You are on page 1of 4

CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0158

ACTIVE EARTHING SYSTEM FOR MV NETWORKS BY MEANS OF POWER


ELECTRONICS
F. J. PAZOS A. AMEZUA I. GUTIÉRREZ G. SANTAMARÍA J. M. GARCÍA V. VALVERDE
Iberdrola - Spain Oldar Electrónica. - Spain Jema – Spain Ingeteam T&D-Spain EHU/UPV-Spain
fj.pazos@iberdrola.es ama@ormazabal.com igu@ormazabal.com g.santamaria@grupojema.com juanmari.garcia@ingeteam.com victor.valverde@ehu.es

ABSTRACT THE “ACTIVE EARTHING” CONCEPT


This paper describes a new technology, the active earthing “Active Earthing” means that any zero-sequence voltage
system, based on a multi-frequency power converter, which can be created injecting the appropriate current. When
combines a new power electronic device with a protection desired and with the desired angle or frequency.
and control system. • In normal operation conditions, with no fault in the
This system allows network enhanced operation and network, neutral voltage can be modified, thus reducing
or increasing one phase-to-earth voltage to any value, as
maintenance, overcoming some of the limitations of the shown in figure 1.
traditional earthing systems, giving rise to relevant • During an earth-fault phase-to-earth voltages can be
improvement in supply continuity. modified as well, being able to eliminate the voltage in
the affected phase.
• Different frequencies can be injected in order to
INTRODUCTION improve the protection system behaviour.
The type of neutral treatment has an important influence in 3
the behaviour of Medium Voltage (MV) networks. It
particularly affects voltage dips, swells and interruptions
and also fault location, since earthing system determines 1
several aspects of earth-faults such as fault current, duration 3
and, to a certain extent, their probability of occurrence.
2
So far, traditionally the MV neutral has been earthed by 1
means of passive elements, such as feeders' capacitances
3
and/or discrete elements namely reactors and resistors or,
simply, solidly earthed. In any case, when a fault happens, 2
conventional earthing systems are not able to modify the 1
current that flows through the fault or network neutral. It
does not provide any other function while there is no fault
in the network. 2

As a simplified summary of the state of the art, it can be Figure 1: Any phase to ground voltage can be created by
assumed that traditional earthing systems are divided into adding the appropriate zero-sequence voltage
the following categories:
• Solid earthing, i.e. null earthing impedance and earth- The aim in developing the active earthing system is to
fault current limited, basically, by the transformer (and incorporate new features, related to system maintenance and
feeder) impedance. It gives rise to high fault currents
and low overvoltages operation.
• Low impedance earthing. Earth-fault current limited by For maintenance purposes, it will improve weak insulation
the impedance value and the transformer impedance. detection, while the operation will take advantage of a
Lower fault currents and higher overvoltages. better detection of high impedance faults. A particular
• Isolated networks. Variable earth-fault current, improvement in this area will be the identification of
depending on feeders’ capacitance. Low fault currents dangerous situations such as a direct contact of live
and high overvoltages conductors to earth.
• Compensated (or resonant) networks. Earth-fault current The enhanced earth-fault location will be useful for both
is kept below some tens of amperes, with high purposes.
overvoltages and longer fault durations. As a consequence, some faults will be prevented from
appearing in the distribution network and those that happen
The new active earthing system has the traditional
advantages of a resonant network, such as arc suppression will be promptly detected and located, thus improving
or low step and touch voltages. However, additional continuity of supply and power quality.
features are achieved by the injection of a controlled
current. To achieve that, the active earthing system comprises an
innovative protection system for the enhancement of earth-

CIRED2009 Session 1 Paper No 0158


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0158

fault detection, faulted phase and feeder identification and As stated, the main feature allows controlling neutral
location. Consequently, the operation of the active earthing voltage and current, obtaining desired phase-to-earth
system will limit the effects of interruptions, in terms of voltages, which can even be cancelled.
reduction of both the number of users affected and duration. As a result, the system provides the network with an active
This active system will behave as a low earth-fault current operation by injecting earth current (zero-sequence current)
earthing network, but with additional features which controlled in value, angle and frequency.
dramatically improve the weak features of isolated or Changing the value of neutral voltage does not affect users,
compensated networks. since the zero-sequence voltage is not transmitted to low
Regarding material stress due to overvoltages, the system
isolation can be periodically checked so the duration of the voltage networks.
overvoltage will be limited, leading to a reduced impact on
material. Another key feature is the ability to choose the instant in
which each function is carried out. For instance, fault
ACTIVE EARTHING SYSTEM DESCRIPTION extinction can be carried out after fault location, in order to
seek points of a feeder with repetitive failures.
This new active earthing system for the MV distribution Timing Control permits to obtain the advantages of each
network, as shown in Figure 2, bases its operation on power earthing system, which allows performing the functions of
electronics and combines them with a protection and control the active system: fault detection, location and extinction or
system, which obtains the necessary measurements to detect insulation testing.
and locate the fault.
It is the use of the power electronics what provides the In order to obtain more accurate magnitude calculations,
active system with the capacity to control the neutral current non-characteristic frequencies are injected for impedance
and voltage throughout time. measurements.
The control of the neutral voltage and current is a key • The value of the injected current is chosen depending on
feature in the system. Both magnitudes are related by the range that the active system has for the most
means of the zero-sequence impedance. This impedance accurate measurements.
value needs to be calculated and updated in order to • Network configuration determines the way that current
maintain a proper system operation. Different criteria are flows. Being controlled current injection, it is known
used to periodically perform the measurement, by injecting how the current flows in normal operation situation. So,
injecting another controlled current when a fault
a low current value of a chosen frequency, not characteristic appears, it is possible to make accurate measurement
in the network. This injection allows calculating accurately comparisons.
the value of the zero-sequence impedance. If they exist, the • The injected current frequency is determined by the
value of the earthing impedance and the inherent unbalance magnitude to be measured, so when capacitances are
of the network are borne in mind. measured, the selected frequency can be lower than the
one of the network and, when inductances need to be
measured accurately, higher one could be used
MV Busbar

HV/MV Transformer MV Feeders

R-S-T

N ACTIVE EARTHING SYSTEM

Protection and Control System


(Converter control and relaying)

By-pass

MV System Earth

Figure 2. Active earthing system real-scale prototype and scheme

CIRED2009 Session 1 Paper No 0158


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0158

oriented maintenance guaranteeing the correct operation of


SYSTEM GENERAL OPERATION the distribution network.
The multi-frequency power converter works differently
depending on the needs.
• For fault extinction, it injects zero-sequence power
frequency current (i.e. 50 or 60 Hz) to cancel the voltage
of the faulted phase.
• For impedance calculations (capacitance calculation,
feeder identification or fault location), the converter
injects non-fundamental frequencies during some
milliseconds. These non-fundamental frequencies,
different from any other signals that can be found in
actual networks, allow measurements without external
influences, which leads to more precise fault location
and better high impedance fault detection.
• For insulation checking, the converter injects both
fundamental and non-fundamental frequency currents. Figure 3: customer supplies (phase-to-phase voltages) do
Fundamental current is necessary to shift the neutral, not suffer any change while an overvoltage is provoked in
while non fundamental currents are used for impedance the selected phase for condition-oriented maintenance.
calculations
Fault detection and location
Several functions are gathered together in one system The network is earthed through a converter, thus allowing
allowing functionality exceeding that achievable with detection of earth-faults by means of a zero sequence
conventional earthing systems. With all these new features: voltage.
• Insulation can be checked, even with the substation in When detecting the fault, the neutral voltage and current
normal operation.
The Active Earthing System is able to simultaneously control permit to maintain the fault for a short but enough
increase a phase-to-earth voltage and inject the time to locate it. For faulted feeder identification and fault
necessary signals for the protection system. location current is injected in the neutral, which a different
Thus, the protection system is able to detect and locate frequency, f0, from the network, i.e. 50 or 60 Hz, as shown
weak insulation points in overhead lines or in figure 4. As can be seen, the behaviour of the faulty
insufficiently rated surge arresters, allowing the feeder and sound feeders are completely different.
condition based maintenance of MV feeders. Therefore, the device identifies the faulted phase by
• During a feeder fault, the enhanced fault location can be comparing the f0 frequency zero-sequence voltage angle to
applied for both for transient and permanent earth-faults. that of the reference voltage.
A comparison between the proportion of the resistance and
The transient ones can be firstly located, for
maintenance purposes, and then extinguished without inductance will be also made for each feeder to find out the
opening the circuit breaker. faulted one and the distance from the bus-bar to the fault.
In case of permanent faults, it can be identified if the
fault is due to a contact (fallen line or a tree touching the
conductor) or if it is a leakage current due to a broken
insulator.
In case of a contact-fault, the point of fault will be also
located and, after that, tripped by the protection system
if necessary.
However, in case of a weak insulation points or partially
damaged underground cables, the new system will give
the chance to reduce faulted phase-to-earth voltage, to
keep the line working while the problem is fixed.

Network insulation testing and condition-oriented


maintenance
Controlled voltage changes are used to check the network Figure 7: Faulted feeder detection by comparison of the
insulation or minimise an insulation leakage problem until it calculated reactance (X) for each feeder, before and
is fixed. The protection features include a detection and during the fault
location of insulation failures. This occasional revision and
the fact that weak insulation points, cable solid insulation
and surge arresters are found, will allow a condition

CIRED2009 Session 1 Paper No 0158


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0158

• Fault detection: earthing through the converter leads


Fault current control and transient earth-fault detecting the fault as easily as in a medium or solid
extinction earthing system
Finally, the converter injects a neutral current of network • Faulted feeder identification and fault location: the
frequency, in a way that the phase-to-earth voltage of the injection of multi-frequency currents in the neutral of
the network allows high impedance fault location and
faulted phase is reduced to zero.
identification of contact-faults.
This will allow the fault extinction in case of being non- • Network condition oriented maintenance: when
permanent faults, which are extinguished when the fault required by the user, an undervoltage or an overvoltage
current is maintained below some tens of amperes. is provoked in the selected phase voltage, while
In case of permanent earth-faults, the voltage of the faulted detection and location are accomplished as stated before
phase can be reduced to suppress the arc but limiting the • In case of a weak insulation points or partially damaged
overvoltages suffered by the sound phases, while the fault is underground cables, the new system will give the
being isolated and fixed. chance to reduce faulted phase-to-earth voltage, to keep
The failure of the voltage reduction to suppress the arc the line working while the problem is fixed.
entails the presence of a contact-fault (basically an All the functionalities of this patented system lead to an
extremely short arc). In this case, the line can be improved network performance for earth-faults, providing a
immediately tripped. real possibility to carry out condition oriented maintenance.
The timing of this process can be observed in figure 5. After The use of power electronics technology in MV distribution
a phase-to-earth-fault is detected, the active earthing system networks is pointed out as a valuable resource for the
starts the neutral current injection to control the neutral utilities to improve network maintenance and continuity of
voltage, cancelling phase-to-earth voltage on the faulted supply.
phase, leading to the extinction of the transient fault.
After the corresponding integration tests and preceding the
  final operation of the system, several real tests are going to
be held in the MV substation of Guernica. The latest results
of the application of this innovative system will be
presented at CIRED 2009 session.

ACKNOWLEDGMENT
The Department of Industry, Commerce and Tourism of the
Basque Government and the Spanish Ministry of Industry,
Tourism and Commerce are supporting this project.

BIBLIOGRAPHY
[1] W. Petersen, "Protection of Alternating-Elctric-
Current Systems", US Patent, 1925
Figure 5: timing of earth-fault extinction [2] Lehtonen, Hakolo, “Neutral Earthing and Power System
(Fault detection, feeder identification and fault location before
extinction has been removed for the sake of graph clarity)
Protection”, Vaasa, Finland, ISBN 952-90-7913-3, 1996.
[3] G. Druml, A. Kugi, O.Seifert, "New Method to Control
Petersen Coils by Injection of Two Frequencies",
CONCLUSIONS Proceedings of the 18th International Conference CIRED
The novel earthing system presented allows network 2005
operation and maintenance (O&M) and continuity of supply [4] G. Druml, A. Kugi, B. Parr, “Control of Petersen Coils”,
of the MV distribution network in which it is installed by XI. International Symposium on Theoretical Electrical
overcoming the limitations of the traditional earthing Engineering, 2001.
systems used currently in distribution network MV [5] J. Grainger, W. Stevenson, Jr., “Power System
substations due to the capability of controlling the neutral Analysis”, Singapore, 1994.
current and voltage of the network. It is based on the [6] J. Roberts, H. J. Altuve, D. Hou, “Review of Ground
combination of a multi-frequency power converter and a Fault Protection Methods for Grounded, Ungrounded and
protection and control system. Compensated Distribution Systems, USA, 2001.
Mentioned improvements, not together achievable by means [7] G. Druml, O.Seifert, "New Method for the State
of conventional earthing systems, are summarised as Evaluation of the Zero-Sequence System", 15th Power
follows: Systems Computation Conference, Liege, 2005
• Transient earth-fault extinction: neutral current and [8] K. Winter, "The RCC Ground Fault Neutralizer – a
voltage control, by the injection of a network frequency Novel Scheme for Fast Earth Fault Protection”, Proceedings
current in the neutral, permits reducing fault current to of the 18th International Conference CIRED 2005.
the minimum as in resonant earthing

CIRED2009 Session 1 Paper No 0158

You might also like