You are on page 1of 106

4/6/2020

Training in Life Safety Code


NFPA-101

4/6/2020 LS Training 1

References
❑ NFPA 101: Life Safety Code®

❑ NFPA 5000: Building Construction and Safety Code®

❑ Designer’s Illustrated Guide to NFPA 101

❑ NFPA 101 Life Safety Code Essentials Seminar Handouts

❑ Performing Plan Reviews For Life safety code Cmpliance

4/6/2020 LS Training 2

1
4/6/2020

Overview
❑ NFPA 101, Classification of Occupancy and Hazard of Contents

❑ NFPA 101, Means Of Egress

❑ NFPA 101, Features of Fire Protection

❑ NFPA 101 & NFPA 72, Fire Detection System

❑ NFPA 101 & NFPA 13, Fire protection system

❑ NFPA 101, Interior Finishing

4/6/2020 LS Training 3

Code Access
www.nfpa.org/101

4/6/2020 LS Training 4

2
4/6/2020

Code Access

4/6/2020 LS Training 5

Code Access

4/6/2020 LS Training 6

3
4/6/2020

Ask questions
if you do not understand!
There is no shame in admitting you do
not understand something.

4/6/2020 LS Training 7

Scope
❑ Danger to Life from Fire
Addresses those construction, protection, and occupancy features necessary to minimize danger to life from
the effects of fire, including smoke, heat, and toxic gases created during a fire.
❑ Egress Facilities
Establishes minimum criteria for the design of egress facilities so as to allow prompt escape of occupants
from buildings or, where desirable, into safe areas within buildings.
❑ Hazardous Materials Emergencies.
Provide for occupant protection during emergency events involving hazardous materials
❑ Injuries from Falls
Reducing injury to occupants from falls
❑ Emergency Communications
Provide for communications to occupants under emergency conditions and to others.
❑ Considerations Not Related to Fire
In Fire Condition, provide an ongoing benefit in other conditions of use, including non-fire emergencies
❑ Other Fire-Related Considerations

.
4/6/2020 LS Training 8

4
4/6/2020

Purpose of Life Safety Code


The purpose of this Code is to provide minimum requirements, with due regard to
function, for the design, operation, and maintenance of buildings and structures for
safety to life from fire. Its provisions will also aid life safety in similar emergencies.

Protection of occupants is achieved by the combination of prevention, protection, egress,


and other features, with due regard to the capabilities and reliability of the features
involved. The level of life safety from fire is defined through requirements directed at the
following:
• Prevention of ignition
❑ To guide the design construction and features of the
• Detection of fire
structure
• Control of firetodevelopment
protect the occupant from the effect of fire.
• Confinement of the effects of fire
• ❑Extinguishment
Provide safe of fire
evacuation from abuilding during fire
• Provision of refuge or evacuation facilities, or both
• Staff reaction
• Provision of fire safety information to occupants

4/6/2020 LS Training 9

Application

❑ Apply to both new construction and existing


buildings and existing structures.

❑ Apply to vehicles, vessels, or other similar


conveyances, as specified in Section 11.6, in
which case such vehicles and vessels shall be
treated as buildings.

4/6/2020 LS Training 10

10

5
4/6/2020

Chapters

Chapter 1: Administration
Chapter 2: Referenced Publication
Chapter 3: Definitions
Chapter 4: General
Chapter 5: Performance Based Option
Chapter 6: Classification Of Occupancy And Hazard Contents
Chapter 7: Means Of Egress
Chapter 8: Feature Of Fire Protection
Chapter 9:building Service And Fire Protection Equipment
Chapter 10: Interior Finish, Contents, And Furnishing
Chapter 11-42: New And Existing Occupancies
Chapter 43: Building Rehabilitation

4/6/2020 LS Training 11

11

Occupancy Classification
Chapter 6 provides in depth details about the occupancy classification.

▪ Assembly Occupancy ▪ Detention and Correctional Occupancy


▪ Educational Occupancy ▪ Residential Occupancy
▪ Day-Care Occupancy ▪ Mercantile Occupancy
▪ Health Care Occupancy ▪ Business Occupancy
▪ Ambulatory Occupancy ▪ Industrial Occupancy
▪ Storage Occupancy

4/6/2020 LS Training 12

12

6
4/6/2020

NFPA 101 Phrasing


Mandatory Requirement Shall be or Shall have

Optional Requirement Where permitted by

Limited Provision Unless Permitted by

How to Do it Where required by

4/6/2020 LS Training 13

13

NFPA 101 Structure and Format

NEW Occupancy Chapter

Existing Occupancy Chapter

4/6/2020 LS Training 14

14

7
4/6/2020

NFPA 101 Structure and Format


Annex A Advisory, Not part of the code

General, Guidance, evacuation


Annex B
rescue type, not mandatory

Support requirement for Hazardous


Annex C
material NEW in 2018 edition

Annex D Referenced publication and


information references

4/6/2020 LS Training 15

15

How To Determine The Requirement


1 Occupancy Classification 5 Refer To The Applicable Chapter

2 New or Existing 6 Occupancy Sub Classification

Verify Compliance With Each


3 Occupant Load 7
Section

Where 2 Occupancy Apply, Use The


4 Hazardous of Contents 8 Precedence Chapter And Check
Special Structure If Applicable

4/6/2020 LS Training 16

16

8
4/6/2020

Steps

4/6/2020 LS Training 17

17

LS Training 18

18

9
‫‪4/6/2020‬‬

‫‪Flashover‬‬
‫‪19‬‬

‫‪19‬‬

‫مقارنة بين غرفة معيشة محمية بمرشات مياة مع أخرى غير محمية‬

‫‪4/6/2020‬‬ ‫‪LS Training‬‬ ‫‪20‬‬

‫‪20‬‬

‫‪10‬‬
4/6/2020

Equivalency Statement

1.4 * Equivalency.
Nothing in this Code is intended to prevent the use of systems, methods, or devices of equivalent or superior
quality, strength, fire resistance, effectiveness, durability, and safety over those prescribed by this Code.

A.‍1.4
Before a particular mathematical fire model or evaluation system is used, its purpose and limitations
need to be known. The technical documentation should clearly identify any assumptions included in
the evaluation. Also, it is the intent of the Committee on Safety to Life to recognize that future
editions of this Code are a further refinement of this edition and earlier editions. The changes in
future editions will reflect the continuing input of the fire protection/life safety community in its
attempt to meet the purpose stated in this Code.

4/6/2020 LS Training 21

21

Assembly Occupancy
▪ Assembly Occupancy. An occupancy (1) used for a gathering of
50 or more persons for deliberation, worship, entertainment, eating,
drinking, amusement, awaiting transportation, or similar uses; or (2)
used as a special amusement building, regardless of occupant load.
o Armories
o Assembly halls
o Auditoriums
o Bowling lanes
o Club rooms
o College and university classrooms, 50 person and over
o Conference rooms
o Court rooms
o Gymnasiums
o Libraries
o Pool room
o Museums
o Restaurants

#6.1.2
4/6/2020 LS Training 22

22

11
4/6/2020

Educational Occupancy
▪ Educational Occupancy. An occupancy used for educational
purposes through the twelfth grade by six or more persons for 4 or
more hours per day or more than 12 hours per week.
o Academies
o Kindergartens
o School

#6.1.3
4/6/2020 LS Training 23

23

Day-Care Occupancy
▪ Day-Care Occupancy. An occupancy In which four or more clients receive care,
maintenance, and supervision, by other than their relatives or legal guardians, for
less than 24 hours per day.
o Adult day-care occupancies, except where part of health care occupancy
o Child day-care occupancies
o Day-care homes
o Kindergarten classes that are incidental to child day-care occupancy
o Nursery school

#6.1.4
4/6/2020 LS Training 24

24

12
4/6/2020

Health Care Occupancy


▪ Health Care Occupancy. An occupancy used to provide
medical or other treatment or care simultaneously to four
or more patients on an inpatient basis, where such patients
are mostly incapable of self-preservation due to age,
physical or mental disability, or because of security
measures not under the occupants’ control.
o Hospitals
o Limited Care Facilities
o Nursing homes

#6.1.5
4/6/2020 LS Training 25

25

Ambulatory Health Care Occupancy


▪ Ambulatory Health Care Occupancy. An occupancy
used to provide services or treatment simultaneously to
four or more patients that provides, on an outpatient
basis, one or more of the following:
(1) Treatment for patients that renders the patients incapable of taking
action for self-preservation under emergency conditions without the
assistance of others

(2) Anesthesia that renders the patients incapable of taking action for
self-preservation under emergency conditions without the assistance of
others

(3) Emergency or urgent care for patients who, due to the nature of
their injury or illness, are incapable of taking action for self-preservation
under emergency conditions without the assistance of others

#6.1.6
4/6/2020 LS Training 26

26

13
4/6/2020

Detention and Correctional Occupancy


▪ Detention and Correctional Occupancy. An occupancy
used to house one or more persons under varied degrees
of restraint or security where such occupants are mostly
incapable of self-preservation because of security
measures not under the occupants’ control.
o Adult and juvenile substance abuse centers
o Adult and juvenile work camps
o Adult community residential centers
o Adult correctional institutions
o Adult local detection facilities

#6.1.7
4/6/2020 LS Training 27

27

Residential Occupancy
▪ Residential Occupancy. An occupancy that provides
sleeping accommodations for purposes other than health
care or detention and correctional
o One and two dwelling units
o Loading or rooming house
o Hotels
o Dormitory
o Apartments

#6.1.8
4/6/2020 LS Training 28

28

14
4/6/2020

Mercantile Occupancy
▪ Mercantile Occupancy. An occupancy used for the
display and sale of merchandise.
o Auction rooms
o Department stores
o Drugstores
o Restaurants with fewer than 50 person
o Shopping centers
o Supermarket

#6.1.10
4/6/2020 LS Training 29

29

Business Occupancy
▪ Business Occupancy. An occupancy used for the
transaction of business other than mercantile.
o Airport traffic control towers
o City halls
o College and university
o Courthouses
o Dentists’ offices
o Doctors’ offices
o General offices

#6.1.11
4/6/2020 LS Training 30

30

15
4/6/2020

Industrial Occupancy
▪ Industrial occupancies shall include factories making
products of all kinds and properties used for operations
such as processing, assembling, mixing, packaging,
finishing or decorating, repairing, and similar operations.
o Drycleaning plants
o Factories of all kinds
o Food processing plants
o Gas plants
o Hangars (for servicing/maintenance)
o Laundries
o Power plants
o Pumping stations
o Refineries
o Sawmills
o Telephone exchanges

#6.1.12
4/6/2020 LS Training 31

31

Storage Occupancy
▪ Storage Occupancy. An occupancy used primarily for the
storage or sheltering of goods, merchandise, products, or
vehicles.
o Barn
o Bulk oil storage
o Cold storage
o Freight terminals
o Grain elevators
o Hangers (for storage only)
o Parking structure
o Warehouses

#6.1.13
4/6/2020 LS Training 32

32

16
4/6/2020

Two or More Occupancies


▪ Multiple Occupancies. Multiple occupancies shall
comply with the requirements of 6.1.14.1 and one of the
following:
o Mixed occupancies — 6.1.14.3
o Separated occupancies — 6.1.14.4

A multiple occupancy where the occupancies are


intermingled

#6.1.14.3
4/6/2020 LS Training 33

33

Two or More Occupancies


▪ Multiple Occupancies. Multiple occupancies shall
comply with the requirements of 6.1.14.1 and one of the
following:
o Mixed occupancies — 6.1.14.3

o Separated occupancies — 6.1.14.4

A multiple occupancy where the occupancies are


separated by fire barriers

#6.1.14.4
4/6/2020 LS Training 34

34

17
4/6/2020

Two or More Occupancies


▪ Multiple Occupancies. Multiple occupancies shall
comply with the requirements of 6.1.14.1 and one of the
following:
o Mixed occupancies — 6.1.14.3

o Separated occupancies — 6.1.14.4

A multiple occupancy where the occupancies are


separated by fire barriers

#6.1.14.4
4/6/2020 LS Training 35

35

Separated occupancies

#Table_6.1.14.4.1(a)
4/6/2020 LS Training 36

36

18
4/6/2020

Incidental occupancies
▪ Incidental use area are based on occupant load
criteria from the definition of the occupancy. To be
considered part of the predominant occupancy.
o Gift Shop in a hotel
o Small Storage in any occupancy
o Education use for less than 6 persons in apartment building
o Assembly use for fewer than 50 persons in a business occupancy
o Offices in educational occupancy

#Table_6.1.14.4.1(a)
4/6/2020 LS Training 37

37

Occupancies Classification
▪ Assembly occupancy design criteria should be
determined on a room-by-room basis, a floor-by-
floor basis, and a total building basis to establish
assembly.
▪ Incorporating the 50 persons threshold on a room-
by-room basis determines classification of occupancy
for assembly use.
▪ When occupant load calculations determine that, on
a room-by-room basis, each room is less than 50
occupants, the rooms should be identified as
incidental to the predominant occupancy, as in
6.1.2.2.

#6.1.14.4
4/6/2020 LS Training 38

38

19
4/6/2020

Occupancies Classification
▪ In this example, each room has an occupant load of
49 persons, calculated using assembly use occupant
load factor for less concentrated use, as covered in
Table 7.3.1.2.
▪ Based on the 50-person threshold, none of the three
rooms, on a room-by-room basis, meet the 50-
person criterion, thus there is no assembly
occupancy
▪ To avoid Classifying the three meeting rooms as an
assembly occupancy, do not aggregate the occupant
loads of the rooms. Aggregates of the occupants
loads is applicable when each room exceeds the 50
person threshold.

#6.1.14.4
4/6/2020 LS Training 39

39

Occupancies Classification
▪ In this example, three meeting rooms. One has an
occupant load of 90 persons and the other two each
have an occupant load of 120 persons
▪ When each room exceeds the 50-person threshold,
the rooms are subject to the criteria.
▪ An alarm system should be specified for assembly
occupancies with occupant loads of more than 300
persons, as covered in 12.3.4.1. Thus, the 330-
persons combined occupant load shown mandates a
fire alarm system for the assembly occupancies

#6.1.14.4
4/6/2020 LS Training 40

40

20
4/6/2020

Occupancies Classification
▪ Considered individually, each meeting room has an
occupant load in excess of the 50-pereon threshold
as covered in 6.1.2.1. Therefore, each room is
classified as an assembly occupancy.
▪ Each room design is applicable to LSC 12
▪ When each room exceeds the 50-person threshold,
the rooms are subject to the criteria.
▪ Occupant loads of the three rooms are aggregated to
establish an assembly occupancy with a 330-person
occupant load on a floor-by-floor basis, as in 12.1.4

#6.1.14.4
4/6/2020 LS Training 41

41

Hazardous Classification

Chapter 6 provides in depth details about the classification of hazards.

▪ Low Hazard
▪ Ordinary Hazard
▪ High Hazard

4/6/2020 LS Training 42

42

21
4/6/2020

Hazardous Classification

Chapter 6 provides in depth details about the classification of hazards.

▪ Low Hazard
▪ Ordinary Hazard
▪ High Hazard

4/6/2020 LS Training 43

43

Low Hazard

▪ Low Hazard. Low hazard contents shall be classified as those


of such low combustibility that no self-propagating fire
therein can occur.

4/6/2020 LS Training 44

44

22
4/6/2020

Ordinary Hazard

▪ Ordinary Hazard. Ordinary hazard contents shall be


classified as those that are likely to burn with moderate
rapidity or to give off a considerable volume of smoke.

4/6/2020 LS Training 45

45

High Hazard

▪ High Hazard. High hazard contents shall be classified as


those that are likely to burn with extreme rapidity or from
which explosions are likely.

4/6/2020 LS Training 46

46

23
4/6/2020

Building Hight
• 3.3.37.7 * High-Rise Building.
• A building where the floor of an occupiable story is greater
than 75 ft (23 m) above the lowest level of fire department
vehicle access
Tips:
The below dose not included as stories:
1. Stories below level of exit discharge
2. Mezzanines
3. One Story above grade parking level is not
considered a story except for:
• Assembly occupancy
• Health care occupancy
• Ambulatory health care occupancy
• Detention and correctional occupancy

4/6/2020 LS Training 47

47

Building Hight

• 2 Stories in Hight for Assembly


occupancy
• 6 Stories in Hight for business
occupancy

• 2 Stories in Hight for Assembly occupancy


• 6 Stories in Hight for business occupancy
• Stories below exit discharge not counted
• Mezzanine is not counted

4/6/2020 LS Training 48

48

24
4/6/2020

NFPA 101 Life Safety Code & NFPA 5000


Building Construction Code
Building Construction

❑ Buildings occupied in accordance with the individual


occupancy chapters, Chapters 11 through 43, shall
meet the minimum construction requirements of
those chapters.

❑ Determine the requirements for the construction


classification by NFPA 220 & NFPA 5000.

❑ From NFPA 5000 you can know the construction type


and required fire resistance rating protection

4/6/2020 LS Training 49

49

NFPA 5000 Building Construction Code


Building Construction

❑ To determine the construction type, you should know

o Building occupancy classification


o Number of stories/floors
o Maximum building height
o Maximum floor area
o The building is sprinklered or non-sprinklered

4/6/2020 LS Training 50

50

25
4/6/2020

NFPA 5000 Building Construction


Code
Building Construction

❑ For Example:

o The building is Industrial ordinary hazard


o The No. of stories is 2 stories
o Maximum building height is 37 ft
o Maximum floor area is 15,600 𝑓𝑡 2
o The building is non-sprinklered

The Construction Type is Type II (111)

4/6/2020 LS Training 51

51

NFPA 5000 Building Construction Code


Building Construction

❑ Buildings and structures shall be


classified according to their type
of construction, which shall be
based upon one of five basic
types of construction designated
as Type I, Type II, Type III, Type
IV, and Type V, with fire
resistance ratings not less than
those specified in this table

4/6/2020 LS Training 52

52

26
4/6/2020

Means of Egress

Chapter 7 provides in depth details about the construction and


design of means of egress.

▪ Exit #3.3.83, 7.1.2.2 (9)


▪ Exit Access #3.3.84, 7.1.2.2 (10)
▪ Exit Discharge #3.3.85, 7.1.2.2 (11)
▪ Public Way #3.3.220

#3.3.83, 7.1.2.2

4/6/2020 LS Training 53

53

Means of Egress

Chapter 7 provides in depth details about the construction and


design of means of egress.

▪ Exit #3.3.83, 7.1.2.2 (9)


▪ Exit Access #3.3.84, 7.1.2.2 (10)
▪ Exit Discharge #3.3.85, 7.1.2.2 (11)
▪ Public Way #3.3.220

4/6/2020 LS Training 54

54

27
4/6/2020

Exist Enclosure and Protection

NFPA 1010Section 8.2 and 8.3 details the requirements for exit
enclosure and protection

#8.2
4/6/2020 LS Training 55

55

Determine The Fire Resistance Rating

#8.2.4

4/6/2020 LS Training 56

56

28
4/6/2020

Fire Barriers / Horizontal Continuity

#8.3.1.2

4/6/2020 LS Training 57

57

Fire Barriers / Horizontal Continuity

#8.3.1.2

4/6/2020 LS Training 58

58

29
4/6/2020

Fire Barriers Classification

#8.3.1.2

4/6/2020 LS Training 59

59

Fire Barriers Classification

• 3-hour fire resistance rating


• 2-hour fire resistance rating
• 1-hour fire resistance rating
• 1/2-hour fire resistance rating

#8.3.1.1

4/6/2020 LS Training 60

60

30
4/6/2020

Fire Door and Windows

#8.3.4.2 Fire Doors

#8.2.3
#8.3.2
#8.3.3
Fire Windows

#8.3.3.(3&4)

4/6/2020 LS Training 61

61

Fire Door and Windows

#8.3.3.(3&4)

4/6/2020 LS Training 62

62

31
4/6/2020

Table 8.3.3.2.2 Minimum Fire


Rating for Opening Protectives in
Fire Resistance Rated Assemblies
and Fire-Rated Glazing Markings

4/6/2020 LS Training 63

63

Penetration in Fire Barriers

#8.3.5

4/6/2020 LS Training 64

64

32
4/6/2020

Fire Barriers

1. Fire protection rated door with closer #8.3.3.


2. Fire windows # 8.3.3.5 through 8.3.3.12.
3. Pipe and conduit # 8.3.5.1.
4. Fire damper or HVAC duct penetrations # 8.3.5.7.

4/6/2020 LS Training 65

65

Exit Enclosures
Requirements include:

• Fire-resistance separation
• Openings
• Penetrations, and
• Uses

#7.1.3.2

4/6/2020 LS Training 66

66

33
4/6/2020

Vestibule Separations

#7.1.3.2.1 (9)a

4/6/2020 LS Training 67

67

Openings

#7.1.3.2.1 (9)

4/6/2020 LS Training 68

68

34
4/6/2020

Penetrations

Penetrations are permitted by 7.1.3.2.1(10) for:


• Water and steam piping necessary for the heating and cooling of the exit enclosure
• Electrical conduit serving the exit enclosure
• Fire alarm system circuit wiring installed in the metallic conduit and serving the building
• Standpipe and sprinkler piping serving the building Uses

#7.1.3.2.1 (10)

4/6/2020 LS Training 69

69

Other Uses

#7.1.3.2.2

4/6/2020 LS Training 70

70

35
4/6/2020

Egress Reliability

#7.1.10

4/6/2020 LS Training 71

71

Other requirements

#7.1.5, 7.1.6, 7.1.7

4/6/2020 LS Training 72

72

36
4/6/2020

NFPA 101 Life Safety Code


Means of Egress Components

❑ Doors

o Doors in means of egress shall not be less than 810 mm in


clear width.

o Existing buildings…shall not be less than 710mm door leaf


width

o Rooms < 6.5 sq. m. that are not required to be accessible


to persons with severe mobility impairments, shall not be
less than 610 mm door leaf width.

Pivot Hinged Balance Door

4/6/2020 LS Training 73

73

Door Width

#7.2.1

4/6/2020 LS Training 74

74

37
4/6/2020

Door Width

Side Hinged Door


#7.2.1 Doors With Panic Hardware

4/6/2020 LS Training 75

75

Side-hinged Or Pivoted Swinging Type

Side Hinged Door Pivot Hinged Balance Door


#7.2.1.4

4/6/2020 LS Training 76

76

38
4/6/2020

Roof Doors
Means of Egress Components

❑ waterproofing issues
A door sill is now allowed in locations that are not normally
occupied such as roof access doors.

4/6/2020 LS Training 77

77

Door Swinging Direction

Door leaves required to be of the side-hinged or pivoted winging type


shall swing in the direction of egress travel if:

1. The room or area has an occupant load of 50 or more (with some


exceptions)
2. The door assembly is used in an exit enclosure, unless the door
opening serves an individual living unit that opens directly into an
enclosure, or
3. The door opening serves a high hazard contents area, as shown here

#7.2.1.4.2

4/6/2020 LS Training 78

78

39
4/6/2020

NFPA 101 Life Safety Code


Means of Egress Components

❑ Doors

o Doors required to be of the side-hinged or


pivoted-swinging type shall swing in the direction
of travel where serving a room or area with an
occupant load of 50 or more

o During its swing, any door leaf shall leave not less
than one-half of the required width of a corridor
unobstructed

o When fully open, any door shall not project more


than 180 mm into the required width of a corridor.

4/6/2020 LS Training 79

79

Stairs
Means of Egress Components

❑ Stairs

o Stairs used as a component in the means of egress


shall conform to the general requirements of NFPA
Section 7.1

o Total Cumulative Occupant Load Assigned to the Stair


• <2000 Persons Stair width ≥ 1120mm
• ≥2000 Persons Stair width ≥ 1420mm

4/6/2020 LS Training 80

80

40
4/6/2020

Stairs
Means of Egress Components

Stairways serving 2000 or more persons must be a


minimum of 56 in. wide.

NFPA101 7.2.2.2.1.2

4/6/2020 LS Training 81

81

Guards and Handrails


Means of Egress Components

Guards:
• Open side of a walking surface
• Required where there is a vertical drop of at least30 in.

Handrails:
• Stair or ramp
• Required on both sides unless otherwise permitted

NFPA101 7.2.2.4

4/6/2020 LS Training 82

82

41
4/6/2020

Handrail Details
• Height
• Additional handrails
• Wall clearance
• Shape
• Brackets or balusters
• Length

#7.2.2.4.5

4/6/2020 LS Training 83

83

Perpendicular Handrails
• For standard stairs, at least one handrail
must be installed at a right angle to the
leading edge of the stair treads.

#7.2.2.4.4

4/6/2020 LS Training 84

84

42
4/6/2020

Guard Details
Guard detail requirements include:
• Measuring criteria
• Height
• Intermediate rail distance

4/6/2020 LS Training 85

85

Enclosed, Usable Space


• Usable space under a stair is permitted to be
considered outside the exit enclosure if the
walls and soffits of the enclosed space meet
the same protection requirements as the stair
enclosure.

#7.2.2.5.3

4/6/2020 LS Training 86

86

43
4/6/2020

Stair Sign Location

#7.2.2.5.4

4/6/2020 LS Training 87

87

Stair Sign Examples


• (L) through (0). (L) The stairway identification shall be located at the top of the sign
• (M)* Signage that reads NO ROOF ACCESS shall designate stairways
• (N) The floor level number shall be located below the stairway identifier
• (O) Identification of the lower and upper terminus of the stairway

#7.2.2.5.4.

4/6/2020 LS Training 88

88

44
4/6/2020

Horizontal exits
Horizontal exits:
• Provide passage from one building area into another
building area
• May not provide more than one-half of the required
number of exits
• May not provide more than one-half of the required egress
capacity
• May be used as part of a defend-in-place protection
strategy in health care and detention facilities

#7.2.4

4/6/2020 LS Training 89

89

Vertical Continuity : Option1

• The fire barrier used to create the horizontal exit must


extend to the finished ground level.

#7.2.4.3.1(2)

4/6/2020 LS Training 90

90

45
4/6/2020

Vertical Continuity: Option2


• If a 2-hour separation is not provided on all levels below
the required horizontal exit, including area below the LED,
exit discharge of all stairways must be to the exterior.

#7.2.4.3.3

4/6/2020 LS Training 91

91

Vertical Continuity
• The 2-hour wall may be omitted below the LED if:
• The LED floor is 2-hours
• The areas below the LED do not have a horizontal exit, and
• The area discharges to the exterior

4/6/2020 LS Training 92

92

46
4/6/2020

Horizontal Exits

4/6/2020 LS Training 93

93

Horizontal Exits

4/6/2020 LS Training 94

94

47
4/6/2020

Horizontal Exits

4/6/2020 LS Training 95

95

Horizontal Exits
Opening
Protection

4/6/2020 LS Training 96

96

48
4/6/2020

Extensions at Exterior Walls

#7.2.4.3.4(1)

4/6/2020 LS Training 97

97

Extensions Alternative

#7.2.4.3.4(2)

4/6/2020 LS Training 98

98

49
4/6/2020

Exit Passageway
• An exit passageway serves as a horizontal
means of exit travel that is protected from
fire in a manner similar to an enclosed
interior exit stair.

#7.2.6

4/6/2020 LS Training 99

99

Exit Passageway as Discharge from Stair


• The door between the stair and the exit
passageway is not required.

#7.2.6.3

4/6/2020 LS Training 100

100

50
4/6/2020

Additional Egress Components


Other egress components include:
• Outside stairs
• Smokeproof enclosures
• Escalators/Moving walks
• Fire escape stairs
• Fire escape ladders
• Elevators in towers

#7.2.7, 7.2.8, and 7.2.9.

4/6/2020 LS Training 101

101

Calculating Capacity
Calculating Capacity
1. Determine Occupant Load
2. Determine Clear Width of Components
3. Determine Capacity of Components
4. Determine Most Restrictive Component
5. Determine If Egress Capacity is Sufficient

#7.3

4/6/2020 LS Training 102

102

51
4/6/2020

Step 1: Determine Occupant Load


Use Table 7.3.1.2
Actual maximum number of
occupants, but not less than

Floor area
Occupant Load Factor

4/6/2020 LS Training 103

103

4/6/2020 LS Training 104

104

52
4/6/2020

4/6/2020 LS Training 105

105

4/6/2020 LS Training 106

106

53
4/6/2020

4/6/2020 LS Training 107

107

Egress Sizing and Arrangement

4/6/2020 LS Training 108

108

54
4/6/2020

Egress Sizing and Arrangement


200 ft. x 143 ft. floor space:
• Two 300 ft2 conference rooms
• Remainder used as offices
• All doors 32 in. of clear width
• Sidewalks at least 48 in. clear width
• Level 1 is the level of exit discharge
• Two stairs

4/6/2020 LS Training 109

109

Egress Sizing and Arrangement


200 ft. x 143 ft. floor space:
• Two 300 ft2 conference rooms
• Remainder used as offices
• All doors 32 in. of clear width
• Sidewalks at least 48 in. clear width
• Level 1 is the level of exit discharge
• Two stairs

4/6/2020 LS Training 110

110

55
4/6/2020

Egress Sizing and Arrangement


Gross area: 28,600 ft2
Net area: 600 ft2
Use factor: 15 ft2/person
Net area Gross - Net
Occupant Load = +
Use Factor Use Factor
600 ft2 28,600 ft2 - 600 ft2
Occupant Load = +
15 ft2/person 100 ft2/person

= 40 + 280
= 320 Persons
4/6/2020 LS Training 111

111

Determine Clear Width of Components


Step 2

4/6/2020 LS Training 112

112

56
4/6/2020

Determine Component Capacity


Step 3:
• Table 7.3.3.1 shows egress capacity for
approved components of means of egress.
• Egress capacity is the component's clear
width divided by the capacity factor.

Use Table 7.3.3.1


4/6/2020 LS Training 113

113

Egress Sizing and Arrangement


Step 4:
To determine the most restrictive
1. Identify components
2. Identify capacity factors
3. Determine capacity
4. Identify most restrictive component

4/6/2020 LS Training 114

114

57
4/6/2020

Determine if Egress Capacity Is Sufficient


Step 5:
Capacity must be > maximum occupant load.
• 2 means of egress, each with capacity of 147
• Occupant load = 320

Egress capacity = 2 x 147 = 294


Occupant load = 320

capacity < load


294 <320
Egress capacity is NOT adequate

4/6/2020 LS Training 115

115

Determining Egress Capacity for Stair


Where an egress serves more than one story:

• Occupant load of each story is considered individually


• Required egress capacity may not be decreased in
direction of travel
• Required capacities are added together for converging
means of
• egress

4/6/2020 LS Training 116

116

58
4/6/2020

LED

4/6/2020 LS Training 117

117

LED

4/6/2020 LS Training 118

118

59
4/6/2020

Distribution of Egress Capacity


The loss of any one means of egress must leave available not less than 50 percent of the required
capacity.

4/6/2020 LS Training 119

119

Number of Means of Egress


Subsection X.2.4 of each occupancy chapter
identifies the requirements for number of
means of egress.

4/6/2020 LS Training 120

120

60
4/6/2020

Number of Exits

4/6/2020 LS Training 121

121

Number of Exits:
Business

4/6/2020 LS Training 122

122

61
4/6/2020

Number of Exits:
Business

4/6/2020 LS Training 123

123

Number of Exits:
Business

4/6/2020 LS Training 124

124

62
4/6/2020

Number of Exits:
Business

4/6/2020 LS Training 125

125

Number of Exits:
Business

4/6/2020 LS Training 126

126

63
4/6/2020

Number of Exits: Business


200 ft. x 143 ft. floor space:

4/6/2020 LS Training 127

127

Business Occupancy: Single Exit


Exception:
• Occupant Load < 100 People
• Travel distance < 100 ft

4/6/2020 LS Training 128

128

64
4/6/2020

Egress Arrangement

4/6/2020 LS Training 129

129

Minimum Width
Minimum width:
• As required for a given component
• Not less than 36 in.

4/6/2020 LS Training 130

130

65
4/6/2020

Limited Exit Access


• 6 Persons or Fewer
• Travel of Less than 50 ft.

4/6/2020 LS Training 131

131

Corridor Minimums
Business Occupancy : Not Less than 44 in.

4/6/2020 LS Training 132

132

66
4/6/2020

Travel Distance
Maximum allowed travel distance based on:
• Number, age, and physical condition of
building occupants
• Type and number of obstructions
• Number of people in any room or space
• Amount and nature of combustibles
• Rapidity with which fire may spread

4/6/2020 LS Training 133

133

4/6/2020 LS Training 134

134

67
4/6/2020

4/6/2020 LS Training 135

135

Travel Distance: Exit Stair


Travel distance is measured from most remote point subject to occupancy to where the exit begins.

4/6/2020 LS Training 136

136

68
4/6/2020

Travel Distance: Open Stair


Travel distance is measured from most remote point subject to occupancy to where the exit begins.

4/6/2020 LS Training 137

137

Common Paths of Travel

4/6/2020 LS Training 138

138

69
4/6/2020

Common
Paths of Travel

4/6/2020 LS Training 139

139

Common
Paths of Travel

4/6/2020 LS Training 140

140

70
4/6/2020

Common Paths of Travel

4/6/2020 LS Training 141

141

Common Paths of Travel

For business occupancies, common path of travel not over 75 ft.


Common path of travel not over 100 ft. permitted:
• In building protected by approved automatic sprinkler system
• Within single tenant space with occupant load of 30 people or fewer

4/6/2020 LS Training 142

142

71
4/6/2020

NFPA 101 Life Safety Code


Common Path & Dead End

❑ Dead End: is similar to a common path of travel, a


dead end can exist where there is no path of travel from an
occupied space but can also exist where an occupant enters a
corridor thinking there is an exit at the end (a)

❑ Common Path of Travel: Common path of travel is


measured in the same manner as travel distance but terminates
at that point where two separate and distinct routes become
available.
Paths that merge are common paths of travel. (b)

4/6/2020 LS Training 143

143

Dead-End Corridors

4/6/2020 LS Training 144

144

72
4/6/2020

Dead-End
Corridors

4/6/2020 LS Training 145

145

Dead-End
Corridors

4/6/2020 LS Training 146

146

73
4/6/2020

Dead-End Corridors

4/6/2020 LS Training 147

147

NFPA 101 Life Safety Code


Travel Distance, Common Path & Dead End Table

4/6/2020 LS Training 148

148

74
4/6/2020

Remoteness
Arrangements of means of Egress

❑ Where two exits, exit accesses, or exit discharges are


required

o In Sprinklered Building :
➢ They shall be located at a distance from one another not
less than one-half the length of the maximum overall
diagonal dimension of the building or area to be served.

o Non-Sprinklered Building:
➢ They shall be located at a distance from one another not
less than one-Third the length of the maximum overall
diagonal dimension of the building or area to be served.

4/6/2020 LS Training 149

149

4/6/2020 LS Training 150

150

75
4/6/2020

4/6/2020 LS Training 151

151

4/6/2020 LS Training 152

152

76
4/6/2020

4/6/2020 LS Training 153

153

Discharge from Building


Discharge from Building

❑ Exits shall terminate directly, at a public way or at an


exterior exit discharge

❑ Not more than 50% of the required number of exits


permitted to discharge interior the building.

4/6/2020 LS Training 154

154

77
4/6/2020

Discharge from Building

❑ Exits shall terminate directly, at a public way or at an


exterior exit discharge

❑ Not more than 50% of the required number of exits


permitted to discharge interior the building.

4/6/2020 LS Training 155

155

Egress Visibility and Marking

4/6/2020 LS Training 156

156

78
4/6/2020

Illumination of Means of Egress

#7.8

4/6/2020 LS Training 157

157

Illumination of Means of Egress

#7.8

4/6/2020 LS Training 158

158

79
4/6/2020

Illumination
Illumination is required throughout the exit (e.g., an enclosed exit
stair or exit passageway).

4/6/2020 LS Training 159

159

Illumination

4/6/2020 LS Training 160

160

80
4/6/2020

Illumination

4/6/2020 LS Training 161

161

Illumination Levels Required


Illumination requirements:
• At least 1 ft.-candle at floor level
• At least 10 ft.-candle during stair use (new stairs)
Requirements may be reduced:
• When showing motion pictures or presentations
• Where operations require low lighting levels

4/6/2020 LS Training 162

162

81
4/6/2020

Illumination Levels Required

4/6/2020 LS Training 163

163

Emergency Lighting
Section 7.9 requires emergency lighting for
designated egress paths.
Where maintenance of illumination depends on
changing from one energy source to another, a delay
of not more than 10 seconds shall be permitted.

4/6/2020 LS Training 164

164

82
4/6/2020

Emergency Lighting
New emergency power systems for
emergency lighting must be at least:
• Type 10
• Class 1.5
• Level 1

4/6/2020 LS Training 165

165
Maintenance / Testing

4/6/2020 LS Training 166

166

83
4/6/2020

Maintenance/Testing
Required emergency lighting shall be tested in
accordance with one of three options:
• Manual
• Self-testing
• Self-diagnostic

4/6/2020 LS Training 167

167

Self-Diagnostic/Testing

4/6/2020 LS Training 168

168

84
4/6/2020

BS Testing Method

4/6/2020 LS Training 169

169

Emergency Lighting: Existing Business


Emergency lighting is required for existing business occupancies if:
• The building is three or more stories in height
• The occupancy is 100 or more occupants above or below the level of discharge
• Total occupancy is 1,000 or more

4/6/2020 LS Training 170

170

85
4/6/2020

Marking of Means of Egress


Subsection 2.10 of each occupancy chapter: When marking of
means of egress is required Section 7.10: Details for how and
where exit access signage should be provided.

4/6/2020 LS Training 171

171

Exit Signs
Approved sign, Readily visible from any direction

4/6/2020 LS Training 172

172

86
4/6/2020

Sign Visibility
Two signs readily visible from any direction

4/6/2020 LS Training 173

173

Directional Exit Sign


A directional sign must be placed where the direction of
travel to reach the nearest exit is not apparent.

4/6/2020 LS Training 174

174

87
4/6/2020

External Sign Illumination


Subsection 7.10.6 outlines requirements for externally
illuminated signs:
• Size of signs
• Size and location of directional indicator
• Level of illumination

4/6/2020 LS Training 175

175

Internal Sign Illumination


Internally illuminated signs must be laboratory tested
and listed in accordance with ANSI/UL 924.

4/6/2020 LS Training 176

176

88
4/6/2020

NO Exit
Any door that is likely to be mistaken for an exit
must be identified by a sign that says NO EXIT.

4/6/2020 LS Training 177

177

Testing and Maintenance


Testing is required:
• Every 30 days
• In accordance with 7.9.3

4/6/2020 LS Training 178

178

89
4/6/2020

High-Hazard Contents
High hazard contents are classified as those
that are likely to burn with extreme rapidity
or from which explosions are likely.

4/6/2020 LS Training 179

179

Mechanical/Boiler/Furnace Rooms
Section 7.12 applies, in all buildings, to:
• Mechanical equipment rooms
• Boiler rooms
• Furnace rooms

4/6/2020 LS Training 180

180

90
4/6/2020

The intent is to protect


occupants located in
rooms or spaces adjacent
to hazardous storage from
fire and/or smoke.

4/6/2020 LS Training 181

181

Designing hazardous storage


rooms with smoke-resistive
assemblies and sprinklers is an
option to the design illustrated

4/6/2020 LS Training 182

182

91
4/6/2020

The degree of hazard for rooms


designed for the use or
processing of hazardous
materials mandates the more
restrictive design elements
shown in Figure 1.19(c) to
protect occupants in adjacent
rooms or spaces

4/6/2020 LS Training 183

183

Mechanical/Boiler/Furnace Rooms: Common


Path of Travel
Common path of travel: 50 ft.

4/6/2020 LS Training 184

184

92
4/6/2020

Mechanical/Boiler/Furnace Rooms: Single


Means of Egress
A story used exclusively for mechanical equipment, boilers, or
furnaces may be served by a single exit.

4/6/2020 LS Training 185

185

Requirements For Special Structures and


High-rise Buildings

4/6/2020 LS Training 186

186

93
4/6/2020

Special structures
1. Open Structures
2. Towers
3. Water-Surrounded Structures
4. Piers Open Structures Towers Water-Surrounded Structures
5. Vehicles and Vessels
6. Underground and Limited Access
7. Structures
8. Permanent and Temporary Membrane
9. Structures
Underground and Vehicles and Vessels Piers
10. Tents
Limited Access
Structures

4/6/2020 LS Training 187

187

Exit Signs
Requirements for high-rise buildings in Section 11.8 apply to:
• New high-rise buildings
• Existing high-rise buildings if referenced by the occupancy
chapter

4/6/2020 LS Training 188

188

94
4/6/2020

High-Rise Building Requirements


• Sprinklers
• Standpipe
• Alarm and communications
• Standby power
• Emergency command center, and
• Stairway video monitoring

4/6/2020 LS Training 189

189

Vertical Openings

4/6/2020 LS Training 190

190

95
4/6/2020

Vertical Continuity and Openings


The principal structural weakness responsible for the vertical
spread of fire is the absence of the fire cutoffs at openings
between floors.

4/6/2020 LS Training 191

191

Continuity Exemptions: Floor Penetrations


Section 8.6.3 outlines exemptions for specific
listed floor penetrations.

4/6/2020 LS Training 192

192

96
4/6/2020

Communicating Space
Communicating space is permitted if it meets
alternative protection criteria, unless prohibited by
the occupancy chapter.

4/6/2020 LS Training 193

193

4/6/2020 LS Training 194

194

97
4/6/2020

Atrium
This is permitted unless prohibited by the
occupancy chapter.

4/6/2020 LS Training 195

195

Protected Two-Story Opening


A vertical opening serving as other than an exit
enclosure connecting only two adjacent stories
and piercing only one floor shall be permitted to
be open to one of the two stories.

4/6/2020 LS Training 196

196

98
4/6/2020

Two-Story Convenience Openings


Two-story convenience openings are permitted if they meet the
requirements of 8.6.9.

Key criteria:
• Connects two floors only
• Not a required means of egress
• Separated from the corridors
• Separated from unprotected openings serving other floors

4/6/2020 LS Training 197

197

Expansion Joints
Fire protection-rated expansion or seismic joints with
minimum rating of not less than the required fire
resistance rating of the floor are permitted.

4/6/2020 LS Training 198

198

99
4/6/2020

Escalators
New escalators and existing
escalators not serving as exits need
not be enclosed under certain
conditions.

4/6/2020 LS Training 199

199

Hazardous Area

4/6/2020 LS Training 200

200

100
4/6/2020

Protection of Hazardous Areas: 1-


hour Fire Barrier
Any area having a degree of hazard greater
than normally found in that occupancy must
be protected in one of three ways. It may be:
• Enclosed with afire barrier with no windows
with a 1 hour fire resistance rating
• Protected with automatic extinguishing
systems
• Both enclosed with 1-hour barrier and
protected by automatic extinguishing
systems where the hazard is severe

4/6/2020 LS Training 201

201

Smoke Partitions for Sprinkler Protected New


Hazardous Areas
8.7.1.2 requires a smoke partition
enclosure in accordance with 8.4 to
protect the hazardous area with
automatic sprinklers in lieu of afire
barrier enclosure.

4/6/2020 LS Training 202

202

101
4/6/2020

Smoke Partitions
Where required elsewhere in the Code, smoke
partitions shall be provided to limit the transfer
of smoke

4/6/2020 LS Training 203

203

Smoke Barriers
A limited number of occupancies require smoke barriers.

4/6/2020 LS Training 204

204

102
4/6/2020

Smoke Barriers
Doors in smoke barriers shall close the opening, leaving only the minimum clearance necessary for
proper operation, and shall be without louvers or grilles.

4/6/2020 205

205

Smoke Partitions for Sprinkler Protected New


Hazardous Areas
The continuity of the smoke barrier addresses
potential openings in the smoke barrier wall.

4/6/2020 LS Training 206

206

103
4/6/2020

Interior Finishes

❑ Chapter 10 provides in depth details about the


interior finishing requirements

4/6/2020 LS Training 207

207

Interior Finishing

❑ Interior finishes are broken down into three classifications:


o Class A Interior Wall and Ceiling Finish (flame spread 0-25,
smoke development 0-450)
o Class B Interior Wall and Ceiling Finish (flame spread 26-75,
smoke development 0-450)
o Class C Interior Wall and Ceiling Finish (flame spread , smoke
development 0-450)
o Where the standards require C, A or B can also be used
o Where the standards require B, A can also be used

4/6/2020 LS Training 208

208

104
4/6/2020

Interior Finishes

4/6/2020 LS Training 209

209

Interior Finishing

❑ Industrial Occupancy
o Interior Finishes in industrial
occupancies can be Class A, B, or C
o In exit enclosures, interior finishes
shall be Class A or Class B
o Floor finishes in exit enclosures
including stair treads and risers shall
be not less than Class II.

4/6/2020 LS Training 210

210

105
4/6/2020

Interior Finishing
Interior Finishing

❑ The interior finish shall comply with all of the following


when tested using method B of the test protocol of
NFPA 265:
o During the 40 kW exposure, flames shall not spread to
the ceiling.
o The flame shall not spread to the outer extremities of the
samples on the 8 ft × 12 ft (2440 mm × 3660 mm) walls.
o Flashover, as described in NFPA 265, shall not occur.
o For new installations, the total smoke released
throughout the test shall not exceed 1000 m2.

4/6/2020 LS Training 211

211

Any Question?

4/6/2020 LS Training 212

212

106

You might also like