Professional Documents
Culture Documents
Active Earthing System For MV Networks by Means of Power Electronics
Active Earthing System For MV Networks by Means of Power Electronics
Paper 0158
As a simplified summary of the state of the art, it can be Figure 1: Any phase to ground voltage can be created by
assumed that traditional earthing systems are divided into adding the appropriate zero-sequence voltage
the following categories:
• Solid earthing, i.e. null earthing impedance and earth- The aim in developing the active earthing system is to
fault current limited, basically, by the transformer (and incorporate new features, related to system maintenance and
feeder) impedance. It gives rise to high fault currents
and low overvoltages operation.
• Low impedance earthing. Earth-fault current limited by For maintenance purposes, it will improve weak insulation
the impedance value and the transformer impedance. detection, while the operation will take advantage of a
Lower fault currents and higher overvoltages. better detection of high impedance faults. A particular
• Isolated networks. Variable earth-fault current, improvement in this area will be the identification of
depending on feeders’ capacitance. Low fault currents dangerous situations such as a direct contact of live
and high overvoltages conductors to earth.
• Compensated (or resonant) networks. Earth-fault current The enhanced earth-fault location will be useful for both
is kept below some tens of amperes, with high purposes.
overvoltages and longer fault durations. As a consequence, some faults will be prevented from
appearing in the distribution network and those that happen
The new active earthing system has the traditional
advantages of a resonant network, such as arc suppression will be promptly detected and located, thus improving
or low step and touch voltages. However, additional continuity of supply and power quality.
features are achieved by the injection of a controlled
current. To achieve that, the active earthing system comprises an
innovative protection system for the enhancement of earth-
Paper 0158
fault detection, faulted phase and feeder identification and As stated, the main feature allows controlling neutral
location. Consequently, the operation of the active earthing voltage and current, obtaining desired phase-to-earth
system will limit the effects of interruptions, in terms of voltages, which can even be cancelled.
reduction of both the number of users affected and duration. As a result, the system provides the network with an active
This active system will behave as a low earth-fault current operation by injecting earth current (zero-sequence current)
earthing network, but with additional features which controlled in value, angle and frequency.
dramatically improve the weak features of isolated or Changing the value of neutral voltage does not affect users,
compensated networks. since the zero-sequence voltage is not transmitted to low
Regarding material stress due to overvoltages, the system
isolation can be periodically checked so the duration of the voltage networks.
overvoltage will be limited, leading to a reduced impact on
material. Another key feature is the ability to choose the instant in
which each function is carried out. For instance, fault
ACTIVE EARTHING SYSTEM DESCRIPTION extinction can be carried out after fault location, in order to
seek points of a feeder with repetitive failures.
This new active earthing system for the MV distribution Timing Control permits to obtain the advantages of each
network, as shown in Figure 2, bases its operation on power earthing system, which allows performing the functions of
electronics and combines them with a protection and control the active system: fault detection, location and extinction or
system, which obtains the necessary measurements to detect insulation testing.
and locate the fault.
It is the use of the power electronics what provides the In order to obtain more accurate magnitude calculations,
active system with the capacity to control the neutral current non-characteristic frequencies are injected for impedance
and voltage throughout time. measurements.
The control of the neutral voltage and current is a key • The value of the injected current is chosen depending on
feature in the system. Both magnitudes are related by the range that the active system has for the most
means of the zero-sequence impedance. This impedance accurate measurements.
value needs to be calculated and updated in order to • Network configuration determines the way that current
maintain a proper system operation. Different criteria are flows. Being controlled current injection, it is known
used to periodically perform the measurement, by injecting how the current flows in normal operation situation. So,
injecting another controlled current when a fault
a low current value of a chosen frequency, not characteristic appears, it is possible to make accurate measurement
in the network. This injection allows calculating accurately comparisons.
the value of the zero-sequence impedance. If they exist, the • The injected current frequency is determined by the
value of the earthing impedance and the inherent unbalance magnitude to be measured, so when capacitances are
of the network are borne in mind. measured, the selected frequency can be lower than the
one of the network and, when inductances need to be
measured accurately, higher one could be used
MV Busbar
R-S-T
By-pass
MV System Earth
Paper 0158
Paper 0158
ACKNOWLEDGMENT
The Department of Industry, Commerce and Tourism of the
Basque Government and the Spanish Ministry of Industry,
Tourism and Commerce are supporting this project.
BIBLIOGRAPHY
[1] W. Petersen, "Protection of Alternating-Elctric-
Current Systems", US Patent, 1925
Figure 5: timing of earth-fault extinction [2] Lehtonen, Hakolo, “Neutral Earthing and Power System
(Fault detection, feeder identification and fault location before
extinction has been removed for the sake of graph clarity)
Protection”, Vaasa, Finland, ISBN 952-90-7913-3, 1996.
[3] G. Druml, A. Kugi, O.Seifert, "New Method to Control
Petersen Coils by Injection of Two Frequencies",
CONCLUSIONS Proceedings of the 18th International Conference CIRED
The novel earthing system presented allows network 2005
operation and maintenance (O&M) and continuity of supply [4] G. Druml, A. Kugi, B. Parr, “Control of Petersen Coils”,
of the MV distribution network in which it is installed by XI. International Symposium on Theoretical Electrical
overcoming the limitations of the traditional earthing Engineering, 2001.
systems used currently in distribution network MV [5] J. Grainger, W. Stevenson, Jr., “Power System
substations due to the capability of controlling the neutral Analysis”, Singapore, 1994.
current and voltage of the network. It is based on the [6] J. Roberts, H. J. Altuve, D. Hou, “Review of Ground
combination of a multi-frequency power converter and a Fault Protection Methods for Grounded, Ungrounded and
protection and control system. Compensated Distribution Systems, USA, 2001.
Mentioned improvements, not together achievable by means [7] G. Druml, O.Seifert, "New Method for the State
of conventional earthing systems, are summarised as Evaluation of the Zero-Sequence System", 15th Power
follows: Systems Computation Conference, Liege, 2005
• Transient earth-fault extinction: neutral current and [8] K. Winter, "The RCC Ground Fault Neutralizer – a
voltage control, by the injection of a network frequency Novel Scheme for Fast Earth Fault Protection”, Proceedings
current in the neutral, permits reducing fault current to of the 18th International Conference CIRED 2005.
the minimum as in resonant earthing