fiber SK-F485C connection automatic half duplex
cable duplex is 62.5 (two-wire) or terminal transmitter enable
micron. Multimode strip, and jumper control, for any baud
fiber data rate 115.2K selectable bias / rate / data bits
bits/second termination
• Maximum attenuation
5.5db
SK-F485C Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
PHYSICAL WIRING
Dimensions: 4.75”W x 4.25”H x 1.0”D Follow the table for wiring the SK-F485C to a
ENVIRONMENTAL compatible FACP.
Operating Temperature: 32ºF-120ºF (0ºC -49ºC)
Humidity: 10%-93% non-condensing SK-F485C FACP SBUS OUT
TERMINALS TERMINALS
ELECTRICAL
External Power Supply: 9 - 35VDC @ 125mA max.
+ +
– –
ORDERING INFORMATION
A A
SK-F485C: Copper to Fiber Converter
B B
ACCESSORIES
5815RMK: Remote Mounting Kit 10.2" H x 10.4" W
x 3" D. Cabinet holds up to two SK-486C. Red AGENCY LISTINGS AND APPROVALS
5815RMKB: Remote Mounting Kit 10.2" H x 10.4"
• CSFM
W x 3" D. Cabinet holds up to two SK-486C. Black
• UL Listed
The 6815 communicates with the FACP via an RS 485 system bus. A green
LED on the 6815 board blinks to indicate good communication. If an
addressable device on a 6815 fails, the loop communicates the failure to
the FACP and continues to operate normally
6815
Compatibility
The 6815 is compatible with the following Farenhyt Series FACP's:
• IFP-2100/ECS
• IFP-2100/ECSB
• RFP-2100
• RFP-2100B
• IFP-300/ECS
• FP-300/ECSB
F E AT U R E S & B E N E F I T S
• Adds support for up to • House up to two • SLC wiring used • UL 864 listed,
159 IDP/SK sensors 6815s in the standard wire. Twisted complies with NFPA
and 159 IDP/SK IFP-2100/ECS , pair or shield cable are 72 and 101
modules per IFP-300/ RFP-2100, IFP-300/ not required
• Support for IDP, SK or
ECS or IFP-2100/ECS ECS, RPS-1000
SWIFT devices
panel cabinets, or in the
5815RMK remote
• Communicates with
mounting kit
the FACP via RS 485
system bus
• LED indicates good
communication
6815 Technical Specifications
PHYSICAL ORDERING INFORMATION For a complete listing of all
Dimensions: 4.2"H x 4.8"" W (10.7 x 12.2 cm) 6815: Signaling Line Circuit Expander. compliance approvals and
certifications, please visit
Shipping Weight: 5.6oz (159 g). www.farenhyt.com.
ACCESSORIES
ELECTRICAL RPS-1000: Intelligent Power Module. Cabinet Microsoft, Windows, and
holds two 6815s. the Windows Logo are
Standby & Alarm Current: 78mA max
registered trademarks
5815RMK: Remote Mounting Kit Cabinet holds two or trademarks of
ENVIRONMENTAL 6815s. Red cabinet Microsoft Corporation.
Operating Temperature: 32°F to 120°F (0°C to 5815RMKB: Remote Mounting Kit Cabinet holds
49°C) two 6815s. Black cabinet. SWIFT® and Honeywell®
are registered trademarks
Humidity: 0 to 93% non-condensing SK-NIC-KIT: Remote Mounting Kit Cabinet. holds of and Farenhyt™ is a
one 6815. 10-3.8" W x 10-3/16" H x 3" D trademark of Honeywell
SYSTEM CAPACITY International, Inc.
IFP-2100/ECS FACP supports 63 6815s (but a AGENCY LISTIINGS AND APPROVALS
This document is not
maximum of 2100 SLC devices per system) NFPA 13, NFPA 15, NFPA 16, NFPA 70, &
intended to be used for
IFP-300/ECS FACP supports 63 5815XLs (but a NFPA 72: Central Station; Remote Signalling; Local installation purposes. We
maximum of 300 SLC devices per system) Protective Signalling Systems; Auxiliary Protected try to keep our product
6815 Capacity: 159 IDP or SK sensors and 159 IDP Premises Unit; & Water Deluge Releasing Service. information up-to
or SK modules per loop Suitable for automatic, manual, waterflow, sprinkler date and accurate. We
supervisory (DACT non-coded) signalling services. cannot cover all specific
applications or anticipate
UL listed all requirements. All
CSFM listed specifications are subject
FDNY COA 6245 to change without notice.
FM approved For Technical
Support, Please call
800-446-6444.
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 351620 | A | 11/17
800-328-0103 © 2017 Honeywell International Inc.
SK-NIC
Network Interface Card
The SK-NIC, Network Interface Card, is an optional component of the
Honeywell Farenhyt Series fire alarm control panels. It allows the sub-
assemblies to connect to the Broadband network from remote locations:
INSTALLATION
SK-NIC
The SK-NIC is adaptable for an installation in the standard Honeywell
Farenhyt Series cabinets. Typically, the SK-NIC card is mounted on
standoffs under the motherboard. (Except with the IFP-75). For
instructions on the installation of the SK-NIC, refer to the following
documents:
COMPATIBILITY
The SK-NIC is compatible with the following Farenhyt Series FACP's:
• IFP-2100/ECS or IFP-2100/ECSB
• IFP-300/ECS or IFP-300/ECSB
• IFP-75 or IFP-75B
F E AT U R E S & B E N E F I T S
• Listed under UL® • Provides add-on • SK-NIC-KIT accessory • Has 625K baud
Standard 864, 9th fiber-optic modules kit is available if you ARCNET Repeater
Edition that allow the network want to install the
connection through SK-NIC outside of the
• Provides the capability
single or multi-mode FACP cabinet
for networked FACPs
fiber-optic cables
to connect in Styles 4 •
or 7 configurations • SK-NIC can be
mounted within the
• Offers standard
FACP cabinet. (Except
unshielded, twisted-
with IFP-75)
pair copper wire
network connections.
SK-NIC Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
For Technical
SPECIFICATIONS ORDERING INFORMATION Support, Please call
SK-NIC: Network Interface Card 800-446-6444.
ENVIRONMENTAL
Operating Temperature: 32°F to 120°F (0°C to ACCESSORIES
49°C) SK-NIC-KIT: Accessory kit for installing the SK-NIC
Humidity: 0 to 93% relative humidity (non- outside of the FACP cabinet. Includes one SK-NIC
condensing) Network Card.
SK-FML: Fiber Module, multi-mode
ELECTRICAL: SK-FSL: Fiber Module, single-mode
Operating Voltage: 24VDC
Standby Current: 21mA AGENCY LISTINGS AND APPROVALS
Alarm Current: 21mA UL listed
CSFM approved
WIRING SPECIFICATIONS: NFPA 72
Copper Wire: 16 to 18 AWG twisted-pair, FM approved
unshielded
FDNY COA#: 6162
Up to 3,000 ft. (914.4 m) between each node.
Fiber-Optic Cable: (SK-FML only) Up to 200
microns optimized for 62.5/125 microns. Up to 8
dB loss between nodes.
Fiber-Optic Cable: (SK-FSL only) Optimized for
9/125 micrometer cable @ 1310 nm. Up to 30dB
loss between nodes.
Each fiber loop module can Transmit (TX) or Receive (RX) fiber-optic cable
connecting to the SK-NIC. Up to two fiber loop cards can be added to the
SK-NIC, and both cards may be combined in the same configuration. Both
modules are listed per ANSI/UL Standard 864, 9th addition. SK-FSL (SINGLE MODE FIBER)
Compatibility
The SK-FSL and SK-FML are compatible with the following Honeywell Farenhyt
Series FACPs:
• IFP-2100/ECS or IFP-2100/ECSB
• IFP-300/ECS or IFP-300/ECSB
• IFP-75 or IFP-75B
F E AT U R E S & B E N E F I T S
• Listed per ANSI/UL® • SK-FSL features • Simple plug-in card
Standard 864 9th LC-style connectors installation
edition with a maximum
attenuation of 30db
• SK-FML features
with 9/125
ST-style connectors
micrometer cable
with a maximum
attenuation of 8 dB • Offers the option to
with 62.5/125 combine single and
micrometer cable multi-mode modules
on the same network
card
SK-FML AND SK-FSL Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
For Technical
INSTALLATION ORDERING INFORMATION Support, Please call
The SK-FML and SK-FSL modules are designed to SK-FML: Fiber Module, multi-mode 800-446-6444.
plug into their designated spots on the SK-NIC SK-FSL: Fiber Module, single-mode
card.
ACCESSORIES
ENVIRONMENTAL SK-NIC: Network Interface Card
Operating Temperature: 32°F to 120°F (0°C to SK-NIC-KIT: Accessory kit for installing the SK-NIC
49°C) outside of the FACP cabinet (required for 6700
Humidity: 0 to 93% relative humidity (non panel installation). Includes one SK-NIC Network
condensing) Card.
SK-FML SK-FSL
Connection: ST syle LC style AGENCY LISTINGS AND APPROVALS
Cable Type: 62.5/125 9/125 UL listed
micrometers micrometers FM approved
Standby Current: 0.053A 0.079A CSFM approved
Alarm Current: 0.053A 0.079A NFPA 72
FDNY COA: 6162
cabinet with lock and key and includes external antenna that mounts on
top of the unit. The CELL-MOD houses the GSM communicator inside a
plastic enclosure that may or may not require an external antenna
depending on the installation environment. Both models can be remotely
mounted away from the fire alarm control panel via a 4-wire bus for
CELL-MOD
optimum reception.
F E AT U R E S & B E N E F I T S
• Cellular card comes in • UL 864 and NFPA 72 • Includes Quality of • Programmable • Accounts can be easily
a plastic case or metal code compliant for Service (QOS) supervision time from managed through
enclosure with lock sole, primary, or diagnostics via 1 to 60 minutes on-line management
and key backup AlarmNet which tools
• Provides full data
communications conveys vital
• 4-wire bus connection reporting using
communicator
allows remote • Optional external Contact ID format
information, including
mounting for best antennas
when messages are
reception
received, signal
strength, and message
path used
CELL-CAB-SK / CELL-MOD Technical Specifications
PECIFICATIONS ORDERING INFORMATION For a complete listing of all
CELL-CAB-SK: Cellular module housed in metal compliance approvals and
PHYSICAL certifications, please visit
cabinet with lock and key. Includes external
www.farenhyt.com.
Overall Dimensions: antenna
CELL-CAB-SK: 10.38"W x 10.165"H x 3.176"D CELL-MOD: Cellular module housed in plastic Microsoft, Windows, and
enclosure. (External antenna sold separately) the Windows Logo are
CELL-MOD: 7.809"W x 5.982"H x 1.5"D
registered trademarks
Shipping Weight: 1.3lbs (CELL-MOD) GSM-ANT3DB: 3dB gain external/remote antenna
or trademarks of
5.2lbs (CELL-CAB-SK) 7626-50HC: 50 ft. antenna cable, low loss Microsoft Corporation.
Color: Red
AGENCY LISITINGS AND APPROVALS SWIFT® and Honeywell®
are registered trademarks
ENVIRONMENTAL UL 864, NFPA 72 of and Farenhyt™ is a
Operating Temperature: 32°F to 120°F (0°C to FCC ID: CFS8DLPHS8-US trademark of Honeywell
49°C) International, Inc.
Humidity: 10 to 93% relative humidity (non- COMPATIBILITY
This document is not
condensing) The CELL-CAB-SK and CELL-MOD are intended to be used for
compatible with the following Farenhyt Series installation purposes. We
ELECTRICAL FACPs: try to keep our product
Standby Current: 55mA information up-to
• IFP-75 / IFP-75B date and accurate. We
Alarm Current: 100mA cannot cover all specific
• IFP-300 / IFP-300B applications or anticipate
RADIO TRANSCEIVER all requirements. All
3G Cellular Radio specifications are subject
• IFP-300ECS / IFP-300ECSB to change without notice.
UMTS WCDMA FDD 850/1900MHz
FCC part 15, 22, 24, and 68 compliant For Technical
• IFP-2100 / IFP-2100B Support, Please call
COMMUNICATION PROTOCOLS 800-446-6444.
HSPA+ (4G) and HSPA (HSDPA & HSUPA) (3G) • IFP-2100ECS / IFP-2100ECSB
Port 2 Port 1
copper wire
Compatibility terminals
Fiber
Modules
Copper
Wire Terminal
Farenhyt™ is a trademark, Silent Knight® and Honeywell® are registered trademarks of Honeywell International, Inc.
Compatibility
Specifications
Standby Current: 78mA
Alarm Current: 78mA
Operating Voltage: 24VDC
Operating Temperature: 32°F to 120°F
(0°C to 49°C) Figure 1: Standoff Installation and 6815 Board
Mounting
Mounting Wiring
You can mount the 6815 in a compatible FACP
See Table 1 and Figure 2 to wire a 6815 to a
cabinet, in the 5895XL or RPS-1000 intelligent
compatible FACP or the 5895XL.
power module cabinet, or in the SK-NIC-KIT
remote mounting kit. Table 1: 6815 to FACP Connections
Farenhyt™ is a trademark, Silent Knight® and Honeywell® are registered trademarks of Honeywell International, Inc.
The B210LP and B501 have screw terminals for power (+) and (-) and
remote annunciator connections. Communication takes place over the
power (+) and (-) lines.
INSTALLATION
The B210LP and B501 can be mounted on a variety of junction boxes as
shown in the tables below. B210LP BASE
*Box depth is contingent on base and wire size. Refer to the National Electric
B501 BASE
Code or applicable local codes for appropriate recommendations.
F E AT U R E S & B E N E F I T S
• Plug-in mounting • Rotary address • CSFM Listed
provides ease of switches for fast
• FM Listed
installation installation
• MEA Listed 205-91-E
• Tamper-proof feature • Optional remote LED
Vol, IX
prevents removal of annunciator (P/N
the detector without RA100Z)
the use of a tool
• SEMS screws
• Range of mounting
• 12–22 AWG wire
options to meet any
ranges for installation
application
flexibility
• UL Listed
B210LP and B501 Technical Specifications
For a complete listing of all
PHYSICAL COMPATIBILITY compliance approvals and
certifications, please visit
B210LP Diameter: 6.1” (155 mm) The B210LP and B501 are compatible with the www.farenhyt.com.
B501 Diameter: 4.1” (104 mm) following IDP series detectors:
IDP-Photo: Photoelectric Smoke Detector Microsoft, Windows, and
ELECTRICAL RATINGS the Windows Logo are
IDP-Photo-T: Photoelectric Smoke Detector with
registered trademarks
Operating Voltage: 15 to 32VDC Thermal or trademarks of
Wire Gauge: 18–12 IDP-Acclimate: Multicriteria Photoelectric Smoke Microsoft Corporation.
SLC Standby and Alarm Current: 170μA Detector
Honeywell® and
Terminals IDP-Heat: Fixed Temperature Thermal Detector
System Sensor® are
Terminal 1: Power (–) and Optional RA100Z IDP-Heat-ROR: Rate-of-Rise Detector with registered trademarks
Terminal 2: Power (+) Thermal of and Farenhyt™ is a
IDP-Heat-HT: Fixed High Temperature Thermal trademark of Honeywell
Terminal 3: Optional RA100Z Remote International, Inc.
Annunciator Detector
The B210LP and B501 are compatible with the This document is not
ENVIRONMENTAL following Farenhyt Series FACPs: intended to be used for
installation purposes. We
Operating Temperature: 32º-120ºF (0ºC – 49ºC) • IFP-2100 / IFP-2100ECS / RFP-2100 try to keep our product
Humidity: 10 to 93% non-condensing) information up-to
• IFP-2000 / IFP-2000ECS / RPS-2000 date and accurate. We
ORDERING INFORMATION cannot cover all specific
• IFP-1000 / IFP-1000ECS applications or anticipate
B210LP: 6” Mounting Base
all requirements. All
B501 4: Mounting Base • IFP-300 / IFP-300ECS specifications are subject
B210LPBP: 6” Mounting Base bulk pkg of 10 to change without notice.
• IFP-100 / IFP-100ECS
ACCESSORIES For Technical
RA100Z: Remote LED Annunciator. • IFP-75 Support, Please call
800-446-6444.
XR2B: Detector Removal Tool. A removal and
replacement tool for IDP plug-in detectors.
• IFP-50
Includes the T55-127-000.
M02-04-00: Detector Test Magnet.
M02-09-00: Test Magnet with Telescoping
Handle.
XP-4: Extension Pole for XR2B. Extends from 5 –
15 ft.
T55-127-000: Detector Removal Head.
BCK-200B: Black Detector Kit. For IDP-series
detectors.
F210: Accessory flange ring for B210LP
INSTALLATION
The B224RB can be mounted on a variety of junction
boxes as shown in the tables below.
B224RB RELAY BASE
U.S. Junction Box Selection Guide*
SINGLE GANG 3.5"OCT 4" OCT † 4" SQ
*Box depth is contingent on base and wire size. Refer to the National Electric
Code or applicable local codes for appropriate recommendations.
†With 3.0 mud ring
F E AT U R E S & B E N E F I T S
• One form C contact • Tamper-proof feature • B501 allows for • UL Listed
relay prevents removal of aesthetically pleasing
• CSFM Listed
the detector without installation with
• Support for Class A
the use of a tool Recessed Mounting • FMListed
and Class B wiring
Kit (RMK400)
• Range of mounting
• Fully supervised
options to meet any
• Plug-in mounting application
provides ease of
installation
B224RB Technical Specifications
For a complete listing of all
PHYSICAL COMPATIBILITY compliance approvals and
certifications, please visit
Height: 1.2” (3.1 cm) The B224RB is compatible with the following IDP www.farenhyt.com.
Diameter: 6.1” (15.5cm) series detectors:
Microsoft, Windows, and
• IDP-Photo Photoelectric Smoke Detector
ELECTRICAL RATINGS the Windows Logo are
• IDP-Photo-T Photoelectric Smoke Detector registered trademarks
Wire Gauge: 18–14 or trademarks of
Operating Voltage: 15 – 32VDC with Thermal Microsoft Corporation.
Standby Current: 500 μA max @ 24VDC. • IDP-Acclimate Multicriteria Photoelectric Honeywell® and
Smoke Detector System Sensor® are
RELAY CHARACTERISTICS: registered trademarks
Coil: 2 coil latching relay • IDP-Heat Fixed Temperature Thermal Detector of and Farenhyt™ is a
Contact: 1 Form C contact trademark of Honeywell
• IDP-Heat-ROR Rate-of-Rise Detector with International, Inc.
Resistive: 2A @ 30 VDC Thermal
Inductive: This document is not
• IDP-Heat-HT Fixed High Temperature Thermal intended to be used for
300 mA @ 100 VDC( with 0.35 PF or greater)
Detector installation purposes. We
300 mA @ 120 VAC (with 0.35 PF or greater) try to keep our product
1A @ 30 VDC (with 0.6 PF or greater) The B224RB is compatible with the following information up-to
Farenhyt Series FACPs: date and accurate. We
ENVIRONMENTAL cannot cover all specific
• IFP-2100 / IFP-2100ECS / RFP-2100 applications or anticipate
Operating Temperature: 32º-120ºF (0ºC – 49ºC) all requirements. All
• IFP-2000 / IFP-2000ECS / RPS-2000
Humidity: 10 to 93% non-condensing) specifications are subject
• IFP-1000 / IFP-1000ECS to change without notice.
ORDERING INFORMATION
• IFP-300 / IFP-300ECS For Technical
B224RB: 6” Relay Base Support, Please call
ACCESSORIES • IFP-100 / IFP-100ECS 800-446-6444.
IDP-FIRE-CO can also be used with the B210LP 6” standard base, the
B200SR sounder base or the B224RB relay base.
F E AT U R E S & B E N E F I T S
• Unique ability to • Automatic drift • RealTest ® CO testing • Separates audible
detect all four major compensation of capability signal for fire or CO
elements of a fire, smoke sensor and CO alarm when used with
• UL 268 and UL 2075
smoke, carbon cell B200S/B200S-LF
listed
monoxide (CO), light/ base
• Uses only one address
flame, heat
on the SLC • CO cell end-of-life
• Separate CO detection warning and fault
signal
• CSFM listed
• Highest nuisance
alarm immunity
IDP-FIRE-CO Technical Specifications
PHYSICAL Note: Per UL Standard 2075, the IDP-FIRE-CO has For a complete listing of all
Diameter: 6.875” (17.46 cm) installed in a B200S been tested to the sensitivity limits defined in UL compliance approvals and
Standard 2034. certifications, please visit
base
www.farenhyt.com.
Height: 3.46” (8.79 cm) installed in B200S base
ORDERING INFORMATION Microsoft, Windows, and
Shipping Weight: 4.6 oz
IDP-FIRE-CO: Multi-Criteria CO Detector (base not the Windows Logo are
Color: Ivory registered trademarks
included).
Note: Due to the unique nature of this detector, or trademarks of
ENVIROMENTAL Microsoft Corporation.
please consult your fire alarm control panel
Temperature Range: 32° F to 100° F (0° C to 38° manufacturer for the specific model and Honeywell® is a
C) compatibility. registered trademark
Humidity: 15 to 90% relative humidity (non- of and Farenhyt™ is a
condensing) OPTIONAL ACCESSORIES trademark of Honeywell
Air Velocity: 0 to 4,000 ft/min (0 to 20 m/sec) B200S: Intelligent sounder base International, Inc.
The sounder base “listens in” to the communication between the attached
sensor head and the fire alarm control panel (FACP) to adopt the same
address as the detector, but as a unique device type on the loop. The FACP
can then use that address to command an individual sounder — or a group
of sounders — to activate. In addition, the FACP’s will enable custom tone
B200S-LF
patterns.
The B200S-LF low frequency sounder base is designed to meet the NFPA
72 sleeping space requirement to produce a fundamental frequency of 520
Hz +/- 10% with a square wave or its equivalent. Studies show that a lower
frequency, centered around 520 Hz, is the most ideal to awaken sleeping
occupants, even those with mild to severe hearing loss.
B200S
INSTALLATION
The B200S series sounder bases can be mounted directly to 4” (10.16 cm)
square, 4” (10.16 cm) octagon, 3 1/2” (8.9 cm) octagon, single-gang or
double-gang junction boxes.
F E AT U R E S & B E N E F I T S
• Addressability for • Ability to synchronize • Uses a mechanical • 520 Hz +/– 10%
maximum with other System locking feature that square wave tone
configuration Sensor notification prevents the removal (B200S-LF)
flexibility devices of the attached sensor
• UL Listed
head
• Supports Continuous, • UL 268 and UL 464
• FM Approved
ANSI Temporal 3, ANSI compliant • No external relays and
Temporal 4, and input modules needed
• Pre-wire mounting
March Time tones to supervise the Aux
plate fits various
power
• Custom tone junction box sizes
capability with some
FACP models
B200S and B200S-LF Technical Specifications
For a complete listing of all
compliance approvals and
PHYSICAL COMPATIBILITY
certifications, please visit
Height: 2.0” (5.08 cm) less sensor The B200S and B200S-LF are compatible with www.farenhyt.com.
Width: 6.875” (17.46 cm) the following IDP series detectors:
IDP-Photo: Photoelectric smoke detector Microsoft, Windows, and
Shipping Weight: B200S 0.50 lb. (227 gm); the Windows Logo are
B200S-LF: 0.60 lb. (272 gm) IDP-Photo-T: Photoelectric smoke detector with registered trademarks
thermal or trademarks of
ENVIRONMENTAL IDP-Acclimate: Multicriteria Photoelectric smoke Microsoft Corporation.
Operating Temperature: 32°F - 120°F (0°C-49°C) detector
Honeywell® and
Humidity: 10 to 93% non-condensing) IDP-Heat: Fixed temperature thermal detector System Sensor® are
IDP-Heat-ROR: Rate-of-Rise detector with thermal registered trademark
ELECTRICAL RATINGS IDP-Heat-HT: Fixed high temperature thermal of and Farenhyt™ is a
trademark of Honeywell
Aux power voltage: 16 to 33 VDC (VFWR) detector
International, Inc.
Aux power standby current B200S: .50mA max. IDP-FIRE-CO: Multi criteria CO and smoke sensor
Aux power standby current B200S-LF: .55mA max The B200S and B200S-LF are compatible This document is not
with the following Farenhyt Series FACPs intended to be used for
Aux power alarm current B200S: 35mA max. installation purposes. We
Aux power alarm current B200S-LF: 140mA max. IFP-2100 / IFP-2100ECS / RFP-2100 try to keep our product
SLC operating voltage: 15 to 32 VDC IFP-2000 / IFP-2000ECS / RPS-2000 information up-to
IFP-1000 / IFP-1000ECS date and accurate. We
SLC Standby/Alarm Current: 300 μA max (base cannot cover all specific
only) IFP-300 / IFP-300ECS applications or anticipate
IFP-100 / IFP-100ECS all requirements. All
SOUND OUTPUT IFP-75 specifications are subject
Volume Greater than 85 dBA minimum measured in to change without notice.
IFP-50
a UL reverberant room at 10 feet, 24 Volts (in For Technical
continuous tone). Support, Please call
800-446-6444.
ORDERING INFORMATION
B200S: Sounder Base
B200S-LF: Low Frequency Sounder Base
ACCESSORIES
M02-04-01: Detector Test Magnet
M02-09-01: Telescoping Test Magnet
F E AT U R E S & B E N E F I T S
• Designed to meet UL • Dual LEDs for 360°
268 7th Edition visibility
• New modern profile • Expanded color
options
• Analog
communications
• Low standby current
• Rotary address
switches
Farenhyt Series Black Intelligent Detector Technical Specifications
PHYSICAL IDP-HEAT-HT-W: hermal heat detector, 190°F For a complete listing of all
Height: 2.0" (51mm) installed in B300-6 base high temp, white. -IV: Ivory compliance approvals and
certifications, please visit
Diameter: 6.2" (156mm) installed in B300-6 base www.farenhyt.com.
4.1" (104 mm) installed in B501 base BASES
Weight: 3.4 oz (95 g) B501: 4” mounting base, white. -IV: Ivory (effective Honeywell® and
1/15/2018) System Sensor® are
registered trademark
ENVIRONMENTAL B501BP: 4” mounting base bulk pack, white
of and Farenhyt™ is a
Operating Temperature: (effective 1/15/2018) trademark of Honeywell
Photo: 32°F to 122°F (0°C to 50°C) B300-6: 6” Flanged mounting base, white. -IV: International, Inc.
Ivory
Photo with Thermal: 32°F to 100°F (0°C to 38°C) This document is not
B300-6-BP: 6” Flanged mounting base bulk pack
Heat -Fixed temperature: -4°F to 100°F (-20°C to intended to be used for
38°C) B200S: Intelligent addressable sounder base, installation purposes. We
white. -IV: Ivory (effective 1/15/2018) try to keep our product
Heat -Rate of Rise (ROR): -4°F to 100°F (-20°C to
B200S-LF: Intelligent addressable low frequency information up-to
38°C)
sounder base, white. -IV: Ivory (effective date and accurate. We
Heat -High Temperature: -4°F to 150°F (-20°C to cannot cover all specific
1/15/2018)
66°C) applications or anticipate
B200SR: Intelligent sounder base, white. -IV: Ivory all requirements. All
UL listed Velocity range: Photo/Photo with
(effective 1/15/2018) specifications are subject
Thermal: 0 to 4,000 fpm (0 to 20 m/sec) (suitable
B224RB: Relay base, white. -IV: Ivory (effective to change without notice.
for installation in ducts)
1/15/2018)
Humidity: 10% to 93% non-condensing For Technical
B224BI: Isolator base, white. -IV: Ivory (effective Support, Please call
Thermal Ratings: Fixed Temperature Set point:
1/15/2018) 800-446-6444.
135°F (57°C)
Rate-of-Rise Detection: 15°F/min. (8.3°C/min.) ACCESSORIES
High Temperature Heat: 190°F (88°C) SMB600: Surface Mounting Kit (flanged)
TR300: Accessory Flange Ring for B300 6” Base,
ELECTRICAL RATINGS
bright white. -IV: Ivory
Voltage Range: 15 to 32VDC peak
CK300: Color Kit (includes cover and trim ring),
Operating Current @ 24VDC: 200µA (one white. -IV: Ivory
communication every 5 seconds with green LED
RA100Z: Remote LED annunciator. Ivory
blink on communication)
M02-04-01: Destector test magnet. Ivory
Maximum Current: 4.5mA @ 24VDC (one
communication every 5 seconds with amber LED M02-09-00: telescoping test magnet. Ivory
solid on)
AGENCY LISTINGS AND APPROVALS
Maximum Alarm Current: 2mA @ 24VDC (one
communication every 5 seconds with red LED solid For exact certification listings for each model,
on) please reference the respective agency Web site.
UL listed
ORDERING INFORMATION FM approved
IDP-PHOTO-W: Photoelectric smoke detector, CSFM
bright white. -IV: Ivory
IDP-PHOTO-R-W: Photoelectric smoke detector, COMPATIBILITY
remote test capable, for use with DNR(W) duct The IDP-PHOTO-W/IV, IDP-PHOTO-T-W/IV,
smoke detectors, bright white. -IV: Ivory IDP-PHOTO-R-W/IV, IDP-HEAT-W/IV, IDP-
IDP-PHOTO-T-W: Photoelectric smoke detector HEAT-ROR-W/IV and IDP-HEAT-HT-W/IV are
with thermal sensing, bright white. -IV: Ivory compatible with the following Farenhyt Series
FACPs:
IDP-HEAT-W: Thermal heat detector, 135°F fixed,
• IFP-2100 / IFP-2100ECS / RFP-2100
white. -IV: Ivory
• IFP-2000 / IFP-2000ECS / RPS-2000
IDP-HEAT-ROR-W: Thermal heat detector, 135°F
rate of rise, white. -IV: Ivory • IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
• IFP-100 / IFP-100ECS
For more information
• IFP-75
Learn more about Honeywell’s Farenhyt Series and
other products available by visiting • IFP-50
www.farenhyt.com
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 351629 | Rev A| 12/17
800-328-0103 © 2017 Honeywell International Inc.
B200S / B200S-LF
Intelligent Sounder Base
The B200S sounder base series is designed for new and existing
commercial dwelling unit applications. It offers maximum flexibility in
installation, configuration, and operation to meet or exceed UL 268 and UL
464 requirements.
The sounder base “listens in” to the communication between the attached
sensor head and the fire alarm control panel (FACP) to adopt the same
address as the detector, but as a unique device type on the loop. The FACP
can then use that address to command an individual sounder — or a group
of sounders — to activate. In addition, the FACP’s will enable custom tone
B200S-LF
patterns.
The B200S-LF low frequency sounder base is designed to meet the NFPA
72 sleeping space requirement to produce a fundamental frequency of 520
Hz +/- 10% with a square wave or its equivalent. Studies show that a lower
frequency, centered around 520 Hz, is the most ideal to awaken sleeping
occupants, even those with mild to severe hearing loss.
B200S
INSTALLATION
The B200S series sounder bases can be mounted directly to 4” (10.16 cm)
square, 4” (10.16 cm) octagon, 3 1/2” (8.9 cm) octagon, single-gang or
double-gang junction boxes.
F E AT U R E S & B E N E F I T S
• Addressability for • Ability to synchronize • Uses a mechanical • 520 Hz +/– 10%
maximum with other System locking feature that square wave tone
configuration Sensor notification prevents the removal (B200S-LF)
flexibility devices of the attached sensor
• UL Listed
head
• Supports Continuous, • UL 268 and UL 464
• FM Approved
ANSI Temporal 3, ANSI compliant • No external relays and
Temporal 4, and input modules needed
• Pre-wire mounting
March Time tones to supervise the Aux
plate fits various
power
• Custom tone junction box sizes
capability with some
FACP models
B200S and B200S-LF Technical Specifications
For a complete listing of all
compliance approvals and
PHYSICAL COMPATIBILITY
certifications, please visit
Height: 2.0” (5.08 cm) less sensor The B200S and B200S-LF are compatible with www.farenhyt.com.
Width: 6.875” (17.46 cm) the following IDP series detectors:
IDP-Photo: Photoelectric smoke detector Microsoft, Windows, and
Shipping Weight: B200S 0.50 lb. (227 gm); the Windows Logo are
B200S-LF: 0.60 lb. (272 gm) IDP-Photo-T: Photoelectric smoke detector with registered trademarks
thermal or trademarks of
ENVIRONMENTAL IDP-Acclimate: Multicriteria Photoelectric smoke Microsoft Corporation.
Operating Temperature: 32°F - 120°F (0°C-49°C) detector
Honeywell® and
Humidity: 10 to 93% non-condensing) IDP-Heat: Fixed temperature thermal detector System Sensor® are
IDP-Heat-ROR: Rate-of-Rise detector with thermal registered trademark
ELECTRICAL RATINGS IDP-Heat-HT: Fixed high temperature thermal of and Farenhyt™ is a
trademark of Honeywell
Aux power voltage: 16 to 33 VDC (VFWR) detector
International, Inc.
Aux power standby current B200S: .50mA max. IDP-FIRE-CO: Multi criteria CO and smoke sensor
Aux power standby current B200S-LF: .55mA max The B200S and B200S-LF are compatible This document is not
with the following Farenhyt Series FACPs intended to be used for
Aux power alarm current B200S: 35mA max. installation purposes. We
Aux power alarm current B200S-LF: 140mA max. IFP-2100 / IFP-2100ECS / RFP-2100 try to keep our product
SLC operating voltage: 15 to 32 VDC IFP-2000 / IFP-2000ECS / RPS-2000 information up-to
IFP-1000 / IFP-1000ECS date and accurate. We
SLC Standby/Alarm Current: 300 μA max (base cannot cover all specific
only) IFP-300 / IFP-300ECS applications or anticipate
IFP-100 / IFP-100ECS all requirements. All
SOUND OUTPUT IFP-75 specifications are subject
Volume Greater than 85 dBA minimum measured in to change without notice.
IFP-50
a UL reverberant room at 10 feet, 24 Volts (in For Technical
continuous tone). Support, Please call
800-446-6444.
ORDERING INFORMATION
B200S: Sounder Base
B200S-LF: Low Frequency Sounder Base
ACCESSORIES
M02-04-01: Detector Test Magnet
M02-09-01: Telescoping Test Magnet
With its attractive aesthetics, the B200SR series is ideal for applications
where appearance is critical. For example, the sounder base employs a
separate mounting plate that installs on various junction box sizes to B200SR
eliminate unsightly surfacemount boxes. In addition, the mounting plate
enables pre-wiring of all connections to speed and simplify installation.
The housing then mates with the mounting plate and is locked in position
with two retaining screws, which are covered by the installed sensor head
for added tamper resistance.
The B200SR-LF low frequency sounder base is designed to meet the NFPA
72 sleeping space requirement to produce a fundamental frequency of 520
Hz +/– 10% with a square wave or its equivalent. Studies show that a lower
frequency, centered around 520 Hz, is the most ideal to awaken sleeping
occupants, even those with mild to severe hearing loss.Installation
INSTALLATION
B200SR-LF
The B200SR or B200SR-LF can be mounted directly into a 4” square by at
least 1.5” – 2.1” deep electrical box, using the supplied mounting kit.
F E AT U R E S & B E N E F I T S
• Tone selection via an • Fully compatible with • 520 Hz +/– 10%
onboard jumper existing B501BH- square wave tone
Series sounder base (B200S-LF)
• UL 268 and UL 464
installations
compliant
• Mechanical locking
• Pre-wire mounting
feature prevents the
plate fits various
removal of the
junction box sizes
attached sensor head
B200SR and B200SR-LF Technical Specifications
For a complete listing of all
compliance approvals and
PHYSICAL COMPATIBILITY certifications, please visit
www.farenhyt.com.
Height: 2.0” (5.08 cm) less sensor The B200SR is compatible with the following IDP
Width: 6.875” (17.46 cm) series detectors: Microsoft, Windows, and
IDP-Photo: Photoelectric Smoke Detector the Windows Logo are
Shipping Weight: B200SR 0.50 lb. (227 gm);
registered trademarks
B200SR-LF: 0.60 lb. (272 gm) IDP-Photo-T: Photoelectric Smoke Detector with or trademarks of
Thermal Microsoft Corporation.
ENVIRONMENTAL IDP-Acclimate: Multicriteria Photoelectric Smoke
Detector Honeywell® and
Operating Temperature: Refer to applicable sensor
System Sensor® are
operating temperature range using the base/ IDP-Heat: Fixed Temperature Thermal Detector registered trademark
sensor cross reference chart at systemsensor.com IDP-Heat-ROR: Rate-of-Rise Detector with of and Farenhyt™ is a
Humidity: 10 to 93% non-condensing) Thermal trademark of Honeywell
IDP-Heat-HT: Fixed High Temperature Thermal International, Inc.
ELECTRICAL RATINGS Detector This document is not
External Supply Voltage:16 to 33VDC (VFWR) The B200SR and B200SR-LF are compatible intended to be used for
Alarm Current (B200SR): 35mA maximum with the following Farenhyt Series FACPs: installation purposes. We
IFP-2100 / IFP-2100ECS / RFP-2100 try to keep our product
Alarm Current (B200SR-LF): 125mA maximum
information up-to
SLC Operating Voltage: 15 to 32VDC IFP-2000 / IFP-2000ECS / RPS-2000 date and accurate. We
SLC Standby & Alarm Current: 300 μA maximum IFP-1000 / IFP-1000ECS cannot cover all specific
IFP-300 / IFP-300ECS applications or anticipate
SOUND OUTPUT all requirements. All
IFP-100 / IFP-100ECS specifications are subject
Greater than 85 dBA minimum measured in a UL IFP-75 to change without notice.
reverberant room at 10 feet, 24 Volts (in
IFP-50
continuous tone) For Technical
Support, Please call
ORDERING INFORMATION 800-446-6444.
B200SR: Sounder Base
B200SR-LF: Low Frequency Sounder Base
The B210LP and B501 have screw terminals for power (+) and (-) and
remote annunciator connections. Communication takes place over the
power (+) and (-) lines.
INSTALLATION
The B210LP and B501 can be mounted on a variety of junction boxes as
shown in the tables below. B210LP BASE
*Box depth is contingent on base and wire size. Refer to the National Electric
B501 BASE
Code or applicable local codes for appropriate recommendations.
F E AT U R E S & B E N E F I T S
• Plug-in mounting • Rotary address • CSFM Listed
provides ease of switches for fast
• FM Listed
installation installation
• MEA Listed 205-91-E
• Tamper-proof feature • Optional remote LED
Vol, IX
prevents removal of annunciator (P/N
the detector without RA100Z)
the use of a tool
• SEMS screws
• Range of mounting
• 12–22 AWG wire
options to meet any
ranges for installation
application
flexibility
• UL Listed
B210LP and B501 Technical Specifications
For a complete listing of all
PHYSICAL COMPATIBILITY compliance approvals and
certifications, please visit
B210LP Diameter: 6.1” (155 mm) The B210LP and B501 are compatible with the www.farenhyt.com.
B501 Diameter: 4.1” (104 mm) following IDP series detectors:
IDP-Photo: Photoelectric Smoke Detector Microsoft, Windows, and
ELECTRICAL RATINGS the Windows Logo are
IDP-Photo-T: Photoelectric Smoke Detector with
registered trademarks
Operating Voltage: 15 to 32VDC Thermal or trademarks of
Wire Gauge: 18–12 IDP-Acclimate: Multicriteria Photoelectric Smoke Microsoft Corporation.
SLC Standby and Alarm Current: 170μA Detector
Honeywell® and
Terminals IDP-Heat: Fixed Temperature Thermal Detector
System Sensor® are
Terminal 1: Power (–) and Optional RA100Z IDP-Heat-ROR: Rate-of-Rise Detector with registered trademarks
Terminal 2: Power (+) Thermal of and Farenhyt™ is a
IDP-Heat-HT: Fixed High Temperature Thermal trademark of Honeywell
Terminal 3: Optional RA100Z Remote International, Inc.
Annunciator Detector
The B210LP and B501 are compatible with the This document is not
ENVIRONMENTAL following Farenhyt Series FACPs: intended to be used for
installation purposes. We
Operating Temperature: 32º-120ºF (0ºC – 49ºC) • IFP-2100 / IFP-2100ECS / RFP-2100 try to keep our product
Humidity: 10 to 93% non-condensing) information up-to
• IFP-2000 / IFP-2000ECS / RPS-2000 date and accurate. We
ORDERING INFORMATION cannot cover all specific
• IFP-1000 / IFP-1000ECS applications or anticipate
B210LP: 6” Mounting Base
all requirements. All
B501 4: Mounting Base • IFP-300 / IFP-300ECS specifications are subject
B210LPBP: 6” Mounting Base bulk pkg of 10 to change without notice.
• IFP-100 / IFP-100ECS
ACCESSORIES For Technical
RA100Z: Remote LED Annunciator. • IFP-75 Support, Please call
800-446-6444.
XR2B: Detector Removal Tool. A removal and
replacement tool for IDP plug-in detectors.
• IFP-50
Includes the T55-127-000.
M02-04-00: Detector Test Magnet.
M02-09-00: Test Magnet with Telescoping
Handle.
XP-4: Extension Pole for XR2B. Extends from 5 –
15 ft.
T55-127-000: Detector Removal Head.
BCK-200B: Black Detector Kit. For IDP-series
detectors.
F210: Accessory flange ring for B210LP
The DNR and DNRW feature a pivoting housing that is flexible enough to fit
configurations from square to rectangular. They feature low-flow
technology that enables duct smoke detection throughout a broad range
DNR
of airflow environments. Many difficult to solve HVAC applications occur in
low airflow duct applications where reliable smoke detection is critical.
These duct detectors can detect smoke at air speed velocities of 100 feet
per minute or greater, while continuing the same reliable performance to
4000 feet per minute.
INSTALLATION
The DNR and DNRW are designed for use in air handling systems that have
air velocities or 100 to 4000 feet per minute (0.5 – 20.3 m/s).
F E AT U R E S & B E N E F I T S
• Photoelectric, • Patented sampling • Provides trouble • Transparent cover for • DNRW is listed as a
integrated low-flow tube installs from signal in the event the convenient visual watertight enclosure
technology front or back of the sensor cover is inspection allowing for use in the
(IDP-Photo or detector with no tools removed or improperly most extreme
• UL 268A listed
IDP-PhotoR detector required installed environments
head sold separately) • Remote testing
• Available space within • Easily accessible code • CSFM Listed
capability
• Air velocity rating from housing to wheels on sensor head
• MEA Listed -
100 to 4000 feet per accommodate (IDP-Photo sold
225-02-E Vol. V
minute (0.5 to 20.32 mounting of relay separately)
meters per second) module
• UL recognized field
• Support for Class B or • Easy to clean replaceable power and
Class A wiring sensor boards
DNR / DNRW Technical Specifications
For a complete listing of all
compliance approvals and
PHYSICAL ACCESSORIES certifications, please visit
(Rectangular): 14.38" (37 cm) L x 5" (12.7 cm) W x DST1: Metal Sampling Tube Duct Width up to 1’ www.farenhyt.com.
2.5" (6..6 cm) D DST1-5: Metal Sampling Tube Duct Widths 1’ - 2’ Microsoft, Windows, and
(Square): 7.75 " (19.7cm) L x 9 " (22.9cm) W x 2.5" DST3: Metal Sampling Tube Duct Widths 2’ – 4’ the Windows Logo are
(6.35cm) D DST5: Metal Sampling Tube Duct Widths 4’ – 8’ registered trademarks
Weight: 1.6 lb. DST10: Metal Sampling Tube Duct Widths 8’ – 12’
or trademarks of
Microsoft Corporation.
DH400OE-1: Weatherproof Enclosure
ENVIRONMENTAL
EXT: Metal Exhaust Tube Duct width 1’ Honeywell® is a
Operating Temperature: -4°F to -158°F (-20°C to registered trademark
-70°C) RA100Z: Remote LED Annunciator of and Farenhyt™ is a
Humidity: 0 to 95% non-condensing) DCOIL: Duct Accessory Coil. (see important note trademark of Honeywell
for detail) International, Inc.
AIR VELOCITY RTS151: Magnetic Remote Test station This document is not
100 to 4000 ft/min (0.5 – 20.3 m/s) RTS151KEY: Key-Activated Remote Test station intended to be used for
M02-04-00: Test Magnet installation purposes. We
ELECTRICAL try to keep our product
P48-21-00: Replacement End Cap for Metal
information up-to
Please see detector head installation manual for Sampling Tube date and accurate. We
electrical specifications cannot cover all specific
COMPATIBILITY applications or anticipate
ORDERING INFORMATION all requirements. All
The DNR and DNRW are compatible with the specifications are subject
DNR: Intelligent non-relay duct smoke detector
following Farenhyt Series FACPs: to change without notice.
DNRW: Watertight non-relay duct smoke detector
IDP-PhotoR: Addressable Photoelectric Detector For Technical
with remote test capability (not included with DNR) • IFP-2100 / ECS / RFP-2100 Support, Please call
800-446-6444.
IDP-Relay: Addressable Relay Module, must be • IFP-2000 / ECS / RPS-2000
added if relay function is required, (fits in housing)
• IFP-1000 / ECS
• IFP-300 / ECS
• IFP-100 / ECS
• IFP-75
• IFP-50
• IFP-25
detection. In a real fire, the smoke and heat sensors work together to make
the quickest possible decision. The photo sensor is optimized for
smoldering fires, the heat sensors are rate-of-rise compensated to provide
a faster response to flaming fires. The on-board intelligent software
combines both signals to give an early alarm.
F E AT U R E S & B E N E F I T S
• Reliable analog • Microprocessor-based • Dual LED indicators • Transient smoke • CSFM Listed
communications for design to provide for 360º visibility conditions are ignored
• MEA Listed 225-02-E
trouble-free operation maximum features
• On-board drift • Plug-in mounting Vol. V
• Age resistant polymer • Simple field cleaning compensation reduces provides ease of
housing for code compliance maintenance installation
• Dual electronic • 0.025” mesh bug • Detector transmits • Tamper-proof feature
thermistor design screen to keep signal to indicate available on mounting
unwanted insects out maintenance is bases
• Superior EMI
required
resistance for • Variety of mounting • Rotary address
reliability options to meet any • Detector sensitivity switches for fast
application increases in hot fires installation
• UL Listed
IDP-ACCLIMATE Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademark
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
Listed for operation from -22ºF to 131ºF (-30ºC to 55ºC), the IDP-BEAM
IDP-BEAM
and IDP-BEAM-T can be used in applications to provide early warning in
environments where temperature extremes exceed the capability of other
types of smoke detectors.
F E AT U R E S & B E N E F I T S
• 16 to 328 foot • Removable plug-in • Optional remote test • Paintable cover
protection range terminal blocks station
• UL Listed
• Single-ended, • Digital display for easy • Rotary address
• CSFM Listed
reflective design alignment switches for fast
installation • MEA Listed 95-01-E
• User friendly • Built-in automatic
Vol. II
alignment procedure gain control
compensates for
• Six user selectable
signal deterioration
sensitivity levels
from dust build-up
• Optional integral
NFPA 72 sensitivity
test feature
IDP-BEAM and IDP-BEAM-T Technical Specifications
For a complete listing of all
compliance approvals and
OPERATING ORDERING INFORMATION certifications, please visit
Protection Range: 16’ – 328’ (5 – 100 m) IDP-Beam: Beam Smoke Detector www.farenhyt.com.
Adjustment Angle: +/–10º horizontal & vertical IDP-Beam-T: Beam Smoke Detector with Test Microsoft, Windows, and
(optics move independent of the unit) Feature the Windows Logo are
Sensitivity Levels: Level 1–25%; Level 2–30%; registered trademarks
Level 3–40%; Level 4–50%; Acclimate Level 1–30 ACCESSORIES or trademarks of
to 50%; Acclimate Level 2–40 to 50% BEAMLRK: Long Range Accessory Kit. Required for Microsoft Corporation.
Fault Condition (Trouble): 96% or more applications in excess of 230 ft (70m). Honeywell® and
obscuration blockage in alignment mode; improper BEAMMMK: Multi-Mount Kit. Provides ceiling or System Sensor® are
alignment; self-compensation limit reached wall mount capability with increased angular registered trademarks
Alignment Aid: Optical gunsight; integral signal adjustment for either the beam or the reflector. of and Farenhyt™ is a
When installed with the transmitter/receiver unit, trademark of Honeywell
strength indication; 2-digit display
BEAMSMK must also be used. International, Inc.
LEDs: Normal–flashing green; Yellow–trouble;
Red–alarm BEAMSMK: Surface Mount Kit This document is not
Test/Rest Feature: Integral sensitivity test filter RTS151: Remote Test Station. Used to initiate the intended to be used for
NFPA sensitivity test function. installation purposes. We
(IDP-Beam-T only); sensitivity filter (incremental
try to keep our product
scale on reflector); local test switch; local reset RTS151KEY: Remote Test Station with Key Lock information up-to
switch; remote test and reset switch (compatible BEAMHK: Heater Kit for Transmitter/Receiver Unit. date and accurate. We
with RTS151 and RTS151KEY test station) See electrical requirement. cannot cover all specific
BEAMHKR: Heater Kit for Reflector. See electrical applications or anticipate
PHYSICAL all requirements. All
requirements.
Detector: 10”H x 7.5”W x 3.3”D (25.4 x 19.1 x 8.4 specifications are subject
to change without notice.
cm) COMPATIBILITY
Reflector for 16’ – 230’: 7.9” H (20 cm) x 9.1” W (23 The IDP-BEAM and IDP-BEAM-T are compatible For Technical
cm) with the following Farenhyt Series FACPs: Support, Please call
800-446-6444.
Reflector for Beyond 230’: 15.7” H (40 cm) x 18.1”
W (46 cm) • IFP-2100 / IFP-2100ECS / RFP-2100
Shipping Weight: 3.9 lbs (1.8 kg) • IFP-2000 / IFP-2000ECS / RPS-2000
ENVIRONMENTAL • IFP-1000 / IFP-1000ECS
Operating Temperature: 32º-100ºF (0ºC–38ºC)
Humidity: 10 to 93% non-condensing) • IFP-300 / IFP-300ECS
F E AT U R E S & B E N E F I T S
• Sleek, low-profile • Superior EMI • Plug-in mounting • Tamper-proof feature • UL Listed
design resistance for provides ease of available on mounting
• CSFM Listed
reliability installation bases
• Reliable analog
• MEA Listed 383-02-E
communications for • Variety of mounting • Optional remote LED • Rotary address
Vol. VI
trouble-free operation options to meet any annunciator (System switches for fast
application Sensor ® PN RA100Z) installation
• Age resistant polymer
housing • Dual LED indicators
for 360º visibility
• Innovative thermistor
sensing circuit • Detector transmits
signal to indicate
maintenance is
required
IDP-HEAT, IDP-HEAT-HT and IDP-HEAT-ROR Technical Specifications
For a complete listing of all
compliance approvals and
PHYSICAL COMPATIBILITY certifications, please visit
Height: 2.0” (5.08cm) The IDP-HEAT, IDP-HEAT-HT, and IDP-HEAT-
www.farenhyt.com.
Diameter: 4.1" (10.4CM) installed in B501 base. Microsoft, Windows, and
6.1" installed in B210LP base ROR are compatible with the following IDP series
the Windows Logo are
Shipping Weight: 4.8oz bases: registered trademarks
or trademarks of
ELECTRICAL RATINGS • B210LP 6” Mounting Base Microsoft Corporation.
Operating Voltage: 15 – 32VDC Honeywell® and
SLC Standby and Alarm Current: 300 μA • B501 4” Mounting Base System Sensor® are
registered trademarks
• B224BI 6” Isolator Base of and Farenhyt™ is a
ENVIRONMENTAL
trademark of Honeywell
Operating Temperature • B224RB 6” Relay Base International, Inc.
IDP-Heat & IDP-Heat-ROR: -4°F - 100 °F (-20°C
- 38°C) • B200SR 6” Sounder Base This document is not
intended to be used for
IDP-Heat-HT: -4°F - 150 °F (-20°C - 66°C)
The IDP-HEAT, IDP-HEAT-HT, and IDP-HEAT- installation purposes. We
Humidity: 10 to 93% non-condensing) try to keep our product
ROR are compatible with the following Farenhyt information up-to
THERMAL RATINGS Series FACPs: date and accurate. We
cannot cover all specific
IDP-Heat: Fixed temperature setpoint 135ºF
applications or anticipate
(57ºC) • IFP-2100 / IFP-2100ECS / RFP-2100 all requirements. All
IDP-Heat-HT: High temperature heat 135ºF – specifications are subject
190ºF (57ºC – 88ºC) • IFP-2000 / IFP-2000ECS / RPS-2000 to change without notice.
IDP-Heat-ROR: Rate-of-rise detection 15ºF/min
• IFP-1000 / IFP-1000ECS For Technical
(9ºC/min) Support, Please call
• IFP-300 / IFP-300ECS 800-446-6444.
ORDERING INFORMATION
IDP-Heat: Fixed temperature thermal detector • IFP-100 / IFP-100ECS
IDP-Heat-HT: Fixed high temperature thermal
detector • IFP-75
IDP-Heat-ROR: Fixed temperature and rate-of- • IFP-50
rise thermal detector
ACCESSORIES
RA100Z: Remote LED Annunciator.
XR2B: Detector Removal Tool. A removal and
replacement tool for IDP plug-in detectors.
Includes the T55-127-000.
M02-04-01: Detector test magnet
M02-09-00: Test Magnet with telescoping handle
XP-4: Extension pole for XR2B. Extends from 5 –
15 ft.
T55-127-000: Detector removal head.
BCK-200B: Black detector kit. For IDP-series
detectors.
* Unless otherwise noted, specifications apply to
IDP thermal detectors.
F E AT U R E S & B E N E F I T S
• Sleek, low-profile • Superior EMI • Plug-in mounting • Tamper-proof feature • UL Listed
design resistance for provides ease of available on mounting
• CSFM Listed
reliability installation bases
• Reliable analog
• MEA Listed 383-02-E
communications for • Variety of mounting • Optional remote LED • Rotary address
Vol. VI
trouble-free operation options to meet any annunciator (System switches for fast
application Sensor ® PN RA100Z) installation
• Age resistant polymer
housing • Dual LED indicators
for 360º visibility
• Innovative thermistor
sensing circuit • Detector transmits
signal to indicate
maintenance is
required
IDP-HEAT, IDP-HEAT-HT and IDP-HEAT-ROR Technical Specifications
For a complete listing of all
compliance approvals and
PHYSICAL COMPATIBILITY certifications, please visit
Height: 2.0” (5.08cm) The IDP-HEAT, IDP-HEAT-HT, and IDP-HEAT-
www.farenhyt.com.
Diameter: 4.1" (10.4CM) installed in B501 base. Microsoft, Windows, and
6.1" installed in B210LP base ROR are compatible with the following IDP series
the Windows Logo are
Shipping Weight: 4.8oz bases: registered trademarks
or trademarks of
ELECTRICAL RATINGS • B210LP 6” Mounting Base Microsoft Corporation.
Operating Voltage: 15 – 32VDC Honeywell® and
SLC Standby and Alarm Current: 300 μA • B501 4” Mounting Base System Sensor® are
registered trademarks
• B224BI 6” Isolator Base of and Farenhyt™ is a
ENVIRONMENTAL
trademark of Honeywell
Operating Temperature • B224RB 6” Relay Base International, Inc.
IDP-Heat & IDP-Heat-ROR: -4°F - 100 °F (-20°C
- 38°C) • B200SR 6” Sounder Base This document is not
intended to be used for
IDP-Heat-HT: -4°F - 150 °F (-20°C - 66°C)
The IDP-HEAT, IDP-HEAT-HT, and IDP-HEAT- installation purposes. We
Humidity: 10 to 93% non-condensing) try to keep our product
ROR are compatible with the following Farenhyt information up-to
THERMAL RATINGS Series FACPs: date and accurate. We
cannot cover all specific
IDP-Heat: Fixed temperature setpoint 135ºF
applications or anticipate
(57ºC) • IFP-2100 / IFP-2100ECS / RFP-2100 all requirements. All
IDP-Heat-HT: High temperature heat 135ºF – specifications are subject
190ºF (57ºC – 88ºC) • IFP-2000 / IFP-2000ECS / RPS-2000 to change without notice.
IDP-Heat-ROR: Rate-of-rise detection 15ºF/min
• IFP-1000 / IFP-1000ECS For Technical
(9ºC/min) Support, Please call
• IFP-300 / IFP-300ECS 800-446-6444.
ORDERING INFORMATION
IDP-Heat: Fixed temperature thermal detector • IFP-100 / IFP-100ECS
IDP-Heat-HT: Fixed high temperature thermal
detector • IFP-75
IDP-Heat-ROR: Fixed temperature and rate-of- • IFP-50
rise thermal detector
ACCESSORIES
RA100Z: Remote LED Annunciator.
XR2B: Detector Removal Tool. A removal and
replacement tool for IDP plug-in detectors.
Includes the T55-127-000.
M02-04-01: Detector test magnet
M02-09-00: Test Magnet with telescoping handle
XP-4: Extension pole for XR2B. Extends from 5 –
15 ft.
T55-127-000: Detector removal head.
BCK-200B: Black detector kit. For IDP-series
detectors.
* Unless otherwise noted, specifications apply to
IDP thermal detectors.
F E AT U R E S & B E N E F I T S
• Sleek, low-profile • Superior EMI • Plug-in mounting • Tamper-proof feature • UL Listed
design resistance for provides ease of available on mounting
• CSFM Listed
reliability installation bases
• Reliable analog
• MEA Listed 383-02-E
communications for • Variety of mounting • Optional remote LED • Rotary address
Vol. VI
trouble-free operation options to meet any annunciator (System switches for fast
application Sensor ® PN RA100Z) installation
• Age resistant polymer
housing • Dual LED indicators
for 360º visibility
• Innovative thermistor
sensing circuit • Detector transmits
signal to indicate
maintenance is
required
IDP-HEAT, IDP-HEAT-HT and IDP-HEAT-ROR Technical Specifications
For a complete listing of all
compliance approvals and
PHYSICAL COMPATIBILITY certifications, please visit
Height: 2.0” (5.08cm) The IDP-HEAT, IDP-HEAT-HT, and IDP-HEAT-
www.farenhyt.com.
Diameter: 4.1" (10.4CM) installed in B501 base. Microsoft, Windows, and
6.1" installed in B210LP base ROR are compatible with the following IDP series
the Windows Logo are
Shipping Weight: 4.8oz bases: registered trademarks
or trademarks of
ELECTRICAL RATINGS • B210LP 6” Mounting Base Microsoft Corporation.
Operating Voltage: 15 – 32VDC Honeywell® and
SLC Standby and Alarm Current: 300 μA • B501 4” Mounting Base System Sensor® are
registered trademarks
• B224BI 6” Isolator Base of and Farenhyt™ is a
ENVIRONMENTAL
trademark of Honeywell
Operating Temperature • B224RB 6” Relay Base International, Inc.
IDP-Heat & IDP-Heat-ROR: -4°F - 100 °F (-20°C
- 38°C) • B200SR 6” Sounder Base This document is not
intended to be used for
IDP-Heat-HT: -4°F - 150 °F (-20°C - 66°C)
The IDP-HEAT, IDP-HEAT-HT, and IDP-HEAT- installation purposes. We
Humidity: 10 to 93% non-condensing) try to keep our product
ROR are compatible with the following Farenhyt information up-to
THERMAL RATINGS Series FACPs: date and accurate. We
cannot cover all specific
IDP-Heat: Fixed temperature setpoint 135ºF
applications or anticipate
(57ºC) • IFP-2100 / IFP-2100ECS / RFP-2100 all requirements. All
IDP-Heat-HT: High temperature heat 135ºF – specifications are subject
190ºF (57ºC – 88ºC) • IFP-2000 / IFP-2000ECS / RPS-2000 to change without notice.
IDP-Heat-ROR: Rate-of-rise detection 15ºF/min
• IFP-1000 / IFP-1000ECS For Technical
(9ºC/min) Support, Please call
• IFP-300 / IFP-300ECS 800-446-6444.
ORDERING INFORMATION
IDP-Heat: Fixed temperature thermal detector • IFP-100 / IFP-100ECS
IDP-Heat-HT: Fixed high temperature thermal
detector • IFP-75
IDP-Heat-ROR: Fixed temperature and rate-of- • IFP-50
rise thermal detector
ACCESSORIES
RA100Z: Remote LED Annunciator.
XR2B: Detector Removal Tool. A removal and
replacement tool for IDP plug-in detectors.
Includes the T55-127-000.
M02-04-01: Detector test magnet
M02-09-00: Test Magnet with telescoping handle
XP-4: Extension pole for XR2B. Extends from 5 –
15 ft.
T55-127-000: Detector removal head.
BCK-200B: Black detector kit. For IDP-series
detectors.
* Unless otherwise noted, specifications apply to
IDP thermal detectors.
The IDP-PhotoR is a remote test capable detector for use with the DNR (W)
duct smoke detectors. It is UL 268A listed when used with the DNR (W)
duct smoke detector.
Installation
The IDP-Photo and IDP-Photo-T plug into a compatible IDP-series detector
base. The IDP-PhotoR is a remote test capable detector for use with the
DNR (W) duct smoke detector.
F E AT U R E S & B E N E F I T S
• Sleek, low-profile • Superior EMI • Detector transmits • Tamper-proof feature • MEA Listed 225-02-E
design resistance for signal to indicate available on mounting Vol. V
reliability maintenance is bases
• Reliable analog
required
communications for • Simple field cleaning • Listed for use in duct
trouble-free operation for code compliance • Optional remote LED applications
annunciator (System
• Age resistant polymer • Variety of mounting • Rotary address
Sensor ® PN RA100Z)
housing options to meet any switches for fast
application • Plug-in mounting installation
• Dual electronic
provides ease of
thermistor design on • Dual LED indicators • UL Listed
installation
the IDP-Photo-T for 360º visibility
• FM Approved
• CSFM Listed
IDP-PHOTO, IDP-PHOTOR and IDP-PHOTO-T Technical Specifications
For a complete listing of all
PHYSICAL COMPATIBILITY compliance approvals and
Height: 2.0” (5.08cm) less sensor The IDP-PHOTO, IDP-PHOTO-T and IDP- certifications, please visit
PHOTOR are compatible with the following IDP www.farenhyt.com.
Diameter: 4.1" (10.4CM) installed in B501 base
series detector bases: Microsoft, Windows, and
ENVIRONMENTAL the Windows Logo are
Operating Temperature: • B210LP 6” Mounting Base registered trademarks
or trademarks of
IDP-PHOTO: 32°F - 120 °F (0°C - 49°C) • B501 4” Mounting Base Microsoft Corporation.
IDP-PHOTO-T: 32°F - 100 °F (0°C - 38°C)
• B224BI 6” Isolator Base Honeywell® is a
Humidity: 10 to 93% non-condensing) registered trademark
• B224RB 6” Relay Base of and Farenhyt™ is a
ELECTRICAL RATINGS
• B200SR 6” Sounder Base trademark of Honeywell
Operating Voltage: 15 – 32VDC International, Inc.
SLC Standby and Alarm Current: 300 μA The IDP-PHOTO, IDP-PHOTO-T and IDP-
This document is not
PHOTOR are compatible with the following intended to be used for
OTHER RATINGS
Farenhyt Series FACPs: installation purposes. We
IDP-PHOTO-T Thermal: Fixed temperature set try to keep our product
point 135ºF (57ºC) • IFP-2100 / IFP-2100ECS / RFP-2100 information up-to
Velocity: 0 – 4000 fpm (0 – 20 m/sec) (suitable for • IFP-2000 / IFP-2000ECS / RPS-2000 date and accurate. We
installation in ducts) cannot cover all specific
• IFP-1000 / IFP-1000ECS applications or anticipate
IDP-PHOTO Insect Screen Hole Size: 0.016” (0.41 all requirements. All
mm)nominal • IFP-300 / IFP-300ECS specifications are subject
to change without notice.
ORDERING INFORMATION • IFP-100 / IFP-100ECS
For Technical
IDP-PHOTO: Photoelectric Smoke Detector • IFP-75 Support, Please call
IDP-PHOTO-T: Photoelectric Smoke Detector with 800-446-6444.
Thermal (135ºF) • IFP-50
IDP-PHOTOR: Photoelectric Smoke Detector,
remote test capable, for use with DNR (W) duct
smoke detector
ACCESSORIES
RA100Z: Remote LED Annunciator.
XR2B: Detector Removal Tool. A removal and
replacement tool for IDP plug-in detectors.
Includes the T55-127-000.
M02-04-01: Detector Test Magnet
M02-09-00: Test Magnet with Telescoping Handle
XP-4: Extension Pole for XR2B. Extends from 5 –
15 ft.
T55-127-000: Detector Removal Head.
BCK-200B: Black Detector Kit. For IDP-series
detectors.
* Unless otherwise noted, specifications apply to
IDP-Photo and IDP-Photo
The IDP-PhotoR is a remote test capable detector for use with the DNR (W)
duct smoke detectors. It is UL 268A listed when used with the DNR (W)
duct smoke detector.
Installation
The IDP-Photo and IDP-Photo-T plug into a compatible IDP-series detector
base. The IDP-PhotoR is a remote test capable detector for use with the
DNR (W) duct smoke detector.
F E AT U R E S & B E N E F I T S
• Sleek, low-profile • Superior EMI • Detector transmits • Tamper-proof feature • MEA Listed 225-02-E
design resistance for signal to indicate available on mounting Vol. V
reliability maintenance is bases
• Reliable analog
required
communications for • Simple field cleaning • Listed for use in duct
trouble-free operation for code compliance • Optional remote LED applications
annunciator (System
• Age resistant polymer • Variety of mounting • Rotary address
Sensor ® PN RA100Z)
housing options to meet any switches for fast
application • Plug-in mounting installation
• Dual electronic
provides ease of
thermistor design on • Dual LED indicators • UL Listed
installation
the IDP-Photo-T for 360º visibility
• FM Approved
• CSFM Listed
IDP-PHOTO, IDP-PHOTOR and IDP-PHOTO-T Technical Specifications
For a complete listing of all
PHYSICAL COMPATIBILITY compliance approvals and
Height: 2.0” (5.08cm) less sensor The IDP-PHOTO, IDP-PHOTO-T and IDP- certifications, please visit
PHOTOR are compatible with the following IDP www.farenhyt.com.
Diameter: 4.1" (10.4CM) installed in B501 base
series detector bases: Microsoft, Windows, and
ENVIRONMENTAL the Windows Logo are
Operating Temperature: • B210LP 6” Mounting Base registered trademarks
or trademarks of
IDP-PHOTO: 32°F - 120 °F (0°C - 49°C) • B501 4” Mounting Base Microsoft Corporation.
IDP-PHOTO-T: 32°F - 100 °F (0°C - 38°C)
• B224BI 6” Isolator Base Honeywell® is a
Humidity: 10 to 93% non-condensing) registered trademark
• B224RB 6” Relay Base of and Farenhyt™ is a
ELECTRICAL RATINGS
• B200SR 6” Sounder Base trademark of Honeywell
Operating Voltage: 15 – 32VDC International, Inc.
SLC Standby and Alarm Current: 300 μA The IDP-PHOTO, IDP-PHOTO-T and IDP-
This document is not
PHOTOR are compatible with the following intended to be used for
OTHER RATINGS
Farenhyt Series FACPs: installation purposes. We
IDP-PHOTO-T Thermal: Fixed temperature set try to keep our product
point 135ºF (57ºC) • IFP-2100 / IFP-2100ECS / RFP-2100 information up-to
Velocity: 0 – 4000 fpm (0 – 20 m/sec) (suitable for • IFP-2000 / IFP-2000ECS / RPS-2000 date and accurate. We
installation in ducts) cannot cover all specific
• IFP-1000 / IFP-1000ECS applications or anticipate
IDP-PHOTO Insect Screen Hole Size: 0.016” (0.41 all requirements. All
mm)nominal • IFP-300 / IFP-300ECS specifications are subject
to change without notice.
ORDERING INFORMATION • IFP-100 / IFP-100ECS
For Technical
IDP-PHOTO: Photoelectric Smoke Detector • IFP-75 Support, Please call
IDP-PHOTO-T: Photoelectric Smoke Detector with 800-446-6444.
Thermal (135ºF) • IFP-50
IDP-PHOTOR: Photoelectric Smoke Detector,
remote test capable, for use with DNR (W) duct
smoke detector
ACCESSORIES
RA100Z: Remote LED Annunciator.
XR2B: Detector Removal Tool. A removal and
replacement tool for IDP plug-in detectors.
Includes the T55-127-000.
M02-04-01: Detector Test Magnet
M02-09-00: Test Magnet with Telescoping Handle
XP-4: Extension Pole for XR2B. Extends from 5 –
15 ft.
T55-127-000: Detector Removal Head.
BCK-200B: Black Detector Kit. For IDP-series
detectors.
* Unless otherwise noted, specifications apply to
IDP-Photo and IDP-Photo
The IDP-PhotoR is a remote test capable detector for use with the DNR (W)
duct smoke detectors. It is UL 268A listed when used with the DNR (W)
duct smoke detector.
Installation
The IDP-Photo and IDP-Photo-T plug into a compatible IDP-series detector
base. The IDP-PhotoR is a remote test capable detector for use with the
DNR (W) duct smoke detector.
F E AT U R E S & B E N E F I T S
• Sleek, low-profile • Superior EMI • Detector transmits • Tamper-proof feature • MEA Listed 225-02-E
design resistance for signal to indicate available on mounting Vol. V
reliability maintenance is bases
• Reliable analog
required
communications for • Simple field cleaning • Listed for use in duct
trouble-free operation for code compliance • Optional remote LED applications
annunciator (System
• Age resistant polymer • Variety of mounting • Rotary address
Sensor ® PN RA100Z)
housing options to meet any switches for fast
application • Plug-in mounting installation
• Dual electronic
provides ease of
thermistor design on • Dual LED indicators • UL Listed
installation
the IDP-Photo-T for 360º visibility
• FM Approved
• CSFM Listed
IDP-PHOTO, IDP-PHOTOR and IDP-PHOTO-T Technical Specifications
For a complete listing of all
PHYSICAL COMPATIBILITY compliance approvals and
Height: 2.0” (5.08cm) less sensor The IDP-PHOTO, IDP-PHOTO-T and IDP- certifications, please visit
PHOTOR are compatible with the following IDP www.farenhyt.com.
Diameter: 4.1" (10.4CM) installed in B501 base
series detector bases: Microsoft, Windows, and
ENVIRONMENTAL the Windows Logo are
Operating Temperature: • B210LP 6” Mounting Base registered trademarks
or trademarks of
IDP-PHOTO: 32°F - 120 °F (0°C - 49°C) • B501 4” Mounting Base Microsoft Corporation.
IDP-PHOTO-T: 32°F - 100 °F (0°C - 38°C)
• B224BI 6” Isolator Base Honeywell® is a
Humidity: 10 to 93% non-condensing) registered trademark
• B224RB 6” Relay Base of and Farenhyt™ is a
ELECTRICAL RATINGS
• B200SR 6” Sounder Base trademark of Honeywell
Operating Voltage: 15 – 32VDC International, Inc.
SLC Standby and Alarm Current: 300 μA The IDP-PHOTO, IDP-PHOTO-T and IDP-
This document is not
PHOTOR are compatible with the following intended to be used for
OTHER RATINGS
Farenhyt Series FACPs: installation purposes. We
IDP-PHOTO-T Thermal: Fixed temperature set try to keep our product
point 135ºF (57ºC) • IFP-2100 / IFP-2100ECS / RFP-2100 information up-to
Velocity: 0 – 4000 fpm (0 – 20 m/sec) (suitable for • IFP-2000 / IFP-2000ECS / RPS-2000 date and accurate. We
installation in ducts) cannot cover all specific
• IFP-1000 / IFP-1000ECS applications or anticipate
IDP-PHOTO Insect Screen Hole Size: 0.016” (0.41 all requirements. All
mm)nominal • IFP-300 / IFP-300ECS specifications are subject
to change without notice.
ORDERING INFORMATION • IFP-100 / IFP-100ECS
For Technical
IDP-PHOTO: Photoelectric Smoke Detector • IFP-75 Support, Please call
IDP-PHOTO-T: Photoelectric Smoke Detector with 800-446-6444.
Thermal (135ºF) • IFP-50
IDP-PHOTOR: Photoelectric Smoke Detector,
remote test capable, for use with DNR (W) duct
smoke detector
ACCESSORIES
RA100Z: Remote LED Annunciator.
XR2B: Detector Removal Tool. A removal and
replacement tool for IDP plug-in detectors.
Includes the T55-127-000.
M02-04-01: Detector Test Magnet
M02-09-00: Test Magnet with Telescoping Handle
XP-4: Extension Pole for XR2B. Extends from 5 –
15 ft.
T55-127-000: Detector Removal Head.
BCK-200B: Black Detector Kit. For IDP-series
detectors.
* Unless otherwise noted, specifications apply to
IDP-Photo and IDP-Photo
INSTALLATION
The IDP-PULL-SA and IDP-PULL-DA can be surface mounted to an SB-I/O
surface back box or semi-flush mounted on a standard single-gang with a
minimum depth of 2.13”(5.40 cm) or double gang or 4” (10.61 cm) square
electrical box. You can also use the optional (System Sensor® PN BG-TR)
trim ring if the station is being semi-flush mounted.
IDP-PULL-SA
COMPATIBILITY
The IDP-PULL-SA and IDP-PULL-DA are compatible with the following
Honeywell Farenhyt Series FACPs:
• IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50 IDP-PULL-DA
F E AT U R E S & B E N E F I T S
• Installer can open • Key operated test and • Meets the Americans • Reliable analog • Handle latches in
station without reset lock using lock with Disabilities Act communications for down position and the
causing an alarm plate actuator Accessibility trouble-free operation word Activated
condition Guidelines (ADAAG) appears, clearly
• Key matches • Braille text on station
controls and operating indicating the station
• Dual-color LED is compatible FACP handle
mechanisms has been pulled
visible through handle locks
guidelines (Section • Rotary address
of station blinks green • UL Listed, including
• Meets ADA 4.1.3[13]) switches for fast
to indicate normal UL 38, Standard of
requirement for 5 lbs installation
operation and remains • Shell, door, and handle Manually Actuated
maximum pull force to
steady red in an alarm molded from durable Signaling System
active
condition LEXAN ®
• CSFM Listed
• MEA Listed
IDP-PULL-SA and IDP-PULL-DA Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® and
System Sensor® are
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
ELECTRICAL RATINGS
Operating Voltage: 15 – 32VDC
SLC Standby and Alarm Current: 350μA
Wire Gauge: Up to 12AWG (3.1 mm2)
ENVIRONMENTAL
Operating Temperature: 32º-120ºF (0ºC – 49ºC)
Humidity: 10 to 93% non-condensing)
INSTALLATION
The IDP-PULL-SA and IDP-PULL-DA can be surface mounted to an SB-I/O
surface back box or semi-flush mounted on a standard single-gang with a
minimum depth of 2.13”(5.40 cm) or double gang or 4” (10.61 cm) square
electrical box. You can also use the optional (System Sensor® PN BG-TR)
trim ring if the station is being semi-flush mounted.
IDP-PULL-SA
COMPATIBILITY
The IDP-PULL-SA and IDP-PULL-DA are compatible with the following
Honeywell Farenhyt Series FACPs:
• IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50 IDP-PULL-DA
F E AT U R E S & B E N E F I T S
• Installer can open • Key operated test and • Meets the Americans • Reliable analog • Handle latches in
station without reset lock using lock with Disabilities Act communications for down position and the
causing an alarm plate actuator Accessibility trouble-free operation word Activated
condition Guidelines (ADAAG) appears, clearly
• Key matches • Braille text on station
controls and operating indicating the station
• Dual-color LED is compatible FACP handle
mechanisms has been pulled
visible through handle locks
guidelines (Section • Rotary address
of station blinks green • UL Listed, including
• Meets ADA 4.1.3[13]) switches for fast
to indicate normal UL 38, Standard of
requirement for 5 lbs installation
operation and remains • Shell, door, and handle Manually Actuated
maximum pull force to
steady red in an alarm molded from durable Signaling System
active
condition LEXAN ®
• CSFM Listed
• MEA Listed
IDP-PULL-SA and IDP-PULL-DA Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® and
System Sensor® are
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
ELECTRICAL RATINGS
Operating Voltage: 15 – 32VDC
SLC Standby and Alarm Current: 350μA
Wire Gauge: Up to 12AWG (3.1 mm2)
ENVIRONMENTAL
Operating Temperature: 32º-120ºF (0ºC – 49ºC)
Humidity: 10 to 93% non-condensing)
The IDP-RELAY-6 contacts can be used for virtually any normally open or
normally closed application. Each IDP-RELAY- 6 is programmed with a
unique signaling line circuit (SLC) loop address. When an event occurs that
controls the IDP-RELAY-6, the relay is triggered by the FACP.
IDP-RELAY-6
Installation
The IDP-RELAY-6 mounts in the Honeywell IDP-ACB cabinet (PN IDP-
ACB). The IDP-ACB has a built-in chassis that will accommodate one or two
IDP-RELAY-6 modules.
COMPATIBILITY
The IDP-RELAY-6 is compatible with the following Farenhyt Series FACPs:
F E AT U R E S & B E N E F I T S
• Six Form C contacts • Two module mounting • Mounting hardware • UL Listed
in the IDP-ACB included
• Removable 12 to • CSFM Listed
cabinet
18AWG plug-in • Class A or B operation
• MEA Listed 386-02-E
terminal blocks • Up to three unused
Vol. II
modules can be
• Relay programming is
disabled
completely flexible–
can be mapped to • Rotary address
zone conditions switches for fast
installation
• Individual LED for
each relay contact
IDP-RELAY-6 Technical Specifications
For a complete listing of all
SPECIFICATIONS* ORDERING INFORMATION compliance approvals and
certifications, please visit
Physical: 6.8" H x 5.8"W x 1.25" D IDP-RELAY-6: Six Relay Module www.farenhyt.com.
Shipping Weight: 6.3oz (196g)
ACCESSORIES Microsoft, Windows, and
the Windows Logo are
ELECTRICAL RATINGS IDP-ACB: Cabinet. 15.25" H x 12.5" W x 3"D
registered trademarks
Operating Voltage: 15 to 32VDC or trademarks of
Standby Current: 1.45mA maximum Microsoft Corporation.
Alarm Current: 30 mA/Relay Pulse (15.6 mS pulse Honeywell® and
duration) pulse under panel control System Sensor® are
Relay Contact Ratings: registered trademarks
2.0A @ 25VAC (PF=.35), non-coded of and Farenhyt™ is a
trademark of Honeywell
3.0A @ 30VDC resistive, non-coded International, Inc.
2.0A @ 30VDC resistive, coded
This document is not
0.46A @ 30VDC (L/R=20ms), non-coded
intended to be used for
0.7A @ 70.7VAC (PF=.35), non-coded installation purposes. We
0.9A @ 125VDC resistive, non-coded try to keep our product
0.5A @ 125VAC (PF=.75), non-coded information up-to
date and accurate. We
0.3A @ 125VAC (PF=.35), non-coded cannot cover all specific
applications or anticipate
ENVIRONMENTAL all requirements. All
Operating Temperature: 32º-120ºF (0ºC – 49ºC) specifications are subject
to change without notice.
Humidity: 10 to 85% non-condensing)
For Technical
Support, Please call
800-446-6444.
The IDP-RELAY contacts can be used for virtually any normally open or
normally closed application. Each IDP-RELAY is programmed with a
unique signaling line circuit (SLC) loop address. When an event occurs that
controls the IDP-RELAY, the relay is triggered by the FACP. IDP-RELAY
INSTALLATION
The IDP-RELAY mounts directly into a 4” square electrical box. The box
must have a minimum depth of 2-1/8”. A surface mount electrical box
(System Sensor® PN SMB500) is available from Honeywell.
COMPATIBILITY
The IDP-RELAY is compatible with the following Farenhyt Series FACPs:
F E AT U R E S & B E N E F I T S
• Two sets of Form C • Relay programming is • Rotary address • UL Listed
contacts completely flexible– switches for fast
• CSFM Listed
can be mapped to installation
• Contacts are rated for
zone conditions • MEA Listed 386-02-E
a variety of amps (see • SEMS screws for easy
Vol. II
Specifications) • Polling LED visible wiring
through the cover
• Panel controlled
plate
status LED that
flashes green in
normal state and is
solid red in alarm
IDP-RELAY Technical Specifications
For a complete listing of all
SPECIFICATIONS* ORDERING INFORMATION compliance approvals and
certifications, please visit
Physical: 4.275" H x 4".675 W x 1.4 D IDP-RELAY: Relay Module www.farenhyt.com.
Shipping Weight: 6.3oz (196g)
ACCESSORIES Microsoft, Windows, and
ELECTRICAL RATINGS SMB500: 4” Square Surface Mount Electrical Box the Windows Logo are
registered trademarks
Operating Voltage: 15 to 32VDC CB500: Module Barrier. Used to separate power or trademarks of
Standby Current: 300μA max @ 24VDC (one limited and non-power limited wiring in a junction Microsoft Corporation.
communication every 5 sec. with LED enabled) box.
Honeywell® and
LED Current: 5.5 mA (with LED latched on) System Sensor® are
Relay Contact Ratings: registered trademarks
2.0A @ 25VAC (PF=.35), non-coded of and Farenhyt™ is a
trademark of Honeywell
3.0A @ 30VDC resistive, non-coded International, Inc.
2.0A @ 30VDC resistive, coded
0.46A @ 30VDC (L/R=20ms), non-coded This document is not
intended to be used for
0.7A @ 70.7VAC (PF=.35), non-coded installation purposes. We
0.9A @ 125VDC resistive, non-coded try to keep our product
0.5A @ 125VAC (PF=.75), non-coded information up-to
date and accurate. We
0.3A @ 125VAC (PF=.35), non-coded cannot cover all specific
applications or anticipate
ENVIRONMENTAL all requirements. All
Operating Temperature: 32º-120ºF (0ºC – 49ºC) specifications are subject
to change without notice.
Humidity: 10 to 93% non-condensing)
For Technical
Support, Please call
800-446-6444.
INSTALLATION
IDP-RELAYMON-2
The IDP-RELAYMON-2 mounts directly into a 4” square electrical box. The
box must have a minimum depth of 2-1/8”. A surface mount electrical
box (System Sensor® PN SMB500) is available from Honeywell.
COMPATIBILITY
The IDP-REALYMON-2 is compatible with the
following Farenhyt Series FACPs:
F E AT U R E S & B E N E F I T S
• Monitor two circuits, • Relay programming is • SEMS screws for easy
with unique completely flexible – wiring
addresses, can be mapped to
• UL Listed
simultaneously zone conditions
• CSFM Listed
• Two Form C relay • Individual LEDs for
contacts with each each monitored input • FM Approved
having a unique and relay output
address
• Rotary address
• Fully supervised switches for fast
support for Class B installation
input wiring
•
IDP-REALYMON-2 Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
SPECIFICATIONS ORDERING INFORMATION
www.farenhyt.com.
Physical: 4.675"H x 4.275"W x 1.4"D (mounts to a 4" IDP-RELAYMON-2: Relay/Monitor module
square by 2 1/8" deep box). Microsoft, Windows, and
Shipping Weight: 6.3oz (196g) ACCESSORIES the Windows Logo are
registered trademarks
SMB500: 4” square surface mount electrical box or trademarks of
ELECTRICAL RATINGS Microsoft Corporation.
Operating Voltage: 15 to 32VDC
Honeywell® and
Standby & Alarm Current: 1.3mA
System Sensor® are
registered trademarks
ENVIRONMENTAL of and Farenhyt™ is a
Operating Temperature: 32º-120ºF (0ºC – 49ºC) trademark of Honeywell
Humidity: 10 to 93% non-condensing) International, Inc.
The inputs on the IDP-ZONE-6 share a common FACP signaling line circuit
(SLC) input, and the initiating device circuits share a common external
power supply. Otherwise, each input on the module operates
independently from the others. If needed, you can disable a maximum of
two unused inputs on the IDP-ZONE-6 board.
INSTALLATION
The IDP-Zone-6 mounts in the IDP-ACB cabinet. The IDP-ACB has a
built-in chassis that will accommodate one or two IDP Zone-6 modules.
F E AT U R E S & B E N E F I T S
• Converts a • Individual LED for • Rotary address • UL Listed
conventional two-wire each relay contact switches for fast
• CSFM Listed
loop to an SLC loop installation
• Two module mounting
• MEA Listed 386-02-E
• Six zone inputs in the IDP-ACB • Mounting hardware
Vol. II
cabinet included
• Fully supervised
• Up to two unused
• Support for Class B
modules can be
and Class A wiring
disabled
• Removable 12 to 18
AWG plug-in terminal
blocks
IDP-ZONE-6 Technical Specifications
For a complete listing of all
compliance approvals and
SPECIFICATIONS ORDERING INFORMATION certifications, please visit
www.farenhyt.com.
Physical: 6.8" H x 5.8"W x 1.25" D IDP-ZONE-6: Six Zone Two-Wire Interface Module
Shipping Weight: 6.3oz (196g) Microsoft, Windows, and
ACCESSORIES the Windows Logo are
ELECTRICAL RATINGS IDP-ACB: Module Cabinet. Cabinet holds two registered trademarks
or trademarks of
Operating Voltage: 15 to 32VDC IDP-ZONE-6. 15.25" H x 12.5" W x 3"D
Microsoft Corporation.
Standby Current: 2mA
COMPATIBILITY Honeywell® and
Alarm Current: 40mA max. (Assumes all six LEDs
System Sensor® are
solid on) The IDP-ZONE-6 is compatible with the registered trademarks
Initiating Device Circuit: Supervised, power-limited following Farenhyt Series FACPs: of and Farenhyt™ is a
Max. IDC Wiring Resistance: 25W max trademark of Honeywell
• IFP-2100 / IFP-2100ECS / RFP-2100 International, Inc.
External Power Supply
Standby Current: 50mA • IFP-2000 / IFP-2000ECS / RPS-2000 This document is not
Alarm Current: 270mA intended to be used for
• IFP-1000 / IFP-1000ECS installation purposes. We
End-of-Line Resistance: 3.9k W try to keep our product
• IFP-300 / IFP-300ECS
information up-to
ENVIRONMENTAL • IFP-100 / IFP-100ECS date and accurate. We
Operating Temperature: 32º-120ºF (0ºC – 49ºC) cannot cover all specific
• IFP-75 applications or anticipate
Humidity: 10 to 93% non-condensing) all requirements. All
• IFP-50
specifications are subject
For a list of detectors compatible with the to change without notice.
IDP-Control
Addressable Notification Module
General
The IDP-CONTROL is an addressable notification module for use with Honeywell
Farenhyt Series fire alarm control panels (FACPs). The IDP-CONTROL gives you the
flexibility to add notification circuits wherever they are needed on an Farenhyt FACP
signaling line circuit (SLC) loop.
Upon command from the FACP, the IDP-CONTROL will disconnect the supervision
and connect the external power supply across the load device. The disconnection of
the supervision provides a positive indication to the panel that the control relay
actually turned on. The external power supply is always relay isolated from the SLC
loop, so that a trouble condition on the power supply will never interfere with the rest
of the system.
Installation
The IDP-CONTROL mounts directly into a 4” square electrical box. The box must have
a minimum depth of 2-1/8”. A surface mount electrical box (System Sensor® PN
IDP-Control Module
SMB500) is available from Honeywell.
Compatibility
The he IDP-CONTROL is compatible with the following Farenhyt Series FACPs: IFP-2100 / IFP-2100ECS / RFP-2100, IFP-2000 / IFP-
2000ECS / RPS-2000, IFP-1000 / IFP-1000ECS, IFP-300 / IFP-300ECS, IFP-100 / IFP-100ECS, IFP-75, and IFP-50.
• Flexible solution for • Panel controlled status • Rotary address • UL Listed • MEA Listed 386-02-E
adding notification LED that flashes green switches for fast Vol. II
circuits where needed in normal state and is installation • CSFM Listed
solid red in alarm
• Support for Class B • SEMS screws for easy
(style Y) or Class A • Polling LED visible wiring
(style Z) wiring through the cover plate
IDP-Control Technical Specifications
PHYSICAL IDP-CONTROL: Notification module. For a complete listing of all
compliance approvals and
Dimensions: 4.5" H x 4"W x 1.25" D ACCESSORIES certifications, please visit:
Shipping Weight: 6.3oz (196g) www.Farenhyt.com
SMB500: 4” Square Surface Mount Electrical Box
ENVIRONMENTAL Farenhyt™ is a trademark of
CB500: Module Barrier. Used to separate power Honeywell International, Inc.
Operating Temperature: 32°F to 120°F (0°C to 49°C) limited and non-power limited wiring in a junction
Humidity:10% to 93% relative humidity (non- Honeywell® is a registered
box trademark of Honeywell
condensing)
AGENCY LISTINGS International Inc.
ELECTRICAL
This document is not intended
NFPA 13, NFPA 70, NFPA 72, UL 2572, UL 1711 &
Operating Voltage: 15 to 32VDC to be used for installation
UL 864: Local Protective Signaling Systems purposes. We try to keep our
Standby & Alarm Current: 350 mA
UL Listed product information up-to-
End-of-Line Resistance: 47k date and accurate. We cannot
SLC Loop Impedance: 40 CSFM: cover all specific applications
MEA Listed: 386-02-E, Volume 2. or anticipate all requirements.
ORDERING INFORMATION All specifications are subject to
change without notice.
INSTALLATION
The IDP-MINIMON can be mounted in a single gang junction box directly
IDP-MINIMON
behind the monitored device. Its small size and light weight allow it to be
installed without rigid mounting requirements.
COMPATIBILITY
The IDP-Minimon compatible with the following Farenhyt SeriesFACPs:
• IFP-2100 / IFP-2100ECS / RFP-2100
• IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50
F E AT U R E S & B E N E F I T S
• Single contact monitor • Rotary address • UL Approved
switches for fast
• Small and lightweight • CSFM Listed
installation
size allows for flexible
• MEA Listed 457-99-E
mounting options • Analog
Vol. V
communications
• Support for Class B
wiring
• Fully supervised
IDP-MINIMON Technical Specifications
For a complete listing of all
compliance approvals and
PHYSICAL ORDERING INFORMATION certifications, please visit
Dimensions: 1.3" H x 2.8" W x .5" D (3.3 x 7x 1.3 cm) IDP-MINIMON: Mini monitoring module www.farenhyt.com.
For Technical
Support, Please call
800-446-6444.
The IDP-ZONE is addressed through the signaling line circuit loop of the
FACP. It transmits the status of one full zone of two-wire detectors to the
FACP. Status conditions are reported as normal, open, or alarm. The
IDP-ZONE supervises the zone of detectors and the connection of the
external power supply. All two-wire detectors being monitored must be UL
compatible with the IDP-ZONE. IDP-ZONE
INSTALLATION
The IDP-ZONE mounts directly into a 4” square electrical box. The box must
have a minimum depth of 2-1/8”. A surface mount electrical box (System
Sensor® PN SMB500) is available from Honeywell.
COMPATIBILITY
The IDP-ZONE is compatible with the following Farenhyt Series FACPs:
F E AT U R E S & B E N E F I T S
• Converts a • Panel controlled • UL Listed
conventional two-wire status LED that
• CSFM Listed
loop to an SLC loop flashes green in
normal state and is • MEA Listed 386-02-E
• Fully supervised
solid red in alarm Vol. II
• Support for Style B
• Rotary address
and Style D wiring
switches for fast
installation
• SEMS screws for easy
wiring
IDP-ZONE Technical Specifications
For a complete listing of all
compliance approvals and
SPECIFICATIONS ORDERING INFORMATION certifications, please visit
Physical: 4.5" H x 4"W x 1.25" D IDP-ZONE: Two-wire interface module www.farenhyt.com.
Shipping Weight: 6.3oz (196g) Microsoft, Windows, and
ACCESSORIES the Windows Logo are
ELECTRICAL RATINGS SMB500: 4” Square Surface Mount Electrica Box registered trademarks
Operating Voltage: 15 to 32VDC or trademarks of
Microsoft Corporation.
External Power Supply
Alarm Current: 90mA per module Honeywell® and
System Sensor® are
Standby Current: 12mA @ 24 VDC (nominal)
registered trademarks
Standby & Alarm Current: 300 μA max @ 24 VDC of and Farenhyt™ is a
(one communication every 5 sec. with LED enabled) trademark of Honeywell
End-of-Line Resistance: 3.9kW International, Inc.
SLC Loop Impedance: 40W This document is not
Initiating Device Circuit Wiring Resistance: 25W intended to be used for
max installation purposes. We
try to keep our product
ENVIRONMENTAL information up-to
date and accurate. We
Operating Temperature: 32º-120ºF (0ºC – 49ºC) cannot cover all specific
Humidity: 10 to 93% non-condensing) applications or anticipate
all requirements. All
specifications are subject
to change without notice.
For Technical
Support, Please call
800-446-6444.
The ISO-6 Six Fault Isolator Module has an amber LED indicator that will
blink in the normal state for each of the six inputs and will latch on during a
short circuit condition. The module will automatically restore the
communications loop to normal condition when the short circuit is
removed.
The ISO-6 Six Isolator Module is an automatic switch that opens when the
line voltage drops below four volts. Isolator modules should be spaced
ISO-6
between groups of sensors or modules in a loop to protect the rest of the
loop. If a short occurs between any two isolators, then both isolators
immediately switch to an open circuit state and isolate the devices
between them. The remaining units on the loop continue to fully operate.
Applications
The ISO-6 Fault Isolator Modules should be spaced between groups of
sensors in an SLC to protect the rest of the loop. Use to isolate short circuit
problems within a section of a loop so that other sections can continue to
operate normally. The ISO-6 supports a maximum of 25 devices between
isolators.
F E AT U R E S & B E N E F I T S
• Removable 12 to 18 • Mount up to two • UL Listed
AWG plug-in terminal modules in IDP-ACB
• CSFM Listed
blocks enclosure (optional)
• FM Approved
• Individual LED status • Mounting hardware
indicators included
• Six individual, Class B
isolator circuits
ISO-6 Technical Specifications
For a complete listing of all
compliance approvals and
SPECIFICATIONS ORDERING INFORMATION certifications, please visit
Physical: 6.8"H x 5.8"W x 1.0"D ISO-6: Six Isolator module www.farenhyt.com.
Shipping Weight: 1.1 lbs (.50g) including pkg. Microsoft, Windows, and
Mounting Option: IDP-ACB ACCESSORIES
the Windows Logo are
IDP-ACB: Optional cabinet for one or two modules. registered trademarks
ELECTRICAL RATINGS Dimensions: 12.5”W x 15.25”H x 3”D (31.8 cm W x or trademarks of
Operating Voltage: 15 to 32VDC 38.7cm H x 7.6 cm D) Microsoft Corporation.
For Technical
Support, Please call
800-446-6444.
IDP-ACB
F E AT U R E S & B E N E F I T S
• Has a built-in
mounting plate that
positions the module
boards so that all of
the status indicators
are visible.
• One to two module
mounting in cabinet
• UL Listed
IDP-ACB Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® and
System Sensor® are
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
COMPATIBILITY
The IDP-ACB will accommodate one or two of the
following modules:
• IDP-Monitor-10
• IDP-Zone-6
• IDP-Relay-6
• IDP-Control-6
Upon command from the FACP, the IDP-CONTROL-6 will disconnect the
IDP-CONTROL-6
supervision and connect the external power supply across the load device.
The disconnection of the supervision provides a positive indication to the
panel that the control relay actually turned on. The external power supply is
always relay isolated from the SLC loop, so that a trouble condition on the
power supply will never interfere with the rest of the system.
F E AT U R E S & B E N E F I T S
• Flexible solution for • Individual LED for • Rotary address • Mounting hardware
adding notification each module switches for fast included
circuits where needed installation
• Two module mounting • UL Listed
• Removable 12 to 18 in the IDP-ACB
AWG plug-in terminal cabinet
blocks
• Unused modules can
• Support for Class B or be disabled
Class A wiring
IDP-CONTROL-6 Technical Specifications
For a complete listing of all
PHYSICAL INSTALLATION compliance approvals and
certifications, please visit
Dimensions: 6.8" H x 5.8"W x 1.25" D The IDP-CONTROL-6 mounts in the Honeywell www.farenhyt.com.
Shipping Weight: 6.3oz (196g)
IDP-ACB cabinet (P/N IDP-ACB). The IDP-ACB Microsoft, Windows, and
the Windows Logo are
ELECTRICAL RATINGS has a built-in chassis that will accommodate one
registered trademarks
Operating Voltage: 15 to 32VDC or two IDP-Control-6 modules. or trademarks of
Standby Current: 2.65mA @ 24V Microsoft Corporation.
Alarm Current: 35mA maximum (assumes all six Honeywell® and
relays have been switched once and all six LEDs COMPATIBILITY
System Sensor® are
solid on) The IDP-CONTROL-6 is compatible with the registered trademarks
End-of-Line Resistance: 47kW following Farenhyt Series FACPs: of and Farenhyt™ is a
Maximum SLC Wiring Resistance: 41W • IFP-2100 / IFP-2100ECS / RFP-2100 trademark of Honeywell
International, Inc.
Maximum NAC Wiring Resistance: 40W • IFP-2000 / IFP-2000ECS / RPS-2000
• IFP-1000 / IFP-1000ECS This document is not
ENVIRONMENTAL intended to be used for
Operating Temperature: 32º-120ºF (0ºC – 49ºC)
• IFP-300 / IFP-300ECS installation purposes. We
try to keep our product
Humidity: 10 to 85% non-condensing) • IFP-100 / IFP-100ECS information up-to
• IFP-75 date and accurate. We
ORDERING INFORMATION cannot cover all specific
• IFP-50 applications or anticipate
IDP-CONTROL-6: Six Input notification module
all requirements. All
specifications are subject
ACCESSORIES to change without notice.
IDP-ACB: Cabinet. 15.25" H x 12.5" W x 3"D
For Technical
Support, Please call
800-446-6444.
INSTALLATION
IDP-ISO
The IDP-ISO mounts directly into a 4” square electrical box. The box
must have a minimum depth of 2-1/8”. A surface mount electrical
box (System Sensor® PN SMB500) is available from Honeywell.
COMPATIBILITY
The IDP-ISO is compatible with the following Farenhyt Series FACPs:
• IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50
F E AT U R E S & B E N E F I T S
• Isolates short circuits • Standard 4 inch • UL Listed
on an SLC loop electrical box
• CSFM Listed
mounting
• Protects the modules
• MEA Listed 427-91-E
on the SLC loop so • SEMS screws for easy
Vol. X
other devices continue wiring
to operate
• Panel controlled
status LED that
flashes green in
normal state and is
solid red in alarm
IDP-ISO Technical Specifications
PHYSICAL ORDERING INFORMATION For a complete listing of all
Dimensions: 4.5" H x 4" W x .25 D ( 11.4 x 10.2 x IDP-ISO: Line Isolator Module compliance approvals and
certifications, please visit
.6cm)
www.farenhyt.com.
Shipping Weight: 6.3oz (196g? ACCESSORIES
SMB500: 4” Square Surface Mount Electrical Box Microsoft, Windows, and
ELECTRICAL RATINGS the Windows Logo are
registered trademarks
Operating Voltage: 15 – 32 VDC or trademarks of
Standby Current: 450 μA max (not isolating; relay Microsoft Corporation.
closed)
Honeywell® and
Isolation Current: 5mA max
System Sensor® are
Fault Detection Delay: 250ms min. registered trademarks
Fault Detection Threshold: 4V of and Farenhyt™ is a
Line Restoration Threshold: 7V trademark of Honeywell
International, Inc.
ENVIRONMENTAL This document is not
Operating Temperature: 32º-120ºF (0ºC – 49ºC) intended to be used for
installation purposes. We
Humidity: 10 to 93% non-condensing)
try to keep our product
information up-to
date and accurate. We
cannot cover all specific
applications or anticipate
all requirements. All
specifications are subject
to change without notice.
For Technical
Support, Please call
800-446-6444.
IDP-MONITOR-2
Installation
The IDP-MONITOR-2 mounts directly into a 4” square electrical box. The
box must have a minimum depth of 2-1/8”. A surface mount electrical box
(System Sensor® PN SMB500) is available from Honeywell.
COMPATIBILITY
The IDP-MONITOR-2 is compatible with the following Honeywell Farenhyt
Series FACPs:
• IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50
F E AT U R E S & B E N E F I T S
• Monitor two circuits, • Panel controlled • SEMS screws for easy • CSFM Listed
with unique status LED that wiring
• MEA Listed 457-99-E
addresses, flashes green in
• UL Listed Vol. V
simultaneously normal state and is
solid red in alarm
• Support for Class B
wiring • Rotary address
switches for fast
• Fully supervised
installation
IDP-MONITOR-2 Technical Specifications
For a complete listing of all
compliance approvals and
PHYSICAL certifications, please visit
Dimensions: 4.5" H x 4" W x 1.3 D ( 11.4 x 10.2 x www.farenhyt.com.
3.2cm) Microsoft, Windows, and
Shipping Weight: 6.3oz (196g) the Windows Logo are
registered trademarks
ELECTRICAL RATINGS or trademarks of
Microsoft Corporation.
Operating Voltage: 15 – 32VDC
Maximum Current Draw: 6.4mA (LED on) Honeywell® and
SLC Standby & Alarm Current: 750μA max @ 24 System Sensor® are
registered trademarks
VDC (one communication every sec with 47k EOL)
of and Farenhyt™ is a
End of Line Resistance: 47kW trademark of Honeywell
International, Inc.
ENVIRONMENTAL
This document is not
Operating Temperature: 32º-120ºF (0ºC – 49ºC) intended to be used for
Humidity: 10 to 93% non-condensing) installation purposes. We
try to keep our product
ORDERING INFORMATION information up-to
date and accurate. We
IDP-MONITOR-2: Dual Monitoring Module cannot cover all specific
applications or anticipate
ACCESSORIES all requirements. All
specifications are subject
SMB500: 4” Square Surface Mount Electrical Box
to change without notice.
For Technical
Support, Please call
800-446-6444.
Installation
You can install up to two IDP-MONITOR-10 modules in an accessory
cabinet (Honeywell P/N IDP-ACB). The accessory cabinet has a built-in
mounting plate that positions the module boards so that all of the status
indicators are visible.
Compatibility
The IDP-MONITOR-10 is compatible with the following Farenhyt Series
FACPs:
F E AT U R E S & B E N E F I T S
• 10 contact monitor • Mount up to two • Mounting hardware
modules in one included
• Support for Class A
accessory cabinet
and Class B wiring • UL Listed
(P/N IDP-ACB)
• Fully supervised • CSFM Listed
• Rotary address
• LED indicator for each switches for fast • MEA Listed 386-02-E
input installation Vol. II
• Disable unused • Removable 12 to 18
addresses AWG plug in terminal
blocks for easy wiring
and troubleshooting
IDP-MONITOR-10 Technical Specifications
For a complete listing of all
compliance approvals and
PHYSICAL ORDERING INFORMATION certifications, please visit
www.farenhyt.com.
Dimensions: 6.8" H x 5.8"W x 1.25" D IDP-Monitor-10: 10 Input monitoring module
Shipping Weight: 6.3oz (196g) Microsoft, Windows, and
ACCESSORIES the Windows Logo are
ELECTRICAL RATINGS IDP-ACB: Module Cabinet. 15.25" H x 12.5" W x 3"D registered trademarks
or trademarks of
Wire Gauge: 12-18 AWG Microsoft Corporation.
Operating Voltage: 15 to 32VDC
Honeywell® and
Standby Current: 3.5mA
System Sensor® are
Alarm Current: 55mA max. (Assumes all ten LEDs registered trademarks
solid on) of and Farenhyt™ is a
Initiating Device Circuit Voltage: 10.2VDC max trademark of Honeywell
International, Inc.
Initiating Device Circuit Current: 240μA max
SLC Wiring Resistance: 40W max.W This document is not
intended to be used for
ENVIRONMENTAL installation purposes. We
try to keep our product
Operating Temperature: 32º-120ºF (0ºC – 49ºC) information up-to
Humidity: 10 to 93% non-condensing) date and accurate. We
cannot cover all specific
applications or anticipate
all requirements. All
specifications are subject
to change without notice.
For Technical
Support, Please call
800-446-6444.
INSTALLATION
The IDP-MONITOR mounts directly into a 4” square electrical box. The box
must have a minimum depth of 2-1/8”. A surface mount electrical box IDP-MONITOR
(System Sensor® PN SMB500) is available from Honeywell.
COMPATIBILITY
The IDP-MONITOR is compatible with the following Honeywell Farenhyt
Series FACPs:
F E AT U R E S & B E N E F I T S
• Isolates short circuits • Panel controlled • UL Listed
on an SLC loop status LED that
• CSFM Listed
flashes green in
• Protects the modules
normal state and is • MEA Listed 427-91-E
on the SLC loop so
solid red in alarm Vol. X
other devices continue
to operate • Standard 4 inch
electrical box
mounting
• SEMS screws for easy
wiring
IDP-MONITOR Technical Specifications
For a complete listing of all
PHYSICAL ORDERING INFORMATION compliance approvals and
certifications, please visit
4.5" H x 4" W x 1.25 D ( 11.4 x 10.2 x 3cm) IDP-MONITOR: Monitoring Module
www.farenhyt.com.
Shipping Weight: 6.3oz (196g?
ACCESSORIES Microsoft, Windows, and
ELECTRICAL RATINGS SMB500: 4” Square surface mount electrical box the Windows Logo are
registered trademarks
Operating Voltage: 15 – 32VDC
or trademarks of
Current Draw (LED on): 5.0mA max Microsoft Corporation.
Operating Current (LED flashing): 375μA
Honeywell® and
Standby Current: 400 μA max @ 24 VDC (one System Sensor® are
communication every 5 sec with 47K EOL); 550 μA registered trademarks
max @ 24 VDC (one communication every 5 sec of and Farenhyt™ is a
with EOL <1K) trademark of Honeywell
5.5 mA (with LED latched on) International, Inc.
LED Current: 5.5 mA (with LED latched on) This document is not
End-of-Line Resistance: 47K W intended to be used for
Initiating Device Circuit Wiring Resistance: 1,500 installation purposes. We
W max try to keep our product
information up-to
SLC Loop Resistance: 40 W max.
date and accurate. We
cannot cover all specific
ENVIRONMENTAL applications or anticipate
Operating Temperature: 32º-120ºF (0ºC – 49ºC) all requirements. All
Humidity: 10 to 93% non-condensing) specifications are subject
to change without notice.
For Technical
Support, Please call
800-446-6444.
The remote annunciator connects to the control panel via the RS-485
system bus. When the system is in normal operation and has AC power, the
Power LED is lit and all other LEDs are off. The other LEDs turn on as
alarms, supervisories, troubles, system silenced and AC power losses occur.
INSTALLATION
The RA-1000 can be surface or flush mounted. Use the optional trim ring
for surface mounts. When flush mounting an electrical box is optional. If RA-1000R /RA-1000
using an electrical box, use a 4S, single-gang, or double-gang box.
COMPATIBILITY
The RA-1000 is compatible with the following Farenhyt Series FACPs:
• IFP-2100 / IFP-2100ECS
• IFP-1000/ECS
• IFP-100/ECS
• IFP-300 / IFP-300ECS
• IFP-75
• IFP-50
F E AT U R E S & B E N E F I T S
• 80-character backlit • Initiate and end fire • Five Status LEDs for; • Support for
LCD display (4 lines drills with a single key alarms, supervisory, simultaneous use of
with 20 characters on press trouble, silence and AC multiple RA-1000s
each line) power indications
• View current status by • Wiring lengths up to
• Tactile/audible alarms, supervisories, • Available in red or gray 6000 ft. from the
feedback or troubles color FACP (depending on
wire gauge and
• RS-485 SBUS • On-board piezo • UL listed, complies
number of devices on
interface to panel sounder audibly with NFPA 72
SBUS)
indicates alarms,
• Larger keypad buttons • Accepts user codes or
troubles, and
for system reset and fire fighter’s key
supervisories
silence
RA-1000 Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
For Technical
SPECIFICATIONS ORDERING INFORMATION Support, Please call
Dimensions: 9.1”W x 7.4”H x 1.5”D (23.1W x 18.8H x RA-1000R: Remote Annunciator. Four line LCD 800-446-6444.
3.8D cm) annunciator with 20 characters per line. Red.
RA-1000: Remote Annunciator. Four line LCD
ENVIRONMENTAL annunciator with 20 characters per line. Gray.
Operating Temperature: 32°F to 120°F (0°C to
49°C) OPTIONAL ACCESSORIES
Humidity: 10% to 93% relative humidity (non- 5860TR: Red Trim Ring. For surface mounting.
condensing) 5860TG: Gray Trim Ring. For surface mounting.
The remote annunciator connects to the control panel via the RS-
485 system bus. When the system is in normal operation and has
AC power, the Power LED is lit and all other LEDs are off. The other
LEDs turn on as alarms, supervisories, troubles, system silenced
and AC power losses occur
INSTALLATION
The RA-100 can be surface or flush mounted. Use the optional
trim ring for surface mounts. When flush mounting an electrical
box is optional. If using an electrical box, use a 4S, single-gang, or
double-gang box.
RA-100
COMPATIBILITY
The RA-100 is compatible with the following Farenhyt Series FACPs:
• IFP-2100 / IFP-2100ECS
• IFP-1000/ECS
• IFP-100/ECS
• IFP-300 / IFP-300ECS
• IFP-75
• IFP-50
F E AT U R E S & B E N E F I T S
• 80-character backlit • Initiate and end fire • Five Status LEDs for; • Wiring lengths up to • Accepts user codes or
LCD display (4 lines drills with a single key alarms, supervisory, 6000 ft. from the fire fighter’s key
with 20 characters on press trouble, silence and AC control panel
• Support for
each line) power indications
• View current status by • UL listed simultaneous use of
• Tactile/audible alarms, supervisories, • Available in red color multiple RA-100s
• Complies with NFPA
feedback or troubles
72 • Can be flush- or
• RS-485 SBUS • On-board piezo surface mounted. Trim
interface to panel sounder audibly ring available for
indicates alarms, surface mounting.
• Larger keypad buttons
troubles, and
for system reset and
supervisories
silence
RA-100 Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
For Technical
PHYSICAL ORDERING INFORMATION Support, Please call
Flush Mount: (Outside wall)12.25”W x 11.5”H x RA-100: Remote Annunciator. Four line LCD 800-446-6444.
7/8”D (31.1W x 29.2H x 2.2D cm) annunciator with 20 characters per line.
(Inside wall)9-3/8”W x 8-3/8”H x 2”D (23.8W x
21.3H x 5.1D cm) OPTIONAL ACCESSORIES
Surface Mount: (Including Trim Ring) 12.25”W x RA-100TR: Red. Surface Mount Trim Ring
11.5”Hx 3”D (31.1W x 29.2H x 2.2D cm))
AGENCY LISTINGS AND APPROVALS
ENVIRONMENTAL • MEA Approved
Operating Temperature: 32°F to 120°F (0°C to
• CSFM Approved
49°C)
Humidity: 10% to 93% relative humidity (non- • FM Approved
condensing)
• UL listed
ELECTRICAL:
Operating Voltage: 24VDC
Standby Current: 20mA
Alarm Current: 25mA
Wiring Distance: Up to 6,000 ft max. from FACP
(depending on wiring method).
Max per System: IFP-50 or IFP-75 (8); IFP-100/
ECS or IFP-1000/ECS (12); IFP-300/ECS (16);
IFP-2100/ECS (31)
COMPATIBILITY
The RA-2000 or RA-2000GRAY are compatible with the following
Honeywell Farenhyt Series FACPs:
• IFP-2000/ECS
• IFP-2100/ECS
• IFP-75
• IFP-300/ECS
• RPS-2000
• RFP-2100
• ECS-LOC
F E AT U R E S & B E N E F I T S
• Four line LCD display • Can be flush or • Multi-panel • On-board piezo • Available in red or gray
with 40 characters per surface mounted. Trim annunciators will sounder audibly color
line ring (P/N RA-100TR or sound the highest indicates alarms,
• Wiring lengths up to
RA-2000GRAYTR) priority tone from the troubles, and
• Tactile/audible 6000 ft. from the
available for surface panel it is assigned to supervisories
feedback when key is control panel
mounting
pressed on • View current status by • Five Status LEDs for;
• UL listed, complies
annunciator • Multi-panel displays alarms, supervisories, alarms, supervisory,
with NFPA 72
can display the status or troubles trouble, silence and AC
• RS-485 SBUS
and event history of all power indications
interface to panel
the panels they are
• Four programmable
• Initiate and end fire assigned in a network
function keys
drills with a single key
press
RA-2000 Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
For Technical
PHYSICAL ORDERING INFORMATION Support, Please call
Flush Mount RA-2000: Remote Annunciator. Red 800-446-6444.
Outside wall: 12.25”W x 11.5”H x 7/8”D (31.1W x RA-2000GRAY: Remote Annunciator. Gray
29.2H x 2.2D cm)
Inside wall: 9-3/8”W x 8-3/8”H x 2”D (23.8W x OPTIONAL ACCESSORIES
21.3H x 5.1D cm) RA-100TR: Red surface mount trim ring
Surface Mount: (Including Trim Ring) 12.25”W x RA-2000GRAYTR: Gray surface mount trim ring
11.5”H x 3”D (31.1W x 29.2H x 2.2D cm)
AGENCY LISTINGS AND APPROVALS
ENVIRONMENTAL UL listed
Operating Temperature: 32°F to 120°F (0°C to CSFM approved
49°C) NFPA 72
Humidity: 0 to 93% relative humidity (non- FM approved
condensing)
FDNY COA#: 6162
ELECTRICAL
Operating Voltage: 24VDC
Standby Current: 25mA
Alarm Current: 50mA
All sensors offer addressable code wheels and two LEDs. The LEDs are
controlled by the panels. Operation modes include red, green, and amber
colors with various solid or blink patterns.The mesh network within the
SWIFT system creates a child-parent relationship between the devices so
that each device has two parents providing a second path for
communications on every device. If one device can no longer operate for
any reason, the rest of the devices can still communicate with each other,
directly or through one or more intermediate devices. The system also
engages frequency hopping to prevent system interference whether
intentional or accidental.
F E AT U R E S & B E N E F I T S
• Wireless Installation • SWIFT devices • Wireless devices use • Ideal for hard-to-wire • Swift Tools provides
integrate with (4) CR-123A lithium buildings and can be valuable information
• Class A mesh network
previously installed batteries or reliable, combined with for device placement
• Complies with UL FACPs through the long lasting battery hard-wired devices for associated with
Standards for UL 864 SWIFT gateway and life. CR-123A batteries enhanced design and conducting Site
and UL 268 the FACP's SLC loop, have a UL listed life of install options Surveys, diagnostics,
• Frequency hopping for a seamless, easy 2 years. All devices history, statistics and
and cost-effective ship with batteries. mesh visualization.
• Bi-directional system addition Swift Tools can be
communications downloaded from the
• Complies with NFPA Farenhyt website at no
72 Fire Alarm System cost. It is also available
requirements. on the W-USB.
SWIFT Detectors Technical Specifications
PHYSICAL ORDERING INFORMATION For a complete listing of all
Height: 2.4” (61 mm) installed in B501W base WIDP-PHOTO: Wireless photoelectric smoke compliance approvals and
certifications, please visit
Diameter: 4.0 inches (102 mm) installed in B501W detector for use with the WIDP-WGI wireless
www.farenhyt.com.
base gateway, B501W included
Device Weight (includes 4 batteries): 8.1 oz (230 WIDP-ACCLIMATE: Wireless multi criteria Microsoft, Windows, and
g) installed in B501W base photoelectric smoke detector with thermal (135°) the Windows Logo are
for use with the WIDP-WGI wireless gateway, registered trademarks
or trademarks of
ENVIRONMENTAL B501W included
Microsoft Corporation.
Operating Temperature Range: Photo: 32°F to WIDP-HEAT: Wireless fixed-temperature (135° F)
120°F (0°C to 49°C); Photo/thermal with Heat: heat detector for use with the WIDP-WGI wireless SWIFT® and Honeywell®
32°F to 100°F (0°C to 38°C) gateway, B501W included are registered trademarks
of and Farenhyt™ is a
Air Velocity: Photo/thermal with Heat: 0 to 4,000 WIDP-HEAT-ROR: Wireless rate-of-rise (135° F)
trademark of Honeywell
fpm (0 to 20 m/sec) heat detector for use with the WIDP-WGI wireless International, Inc.
Humidity: 10 to 93% relative humidity (non- gateway, B501W included
WIDP-WGI: Wireless Gateway. This document is not
condensing)
intended to be used for
Thermal Ratings: Fixed Temperate Set Point: B501W: 4” wireless mounting base.
installation purposes. We
135°F (57°C); Rate-of-Rise Detection: 15°F/min W-USB: Software interface (via USB port) for try to keep our product
(8.3°C/min) computers running the SWIFT Tools programming information up-to
utility. date and accurate. We
ELECTRICAL cannot cover all specific
AGENCY LISTINGS AND APPROVALS applications or anticipate
Maximum Operating Voltage: 3.3VDC all requirements. All
Maximum Standby Current: 210µA @ 3.3VDC (one Each device complies with part 1 of the FCC rules specifications are subject
communication every 23.9 seconds with LED blink meaning operation is subject to two conditions to change without notice.
enabled) 1) The device may not cause harmful interference
2) The device must accept any interference For Technical Support,
Maximum Alarm Current (LED on): 5 mA @ call 800-446-6444.
3.3VDC (LED on) received including interference that may cause
Radio Frequency Range: 902-928MHz undesired operation.
The listings and approvals below apply to the basic
BATTERY SPECIFICATIONS intelligent wireless detector. In some cases, certain
Battery Type: 4 Panasonic CR123A or 4 Duracell modules may not be listed by certain approval
DL 123A agencies or listing may be in process. Consult
factory for latest listing status.
Battery Life: 2 years
UL Listed: S2424
Battery Replacement: Upon TROUBLE BATTERY
LOW display and/or during annual maintenance CSFM: 7272-0559:0506; 7254-0559:0509
FM: approved
FDNY: (pending)
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 350615 | Rev A |11/17
800-328-0103 © 2017 Honeywell International Inc.
SWIFT®
Intelligent Wireless Modules
SWIFT® wireless modules are intelligent addressable modules which
provide secure, reliable communication to the Fire Alarm Control Panel
(FACP) across a Class A mesh network. Wireless modules create an
opportunity for applications where it is costly (concrete walls/ceilings,
buried wires), obtrusive (surface mount conduit), or possibly dangerous
(asbestos) to use traditional wired devices. In addition, both wired and
wireless devices can be present on the same FACP providing an integrated
wired-wireless solution for increased installation potential.
F E AT U R E S & B E N E F I T S
• Wireless Installation • Complies with NFPA • SWIFT Tools makes • Wireless devices use • SWIFT integrates with
72 Fire Alarm System the survey and (4) CR-123A lithium previously installed
• Class A mesh network
requirements. installation faster and batteries for reliable, FACPs for a seamless,
• Addressable code easier to complete; long lasting battery easy and
• SWIFT Tools also
wheels diagnostics simpler to life. CR-123A batteries cost-effective system
creates a useful
• Commercial understand and view have a UL listed life of addition
graphic representation
applications 2 years.
of the wireless • Bi-directional
• Complies with UL network. It provides communications • Frequency hopping
Standards for UL 864 important system data
and a visual
and UL 268 perspective.
SWIFT Module Technical Specifications
MONITOR MODULE RELAY CONTACT RATINGS For a complete listing of all
Physical Dimensions: Height 4½"; Width 4½"; Depth compliance approvals and
Current Maximum Load Application certifications, please visit
1½"
Rating Voltage Description www.farenhyt.com.
Device Weight (includes 4 batteries): 7.9 oz (224 g)
2A 25 VAC PF=0.35 Non-coded Microsoft, Windows, and
ENVIRONMENTAL the Windows Logo are
3A 30 VDC Resistive Non-coded
registered trademarks
Operating Temperature Range: Photo: 32°F to
2A 30 VDC Resistive Coded or trademarks of
120°F (0°C to 49°C); Microsoft Corporation.
Air Velocity: Photo/thermal with Heat: 0 to 4,000 0.46A 30 VDC (L/R = 20 Non-coded
fpm (0 to 20 m/sec) ms) SWIFT® and Honeywell®
are registered trademarks
Humidity: 10 to 93% relative humidity (non- 0.7A 70.7 VAC PF=0.35 Non-coded of and Farenhyt™ is a
condensing) trademark of Honeywell
0.9A 125 VDC Resistive Non-coded
International, Inc.
ELECTRICAL 0.5A 125 VAC PF=0.75 Non-coded
This document is not
Maximum Operating Voltage: 3.3VDC 0.3A 125 VAC PF = 0.35 Non-coded intended to be used for
Average Operating Current: 210μA, 3.9 EOL installation purposes. We
Maximum Current Draw: 5 mA (LED on) ORDERING INFORMATION try to keep our product
EOL Resistance: 3.9K Ohms information up-to
WIDP-Monitor: Wireless monitor module for use
date and accurate. We
Maximum IDC Wiring Resistance: 10 Ohms with the WIDP-WGI wireless gateway. Includes a cannot cover all specific
Maximum IDC Voltage: 3.2Volts special cover with a tamper magnet built in. applications or anticipate
Recommended for installation in a SMB500 box all requirements. All
Maximum Average IDC Current: 5.5μA
(ordered separately) rather than a metal backbox specifications are subject
Maximum Transmit RF Power: 17dBm for best performance. Ships with 4 Panasonic to change without notice.
Radio Frequency Range: 902-928 MHz Battery CR123A or 4 Duracell DL123A batteries.
Life: 2 years For Technical Support,
WIDP-RELAY: Wireless relay module for use with call 800-446-6444.
the WIDP-WGI wireless gateway. Includes a special
BATTERY SPECIFICATIONS cover with a tamper magnet built in. Recommended
Battery Type: 4 Panasonic CR123A or 4 Duracell DL for installation in an SMB500 box (ordered
123A separately) rather than a metal backbox for best
Battery Life: 2 years performance. Ships with 4 Panasonic CR123A or 4
Battery Replacement: Upon TROUBLE BATTERY Duracell DL123A batteries.
LOW display and/or during annual maintenance WIDP-WGI: Wireless Gateway.
W-USB: Wireless USB radio/antenna dongle that
RELAY MODULE SPECIFICATIONS plugs into the USB port of a PC running SWIFT
PHYSICAL / OPERATING SPECIFICATIONS Tools.
Dimensions: Height 4¼"; Width 4¼"; Depth 1½" SMB500: Optional surface-mount backbox.
Operating Temperature Range: 32°F to 120°F (0°C
to 49°C) AGENCY LISTINGS AND APPROVALS
Operating Humidity Range: 10% to 93% non- Each device complies with part 15 of the FCC rules
condensing meaning operation is subject to two conditions.
1) The device may not cause harmful interference
ELECTRICAL SPECIFICATIONS 2) The device must accept any interference
Maximum Operating Voltage: 3.3VDC received including interference that may cause
Average Operating Current: 210μA undesired operation.
Maximum Current Draw: 5mA (LED on) The listings and approvals below apply to the basic
intelligent wireless detectors. In some cases,
Maximum Transmit RF Power: 17dBm certain modules may not be listed by certain
Radio Frequency Range: 902-928MHzMaximum approval agencies or listing may be in process.
Transmit RF Power: 17 dBm Consult factory for latest listing status.
Radio Frequency Range: 902-928 MHz UL Listed: S2424
CSFM (Monitor Module): 7300-0559:0507
FM: approved
FDNY: approved
For more information
Learn more about Honeywell’s Farenhyt Series and
other products available by visiting
www.farenhyt.com
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 350617 | Rev A | 02/18
800-328-0103 © 2018 Honeywell International Inc.
SWIFT®
Wireless System Gateway
SWIFT® Wireless System can be applied in many situations that are
problematic for traditional wired devices. In cases where areas of a building
are difficult or impossible to wire, visually sensitive, or have restricted
access, SWIFT wireless sensors provide an efficient, reliable solution.
The SWIFT system can be installed using only hand tools. However, the
SWIFT Tools PC utility provides many benefits to a site evaluation (Site
F E AT U R E S & B E N E F I T S
• Wireless mesh • Each gateway • Site Survey feature • SWIFT Tools also • SWIFT Tools makes
technology (902-928 supports up to 50 allows for an creates a useful the survey and
MHz frequency) addresses: 1 wireless evaluation of a site graphic representation installation faster and
gateway and up to 49 before the installation of the wireless easier to complete;
• Cascading-wave mesh
devices network. It provides diagnostics simpler to
operation provides a • Standard "code wheel"
important system data understand and view
verification on • Up to 4 wireless for setting the SLC
and a visual
redundant networks can be address
perspective.
communication paths installed with
• Wireless devices use
overlapping radio
• Any wireless device (4) CR-123A lithium
network coverage
can be added to act as batteries
a repeater
• Battery Life – UL listed
for 2 years
SWIFT TOOLS HAS THE FOLLOWING UTILITIES:
• Site Survey
• Create Mesh Network
• Diagnostics
SWIFT Tools works in a wireless environment with the WIDP-WGI and devices within a range of approximately 20 feet.
SWIFT Tools is designed for systems running Microsoft Windows.
COMPATIBILITY
INSTALLATION
Either recessed or surface enclosures may be used with these Emergency
Telephone Stations. If a recessed enclosure is used, the telephone
assembly must be a model designed for recessed enclosures. The same is
true of surface enclosures.
FFT-STSS
F E AT U R E S & B E N E F I T S
• Single Telephone • Heavy-duty
Station Mount comes construction
in a lockable cabinet
• Doors fit either
containing one remote
recessed or surface
handset. Available in
enclosures
Recessed mount
(FFT-STSR) or surface • Red baked-enamel
mount (FFT-STSS). finish
FFT-STSS / FFT-STSR Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 351132 | B | 02/18
800-328-0103 © 2018 Honeywell International Inc.
FFT-FPJ
Fire Fighters Telephone Phone Jack
TThe FFT-FPJ remote Firefighter Phone Jack provides a quick connect to
the IFP-FFT fire fighter telephone system using a FFT-RHS remote
handset.
The FFT-FPJ are wired to the IFP-FFT Fire Fighter Telephone System audio
circuit. A monitor module detects the connection and its address will turn
on the corresponding IFP-FFT zone LED and PZT will sound. Pressing the
answer switch will connect the local handset to the phone circuit allowing
communication with the remote handset
COMPATIBILITY
The FFT-FPJ is compatible with the IFP-FFT. Firefighters Telephone
System.
FFT-FPJ
INSTALLATION
The FFT-FPJ Fire Fighter Phone Jack mounts to a single-gang electrical
box (4” x 2-1/8” x 2½”) or when the addressable mini-monitor module is
installed with it, a deep single-gang electrical box (4” x 2-1/8” x 3¾”). For
detailed installation instructions see IFP-FFT installation manual P/N
54708.
F E AT U R E S & B E N E F I T S
• Single Telephone • Color coded wires, 6
Station Mount comes inches long, are
in a lockable cabinet prewired to the jack to
containing one remote enable fast and
handset. Available in accurate wiring to the
Recessed mount system.
(FFT-STSR) or surface
mount (FFT-STSS).
FFT-FPJ Technical Specifications
For a complete listing of all
PHYSICAL ORDERING INFORMATION compliance approvals and
certifications, please visit
Dimensions: 4¾ ” W x 2¾” H x 1½” D (12.065 x IFP-FFT: Fire Fighters Telephone
www.farenhyt.com.
6.985 x 3.81 cm) IDP-Minimon: Mini-Monitor module
IDP-ISO: Fault Isolator module Microsoft, Windows, and
ENVIRONMENTAL the Windows Logo are
Operating Temperature: 32ºF-120ºF (0ºC – 49ºC) registered trademarks
MISCELLANEOUS ACCESSORIES
or trademarks of
Humidity: 10% – 93% noncondensing FFT-24: 24 Zone Expander Microsoft Corporation.
FFT-FPJ : Remote Phone Jack
ELECTRICAL Honeywell® is a
FFT-RHS : Fire Fighters Remote Hand Set registered trademarks
The FFT-FPJ is a passive device that does not draw
FFT-HSC: Fire Fighters Handset Cabinet. Holds up of and Farenhyt™ is a
current
to 10 remote handsets trademark of Honeywell
FFT-STSR: Single Telephone Station Recessed. A International, Inc.
AGENCY LISTINGS AND APPROVALS
lockable cabinet containing one remote handset. This document is not
UL: Listed
FFT-STSS: Single Telephone Station Surface intended to be used for
CSFM: 7300-0559:0167
Mount. A lockable cabinet containing one remote installation purposes. We
handset. try to keep our product
information up-to
FFT-BGK: Break Glass Kit for FFTSTS
date and accurate. We
VIP-TR: Flush Mount Trim Ring cannot cover all specific
applications or anticipate
all requirements. All
specifications are subject
to change without notice.
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 351204 | A | 02/18
800-328-0103 © 2018 Honeywell International Inc.
IFP-FFT
Fire Fighters Telephone Control System
The IFP-FFT is a Fire Fighters Telephone communication system. The
IFP-FFT Fire Fighter Telephone System provides supervision, annunciation,
and control for local and remote telephone handsets. The IFP-FFT with
keypad, provides indications of phone activation, and corresponding
trouble conditions. The FFT-24 expander board lets you add additional
zones to the IFP-FFT.
The IFP-FFT can use up to two FFT-24s for a total of 72 zones. Each zone
consists of one addressable monitor module (IDP-Minimon) and a
minimum of one Fire Fighter Telephone Jack (FFT-FPJ).
INSTALLATION
The IFP-FFT can be surface or flush mounted. Use VIP-TR Trim Ring for
flush mounting.
COMPATIBILITY
IFP-FFT
The IFP-FFT is compatible with the following FACPs:
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50
• RPS-1000
F E AT U R E S & B E N E F I T S
• IFP-FFT Fire Fighter • Fire Fighter Phone • Fire Fighter Handset • The IFP-FFT supports • For retrofit projects,
Telephone module for Jack (FFT-FPJ) Cabinet (FFT-HSC) is up to 72 IDP-Minimon IFP-FFT is compatible
control and provides a plug-in used to store ten fire devices on one FFT with any UL listed 24V
annunciation of up to location for the fighter handsets system regulated power
72 remote telephone FFT-RHS (FFT-RHS) supply
• Simplified installation
jacks
• Single telephone • System Status LEDs by using single loop
• A maximum of 10 Fire station mount comes design
• Supports two FFT-24
Fighter Remote in a lockable cabinet
zone expanders • JumpStart ®
Handsets (FFT-RHS) containing one remote
auto-programming
can be used at one handset. Available in
time to communicate Recessed mount
over the telephone (FFT-STSR) or surface
circuit connected to mount (FFT-STSS).
the IFP-FFT
IFP-FFT Technical Specifications
PHYSICAL ORDERING INFORMATION For a complete listing of all
Flush Mount Dimensions: 20¼ ”W x 26¾”H x IFP-FFT: Fire Fighters Telephone compliance approvals and
certifications, please visit
2.5”– 3”D (51.4 W x 68 H x 6.4–7.6 D cm) IDP-Minimon: Mini monitor module www.farenhyt.com.
Overall Dimensions: 20”W x 26½”H x 4.6”D (50.75 IDP-ISO: Fault Isolator Module
W x 67.3 H x 11.8 D cm) Microsoft, Windows, and
Weight: 53 lbs. the Windows Logo are
ECS ACCESSORIES
registered trademarks
Color: Red FFT-24: 24 Zone Expander or trademarks of
FFT-FPJ: Remote Phone Jack Microsoft Corporation.
ENVIRONMENTAL FFT-RHS: Fire Fighters Remote Hand Set Honeywell® is a
Operating Temperature: 32°F to 120°F (0°C to FFT-HSC: Fire Fighters Handset Cabinet. Holds up registered trademarks
49°C) to 10 remote handsets of and Farenhyt™ is a
Humidity: 10 to 93% relative humidity (non- FFT-STSR: Single Telephone Station Recessed. A trademark of Honeywell
condensing) lockable cabinet containing one remote handset. International, Inc.
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 351549 | E | 02/18
800-328-0103 © 2018 Honeywell International Inc.
ECS-DUAL50W /
ECS-DUAL50WB
50/100 Watt Dual Channel Amplifier with
optional Backup Amplifier
The ECS-DUAL50W (red) and ECS-DUAL50WB (black) are intelligent 50 /
100 watt amplifier for use with the IFP-100ECS, IFP-300ECS, IFP-
1000ECS, IFP-2000ECS or IFP-2100ECS. The ECS-DUAL50W is used to
amplify audio message for distribution throughout a facility.
Installation
The ECS-DUAL50W can be surface or flush mounted.
Compatibility
The ECS-DUAL50W is compatible with the following voice evacuation
components:
ECS-DUAL50WB
• IFP-100ECS
• IFP-300ECS
• IFP-1000ECS
• IFP-2000ECS
• IFP-2100ECS
F E AT U R E S & B E N E F I T S
• Amplifier is • Dual channel 50 W • The ECS-DUAL50W • UL 864 and UL 2572 • Distributed between
compatible as: 50W each channel with 50 has it’s own power up to 128 audio
• UL listed for 520Hz
with 50W as backup W backup using supply and backup circuits
signaling when used
ECS-50WBU battery
• 100 W single channel with compatible
• Amplifier Bandwidth • Can be mounted up to speakers
• 100 W single channel
400Hz to 4000Hz 6000 feet away from
with 50 W backup • Up to 16 amplifiers per
ECS-Series control
using ECS-50WBU • Built in backup IFP-2000ECS or
panel
amplifier test feature ECS-2100ECS system
• Dual channel using
allows you to • 120VAC or 240VAC for a maximum of
50W for each channel
physically test that the operation 1600 watts
(IFP-2000ECS or
backup amplifers are
IFP-2100ECS only) • Available in a red or
operating properly
black cabinet
ECS-DUAL50W Technical Specifications
PHYSICAL ORDERING INFORMATION For a complete listing of all
Flush Mount Dimensions: 14.5”W x 24.75”H x ECS-DUAL50W: Intelligent 50 Watt Amplifier, Red compliance approvals and
certifications, please visit
3.4”D (36.8 W x 62.9 H x 8.7 D cm) ECS-DUAL50WB: Intelligent 50 Watt Amplifier, www.farenhyt.com.
Overall Dimensions: 16.1”W x 26.5”H x 4.1”D Black
(40.64 W x 66.7 H x 10.5 D cm) ECS-DUAL50WHV: High Voltage (240VAC) Microsoft, Windows, and
Color: Red or Black 50/100 Watt Dual Channel Amplifier. the Windows Logo are
registered trademarks
or trademarks of
ENVIRONMENTAL ACCESSORIES Microsoft Corporation.
Operating Temperature: 32°F to 120°F (0°C to ECS-50WBU: External Backup Amp.
49°C) Honeywell® is a
RBB: RBB Remote Battery Box Cabinet. Use for
registered trademark
Humidity:10% to 93% relative humidity (non- backup batteries up to 35AH. 16" W x 10" H x 6" D of and Farenhyt™ is a
condensing) trademark of Honeywell
AGENCY LISTINGS International, Inc.
ELECTRICAL NFPA 13, NFPA 70, NFPA 72, UL 2572, UL 1711 &
This document is not
Primary AC: 120VAC @ 60Hz UL 864: Local Protective Signalling Systems
intended to be used for
ECS-DUAL50W 25V: 190mA standby current UL Listed installation purposes. We
ECS-DUAL50W 70V: 190mA standby current CSFM: 7165-0559:0174 try to keep our product
ECS-DUAL50W 25V: 2380mA alarm current FDNY COA: (pending) information up-to
date and accurate. We
ECS-DUAL50W 70V: 2470mA alarm current cannot cover all specific
Primary AC: 240V @50Hz applications or anticipate
ECS-DUAL50WHV 25V: 200mA standby current all requirements. All
specifications are subject
ECS-DUAL50WHV 70V: 200mA standby current to change without notice.
ECS-DUAL50WHV 25V: 1260mA alarm current
For Technical
ECS-DUAL50WHV 70V: 1310mA alarm current
Support, Please call
Total Power: 100 W @ 25 VRMS or 70.7 VRMS 800-446-6444.
• Circuit 1-4: 50W max.
• Circuit 5-8: 50W max
Main ECS Panel SBUS Standby & Alarm: 10mA
Battery Charging Capacity: 7 – 35AH
Battery Size: 18AH max allowed in cabinet. Use
RBB accessory cabinet for larger batteries up to
35AH per system.
Voice Integration Wiring:
Six conductor
Two voice bus
Four SBUS
The ECS-50W/ECS-50WB has its own power supply with battery backup
and four speaker circuits which can be expanded to eight speaker circuits
with the optional ECS-CE4. The ECS-50W/ECS-50WB is fully supervised
by the main panel for trouble conditions.
Compatibility
The ECS-50W / ECS-50WB are compatible with the following Honeywell
Farenhyt Series voice evacuation components: ECS-50W
• IFP-100ECS
• IFP-300ECS / IFP-300ECSB
• IFP-1000ECS
• IFP-2000ECS
• IFP-2100ECS / IFP-2100ECSB
F E AT U R E S & B E N E F I T S
• SBUS addressable, up • ECS-50W uses an • Selectable for 25V or • Available in a red or
to eight ECS-50Ws per easy to install wire 70.7V operation black cabinet
system for a total of harness to connect the
• Six-wire connection to • The ECS-50W/
400 watts ECS-CE4 audio circuit
ECS system: ECS-50WB can be
expander
• Each ECS-50W is Two-wires for the voice surface or flush
supervised and has • Can be mounted up to bus and four-wires for mounted
four onboard audio 6000 feet away from the SBUS connections
• 120 VAC or 240 VAC
circuits expandable to ECS-Series panel
• UL 864 and UL 2572 operation
eight with the
• The ECS-50W has it’s
ECS-CE4 for a system
own power supply and
total of 64 audio
backup battery
circuits.
ECS-50W / ECS-50WB Technical Specifications
PHYSICAL: ORDERING INFORMATION For a complete listing of all
Flush Mount Dimensions: 14.5”W x 24.75”H x ECS-50W: Intelligent 50 Watt Amplifier, Red compliance approvals and
certifications, please visit
3.4”D (36.8 W x 62.9 H x 8.7 D cm) ECS-50WB: Intelligent 50 Watt Amplifier, Black www.farenhyt.com.
Overall Dimensions: 16”W x 26.25”H x 4.1”D (40.6 ECS-50WHV: High Voltage (204VAC) 50 Watt
W x 66.7 H x 10.5 D cm) Amplifier Microsoft, Windows, and
the Windows Logo are
Color: Red or Black
registered trademarks
ACCESSORIES or trademarks of
ENVIRONMENTAL ECS-CE4: Audio Circuit Expander Microsoft Corporation.
Operating Temperature: 32°F to 120°F (0°C to RBB: Remote Battery Box accessory cabinet. Use
49°C) Honeywell® is a
for backup batteries batteries up to 35AH and too
registered trademark
Humidity: 10% to 93% relative humidity (non- large to fit into ECS-50W cabinet of and Farenhyt™ is a
condensing) AB-55: Remote Battery Box accessory cabinet Use trademark of Honeywell
for back batteries up to 35AH International, Inc.
ELECTRICAL SK-SCK: Seismic Compliance Kit This document is not
Module Voltage Standby *Alarm intended to be used for
AGENCY LISTINGS AND APPROVALS installation purposes. We
Curent Current
NFPA 13, NFPA 70, NFPA 72, UL 2572, UL 1711 & try to keep our product
ECS-50W, 120V 350mA 1100mA UL 864: Local Protective Signalling Systems information up-to
date and accurate. We
25V 60HZ UL Listed cannot cover all specific
CSFM 7300-0559:0173 applications or anticipate
ECS-50WHV, 240V 200mA 600mA
City of New York all requirements. All
25V 50HZ specifications are subject
to change without notice.
ECS-50W, 120V 350mA 1200mA
70V 60HZ For Technical
Support, Please call
ECS-50WHV, 240V 200mA 600mA 800-446-6444.
70V 50HZ
*Fully loaded system
Main ECS Panel SBUS: Standby & Alarm: 10mA
Speaker Circuit: 50 watts @ 25Vrms or 70.7Vrms
max.
Battery Charging Capacity: 7 – 35AH
Battery Size: 18AH max allowed in cabinet. Use
RBB accessory cabinet for larger batteries up to
35AH per system and AB-55 for larger batteries up
to 55AH.
Voice Integration Wiring:
Six conductor
Two voice bus
Four SBUS
The RA-2000 and RA-100 have the same height and flush mount
depth as the ECS-RPU so if your installation requires a fully
functioning LOC with annunciation the RA-2000 or RA-100 can
be installed right next to the ECS-RPU for a sleek installation.
INSTALLATION
The ECS-RPU can be surface or flush mounted.
COMPATIBILITY
The ECS-RPU is compatible with the following ECS FACP's:
• IFP-2100ECS (max 15 per system)
F E AT U R E S & B E N E F I T S
• Smaller footprint than • Eight emergency • 6 mappable audio
the ECS-LOC communication switches
message buttons
• Supervised
Microphone
• Connects to control
panel via 4-wire SBUS
and 2-wire VBUS
ECS-RPU Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
ECS-RPU OPEN 180° FOR EASY ACCESS TO BOARD International, Inc.
For Technical
Support, Please call
800-446-6444.
COMPATIBILITY
The ECS-LOC2100 and ECS-LOC2100B are compatible with the following
ECS FACP's: ECS-LOC2100B
• IFP-2100ECS
• IFP-2100ECSB
• IFP-2000ECS
F E AT U R E S & B E N E F I T S
• On-board supervised • After the main panel • Up to 128 mappable • All Call and • Six-wire connection to
microphone unit, up to 15 speaker circuits using Non-Active Call ECS system;
ECS-LOC2100’s can a combination of buttons to quickly Two-wires for the voice
• Available in a red or
be added to provide a ECS-50W, ECS-125W select all active or all bus, and four-wires for
black cabinet
total of 15 command or ECS-DUAL50W’s the non-active output the SBUS connections
• Programmable trigger units. mappable to 64 groups
inputs from an buttons controlling
• The ECS-LOC2100 or
external source, such selected output
ECS-LOC2100B
as a Monaco system, groups
meets the
to either the ECS-RVM
requirements for a
or 5880. Up to eight
LOC
inputs available on the
5880 module
ECS-LOC2100 Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
For Technical
PHYSICAL ORDERING INFORMATION Support, Please call
Overall Dimensions ECS-LOC2100: Local Operator Console 800-446-6444.
20.362”W x 27”H x 5.054”D (51.7 W x 68.6 H x ECS-LOC2100B: Local Operator Console. Black
12.8 D cm)
Color: Red or Black ACCESSORIES
ECS-RVM: Remote voice module
ENVIRONMENTAL RA-2000: Keypad annunciator
Operating Temperature: 32°F to 120°F (0°C to 5880: LED/IO module
49°C) ECS-CE4: 4 speaker circuit expander
Humidity: 0 to 93% relative humidity (non ECS-SW24: 24 switch expander
condensing)
APPROVALS
ELECTRICAL
NFPA 13, NFPA 15, NFPA 16, NFPA 70, &
Standby Current: 105mA
NFPA 72: Central Station; Remote Signalling; Local
Alarm Current: 175mA Protective Signalling Systems; Auxiliary Protected
Voice Integration Wiring: Premises Unit; Water Deluge Releasing Service.
Six conductor
• UL Listed
Two voice bus
Four SBUS • CSFM: 7165-0559:0505
• FM approved
The 5880 LED / IO module can also be used with an ECS-LOC application.
The module provides an effective means to customize your remote.
annunciation, providing 40 programmable LED outputs and eight
supervised dry contact inputs. You can use up to eight 5880 modules on
one ECS-LOC control panel for maximum flexibility. Its compact size
enables it to be mounted inside the EVS-LOC, or in an accessory cabinet.
F E AT U R E S & B E N E F I T S
• Provides additional • Makes access to the • For added fl exibility, it • Up to 32 mappable • The optional VIP-TR
communications and communication can also accept speaker circuits can be trim ring is useful for
control options that system easier when programmable trigger connected on the creating a visual
are also available in immediate and timely inputs from external ECS-LOC using a appealing interface
the ECS primary panel communications are source, such as a combination of the between the panel and
essential Monaco® system, to ECS-50W, ECS-100W mounting wall.
• Useful for extending
either the RVM or ECS-DUAL50W or
system access to
5880. Up to eight ECS-125W amplifiers.
additional areas of a
inputs are available on This is useful for
building or mass
the 5880 module. extended reach during
notification network
times when urgent
emergency
communication is
required.
ECS-LOC Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® is a
registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
Finally, attach the horn, strobe, or horn/strobe to the mounting plate by INDOOR WALL HORN OUTDOOR WALL
STROBE
inserting the product’s tabs in the mounting plate’s grooves. The device will
rotate into position, locking the product’s pins into the mounting plate’s
terminals. The device will temporarily hold in place with a catch until it is
secured with a captured mounting screw.
MODELS AVAILABLE:
• Indoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-wire horn/strobe
F E AT U R E S & B E N E F I T S
• Plug-in design and • Field-selectable • Offers speakers with • Designed with • Built with an updated
protective cover candela settings on both high fidelity and tamper-resistant modern design
reduce ground faults wall and ceiling units: high volume sound construction
15, 15/75, 30, 75, 95, output
• Universal mounting • Three volume
110, 115, 135, 150,
plate for wall and • Compatible with selections and rotary
177, and 185.Uses an
ceiling units System Sensor switch for horn tone.
automatic selection of
synchronization
• Shorting spring on 12- or 24-volt • Horn rated at 88+ dbA
protocol
mounting plate for operation at 15 and 30 at 16 volts
continuity check candela • Electrical
• Outdoor products
before installation compatibility with
• Rotary switch for horn rated from –40°F and
existing SpectrAlert
tone and three volume 151°F (–40°C and
products
settings 66°C).
ENGINEER SPECIFICATIONS
SpectrAlert Advance horns, strobes, and horn/strobes shall mount to a standard 4.0" x 4.0" x 1.5" (10.16 x 10.16 x 3.81 cm) backbox, 4.0"
(10.16 cm) octagonal backbox, or a double-gang backbox. Two wire products shall also mount to a single-gang 2.0" x 4.0" x 1.875" (5.08 x
10.16 x 4.763 cm) backbox. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance
circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™
Module accessory, shall be powered from a noncoded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.
When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;
24-volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall
operate between 32°F and 120°F (0°C and 49°C) from a regulated DC, or full-wave-rectified, unfiltered power supply. Strobes and horn/
strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177,185.
STROBE
The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective
service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall
consist of a xenon flash tube and associated lens/reflector system.
HORN/STROBE COMBINATION
The horn/strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire
protective service. The horn/strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe
light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to
switch between a Temporal 3 pattern and a Non-Temporal (continuous) pattern. These options are set by a multiple position switch. On
four-wire products, the strobe shall be powered independently of the sounder. The horn on horn/strobe models shall operate on a coded
or non-coded power supply.
OUTDOOR PRODUCTS
SpectrAlert Advance outdoor horns, strobes and horn/strobes shall be listed for outdoor use by UL and shall operate between –40°F and
151°F (–40°C and 66°C). The products shall be listed for use with a System Sensor outdoor/weatherproof backbox with half-inch and
three-fourths-inch conduit entries.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit MDL3RA or MDL3WA listed to UL 464 and shall be approved for fire protective service.
The module shall synchronize SpectrAlert strobes at 1 Hz and horns at Temporal 3. Also, while operating the strobes, the module shall
silence the horns on horn/strobe models over a single pair of wires.The module shall mount to a 4.688" x 4.688" x 2.125" (11.906 x 11.906
x 5.398 cm) backbox. The module shall also control two Style Y (class B) circuits or one Style Z (Class A) circuit. The module shall
synchronize multiple zones. Daisy-chaining two or more synchronization modules together will synchronize all the zones they control. The
module shall not operate on a coded power supply.
PHYSICAL
Ceiling-mount dimensions (including lens): 6.8" diameter x 2.5" deep (17.3 cm diameter x 6.4 cm deep)
Wall-mount dimensions (including lens): 5.6" H x 4.7" W x 2.5" D (14.2 cm H x 11.9 cm W x 6.4 cm D)
Horn dimensions: 5.6" H x 4.7" W x 1.3" D (14.2 cm H x 11.9 cm W x 3.3 cm D)
ELECTRICAL
Strobe flash rate: 1 flash per second.
Nominal voltage: regulated 12 VDC/FWR or regulated 24 VDC/FWR. NOTE: Full Wave Rectified (FWR) voltage is a non-regulated, time
varying power source that is used on some power supply and panel outputs.
Operating voltage range: 8 V to 17.5 V (12 V nominal); or 16 V to 33 V (24 V nominal). NOTE: P, S, PC, and SC products will operate at 12 V
nominal only for 15 cd and 15/75 cd.
Input terminal wire gauge: 12 to 18 AWG (3.31 to 0.821 mm²).
ENVIRONMENTAL
Standard Operating Temperature: 32°F to 120°F (0°C to 49°C). K Series operating temperature: –40°F to 151°F (–40°C to 66°C).
Humidity Range: 10 to 93% non-condensing (indoor products)
HORN AND HORN/STROBE ROTARY SWITCH SETTING HORN AND HORN/STROBE OUTPUT (dBA)
Setting Repetition Rate dB Level SOUND 8-17.5V 16-33V
1 Temporal horn High SETTING PATTERN DB DC FWR DC FWR
2 Temporal horn Medium 1 Temporal High 78 78 84 84
3 Temporal horn Low 2 Temporal Medium 74 74 80 80
4 Normal horn High 3 Temporal Low 71 73 76 76
5 Normal horn Medium 4 Non- Temporal High 82 82 88 88
6 Normal horn Low 5 Non- Temporal Medium 78 78 85 85
7* Externally coded High 6 Non- Temporal Low 75 75 81 81
8* Externally coded Medium 7* Coded High 82 82 88 88
9* Externally coded Low 8* Coded Medium 78 78 85 85
*NOTE: Settings 7, 8, and 9 are not available on 9* Coded Low 75 75 81 81
2-wire horn/strobe
*Note: Settings 7, 8, and 9 are not available on 2-wire horn/strobe.
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 350377 | Rev B | 03/18
800-328-0103 © 2018 Honeywell International Inc.
SpectraAlert® Advance
Selectable Output Low Frequency Sounder and
Low Frequency Sounder Strobes
The SpectrAlert® Advance audible visible notification products are UL® 464
Compliant for the 520 Hz low frequency signal. The SpectrAlert Advance
Series offers the most versatile and easy-to-use line of low frequency
sounder and low frequency sounder strobes in the industry. With white and
red plastic housings and listed for dual wall and ceiling mountings, the
SpectrAlert Advance complies with any application requirement. The low
frequency sounder and sounder strobes are rich with features guaranteed
to reduce the installation times and maximize profits.
Like the entire SpectrAlert Advance product line, the wall-mount low
frequency sounder and the low frequency sounder strobes include a variety
of features that increase their application versatility while simplifying the
installation.
LOW FREQUENCY SOUNDERS /
SOUNDER STROBES
All devices feature plug-in designs with minimal intrusion into the backbox,
making installations fast and foolproof while eliminating costly and
time-consuming ground faults.
F E AT U R E S & B E N E F I T S
• Plug-in design with • Low Frequency • Designed with a • Compatible with
minimal intrusion into Sounder rated at 76+ mounting plate MDL3 sync module
the back box dBA at 16 volts shorting spring that
• Listed for ceiling or
checks wiring
• Built with tamper- • Rotary switch for low wall mounting
continuity before
resistant construction frequency sounder
device installation • Meets NFPA 72
tone
• Field-selectable chapter 18 & 29
• Electrically compatible
candela settings on • Includeds a universal requirements for low
with legacy
wall units: 135, 150, mounting plate for frequency sounders
SpectrAlert devices
177, and 185 wall units
ENGINEER SPECIFICATIONS
The SpectrAlert Advance low frequency sounder and low frequency sounder strobes shall mount to a standard 4” x 4” x 1-1/2” (10.16 x
10.16 x 3.81 cm) backbox, 4” (10.16 cm) octagon backbox, or double-gang backbox. Two-wire products shall also mount to a single-gang
2” x 4” x 17/8” (5.08 x 10.16 x 5.39 cm) backbox. A universal mounting plate shall be used for mounting products. The notification
appliance circuit wiring shall terminate at the universal mounting plate.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync.Circuit model MDL3 Listed to UL Standard 464 and shall be approved for fire protective
service. The module shall synchronize SpectrAlert strobes at 1 Hz and low frequency sounder at temporal three. Also, while operating the
strobes, the module shall silence the low frequency sounder on low frequency sounder strobe models over a single pair of wires. The
module shall mount to a 4 11/16” x 4 11/16” x 2 1/8” (11.90 x 11.90 x 5.39 cm) backbox. The module shall also control 2 Style Y (Class B)
circuits or (1) Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules
together will synchronize all the zones they control. The module shall not operate on a coded power supply.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit MDL3RA or MDL3WA listed to UL 464 and shall be approved for fire protective service.
The module shall synchronize SpectrAlert strobes at 1 Hz and horns at Temporal 3. Also, while operating the strobes, the module shall
silence the horns on horn/strobe models over a single pair of wires.The module shall mount to a 4.688" x 4.688" x 2.125" (11.906 x 11.906
x 5.398 cm) backbox. The module shall also control two Style Y (class B) circuits or one Style Z (Class A) circuit. The module shall
synchronize multiple zones. Daisy-chaining two or more synchronization modules together will synchronize all the zones they control. The
module shall not operate on a coded power supply.
PHYSICAL
Wall Mount Dimensions (including lens): 6.4”L x 4.7” W x 2.5” D (162 mm L x 119 mm W x 64 mm D)
Sounder Dimensions: 5.6” L × 4.7” W × 1.3” D (142 mm L × 119 mm W × 33 mm D)
Low Frequency Sounder/Strobe with Surface Mount Back Box Dimensions (SBBR, SBBW): 4”L x 4.7” W x 4.3”D (162 mm L x 120 mm W
x 108 mm D)
Low Frequency Sounder with Surface Mount Back Box Dimensions (SBBR, SBBW): 5.7”L x 4.8” W x 3”D (145 mm L x 120 mm W x 76
mm D)
ELECTRICAL
Strobe Flash Rate: 1 flash per second
Nominal Voltage Low Frequency Sounder Strobe: Regulated 12VDC/FWR or regulated 24 DC/FWR1
Nominal Voltage Range Low Frequency Sounder: Regulated 12 VDC/FWR1
Operating Voltage Range: 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range MDL3 Sync Module: 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
Input Terminal Wire Gauge: 12 to 18 AWG.
ENVIRONMENTAL
Standard Operating Temperature: 32°F to 120°F (0°C to 49°C).
Humidity Range: 10 to 93% non-condensing
UL MAX STROBE CURRENT DRAW ( mA RMS) UL MAX, LOW FREQUENCY CURRENT DRAW (mA RMS)
8-17.5V 16-33V 8-17.5V 16-33V
CANDELA DC FWR DC FWR SOUND PATTERN dB DC FWR DC FWR
High 135 N/A N/A 228 207 Temporal High 191 262 138 166
Candela
150 N/A N/A 246 220 Continuous High 292 384 138 208
Range
177 N/A N/A 281 251 Coded High 292 388 153 205
185 N/A N/A 286 258
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 350809 | Rev B | 03/18
800-328-0103 © 2018 Honeywell International Inc.
L-Series Chimes and Chime /
Strobes
The L-Series product line of wall and ceiling mount chimes and chime
strobes include a variety of features that increase their application
versatility while simplifying the installation. With white and red plastic
housings, System Sensor L-Series can meet virtually any application
requirement.
All devices feature plug-in design with minimal intrusion into the back box,
making the installation fast and foolproof while virtually eliminating costly
and time-consuming ground faults. WALL-MOUNT CHIMES AND WALL/CEILING-
MOUNT CHIME STROBES
Installers can easily adapt devices to a wide range of application
requirements using field-selectable candela settings, automatic selection
of 12-or-24 volt operation, and a rotary switch for chime tones and two
volume selections.
F E AT U R E S & B E N E F I T S
• Built with an updated • Designed with • Automatic selection of • Electrically compatible • Captive mounting
modern aesthetic tamper-resistant 12- or 24-volt with existing screw
design construction operation at 15 and 30 SpectrAlert and
candela SpectrAlert Advance
• Features a Plug-in • Field-selectable
devices
design that allows candela settings: • Five selectable tones
minimal intrusion into Wall: 15, 30, 75, 95, with high and low • Wall models listed for
the backbox 110, 135, 185 volume settings wall mounting only,
Ceiling: 15, 30, 75, 95, ceiling models listed
• Mounting plate
115, 150, 177 for ceiling mounting
shorting spring
only
feature checks wiring • Uses a rotary switch
continuity before for tone and volume
device installation selections
L-Series Specifications
ARCHITECT/ENGINEER SPECIFICATIONS
GENERAL
System Sensor L-Series chimes and chime strobes shall mount to a standard 4×4 × 1½-inch back box, 4-inch octagon back box,
singlegang 2 × 4 × 17/8-inch back box, or double-gang back box. A universal mounting plate shall be used for mounting products. The
notification appliance circuit wiring shall terminate at the universal mounting plate. Also, System Sensor L-Series products, when used
with the Sync•Circuit Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a
nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate
between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series
products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC, or full-wave rectified, unfiltered power supply.
Chime strobes shall have field-selectable candela settings of 15, 30, 75, 95, 110 , 135, and 185 for wall units and 15, 30, 75, 95, 115,
150, and 177 for ceiling units.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit _______ listed to UL 464 and shall be approved for fire protective service. The
module shall synchronize SpectrAlert strobes at 1Hz and all available chime tones. Also, while operating the strobes, the module shall
silence the chimes on chime/strobe models over a single pair of wires. The module shall mount to a 4 11/16 × 4 11/16 × 2 1/8-inch back
box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple
zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not
operate on a coded power supply.
TONE SELECTION
To select the chime tone, use the rotary switch on the back of the product. The current draw and sound measurements for various
chime tone settings are listed below.
HORN STROBE TONES AND SOUND OUTPUT DATA HORN STROBE TONES AND SOUND OUTPUT DATA
SETTINGS REPETITION RATE DB LEVEL SWITCH SOUND PATTERN 8-17V 16-33V
1 1 Second Chime High POSITION dB DC DC FWR
2 1 Second Chime Low 1 1 Second Chime High 61 62 62
3 ¼ Second Chime High 2 1 Second Chime Low 56 55 55
4 ¼ Second Chime Low 3 ¼ Second Chime High 67 70 70
5 Temporal Chime High 4 ¼ Second Chime Low 61 61 61
6 Temporal Chime Low 5 Temporal Chime High 64 66 66
7 5 Second Whoop High 6 Temporal Chime Low 59 60 60
8 5 Second Whoop Low 7 5 Second Whoop High 76 78 78
9 Coded** High 8 5 Second Whoop Low 62 64 64
9 Coded** High 57 51 57
**For chime only.
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
The model's visual signaling text labeled, ALERT, is printed on the white
housing's amber lens strobes and speaker strobes. This visual signaling
label is used to identify the emergency communications in compliance
with ANSI/ UL 1638 — Standard for General Signaling Visible Appliances.
Other Plain or ALERT-printed models provide clear lenses for use with color
lens strobe attachments (amber, blue, green, and red). These models can
easily attach to strobe and speaker strobe devices without a candela
derating.
GENERAL
System Sensor L-Series strobes and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-
gang back box. L-Series compact devices shall mount to a single-gang 2 × 4 × 1 7⁄8-inch back box. L-Series speaker strobes shall mount to
a 4 x 4 x 21/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance
circuit wiring and amplifier wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the
Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal
12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and
17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall
operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes, horn strobes,
and speaker strobes shall have field-selectable candela settings, including 15, 30, 75, 95, 110, 115, 135, 150, 177, and 185.
STROBE
The clear strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service.
Colored lens strobes shall be listed to ANSI/UL 1638 and shall be approved for Private Mode Emergency. The strobe shall be wired as a
primary signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,
flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon fl ash tube and associated lens/
reflector system.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The
module shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence
the horns on horn strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 2 1⁄8-inch back box. The
module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy
chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a
coded power supply.
UL MAX CURRENT DRAW (mA RMA), WALL HORN STROBE, CANDELA RANGE (15-185 cd)
DC INPUT 8-17.5V 16-33V
15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd
Temp Hi 98 158 54 74 121 142 162 196 245
Temp Low 93 154 44 65 111 133 157 184 235
Non-Temporal High 106 166 73 94 139 160 182 211 262
Non-Temporal Low 93 156 51 71 119 139 162 190 239
3.1K Temp Hi 93 156 53 73 119 140 164 190 242
3.1K Temp Low 91 154 45 66 112 133 160 185 235
3.1K Non-Temp Hi 99 162 69 90 135 157 175 208 261
3.1K Non-Temp Low 93 156 52 72 119 138 162 192 242
FWR INPUT 16-33V
15cd 30cd 75cd 95cd 110cd 135cd 185cd
Temporal Hi 83 107 156 177 198 234 287
Temporal Low 68 91 145 165 185 223 271
Non-Temporal High 108 135 181 207 230 264 316
Non-Temporal Low 79 104 157 175 197 235 283
3.1K Temp Hi 81 105 155 177 196 234 284
3.1K Temp Low 68 90 145 166 186 222 276
3.1K Non-Temp Hi 101 131 176 204 230 264 326
3.1K Non-Temp Lo 77 102 156 177 199 234 291
UL MAX CURRENT DRAW (mA RMA), CEILING HORN STROBE, CANDELA RANGE (15-177cd)
DC INPUT 8-17.5V 16-33V
15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temp Hi 103 167 71 90 143 165 162 217 254
Temp Low 96 165 54 71 137 161 157 211 249
Non-Temporal High 106 173 71 90 141 165 182 230 273
Non-Temporal Low 93 166 54 71 124 161 162 216 258
3.1K Temp Hi 111 164 69 94 147 163 164 229 257
3.1K Temp Low 103 163 54 88 143 155 160 212 252
3.1K Non-Temp Hi 111 172 69 94 144 164 175 229 271
3.1K Non-Temp Low 103 169 54 88 131 155 162 217 259
FWR INPUT 16-33V
15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temporal Hi 107 135 179 198 223 254 286
Temporal Low 78 101 151 172 199 229 262
Non-Temporal High 107 135 179 198 223 254 286
Non-Temporal Low 78 101 151 172 199 229 262
3.1K Temp Hi 108 135 179 200 225 255 289
3.1K Temp Low 79 101 150 171 196 229 260
3.1K Non-Temp Hi 108 135 179 200 225 255 289
3.1K Non-Temp Lo 79 101 150 171 196 229 260
HORN TONES AND SOUND OUTPUT DATA
SWITCH SOUND PATTERN 8-17.5V 16-33V For a complete listing of all
POSITION DB DC DC FWR compliance approvals and
certifications, please visit
1 Temporal High 84 89 89 www.farenhyt.com.
2 Temporal Low 75 83 83 Microsoft, Windows, and
3 Non-Temporal High 85 90 90 the Windows Logo are
registered trademarks
4 Non-Temporal Low 76 84 84 or trademarks of
Microsoft Corporation.
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82 Honeywell® and
System Sensor® are
7 3.1 KHz Non-Temporal High 84 89 89 registered trademark
of and Farenhyt™ is a
8 3.1 KHz Non-Temporal Low 77 83 83
trademark of Honeywell
International, Inc.
ORDERING INFORMATION COLORED LENSES This document is not
LENS-A2: Wall-Mount Lens Attachment, Amber intended to be used for
ALERT DEVICES LENS-B2: Wall-Mount Lens Attachment, Blue installation purposes. We
SWL-CLR-ALERT: Strobe, White, Wall, Clear Lens, try to keep our product
LENS-G2: Wall-Mount Lens Attachment, Green information up-to
Alert
LENS-R2: Wall-Mount Lens Attachment, Red date and accurate. We
SWL-ALERT: Strobe, White, Wall, Amber Lens, Alert cannot cover all specific
LENS-AC2: Ceiling-Mount Lens Attachment,
SCWL-CLR-ALERT: Strobe, White, Ceiling, Clear Amber applications or anticipate
Lens, Alert all requirements. All
LENS-BC2: Ceiling-Mount Lens Attachment, Blue specifications are subject
SPSWL-ALERT: Speaker Strobe, White, Wall, Amber
LENS-GC2: Ceiling-Mount Lens Attachment, to change without notice.
Lens,Alert
Green
SPSWL-CLR-ALERT: Speaker Strobe, White, Wall, For Technical
LENS-RC2: Ceiling-Mount Lens Attachment, Red
Clear Lens, Alert Support, Please call
SPSCWL-CLR-ALERT: Speaker Strobe, White, 800-446-6444.
BEZEL KITS*
Ceiling, Clear Lens,Alert
BZR: Wall Red Bezel Kit
PLAIN WALL STROBES BZW: Wall White Bezel Kit
SRL-P: Strobe, Red, Wall, Plain BZGR: Compact Wall Red Bezel Kit
SWL-P: Strobe, White, Wall, Plain BZGW: Compact Wall White Bezel Kit
BZRC: Horn/Strobe Ceiling Red Bezel Kit
PLAIN WALL HORN STROBES BZWC: Horn/Strobe Ceiling White Bezel Kit
P2RL-P: Horn Strobe, Red, Wall, Plain BZSPR: Speaker Wall Red Bezel Kit
P2WL-P: Horn Strobe, White, Wall, Plain BZSPW: Speaker Wall White Bezel Kit
BZSPRC: Speaker Ceiling Red Bezel Kit
PLAIN WALL SPEAKER STROBES BZSPWC: Speaker Ceiling White Bezel Kit
SPSRL-P: Speaker Strobe, Red, Wall, Plain *Each bezel pack ships in a package of 5. For bezel
SPSWL-P: Speaker Strobe, White, Wall, Plain option add -F (FIRE), -AL (ALERT), -EV (EVAC), -AG
(AGENT), -P (Plain), -SP (FUEGO), -PG (FOGO) for
PLAIN CEILING SPEAKER STROBES desired printing.
SPSCWL-SP: Speaker Strobe, White, Ceiling, Plain
AGENCY LISTINGS AND APPROVALS
Notes: All -P models have a plain housing (no
“FIRE” marking on cover). UL: Listed
FM: Approved
CSFM: Listed
The L-Series line of wall-mount horns, strobes, and horn strobes include
a variety of features that increase their application versatility while
simplifying installation. All devices feature plug-in designs with minimal
intrusion into the back box, making installations fast and foolproof
while virtually eliminating costly and time-consuming ground faults.
F E AT U R E S & B E N E F I T S
• Updated Modern • Meets DoD • Automatic selection of • Mounting plate • Compatible with
Aesthetics specification 12- or 24-volt shorting spring checks System Sensor
requirements operation at 15 and 30 wiring continuity synchronization
• Offers small profile
candela before device protocol
devices for horns and • Features a plug-in
installation
horn strobes design with minimal • Uses field-selectable • Listed for wall
intrusion into the back candela settings on • Supports electrically mounting only
• Color lens
box wall units: 15, 30, 75, compatible with
attachments for use
95, 110, 135, 185 existing SpectrAlert
with clear lens wall or • Horn rated at 88+ dBA
and SpectAlert
ceiling strobe at 16 volts • Mounting plate for all
Advance devices
standard and all
• Designed with • Supports rotary switch
compact wall units
tamper-resistant for horn tone and two
construction volume selections
L-SERIES SPECIFICATIONS ARCHITECT/ENGINEER SPECIFICATIONS
GENERAL
L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 1 7/8-inch back box, 4 × 4 × 1½-inch back box,
4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 1 7⁄8-inch back
box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal
mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the
universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-
coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module,
12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance
circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees
Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable
candela settings including 15, 30, 75, 95, 110, 135, and 185.
STROBE
The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The
strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements
for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a
xenon flash tube and associated lens/reflector system.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit model MD L3 listed to UL 464 and shall be approved for fire protective service.
The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module
shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11⁄16 × 4 11⁄16 × 2 1⁄8-inch
back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize
multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module
shall not operate on a coded power supply.
PHYSICAL AGENCY LISTINGS AND APPROVALS
Wall-Mount Dimensions (including lens) : 5.6˝ L × 4.7˝ W × 1.25˝ D UL: Listed
(143 mm L × 119 mm W × 32 mm D) FM: Approved
Compact Wall-Mount Dimensions (including lens): 5.26” L x 3.46” W CSFM: Listed
x 1.93” D (133 mm L x 88 mm W x 49 mm D)
Horn Dimensions : 5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W ×
32 mm D)
Compact Horn Dimensions: 5.25” L x 3.45” W x 1.25” D (133mm L x
88mm W x 32mm D)
ELECTRICAL SPECIFICATIONS
Strobe Flash Rate: 1 flash per second
Nominal Voltage Regulated: 12VDC or regulated 24DC/FWR1
Operating Voltage Range2: 8 to 17.5 V (12 V nominal) or 16 to 33 V (24
V nominal)
Operating Voltage Range (MDL3) Sync Module: 8.5 to 17.5V (12 V
nominal) or 16.5 to 33 V (24V nominal)
Input Terminal Wire Gauge: 12 to 18 AWG
ENVIRONMENTAL
Standard Operating Temperature: 32°F to 120°F (0°C to 49°C)
Humidity Range: 10 to 93% non-condensing
Notes:
1. Full Wave Rectifi ed (FWR) voltage is a non-regulated, time-varying
power source that is used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd.
UL MAX HORN CURRENT DRAW ( mA RMS) UL MAX STROBE CURRENT DRAW ( mA RMS)
SOUND PATTERN DB 8-17.5V 16-33V CANDELA 8-17.5V 16-33V
DC DC FWR DC DC FWR
Temporal High 39 44 54 CANDELA 15 88 43 60
Temporal Low 28 32 54 RANGE 30 143 63 83
Non-Temporal High 43 47 54 75 N/A 107 136
Non-Temporal Low 29 32 54 95 N/A 121 155
Non-Temporal Low 29 32 54 110 N/A 148 179
3.1 KHz Temporal High 39 41 54 135 N/A 172 209
3.1 KHz Temporal Low 29 32 54 185 N/A 222 257
3.1 KHz Non-Temporal High 42 43 54
3.1 KHz Non-Temporal Low 28 29 54
Coded High 43 47 54
3.1 KHz Coded High 42 43 54
UL MAX CURRENT DRAW (mA RMS), 2-WIRE HORN STROBE, CANDELA RANGE (15-115 CD)
8-17.5V 16-33V
DC INPUT 15CD 30CD 15CD 30CD 75CD 95CD 110CD 135CD 185CD
EM Temp Hi 98 158 54 74 121 142 162 196 245
EM Temp Low 93 154 44 65 111 133 157 184 235
EM Cont Hi 106 166 73 94 139 160 182 211 262
EM Cont Low 93 156 51 71 119 139 162 190 239
3.1K Temp Hi 93 156 53 73 119 140 164 190 242
3.1K Temp Low 91 154 45 66 112 133 160 185 235
3.1K Cont Hi 99 162 69 90 135 157 175 208 261
3.1K Cont Low 93 156 52 72 119 138 162 192 242
16VFWR
SWITCH POSITION 15CD 30CD 75CD 95CD 110CD 135CD 185CD
EM Temp Hi 83 107 156 177 198 234 287
EM Temp Low 68 91 145 165 185 223 271
EM Cont Hi 111 135 185 207 230 264 316
EM Cont Low 79 104 157 175 197 235 283
3.1K Temp Hi 81 105 155 177 196 234 284
3.1K Temp Low 68 90 145 166 186 222 276
3.1K Cont Hi 104 131 177 204 230 264 326
3.1K Cont Low 77 102 156 177 199 234 291
HORN AND HORN STROBE OUTPUT (DBA)
8-17.5V 16-33V FWR
SWITCH POSITION SOUND PATTERN DB DC DC
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temporal Low 77 83 83
9 Coded High 85 90 90
10 3.1 KHz Coded High 84 89 89
L-SERIES DIMENSIONS
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
Honeywell® and
System Sensor® are
registered trademark
of and Farenhyt™ is a
trademark of Honeywell
International, Inc.
For Technical
Support, Please call
800-446-6444.
The entire L-Series product line of ceiling-mount strobes and horn strobes
include a variety of features that increase their application versatility while
simplifying installation. All devices feature a plug-in design with minimal
intrusion into the back box, making installations fast and foolproof while
virtually eliminating costly and time consuming ground faults.
Installers can also easily adapt devices to a suit a wide range of application
requirements using field-selectable candela settings, automatic selection
of 12- or 24-volt operation, and a rotary switch for horn tones with two
volume selections.
F E AT U R E S & B E N E F I T S
• Listed for ceiling • Tamper-resistant • Automatic selection of • Contains a mounting • Supports electrically
mounting only construction 12- or 24-volt plate with a shorting Compatible with
operation at 15 and 30 spring feature checks legacy SpectrAlert and
• Features a plug-in • includes a universal
candela wiring continuity SpectrAlert Advance
design with minimal mounting plate for
before device devices
intrusion into the back ceiling units • Field-selectable
installation
box candela settings on
• Produces horn rated
ceiling units: 15, 30, • Compatible with
• Designed with at 88+ dBA at 16 volts
75, 95, 115, 150, 177 System Sensor
tamper-resistant
• Rotary switch for horn synchronizaiton
construction
tone and two volume protocol
• Rotary switch for horn selections
tone and two volume
selections
L-SERIES SPECIFICATIONS ARCHITECT / ENGINEER SPECIFICATIONS
GENERAL
L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or
doublegang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 1 7⁄8-inch back box. A universal mounting plate shall
be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance
circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate
between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or
full-wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field-selectable candela settings including 15,
30, 75, 95, 115, 150, and 177.
STROBE
The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The
strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon
flash tube and associated lens/reflector system.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The
module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall
silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11⁄16 × 4 11⁄16 × 2 1⁄8-inch back
box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple
zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not
operate on a coded power supply.
PHYSICAL AGENCY LISTINGS AND APPROVALS
Ceiling-Mount Dimensions (including lens): 6.8" diameter × 2.5"H UL: Listed
(173 mm diameter × 64 mm high) FM: Approved
Ceiling-Mount Surface Mount Back Box Skirt Dimensions CSFM: Listed
(SBBCR, SBBCW): 6.9" diameter x 3.4"H (175 mm diameter x 86
mm
ELECTRICAL
Nominal Voltage: Regulated 12 DC or regulated 24 DC/FWR1
Operating Voltage Range2: 8 to 17.5 V (12 V nominal) or 16 to 33 V
(24 V nominal)
Operating Voltage Range MDL3 Sync Module: 8.5 to 17.5 V (12 V
nominal) or 16.5 to 33 V (24 V nominal)
Input Terminal Wire Gauge: 12 to 18 AWG
ENVIRONMENTAL
Standard Operating Temperature: 32°F to 120°F (0°C to 49°C)
Humidity Range: 10 to 93% non-condensing
Notes:
1. Full Wave Rectifi ed (FWR) voltage is a non-regulated, time-varying
power source that is used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12V nominal only for 15 and 30 cd
UL MAX STROBE CURRENT DRAW ( mA RMS)
CANDELA 8-17.5V 16-33V FWR
DC DC
15 87 41 60
30 153 63 86
75 N/A 111 142
95 N/A 134 164
115 N/A 158 191
150 N/A 189 228
177 N/A 226 264
ORDERING INFORMATION
CEILING STROBES
SCRL: Strobe, Red
SCWL: Strobe, White
SCWL-CLR-ALERT: Strobe, White, ALERT
ACCESSORIES
TR-2: Universal Wall Trim Ring Red
TR-2W: Universal Wall Trim Ring White
SBBCRL: Ceiling Surface Mount Back Box, Red
SBBCWL: Ceiling Surface Mount Back Box, White
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 351575 | Rev B | 02/18
800-328-0103 © 2018 Honeywell International Inc.
L-Series Indoor Ceiling Speaker
Strobes and Dual Speakers
The L-Series indoor selectable-output speaker strobes and dual voltage
evacuation speakers offer a modern, aesthetic, plug-in design that
reduces costly groud faults. The universal mounting plate can be used in
ceiling applications and its flexable design enables the installer to
pre-wire mounting plates, dress the wires, and confirm wiring continuity
before plugging in the speakers. In addition, a protective plastic cover
prevents nicked wires by covering exposed speaker components.
The low total harmonic distortion of the SP speaker offers high fidelity
sound output while still offering high volume sound output for use in high
ambient noise applications.
F E AT U R E S & B E N E F I T S
• Plug-in design and • Field selectable • Rotary switch • Compatible with • Built with a updated
protective cover candela settings on simplifies field System Sensor modern design
reduce ground faults ceiling units: 15, 30, selection of speaker synchronization
75, 95, 115, 150, and voltage (25 and 70.7 protocol
• Universal mounting
177 Vrms) and power
plate with an onboard • Electrical
settings (¼, ½, 1 and 2
shorting spring tests • Automatic selection of compatibility with
watts)
wiring continuity 12- or 24-volt existing SpectrAlert
before installation operation at 15 and 30 • Speakers offer high and SpectrAlert
candela fidelity and high Advance products
• No extension ring
volume sound output
required • Designed with a
tamper-resistant
construction
L-SERIES SPEAKER AND SPEAKER STROBE SPECIFICATIONS / ARCHITECT & ENGINEER SPECIFICATIONS
GENERAL
L-Series speaker and speaker strobes shall mount to a 4 × 4 × 2 1⁄8-inch back box. A universal mounting plate shall be used for mounting
ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also,
L-Series speaker strobes, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance
circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt rated notification appliance
circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 16.5
and 33 volts. Indoor L-Series products shall operate between 32°F and 120°F from a regulated DC, or full-wave rectified, unfiltered power
supply. Speaker strobes shall have field-selectable candela settings including 15, 30, 75, 95, 115, 150, 177.
SPEAKER
The speaker shall be a System Sensor L-Series model _______ dual-voltage transformer speaker capable of operating at 25.0 or 70.7
nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of
400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power taps and voltage that
are selected by rotary switches.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The
module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 4 11⁄16 × 4 11⁄16 × 2 1⁄8-inch back box. The module
shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining
two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power
supply.
ELECTRICAL
Nominal Voltage (speakers): 25 Volts or 70.7 Volts (nominal)
Maximum Supervisory Voltage (speakers): 50 VDC
Strobe Flash Rate: 1 flash per second
Nominal Voltage (strobes): Regulated 12 VDC or regulated 24 VDC/FWR
Operating Voltage Range (includes fire alarm panels with built in sync): 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage with MDL3 Sync Module: 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
Frequency Range : 400 to 4,000 Hz
Power: ¼, ½, 1, 2 watts
ENVIRONMENTAL
Standard Operating Temperature: 32°F to 120°F (0°C to 49°C)
Humidity Range: 10 to 93% non-condensing
SPEAKER DIMENSIONS
For a complete listing of all
compliance approvals and
certifications, please visit
www.farenhyt.com.
CEILING MOUNT
SPCWL: Speaker only, White
SPCRL: Speaker only, Red
SPSCWL: Speaker Strobe, White
SPSCRL: Speaker Strobe, Red
SPSCWL-P: Plain, Speaker Strobe
SPSCWL-SP: Fuego, Speaker Strobe
SPSCWL-CLR-ALERT: Alert, Speaker Strobe, Clear Lens
ACCESSORIES
SBBCWL: Universal Ceiling SurfaceMount Back Box, White
SBBCRL: Universal Ceiling Surface Mount Back Box. Red
TRC-2W: Universal Ceiling Trim Ring. White
TRC-2: Universal Ceiling Trim Ring. Red
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 351576 | Rev B | 02/18
800-328-0103 © 2018 Honeywell International Inc.
L-series Indoor Wall Speakers
Strobes and Speakers
The L-Series indoor selectable-output speaker strobes and dual-voltage
speakers offer a modern, aesthetic plug-in design that deduce costly
ground faults. The universal mounting plate can be used in wall installation
applications and its flexible design enables the installer to easily perform
the following, pre-wire mounting plates, dress the wires, and confirm
wiring continuity before plugging in the speakers. In addition, this product
provides a protective plastic cover prevents nicked wires by covering
exposed speaker components.
The low total harmonic distortion of the speaker offers high fidelity sound
output while still offering high volume sound output for use in high ambient
noise applications.
F E AT U R E S & B E N E F I T S
• Plug-in design and • Field selectable • Rotary switch • Compatible with • Built with an updated
protective cover candela settings on simplifies field System Sensor modern design
reduce ground faults ceiling units: 15, 30, selection of speaker synchronization
75, 95, 115, 150, and voltage (25 and 70.7 protocol
• Contains a universal
177 Vrms) and power
mounting plate with • Electrical
settings (¼, ½, 1 and 2
an onboard shorting • Uses an automatic compatibility with
watts)
spring tests wiring selection of 12- or existing SpectrAlert
continuity before 24-volt operation at • Offers speakers with and SpectrAlert
installation 15 and 30 candela both high fidelity and Advance products
high volume sound
• No extension ring • Designed with
output
required tamper-resistant
construction
L-SERIES SPEAKER AND SPEAKER STROBE SPECIFICATIONS / ARCHITECT AND ENGINEER SPECIFICATIONS
GENERAL
L-Series speaker and speaker strobes shall mount to a 4 × 4 × 21⁄8-inch back box. A universal mounting plate shall be used for
mountingceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate
Also, L-Series speaker strobes, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt rated notification
appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate
between 16.5 and 33 volts. Indoor L-Series products shall operate between 32°F and 120°F from a regulated DC, or full-wave rectified,
unfiltered power supply. Wallmount speaker strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, 185.
SPEAKER
The speaker shall be a System Sensor L-Series model _______ dual-voltage transformer speaker capable of operating at 25.0 or 70.7
nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of
400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power taps and voltage that
are selected by rotary switches.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The
module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 4 11⁄16 × 4 11⁄16 × 2 1⁄8-inch back box. The module
shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining
two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power
supply.
PHYSICAL
Dimensions, Wall-Mount Length Width Depth
SP Speaker: 6.5 in, 165 mm 5 in, 127 mm 2.3 in, 58 mm
With Surface Mount Back Box: 6.6 in, 168 mm 5.1 in, 130 mm 3.2 in, 82 mm
SPS Speaker/Strobe (including lens and speaker): 6.5 in, 165 mm 5.0 in, 127 mm 2.3 in, 58 mm
With Surface Mount Back Box: 6.6 in, 168 mm 5.1 in, 130 mm 4.55 in, 116 mm
ELECTRICAL
Nominal Voltage (speakers): 25 Volts or 70.7 Volts (nominal)
Maximum Supervisory Voltage (speakers): 50 VDC
Strobe Flash Rate: 1 flash per second
Nominal Voltage (strobes): Regulated 12 VDC or regulated 24 DC/FWR
Operating Voltage Range (includes fire alarm panels with built in sync): 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage with MDL3 Sync Module: 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
Frequency Range: 400 to 4,000 Hz
Power: ¼, ½, 1, 2 watts
ENVIRONMENTAL
Standard Operating Temperature: 32°F to 120°F (0°C to 49°C)
Humidity Range: 10 to 93% non-condensing
DIMENSIONS
WALL-MOUNT SPEAKER
ACCESSORIES
RFPW: 7 in × 9.5 in Retrofit Plate. White
RFP: 7 in × 9.5 in Retrofit Plate. Red
SBBSPW: Surface Mount Back Box for Speakers and Speaker Strobes. White
SBBSPR: Surface Mount Back Box for Speakers and Speaker Strobes. Red
TRW: Wall Mount Trim Ring. White
TR: Wall Mount Trim Ring. Red
Notes: All -P models have a plain housing (no “FIRE” marking on the cover)
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 351577 | Rev B | 02/18
800-328-0103 © 2018 Honeywell International Inc.
L-Series Audible Visible
Accessories
The L-Series offers a wide range of Audible Visible (AV) accessories to
accommodate a variety of application requirements
The Color Lens Attachments install easily on any L-Series strobe devices to
provide distinctive visual signaling.
The Bezel Kits enable installers to easily turn any L-Series Fire or Plain
device into a device that meets ECN/MNS requirements. Bezel kits are
available for all varieties and footprints of L-Series products and come in
FIRE, ALERT, EVAC, AGENT, FUEGO, FOGO, and Plain options making
customization easy.
Universal Trim Rings for wall and ceiling mount devices allow for additional
space within the backbox.
The L-Series Surface Mount Back Boxes are the best solution in locations
where you have a hard surface to mount to.
F E AT U R E S & B E N E F I T S
MP120KL MOUNTING • Compatible with all • Outdoor rated from • Bezel kits available for • Operating
PLATE two-wire L-Series −35°F to 151°F strobes, horns, temperature -40°F to
• Designed for both devices chimes, horn strobes 151°FC
• Wall- or ceiling-mount
indoor and outdoor chime strobes and
lenses available
use COLOR LENS speaker strobes
ATTACHMENTS • Complies and listed
• Offers a plug-in • Bezels options with
• Easily turns any device with UL 1638
design to eliminates FIRE, ALERT, EVAC,
into a strobe for ECS/
ground faults BEZEL KITS AGENT, PLAIN,
MNS events: severe
FUEGO, FOGO
• Includes a power weather, toxic gases, • Easily turn a Fire or
printing
supply that converts sprinkler activation Plain device into a
120 VAC to nominal 24 and more device to meet ECS/ • For use with L-Series
V FWR MNS requirements devices only
SPECIFICATIONS
MP120K
120 VAC mounting plate model MP120KL shall be listed to UL 464 for fi re protective signaling systems. The mounting plate shall power a
twowire L-Series horn, strobe, horn strobe, chime or chime strobe from a 120 VAC supply converted to nominal 24 V FWR. For indoor
applications, the mounting plate shall be installed in a 4 x 4x 2 1/8 -inch junction box.
COMPATIBILITY
MP120KL may be used with any of the following products at all horn and strobe settings: P2RL, P2WL, P2RL-P, P2WL-P, P2RL-SP,
P2WL-SP, PC2RL, PC2WL, SRL, SWL, SRL-P, SWL-P, SRL-SP, SWL-CLR-ALERT, SWL-ALERT, SCRL, SCWL, SCWL-CLR-ALERT, HRL, HWL,
CHRL, CHWL, CHSRL, CHSWL, CHSCRL, CHSCWL.
PHYSICAL SPECIFICATIONS
Standard Operating Temperature: -40°F to 151°F (40°C to 66°C)
Humidity Range: 10 to 93% non-condensing
Nominal Voltage: Regulated 120 VAC
Operating Voltage Range: 96-132 VAC
Current Draw from AC Line: 150 mA max
L-SERIES BEZELS
The L-Series bezels are for installation with strobes, horns, chimes, horn strobes, chime strobes, and speaker strobes. Bezels are
offered in red and white for both wall and ceiling devices. Available in FIRE, ALERT, EVAC, AGENT, Plain (no marking), FUEGO, and
FOGO. Operating temperature shall be -40°F to 151°F.
COMPATIBILITY
Colored lens attachments may be used with the following System Sensor L-Series plain (non-FIRE-printed) strobe models: P2RL-P,
P2WL-P, SRL-P, SWL-P, SPSRL-P, SPSWL-P, SPSCWL-P, or any device used with a non-FIRE printed bezel.
ORDERING INFORMATION
BEZELS*
BZR: Wall Red Bezel Kit
BZW: Wall White Bezel Kit
BZGR: Compact Wall Red Bezel Kit
BZGW: Compact Wall White Bezel Kit
BZRC: Horn Strobe Ceiling Red Bezel Kit
BZWC: Horn Strobe Ceiling White Bezel Kit
BZSPR: Speaker Wall Red Bezel Kit
BZSPW: Speaker Wall White Bezel Kit
BZSPRC: Speaker Ceiling Red Bezel Kit
BZSPWC: Speaker Ceiling White Bezel Kit
*Each bezel pack ships in a package of 5. For desired bezel option add -F (FIRE), -AL (ALERT), -EV (EVAC), -AG (AGENT), -P (Plain),
-SP (FUEGO), -PG (FOGO) for desired printing.
ORDERING INFORMATION (CON'T) For a complete listing of all
compliance approvals and
COLORED LENS certifications, please visit
www.farenhyt.com.
LENS-B2: Wall-mount, blue
LENS-R2: Wall-mount, red Microsoft, Windows, and
the Windows Logo are
LENS-G2: Wall-mount, green
registered trademarks
LENS-A2: Wall-mount, amber or trademarks of
LENS-BC2: Ceiling-mount, blue Microsoft Corporation.
LENS-RC2: Ceiling-mount, red System Sensor® and
LENS-GC2: Ceiling-mount, green Honeywell® are
LENS-AC2: Ceiling-mount, amber registered trademarks
of and Farenhyt™ is a
trademark of Honeywell
RETROFIT PLATES (FOR USE WITH HORN STROBE & SPEAKER STROBE DEVICES)
International, Inc.
RFPW: 9.5" x 7" white
RFP: 9.5" x 7" red This document is not
intended to be used for
installation purposes. We
MOUNTING PLATE
try to keep our product
MP120KL: 120 VAC Adapter Mounting Plate information up-to
date and accurate. We
SYNC MODULES cannot cover all specific
MDL3W: White, 12/24 volt Sync-Circuit module. applications or anticipate
all requirements. All
MDL3R: Red, 12/24 volt Sync-Circuit module specifications are subject
to change without notice.
TRIM RINGS
For Technical Support,
TR-2: Universal wall trim ring, red
call 800-446-6444.
TRC-2: Universal ceiling trim ring, red
TR-2W: Universal wall trim ring, white
TRC-2W: Universal ceiling trim ring, white
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 351578| Rev B | 02/18
800-328-0103 © 2018 Honeywell International Inc.
SpectrAlert® Advance
Outdoor Selectable Output Speaker Strobes
and Dual Voltage Evacuation Speakers
The SpectrAlert® Advance series offers the broadest line of outdoor
speakers and speaker strobes in the industry. From metal and plastic
outdoor back boxes, to white and red plastic housings, to wall and ceiling
mounting options, virtually every application is covered. SpectrAlert
Advance outdoor speakers and speaker strobes offer reliable operation over
the entire temperature range of -40°F to 151°F. They may be used indoors
or outdoors in wet or dry applications. In addition, these speakers provide a
broad frequency response range and low harmonic distortion to provide an
accurate and intelligible broadcast of evacuation messages. High sound
pressure level at all tap settings ensures that messages are clearly heard.
SPECTRALERT ADVANCE
The plug-in design allows the installer to pre-wire mounting plates and
dress the wires before plugging in the speakers to help reduce ground
faults. This design also allows faster installations with instant feedback to
ensure that wiring is properly connected, rotary switches to select voltage
and power settings, and field selectable candela settings for wall and
ceiling speaker strobes.
The weatherproof back boxes have plastic and metal versions. They are
designed to accommodate in-and-out wiring for daisy chaining outdoor
devices. The plastic weatherproof back boxes are shipped with the product
feature removable side flanges and have improved resistance to salt water
corrosion. The screw hole knockouts, located on the back of the
weatherproof back box, eliminate the need to drill holes for screw-in
mounting. Both weatherproof back boxes are available with 3/4 inch top
and bottom conduit entries and 3/4 inch knock-outs at the back. Included
with each back box is a screw-in NPT plug with an O-ring gasket for a
watertight seal. Metal back boxes are available separately.
F E AT U R E S & B E N E F I T S
• Plug-in design • Rotary switch • Compatible with • Field selectable • Ceiling and wall mount
simplifies field System Sensor candela settings on application
• Electrical
selection of speaker synchronization wall and ceiling units
compatibility with
voltage and power protocol
existing SpectrAlert
settings
products • Automatic selection of
• Universal mounting 12- or 24-volt
• Shorting spring on
plate for wall- and operation at 15 and
mounting plate tests
ceiling-mount units 15/75 candela
continuity before
installation
ENGINEER SPECIFICATIONS
GENERAL
SpectrAlert Advance outdoor speaker and speaker strobes shall mount to a weatherproof back box. A universal mounting plate shall be
used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal
mounting plate. Outdoor SpectrAlert Advance products shall operate between –40°F and 151°F from a regulated DC, or full-wave
rectified, unfiltered power supply.
SPEAKER
The Speaker shall be a System Sensor SpectrAlert Advance Model ______ dual voltage transformer speaker capable of operating at 25.0 or
70.7 nominal Vrms. Speaker shall be Listed to UL® Standard S4048 for outdoor fire protective signaling systems. Speaker shall have a
frequency range of 400 to 4000 Hz and shall have an operating temperature from –40°F to 150.8°F. Speaker shall have power taps and
wattage settings which are selected by rotary switches. The speaker must be installed with its weatherproof backbox in order to remain
outdoor approved per UL listing S4048. The speaker shall be suitable for use in air handling spaces, as well as wet environments.
PHYSICAL
Wall-Mount Dimensions
SPS Speaker Strobe: 6.0”L x 5.0”W x 4.9”D (including lens and speaker)
SP Speaker: 6.0”L x 5.0”W x 2.9”D
Ceiling Mount Dimensions
SPS Speaker Strobe: 6.8”Dia x 4.8”D (including lens and speaker)
SP Speaker: 6.8”L x 2.9”D
Wall-Mount Weatherproof Backbox
Dimensions: 6.5”L x 5.5”H x 2.9”D
Ceiling-Mount Weatherproof Backbox
Dimensions: 7.2”Dia x 2.9”D
ELECTRICAL
Nominal Voltage (speakers): 25 Volts or 70.7 Volts (nominal)
Maximum Supervisory Voltage (speakers): 50VDC
Strobe Flash Rate: 1 flash per second
Nominal Voltage (Strobes): Regulated 12VDC/FWR or 24VDC/FWR
Operating Voltage Range (includes fire panels with built-in sync): 8 to 17.5V (12V nominal) or 16 to 33V (24 nominal)
Operating Voltage with MDL Sync Module: 9 to 17.5V (12V nominal) or 17 to 33V (24V nominal)
Frequency Range: 400 to 4000Hz
Power: ¼, ½, 1, 2 watts.
ENVIRONMENTAL
Standard Operating Temperature: –40°F to 151°F (–40°C to 66°C).
CANDELA DERATING
Note: For K series products used in low tempertures,
listed candela ratings must be reduced in accordance with
this table.
30
75 44
95 70
110 110
115 115
135 135
150 150
177 177
185 185
ORDERING INFORMATION For a complete listing of all
SPWK: Wall mount outdoor speaker; white compliance approvals and
certifications, please visit
SPRK: Wall mount outdoor speaker; red www.farenhyt.com.
SPSWK: Wall mount outdoor speaker strobe,
selectable candela (15, 15/75, 30, 75, 95, 100, Microsoft, Windows, and
the Windows Logo are
115); white
registered trademarks
SPSRK: Wall mount outdoor speaker strobe, or trademarks of
selectable candela (15, 15/75, 30, 75, 95, 100, Microsoft Corporation.
115); red
System Sensor®,
SPCWK: Ceiling mount outdoor speaker; white.
SpectrAlert®, and
SPSCWK: Ceiling mount outdoor speaker strobe, Honeywell® are
selectable candela (15, 15/75, 30, 50, 75, 95, 110, registered trademarks
115); white of and Farenhyt™ is a
SPSCWHK: Ceiling mount outdoor speaker strobe, trademark of Honeywell
International, Inc.
selectable candela, high cd (135, 150, 177, 185);
white This document is not
intended to be used for
ACCESSORIES installation purposes. We
MWBB: Wall, metal weatherproof backbox; red try to keep our product
information up-to
MWBBW: Wall, metal weatherproof backbox; white date and accurate. We
MWBBCW: Ceiling, metal weatherproof backbox; cannot cover all specific
white applications or anticipate
all requirements. All
PWBB: Wall, plastic weatherproof backbox; red specifications are subject
PWBBW: Wall, plastic weatherproof backbox; white to change without notice.
PWBBCW: Ceiling, plastic weatherproof backbox,
For Technical Support,
white
call 800-446-6444.
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472 Doc 351636 | Rev A | 03/18
800-328-0103 © 2018 Honeywell International Inc.
RPS-1000 / RPS-1000B
6 Amp Intelligent Distributed Power Module
RPS-1000 is an intelligent distributed power module that adds 6.0 amps of
power, six Flexput™ I/O circuits, and two Form C relay circuits to a
compatible Honeywell Farenhyt Series addressable system. The RPS-1000
is available in a red (RPS-1000) or black (RPS-1000B) cabinet. The
RPS- 1000 connects to the FACP via the RS-485 system bus allowing up
to an additional 6,000 feet of wiring. Each RPS- 1000 is optically isolated
providing ground loop isolation and transient protection. RPS-1000
supports its own backup battery and monitors the AC power.
Compatibility
The RPS-1000 and RPS-1000B are compatible with the following Farenhyt
Series FACP's: RPS-1000B
F E AT U R E S & B E N E F I T S
• 6.0 amps output • Ground loop isolation • Up to 6,000 foot • Room to mount two • Conventional initiation
power and transient wiring distance from 6815 or 5815XL SLC circuits (Class B/Style
protection the RPS-1000 expander modules B & Class A/Style D)
• Supports Class A
both 2- and 4-wire
(Style 6) and Class B • Provides SBUS optical • Battery charging • Six onboard Flexput
(Style 4) configuration isolation and capacity is 35AH circuits programmable • Auxiliary power (for
of the SBUS re-conditions the for: door holders,
• Large cabinet size can
RS- 485 signal continuous power, or
• Two Form C house two 18AH • Notification appliance
resettable power)
programmable relays • Built-in backup batteries or circuits (Class B/Style
rated at 2.5A @ 24 synchronization for RBB accessory Y & Class A/Style Z)
VDC appliances from cabinet can house
System Sensor ®, battery sizes larger
AMSECO, Gentex ®, and that 18AH
Wheelock ®
RPS-1000 / RPS-1000B Technical Specifications
For a complete listing of all
PHYSICAL ORDERING INFORMATION compliance approvals and
Mounting Dimensions: 14.5”W x 24.75”H x 3.9”D RPS-1000: Intelligent Distributed Power Module, certifications, please visit
(36.8 cm W x 62.9 cm H x 9.8 cm D) Red www.farenhyt.com.
Overall Dimensions: 16.1”W x 26.4”H x 4.1”D (40.6 RPS-1000B: Intelligent Distributed Power Module, Microsoft, Windows, and
cm W x 67 cm H x 11.8 cm D) Black the Windows Logo are
Color: Red or Black RPS-1000HV: High voltage (240V) Intelligent registered trademarks
or trademarks of
Distributed Power Module
Microsoft Corporation.
ENVIRONMENTAL ACCESSORIES
Operating Temperature: 32ºF-120ºF (0ºC -49ºC) RBB: Remote Battery Box Accessory Cabinet. 16” W
Honeywell® is a
Humidity: 10%-93% non-condensing registered trademarks
x 10” H x 6” D (406 mm W x 254 mm H x 152 mm D) of and Farenhyt™ is a
AB-55: Remote Battery Box Accessory Cabinet. trademark of Honeywell
ELECTRICAL 20”W x 12” H x 7.5” D International, Inc.
Primary AC: 120 V, 50 or 60Hz, 2.5A, or 240V, 50 or 6815: SLC Expander Module for IDP or SK devices
60Hz, 1.4A This document is not
5815XL: SLC Expander Module for SD devices intended to be used for
Total Accessory Load: 6A @ 24VDC installation purposes. We
SK-SCK: Seismic Compliance Kit
Current try to keep our product
Standby: 40mA AGENCY LISTING AND APPROVALS information up-to
date and accurate. We
Alarm: 160mA NFPA 13, NFPA 70, NFPA 72, UL 2572, UL 1711 & cannot cover all specific
SBUS Standby & Alarm: 10mA UL 864: Local Protective Signalling Systems; applications or anticipate
Flexput Circuits: UL Listed all requirements. All
specifications are subject
Notification: 3amps per circuit (6A system total) CSFM
to change without notice.
Initiation: 100mA power limited @ 24VDC City of New York: 429-92-E Vol IX
For Technical
Support, Please call
800-446-6444.