You are on page 1of 22

NR0609

DS/ES Simulator
Instruction Manual

NR Electric Co., Ltd.


Preface

Preface

1.1 Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.

Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.

Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.

This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.

1.2 Health and Safety


The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.

When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.

Before working in the terminal strip area, the equipment must be isolated.

Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.

Qualified personnel are individuals who:

 Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;

 Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;

 Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;

 Are trained in emergency procedures (first aid).

1.3 Instructions and Warnings


The following indicators and standard definitions are used:

NR0609 DS/ES Simulator i


Date: 2016-01-06
Preface

DANGER! means that death, severe personal injury and considerable equipment damage
will occur if safety precautions are disregarded.

WARNING! means that death, severe personal and considerable equipment damage
could occur if safety precautions are disregarded.

CAUTION! means that light personal injury or equipment damage may occur if safety
precautions are disregarded.

NOTICE! is particularly applies to damage to device and to resulting damage of the protected
equipment.

DANGER!

NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously high
voltage that cause death.

WARNING!

ONLY qualified personnel should work on or in the vicinity of this device. This personnel
MUST be familiar with all safety regulations and service procedures described in this
manual. During operating of electrical device, certain part of the device is under high
voltage. Severe personal injury and significant device damage could result from
improper behavior.

WARNING!

Do NOT touch the exposed terminals of this device while the power supply is on. The
generated high voltage causes death, injury, and device damage.

WARNING!

Thirty seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.

CAUTION!

 Earthing

Securely earthed the earthing terminal of the device.

 Operating environment

ONLY use the device within the range of ambient environment and in an
environment free of abnormal vibration.

ii NR0609 DS/ES Simulator


Date: 2016-01-06
Preface

 Ratings

Check the input ratings BEFORE applying AC voltage/current and power supply to
the device.

 Printed circuit board

Do NOT attach or remove printed circuit board if the device is powered on.

 External circuit

Check the supply voltage used when connecting the device output contacts to
external circuits, in order to prevent overheating.

 Connection cable

Carefully handle connection cables without applying excessive force.

NOTICE!

The firmware may be upgraded to add new features or enhance/modify existing


features, please MAKE SURE that the version of this manual is compatible with the
product in your hand.

Copyright © 2016 NR. All rights reserved.

We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.

The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.

We reserve the rights to make technical improvements without notice.

NR ELECTRIC CO., LTD. Tel: +86-25-87178888


Headquarters: 69, Suyuan Avenue, Jiangning, Nanjing 211102, China Fax: +86-25-87178999
Manufactory: 18, Xinfeng Road, Jiangning, Nanjing 211111, China Website: www.nrelect.com, www.nrec.com

PN: ZL_NR0609_X_Instruction Manual_EN_Overseas General_X Version: R1.00

NR0609 DS/ES Simulator iii


Date: 2016-01-06
Preface

Documentation Structure

The manual provides a functional and technical description of this relay and a comprehensive set
of instructions for the relay’s use and application.

All contents provided by this manual are summarized as below:

1 Function Introduction
Introduce the application, functions and typical wiring about NR0609 DS/ES simulator.

2 Technical Data
Introduce the technical data about NR0609 DS/ES simulator, such as electrical specifications,
mechanical specifications, ambient temperature and humidity range, type tests and the
certifications that our products have passed.

3 Hardware and Installation


Introduce the panel arrangement and the terminal definition of NR0609 DS/ES simulator. A guide
to the mechanical and electrical installation of this relay is also provided, incorporating earthing
recommendations.

4 Manual Version History


List the instruction manual version and the modification history records.

iv NR0609 DS/ES Simulator


Date: 2016-01-06
1 Function Introduction

1 Function Introduction

Table of Contents
1 Function Introduction ....................................................................... 1-a
1.1 Application....................................................................................................... 1-1
1.2 Function Configuration .................................................................................. 1-1
1.3 Typical Wiring .................................................................................................. 1-1

NR0609 DS/ES Simulator 1-a


Date: 2016-01-06
1 Function Introduction

1-b NR0609 DS/ES Simulator


Date: 2016-01-06
1 Function Introduction

1.1 Application
NR0609 disconnector switch/earth switch (DS/ES) simulator is designed according to the usage
characteristic of the actual DS/ES, it can simulate the operating characteristic of DS/ES. It can be
used to replace multi-channel DS/ES to coordinate with secondary equipment to accomplish
related function tests.

1.2 Function Configuration


NR0609 can be used to simulate eight groups of DS/ES, per group of DS/ES can be operated
independently, its functions include:

1) Use the magnetic latching relay to realize the simulation of DS/ES operating characteristic
(status holding after operation);

2) Manually operating button: simulating manually opening and closing operation;

3) Control input interface: accomplishing the opening and closing operation of DS/ES via
external input;

4) Position indicator: indicating the position status of DS/ES;

5) Output contact: simulating DS/ES auxiliary contact.

NR0609 includes internal power transform module, it can transform the external input power to
24V DC power which can be used for internal.

1.3 Typical Wiring


The typical wiring of NR0609 is shown in following figure.

The power transform module will transform the external input power to 24V DC power, which can
be used for DS/ES simulator.

The bottons of the figure can simulate the manually opening and closing operation of DS/ES.
Control input interfaces are equipped with NR0609, the control output of secondary equipment can
be connected to it, then the opening and closing operation of DS/ES can be realized.

The indicators of the figure can be used to indicate the DS/ES position status, the output contact is
the auxiliary contact of DS/ES.

NR0609 DS/ES Simulator 1-1


Date: 2016-01-06
1 Function Introduction

101 201 Close DS/ES 1


DS/ES 1 is open
202 Open DS/ES 1
102
DS/ES 1 is closed

103 203 Close DS/ES 2


DS/ES 2 is open
204 Open DS/ES 2
104
DS/ES 2 is closed

105 205 Close DS/ES 3


DS/ES 3 is open
206 Open DS/ES 3
106
DS/ES 3 is closed

107 207 Close DS/ES 4


DS/ES 4 is open
208 Open DS/ES 4
108
DS/ES 4 is closed

109 209 Close DS/ES 5


DS/ES 5 is open
210 Open DS/ES 5
110
DS/ES 5 is closed

111 211 Close DS/ES 6


DS/ES 6 is open
212 Open DS/ES 6
112
DS/ES 6 is closed

113 213 Close DS/ES 7


DS/ES 7 is open
214 Open DS/ES 7
114
DS/ES 7 is closed

115 215 Close DS/ES 8


DS/ES 8 is open
216 Open DS/ES 8
116
DS/ES 8 is closed

117 217

118 218

119 219 24V_IN+

Position 120 220


common 24V_IN-
terminal
Power
transform
301

302

303

304

305

306
24V_OUT+

24V_OUT-

PWR GND
PWR+

PWR-

Figure 1.3-1 Typical wiring diagram of NR0609

1-2 NR0609 DS/ES Simulator


Date: 2016-01-06
2 Technical Data

2 Technical Data

Table of Contents
2 Technical Data ................................................................................... 2-a
2.1 Electrical Specifications ................................................................................. 2-1
2.2 Mechanical Specifications.............................................................................. 2-1
2.3 Ambient Temperature and Humidity Range .................................................. 2-1
2.4 Type Tests ........................................................................................................ 2-2
2.5 Certifications ................................................................................................... 2-2

NR0609 DS/ES Simulator 2-a


Date: 2016-01-06
2 Technical Data

2-b NR0609 DS/ES Simulator


Date: 2016-01-06
2 Technical Data

2.1 Electrical Specifications


2.1.1 Power Supply
Rated voltage 110Vdc/125Vdc/220Vdc/250Vdc or 110/220Vac
Quiescent condition <3W
Burden
Operating condition <5W

2.1.2 Control Input


Rated voltage 24Vdc
Rated current Approximately 25mA
Burden under operating condition 500Vac

2.1.3 Contact Output


Output mode Potential free contact
Maximal working voltage 380Vac, 250Vdc
Test voltage across open contact 1000V RMS for 1min
5A@380Vac
Continuous carry
5A@250Vdc
6A@3s
Short duration current 15A@0.5s
30A@0.2s
Pickup time <8ms
Dropoff time <8ms
0.65A@48Vdc
Breaking capacity (L/R=40ms) 0.30A@110Vdc
0.15A@220Vdc
Durability (Loaded contact) 10000 operations

2.2 Mechanical Specifications


Housing color Silver grey
Weight per device Approx. 1kg
Pollution degree Ⅱ
Protection class
Front side IP40
Other sides IP40
Rear side IP30

2.3 Ambient Temperature and Humidity Range


Operating temperature -20°C to +55°C
Transport and storage temperature
-40°C to +70°C
range
Permissible humidity 5%-95%, without condensation

NR0609 DS/ES Simulator 2-1


Date: 2016-01-06
2 Technical Data

2.4 Type Tests


2.4.1 Environmental Tests
Dry cold test IEC 60068-2-1:2007 (16 h at -25°C)
Dry heat test IEC 60068-2-2:2007 (16 h at +55°C)
IEC 60068-2-30:2005 (Two (12+12) hour cycles 95%RH, low
Damp heat test, cyclic
temperature -25°C, high temperature +55°C)

2.4.2 Insulation Tests


Standard IEC 60255-27-2013
Input power and output contact part: Test voltage 2kV, 50Hz, 1min
Dielectric tests
24V power and control input part: Test voltage 0.5kV, 50Hz, 1min
Insulation resistance measurements Isolation resistance >100MΩ@500VdC
Input power and output contact part: 5kV
Impulse voltage tests
24V power and control input part: 1kV

2.5 Certifications
 ISO9001:2008

 ISO14001:2004

 OHSAS18001:2007

 ISO10012:2003

 CMMI L5

 EMC: 2004/108/EC, EN50263:1999

 Products safety(PS): 2006/95/EC, EN61010-1:2001

2-2 NR0609 DS/ES Simulator


Date: 2016-01-06
3 Hardware and Installation

3 Hardware and Installation

Table of Contents
3 Hardware and Installation ................................................................ 3-a
3.1 Panel Arrangement ......................................................................................... 3-1
3.2 Terminal Definition .......................................................................................... 3-1
3.3 Structure and Installation ............................................................................... 3-2

NR0609 DS/ES Simulator 3-a


Date: 2016-01-06
3 Hardware and Installation

3-b NR0609 DS/ES Simulator


Date: 2016-01-06
3 Hardware and Installation

3.1 Panel Arrangement

The front panel of NR0609 is shown as below:

OPN 1 OPEN 1 CLOSED 1 CLS 1

OPN 2 OPEN 2 CLOSED 2 CLS 2

OPN 3 OPEN 3 CLOSED 3 CLS 3

OPN 4 OPEN 4 CLOSED 4 CLS 4

OPN 5 OPEN 5 CLOSED 5 CLS 5

OPN 6 OPEN 6 CLOSED 6 CLS 6

OPN 7 OPEN 7 CLOSED 7 CLS 7

OPN 8 OPEN 8 CLOSED 8 CLS 8

NR0609
DS/ES SIMULATOR

Figure 3.1-1 Front panel of NR0609

Where:

The button “OPN 1”~”OPN 8” is manually opening button;

The button “CLS 1”~”CLS 8” is manually closing button;

The signal indicator “OPEN 1”~”OPEN 8” is the open position indicator of corresponding DS/ES;

The signal indicator “CLOSED 1”~”CLOSED 8” is the closed position indicator of corresponding
DS/ES.

3.2 Terminal Definition


The terminal definition of NR0609 is shown as below:

NR0609 DS/ES Simulator 3-1


Date: 2016-01-06
3 Hardware and Installation

101 OPEN 1 CLS 1 201


102 CLOSED 1 OPN 1 202
103 OPEN 2 CLS 2 203
104 CLOSED 2 OPN 2 204
105 OPEN 3 CLS 3 205
106 CLOSED 3 OPN 3 206
107 OPEN 4 CLS 4 207
108 CLOSED 4 OPN 4 208
109 OPEN 5 CLS 5 209
110 CLOSED 5 OPN 5 210
111 OPEN 6 CLS 6 211
112 CLOSED 6 OPN 6 212
113 OPEN 7 CLS 7 213
114 CLOSED 7 OPN 7 214
115 OPEN 8 CLS 8 215
116 CLOSED 8 OPN 8 216
117 217
118 218
119 24V_IN+ 219
120 BO_COM 24V_IN- 220

24V_OUT+
24V_OUT-

PWR+
PWR-
PE
301
302
303
304
305
306
Figure 3.2-1 Rear panel terminal definition

3.3 Structure and Installation


3.3.1 Mechanical Dimension
NOTICE!

It is necessary to leave enough space top and bottom of the cut-out in the cubicle for
heat emission of it.

Following figure shows the dimensions of NR0609 for reference in mounting.

3-2 NR0609 DS/ES Simulator


Date: 2016-01-06
3 Hardware and Installation

110 111
80 35.1
80±0.2 4-Φ3.5

167±0.2
167

177

156

Figure 3.3-1 Dimensions of NR0609

3.3.2 Grounding Guidelines


NOTICE!

All these precautions can only be effective if the station ground is of good quality.

Switching operations in HV installations generate transient over voltages on control signal cables.
There is also a background of electromagnetic RF fields in electrical installations that can induce
spurious currents in the devices themselves or the leads connected to them.

All these influences can influence the operation of electronic apparatus.

On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.

In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.

3.3.3 Cubicle Grounding


The cubicle must be designed and fitted out such that the impedance for RF interference of the
ground path from the electronic device to the cubicle ground terminal is as low as possible.

Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.

NOTICE!

If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of

NR0609 DS/ES Simulator 3-3


Date: 2016-01-06
3 Hardware and Installation

interference by the devices installed and also reduce their immunity to induced
interference.

Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 3.3-2).

The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.

NOTICE!

For metallic connections please observe the voltage difference of both materials
according to the electrochemical code.

The cubicle ground rail must be effectively connected to the station ground rail by a
grounding strip (braided copper).

Figure 3.3-2 Cubicle grounding system

3-4 NR0609 DS/ES Simulator


Date: 2016-01-06
4 Manual Version History

4 Manual Version History


In the latest version of the instruction manual, several descriptions on existing features have been
modified.

Manual version and modification history records

Manual Version
Date Description of change
Source New
R1.00 2016-01-06 Form the original manual.

NR0609 DS/ES Simulator 4-1


Date: 2016-01-06
4 Manual Version History

4-2 NR0609 DS/ES Simulator


Date: 2016-01-06

You might also like