Professional Documents
Culture Documents
REU615 is a voltage protection and control relay for Standardized communication and redundancy
voltage and frequency-based protection in utility and REU615 fully supports the IEC 61850 standard for
industrial power distribution systems, including networks communication and interoperability of substation automation
with distributed power generation. REU615 is also ideal devices, including fast GOOSE messaging and IEC 61850-
for voltage regulation. 9-2 LE, and can now also benefit from the extended
interoperability provided by Edition 2. The voltage relay
Application further supports both the parallel redundancy protocol
REU615 is available in two standard configurations, both (PRP) and the high-availability seamless redundancy (HSR)
of which can be tailored to meet application-specific protocol, together with the DNP3, IEC 60870-5-103 and
requirements using the IEC 61850-compliant Protection and Modbus® protocols. With the protocol adapter SPA-ZC 302,
Control IED Manager PCM600. One has been exclusively Profibus DVP1 can also be used. REU615 is able to use two
designed for busbar under- and overvoltage supervision, communication protocols simultaneously.
load-shedding (disconnection) and restoration (reconnection)
applications. It can also be used for over- and underfrequency For redundant Ethernet communication, REU615 offers either
protection of power generators and other AC equipment such two optical or two galvanic Ethernet network interfaces. A
as capacitor banks. In generator and motor applications, third port with a galvanic Ethernet network interface provides
REU615 provides supplementary protection by detecting any connectivity of any other Ethernet device to an IEC 61850
deviation from the permitted frequency and voltage values. An station bus inside a switchgear bay. The redundant Ethernet
integrated synchro-check function ensures a safe connection solution can be built on the Ethernet-based IEC 61850,
of the equipment to the network. Modbus ® and DNP3 protocols.
The other of the two standard configurations has been The implementation of the IEC 61850 standard in REU615
exclusively designed for automatic and manual voltage covers both vertical and horizontal communication, including
regulation of power transformers with a motor-driven on- GOOSE messaging with both binary and analog signals as
load tap-changer. In small substations with a single power well as parameter setting according to IEC 61850-8-1. Also
transformer and in substations with two or more power IEC 61850-9-2 LE process bus with sending sampled values
transformers operating in parallel, REU615 can be used for of not only analog voltages but now also currents, in addition
load-side voltage regulation. The standard configuration also to receiving sampled values of voltages, is supported. The
includes protection functionality. sampled values can now be used for synchro-check as
well to ensure safe interconnection of two networks. For
To minimize the effects of an arc fault, REU615 can be process bus applications, which require high-accuracy time
equipped with high-speed outputs decreasing the operate synchronization, IEEE 1588 V2 is used, with a time stamp
time by four to six milliseconds compared to conventional resolution of not more than four microseconds. IEEE 1588
binary outputs. V2 is supported in all variants with a redundant Ethernet
communication module. In addition, REU615 supports
Human-machine interface synchronization over Ethernet using SNTP or over a separate
As a member of the Relion® product family, REU615 shares bus using IRIG-B.
the same human-machine interface (HMI) look and feel as the
other Relion protection and control relays and IEDs. The same
look and feel includes the location of a push button with a
certain function and the menu structure.
UL1UL2UL3
Lockout relay
HMI
Time
Authorization
- Web HMI
3× 3× I ESC Clear
ARC AND
50L/50NL O R
L
OR
5×
UFLS/R
CONTROL AND INDICATION 1) MEASUREMENT
81LSH
- U, Uo, f
Object Ctrl 2)
Ind 3)
- Symmetrical components
18×
MAP CB 1 - - Limit value supervision
MAP DC 2 3
Analog interface types 1)
ES 1 2
Current transformer -
1)
Check availability of binary inputs/outputs
from technical documentation Voltage transformer 5
2)
Control and indication function for 1)
Conventional transformer inputs
primary object
3)
Status indication function for
primary object
UL1UL2UL3 SYNC
25
U12
REMARKS
Optional 3× No. of Calculated OR Alternative
function instances value function to be
Io/Uo defined when
ordering
Lockout relay
HMI
Time
Authorization
- Self-supervision
94/86 I ESC Clear
- Time synchronization: IEEE 1588 v2,
SNTP, IRIG-B
A
O R
L
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr - User management
- Web HMI
IL2 0 A
MAP AND
MAP O R
L
OR
6xRTD
2xmA
I∑
TPOSM COLTC
84M 90V
3I
REMARKS
Optional 3× No. of Calculated OR Alternative
function instances Io/Uo value function to be
defined when
Sum of phase ordering
I∑
currents
Standard configurations
Standard
Description
configuration
Voltage and frequency based protection, synchro-check and load-shedding A
Automatic voltage regulator B
1)
Light only
2)
Available only with IEC 61850-9-2
3)
Available only with COM0031-0034
www.abb.com/mediumvoltage
www.abb.com/substationautomation