Professional Documents
Culture Documents
Custom Search
Search
SPONSORED SEARCHES
depression test
Excel Sheets Codes Books House Plans Front Views Video Tutorials
SPONSORED SEARCHES
SPONSORED SEARCHES
FLASH POINT
SOURCES OF BITUMEN
Asphalt Cement shall be oil asphalt or a mixture of refined liquid asphalt and refined solid asphalt,
prepared from crude asphaltic petroleum. It shall be free from admixture with any residues obtained by
the artificial distillation of coal, coal tar or paraffin and shall be homogeneous and free from water. Fire
Point
AR-4000
80 / 100 pen
Warm, mean annual air temperature between 7 °C (45 °F) and AC-20
24 °C (75 °F)
AR-8000
60 / 70 pen
AR-8000
40 / 50 pen
Flash point measures the tendency of the sample to form a flammable mixture with air under
controlled laboratory conditions. It is only one of a number of properties that must be considered
in assessing the overall flammability hazard of a material.
Flash point is used in shipping and safety regulations to differentiate between ‘‘flammable’’ and
‘‘combustible’’ materials.
Flash point can indicate the possible presence of highly volatile and flammable materials in a
relatively nonvolatile or nonflammable material.
Fire point measures the characteristics of the sample to support combustion.
Bituminous materials give rise to volatiles at high temperature, as they are basically the
hydrocarbons. These volatiles catch fire causing a flash, which is very hazardous.
During construction of bituminous pavements, the engineer may restrict the mixing or application
temperatures well within the limits. The test therefore gives indication of critical temperature at
and above which suitable precautions should be taken to eliminate fire hazards during use of
asphalts. In other words heating should be limited to a temperature well below the flash point.
APPARATUS Fire Point
1. Cleveland Cup Apparatus: It consists of test
cup, heating plate, test flame applicator, heater,
thermometer support and heating plate support,
all conforming to the following requirements.
Heater — Heat may be supplied from any convenient source. The use of a gas burner or alcohol
lamp is permitted, but under no circumstances are products of combustion or free flame to be
allowed to come up around the cup. An electric heater controlled by a variable voltage transformer
is preferred. The source of heat shall be centered under the opening of the heating plate with no
local superheating.
Thermometer Support — A device which will hold the thermometer in the specified position during
a test and permits easy removal of the thermometer from the test cup upon completion of a test.
Heating Plate Support — Any convenient support which will hold the heating plate level and steady
may be employed. Fire Point
2. Shield: A shield having an area of 460mm2 and 610mm high and having an open front is used.
Support the apparatus on a level table. Shield the top of the apparatus from strong intensity of light by
any suitable means to permit ready detection of the flash point. Fire Point
Wash the test cup with an appropriate solvent to remove any oil or traces of gum or residue remaining
from a previous test. If any deposits of carbon are present, they should be removed with steel wool.
Flush the cup with cold water and dry for a few minutes over an open flame, on a hot plate, or in an
oven to remove the last traces of solvent and water. Cool the cup to at least 56 °C below the expected
flash point before using.
Support the thermometer in a vertical position with the bottom of the bulb 6.4 mm from the bottom of
the cup and located at a point halfway between the center and side of the cup on the diameter
perpendicular to the line of the sweep of the test flame and on the side opposite to the test flame
burner arm. Fire Point
PROCEDURE
Risknowlogy
Get your HAZOP leadership skill certi ed. Become a
Certi ed HAZOP Expert or Master
Risknowlogy GmbH OPEN
Fill the cup; at any convenient temperature not exceeding 100 °C or above the softening point; so
that the top of the meniscus is at the filling line.
Remove the excess sample using a pipette or other suitable device; however, if there is sample on
the outside of the apparatus, empty, clean, and refill it. Destroy any air bubbles on the surface of
the sample.
Lit the test flame and adjust it to a diameter of 3.8 to 5.4 mm.
Apply heat initially so that the rate of temperature rise of the sample is 14 to 17 °C per minute.
When the sample temperature is approximately 56 °C below the anticipated flash point, decrease
the heat so that the rate of temperature rise for 28°C before the flash point is 5 to 6°C per minute.
Starting at least 28 °C below the flash point, apply the test flame when the temperature read on the
thermometer reaches each successive 2 °C mark. Pass the test flame across the center of the
cup, at right angles to the diameter, which passes through the thermometer. With a smooth,
continuous motion apply the flame either in a straight line or along the circumference of a circle
having a radius of at least 150 mm. The center of the test flame must move in a plane not more
than 2.5 mm above the plane of the upper edge of the cup passing in one direction first, then in the
opposite direction the next lime. The time consumed in passing the test flame across the cup shall
be about one second (1 s.). During the last 17 °C rise in temperature prior to the flash point, care
must be taken to avoid disturbing the vapors in the test cup by careless movements or bathing
near the cup.
Record as the observed flash point the temperature read on the thermometer when a flash
appears at any point on the surface of the material, but does not confuse the true flash with the
bluish halo that sometimes surrounds the test flame.
To determine the fire point, continue heating so that the sample temperature increases at a rate of
5 to 6 °C. Continue the application of the test flame at 2°C intervals until the oil ignites and
continues to burn for at least 5 second. Record the temperature at the point as the fire point of the
oil.
Precautions
1. Do not breathe close to the apparatus as the fumes are injurious to health.
2. Turn the fans off so that the fumes can be accumulated over the cup.
3. Tip of the thermometer should not touch the bottom or sides of the cup.
4. The operator must exercise and take appropriate safety precautions during the initial application of
the test flame, since samples containing low flash material may give an abnormally strong flash
when the test flame is first applied.
Observe and record the barometric pressure at the time of the test. When the pressure differs from 760
mm Hg, correct the flash or fire point, or both, by means of the following equations:
Where:
Record the corrected flash or fire joint value, or both, to the nearest 5 °C or 2°C.
VISCOSITY GRADES
Property AC – 2.5 AC – 5 AC – 10 AC – 20 AC – 40
Note:
FlashAC
Point
– 10COC,
is most
°C commonly
163 used in 177
Pakistan. 219 232 232
min.
0 24
1 30
2 36
3 41
4 47
5 53
6 60
7 67
8 73
9 80
10 112
11 156
12 182
13 202
14 222
15 240
16 256
17 271
18 284
19 299
20 310
21 318
22 329
23 340
24 351
COMMENTS
- EU TRAININGS - -
Your Courses in Spain
Ad eutrainings.eu
Civil Engineering
Interview and Test
Questions
civilengineerspk.com
Interview Questions
civilengineerspk.com
WAPDA Test
Questions conducted
by PTS-3
civilengineerspk.com
PPSC Interview
questions
civilengineerspk.com
Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire
Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire
Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point, Fire Point
Share this:
ANJALI NALANG
Thank you so much.I got lot of information about flash and fire point test from this page.
UBAIDAHMAD
on February 16, 2016 at 15:44 said:
You’re Welcome
mursaleen
on April 9, 2016 at 18:49 said:
thanks alot
UBAIDAHMAD
on April 10, 2016 at 07:47 said:
you’re Welcome
marwa sabry
on August 15, 2016 at 19:34 said:
UBAIDAHMAD
on August 18, 2016 at 15:18 said:
You’re Welcome 🙂
Ali hassan
on February 27, 2017 at 05:14 said:
can you please send me the graph in the last in excel formate.
if its possible, send it at this mail address “alihassan92147@gmail.com”
CIVILENGINEERSPK
on February 27, 2017 at 08:31 said:
Nope. 🙂
Gowtham Ramesh
on August 17, 2017 at 05:54 said:
What are teh samples we can use to conduct test can we use diesel,kerosene,oil etc any lubricant
CIVILENGINEERSPK
on August 17, 2017 at 09:48 said:
Jawad Ahmad
on December 29, 2017 at 12:53 said:
Jawad.dws@gmail.com
CIVILENGINEERSPK
on December 29, 2017 at 19:19 said: