You are on page 1of 27

Power Intake Stability Analysis

Base Pressure(kN/m2) Sliding


Check for
Load stress
Condition Permissible FOS(Calc Permissible
B A Check Check (Tension/Com
stress ulated) FOS pression)

Load combination 1 : Construction


Case 1 200.26 182.06 172.50 Unsafe Infinity >1.3 Safe Compression
Load combination 2 : Construction + Earthquake
Case 1 175.91 193.66 225.00 Safe 11.16 >1.1 Safe Compression
Case 2 189.26 205.80 225.00 Safe 11.92 >1.1 Safe Compression
Case 3 211.26 158.31 225.00 Safe 11.16 >1.1 Safe Compression
Case 4 224.61 170.45 225.00 Safe 11.92 >1.1 Safe Compression
Load combination 3 : Normal Operation
Case 1 133.12 148.29 150.00 Safe 3.52 >1.7 Safe Compression
Load combination 4 : Normal Operation + Earthquake
Case 1 103.23 163.88 172.50 Safe 2.20 >1.3 Safe Compression
Case 2 119.89 175.81 172.50 Unsafe 2.43 >1.3 Safe Compression
Case 3 159.51 136.20 172.50 Safe 6.25 >1.3 Safe Compression
Case 4 142.84 124.26 172.50 Safe 5.64 >1.3 Safe Compression
Load combination 5 : Flood condition
Case 1 90.68 158.82 225.00 Safe 1.26 >1.1 Safe Compression
Stability Analysis

M.P.F. 530.20

F.S.L. 525.00

SECTION- 1-1

518.35
516.00

B A

17.25m

M.P.F. 530.20

F.S.L. 525.00

SECTION- 2-2

17.25m

SECTION- 2-2
Part-3 Part-1 Part-2

UPSTREAM VIEW
Refer Code : EM 1110-2-2100-Stability Analysis of Concrete Structure

Material Properties : Unit Value


Unit weight of concrete(P.C.C.) kN/m3 24.00
Unit weight of water kN/m3 9.81
Foundation Shear Strength Parameters :
Cohesion of the material at the Plane Considered (C ) kN/m2 0.00
Friction angle φ degree(°) 30.00
Coefficient of Internal Friction of the material (tan φ ) 0.58
Saturated Unit weight of the soil kN/m3 21.30
Safe Bearing Pressure kN/m2 150.00
Reservoir Water Levels :
Full Supply Level (F.S.L) m 525.00
Maximum Water Level for PMF m 530.20

Dimensions Unit Value


Width of the structure (B) m 11.20
Width for Part 1 m 3.30
Width for Part 2 m 3.95
Width for Part 3 m 3.95
weighted Length of the structure (L) m 17.25

Area & weight calculation of structure Unit Value


For Part 1
Area m2 110.12
Width considered for Part-1 m 3.30
Number of blocks Nos. 1.00
weight kN 8721.50
For Part-2
Area m2 148.79
Width considered for Part-2 m 3.95
Number of blocks Nos. 1.00
weight kN 14105.29
For Part-3
Area m2 148.79
Width considered for Part-3 m 3.95
Number of blocks Nos. 1.00
weight kN 14105.29
Total Self weight of the structure kN 36932.09

Elevations Unit Value


Bottom Elevation of the Structure for Hydrostatic pressure calaculation m 516.00
Elevations of point A m 515.85

Weight of water inside and near intake portion Unit Value

Area of water inside intake(refer section1-1 ) for Normal operation m2 56.82


Weight of water kN 1839.43
Area of water inside intake(refer section1-1 ) for Flood condition m2 21.95
Weight of water kN 710.59
Area of water near intake for Normal condition m2 24.26
Weight of water kN 2665.49
Area of water near intake for Flood condition m2 60.35
Weight of water kN 6630.78
Centeroid calculation of structure x y
For Part 1
Center of gravity consindering origin point A -8.38 5.50
For Part 2
Center of gravity consindering origin point A -8.88 5.26
For Part 3
Center of gravity consindering origin point A -8.88 5.26
Center of gravity for complete structure -8.76 5.32

Earthquake Parameters:
DBE Case
Horizontal Acceleration Coefficient 0.05
Vertical Acceleration Coefficient 0.03

Requirements for Location of the Resultant – All Structures


Site information category Usual Unusual Extreme
100% Base in 75% Base in Resultant
All Categories
Compression Compression Within Base

Required Factors of Safety for Sliding - Critical Structures


Site information category Usual Unusual Extreme
Well Defined 1.70 1.30 1.10
Ordinary 2.00 1.50 1.10

Limited - - -

Vertical Force Horizontal force Moment about Toe


Sign Convention Down Wards(+) Up Towards U/s (+) Clock (-) Anti-
Wards(-) Towards D/s(-) Clock (+)

(*As per EM-1110-2-2100 the bearing capacity is increased by 15% for unusual load condition and 50 % for
extreme load condition)
Load Combination 1:(Construction Condition)

Case-1

Calculation due to Self Weight Value Unit


B 11.20 m
L 17.25 m
Self weight of the structure kN
36932.09 Downward
CG from point A(horizontal
m
distance) 8.76
Moment 323596.19 kN-m Anti-clock wise

Net Vertical Force 36932.09 kN Downward


Resisting Moment 323596.19 kN-m Anti-clock wise
Overturning moment 0.00 kN-m Clock wise
Net Moment 323596.19 kN-m Anti-clock wise

Check for sliding

V Tan φ + CA
F =
H

V Net Vertical force = 36932.09 kN


H Net Horizontal Force = 0.00 kN
Coeff. of Internal Friction of the
Tan φ 0.58
material =
Cohesion of the material at the
C 0.00
Plane Cons. = kN/m2
Area under consideration for
A cohesion 193.20
= m2
Factor of Safety against sliding
F Infinity
= >1.3 Safe

Check for stress


Distance of Value Unit
resultant from
X = ∑M/∑V m
point A 8.76
e = L/2-X m
Eccentricity -0.14
L/6 m
2.88 Compression

Bearing pressure kN/m2) Point


A 182.06 ∑V*(1±6*e/L)

Bearing pressure (kN/m2) Point


B 200.26 B*L

Allowable bearing pressure 172.50 kN/m2 Unsafe


Load Combination 2 : (Construction Condition + Earth Quake)

Case-1(Horizontal Seismic force towards D/s & Vertical seismic force upward)

Calculation due to Self Weight Value Unit

B 11.2 m
L 17.25 m
Self weight of the structure Downward
36932.09 kN

CG from point A(horizontal distance)


8.76 m
Moment due to Self weight Anti-clock wise
323596.19 kN-m

Horizontal seismic force Value Unit


CG from point A(Vertical distance) 5.32 m
Horizontal seismic force Towards D/s
1846.60 kN
Moment 9817.80 kN-m Clockwise

Vertical seismic force Value Unit


CG from point A(Horizontal distance)
8.76 m
Vertical seismic force
1231.07 kN Upward
Moment 10786.54 kN-m Clockwise

Value Unit
Net vertical forces
35701.02 kN Downward
Resisting Moment
323596.19 kN-m Anti-clock wise
Overturning moment
20604.34 kN-m Clockwise
Net Moment
302991.85 kN-m Anti-clock wise

Check for sliding

V Tan φ + CA
F =
H

V Net Vertical force = 35701.02 kN


H Net Horizontal force = 1846.60 kN
Coeff. of Internal Friction of the
Tan φ 0.58
material =

C Cohesion of the material at the Plane 0.00 kN/m2


Cons. =
Area under consideration for
A 193.20 m2
cohesion =

F 11.16 >1.1 Safe


Factor of Safety against sliding =
Check for stress Value Unit
Distance of
resultant from
point A X = ∑M/∑V 8.49 m
Eccentricity e = L/2-X 0.14 m
L/6 2.88 m Compression

Bearing pressure (kN/m2)


193.66 ∑V*(1±6*e/L)
Point A

Bearing pressure (kN/m2)


175.91 B*L
Point B

Allowable bearing pressure 225.00 kN/m2 Safe

Limit of resultant location


Location of
Resultant force is
resultant force 8.49 m
within the base
from point A
Case-2 (Horizontal Seismic force towards D/s & Vertical seismic force downward)

Calculation due to Self Weight


Value Unit
B 11.20 m
L 17.25 m

Self weight of the structure Downward


36932.09 kN

CG from point A(horizontal distance)


8.76 m
Moment due to Self weight Anti-clock wise
323596.19 kN-m

Horizontal seismic force Value Unit


CG from point A(Vertical distance)

5.32 m
Horizontal seismic force
Towards D/s
1846.60 kN
Moment 9817.80 kN-m Clockwise

Vertical seismic force


Value Unit

CG from point A(Horizontal distance)


8.76 m
Vertical seismic force 1231.07 kN Downward
Moment Anti-clock wise
10786.54 kN-m

Value Unit
Net vertical forces
38163.16 kN Downward
Resisting Moment
334382.73 kN-m Anti-clock wise
Overturning moment 9817.80 kN-m Clockwise
Net Moment
324564.93 kN-m Anti-clock wise

Check for sliding

V Tan φ + CA
F =
H

V Net Vertical force = 38163.16 kN


H Net Horizontal Force = 1846.60 kN
Coeff. of Internal Friction of the
Tan φ 0.58
material =

C Cohesion of the material at the Plane 0.00


Cons. = kN/m2
Area under consideration for
A 193.20
cohesion = m2
F Factor of Safety against sliding = 11.92 >1.1 Safe

Check for stress Value Unit


Distance of
resultant from X = ∑M/∑V
point A 8.50 m
Eccentricity e = L/2-X 0.12 m
L/6 2.88 m Compression
Bearing pressure (kN/m2)
∑V*(1±6*e/L)
Point A
205.80

Bearing pressure (kN/m2)


B*L
Point B
189.26

Allowable bearing pressure 225.00 kN/m2 Safe

Limit of resultant location


Location of
Resultant force is
resultant force 8.50 m
within the base
from point A
Case-3 (Horizontal Seismic force towards U/s & Vertical seismic force upward)

Calculation due to Self Weight Value Unit


B 11.20 m
L 17.25 m
Self weight of the structure
Downward
36932.09 kN
CG from point A(horizontal distance)
8.76 m
Moment due to Self weight
Anti-clock wise
323596 kN-m

Horizontal seismic force


Value Unit
CG from point A(Vertical distance)
5.32 m
Horizontal seismic force
Towards U/s
1846.60 kN
Moment 9817.80 kN-m Clockwise

Vertical seismic force Value Unit


CG from point A(Horizontal distance) 8.76 m
Vertical seismic force 1231.07 kN Upward
Moment
Anti-clock wise
10786.54 kN-m

Value Unit
Net vertical forces 35701.02 kN Downward
Resisting Moment
333413.99 kN-m Anti-clock wise
Overturning moment
10786.54 kN-m Clockwise
Net Moment
322627.45 kN-m Anti-clock wise

Check for sliding

V Tan φ + CA
F =
H

V = Net Vertical force 35701.02 kN


H = Net Horizontal force 1846.60 kN

Tan φ = Coeff. of Internal Friction of the 0.58


material

C = Cohesion of the material at the 0.00


Plane Cons. kN/m2

A = Area under consideration for 193.20


cohesion m2
F = Factor of Safety against sliding 11.16 >1.1 Safe

Check for stress Value Unit


Distance of
resultant from
point A X = ∑M/∑V = 9.04 m
Eccentricity e = L/2-X = -0.412 m
L/6 = 2.88 m Compression
Bearing pressure (kN/m2)
∑V*(1±6*e/L)
Point A 158.31
Bearing pressure (kN/m2)
B*L
Point B 211.26

Allowable bearing pressure 225.00 kN/m2 Safe

Limit of resultant location


Location of Resultant force is
resultant force 9.04 m within the base
from point A
Case-4 (Horizontal Seismic force towards U/s & Vertical seismic force downward)

Calculation due to Self Weight


Value Unit
B 11.20 m
L 17.25 m
Self weight of the structure Downward
36932.09 kN

CG from point A(horizontal distance)


8.76 m
Moment due to Self weight 323596.19 kN-m Anti-clockwise

Horizontal seismic force


Value Unit
CG from point A(Vertical distance)
5.32 m
Horizontal seismic force 1846.60 kN Towards U/s
Moment 9817.80 kN-m Anti-clockwise

Vertical seismic force


Value Unit

CG from point A(Horizontal distance)


8.76 m
Vertical seismic force 1231.07 kN Downward
Moment 10786.54 kN-m Anti-clockwise

Value Unit
Net vertical forces
38163.16 kN Downward
Resisting Moment
344200.53 kN-m Anti-clock wise
Overturning moment 0.00 kN-m Clockwise
Net Moment
344200.53 kN-m Anti-clock wise

Check for sliding

V Tan φ + CA
F =
H

V = Net Vertical force 38163.16 kN


H = Net Horizontal force 1846.60 kN
Coeff. of Internal Friction of the
Tan φ = material 0.58
Cohesion of the material at the
C = 0.00
Plane Cons. kN/m2

A = Area under consideration for 193.20


cohesion m2
F = Factor of Safety against sliding 11.92 >1.1 Safe

Check for stress Value Unit


Distance of
resultant from
point A X = ∑M/∑V = 9.02 m
Eccentricity e = L/2-X = -0.39 m
L/6 = 2.88 m Compression
Bearing pressure (kN/m2)
Point A 170.45 ∑V*(1±6*e/L)

Bearing pressure (kN/m2)


Point B 224.61 B*L

Allowable bearing pressure 225.00 kN/m2 Safe

Limit of resultant location


Location of Resultant force is
resultant force 9.02 m within the base
from point A
Load Combination 3 : (Normal Operation)

Case-1

Calculation due to Self Weight Value Unit


B 11.20 m
L 17.25 m
Self weight of the structure
Downward
36932.09 kN
CG from point A(horizontal distance) 8.76 m
Anti-
Moment due to Self weight
323596.19 kN-m clockwise

Water inside power intake Value Unit


CG from point A(Horizontal distance) 6.60 m
Weight of water inside power intake Downward
1839.43 kN
Anti-
Moment
12140.26 kN-m clockwise

Water near power intake Value Unit


CG from point A(Horizontal distance) 15.52 m
Weight of water near power intake 2665.49 kN Downward
Anti-
Moment
41368.48 kN-m clockwise

Uplift water force Value Unit


CG from point A(Horizontal distance) 9.32 m 17.25 m
Uplift water force(Upward) 14253.33 kN 91.57 55.98
Moment 132841.04 kN-m Clockwise

0
Hydrostatic force Value Unit
CG from point A(Horizontal distance)
3.15 m 9m
Hydrostatic force 4449.82 kN Towards D/S
Moment 14016.92 kN-m Clockwise 88.29

Value Unit
Net vertical forces
27183.69 kN Anti-clock
Downward
Resisting Moment 377104.93 kN-m wise
Overturning moment 146857.96 kN-m Clockwise
Anti-clock
Net Moment
230246.97 kN-m wise

Check for sliding

+ CA
V Tan φ
F =
H

V Net Vertical force = 27183.69 kN


H Net horizontal force = 4449.82 kN
Tan φ Coeff. of Internal Friction of the material = 0.58
C Cohesion of the material at the Plane Cons. = 0.00 kN/m2
A Area under consideration for cohesion = 193.20 m2
F Factor of Safety against sliding = 3.52 >1.7 Safe
Check for stress Value Unit

Distance of resultant from point A


X = ∑M/∑V 8.47 m
Eccentricity e = L/2-X 0.15 m
L/6 2.88 m Compression

Bearing pressure(kN/m2) Point A 148.29 ∑V*(1±6*e/L)


Bearing pressure(kN/m2) Point B 133.12 B*L

Allowable bearing pressure 150.00 kN/m2 Safe


Load Combination 4: (Normal Operation + Earthquake)

Case-1(Horizontal Seismic force towards D/s & Vertical seismic force upward)

Calculation due to Self Weight Value Unit


B 11.20 m
L 17.25 m

Self weight of the structure Downward


36932.09 kN

CG from point A(horizontal distance)


8.76 m
Moment due to Self weight Anti-clockwise
323596.19 kN-m

Water inside power intake Value Unit

CG from point A(Horizontal distance)


6.60 m
CG from point A(Vertical distance) 4.26 m
Weight of water inside power intake 1839.43 kN Downward

Moment Anti-clockwise
12140.26 kN-m

Horizontal seismic force kN Towards D/s


91.97
Moment 391.80 kN-m
Vertical seismic force 61.31 kN Upward
Moment 404.68 kN-m Clockwise

Water near power intake Value Unit

CG from point A(Horizontal distance)


15.52 m
CG from point A(Vertical distance) 5.94 m
Weight of water near power intake 2665.49 kN Downward
Moment 41368.48 kN-m Anti-clockwise
Horizontal seismic force 133.27 kN Towards D/s
Moment 791.65 kN-m
Vertical seismic force 88.85 kN Upward
Moment 1378.95 kN-m Clockwise

Uplift water force Value Unit 17.25 m


CG from point A(Horizontal distance) 91.57 55.98
9.32 m
Uplift water force 14253.33 kN Upward
Moment 132841.04 kN-m Clockwise

Horizontal seismic force Value Unit


CG from point A(Vertical distance)
5.32 m
Horizontal seismic force 1846.60 kN Towards D/s
Moment 9817.80 kN-m Clockwise
Vertical seismic force Value Unit
CG from point A(Horizontal distance)
8.76 m
Vertical seismic force 1231.07 kN Upward
Moment 10786.54 kN-m Clockwise

0
Hydrostatic force Value Unit
CG from point A(Horizontal distance)
3.15 m

Hydrostatic force Towards D/s


4449.82 kN 9m
Moment 14016.92 kN-m Clockwise

88.29
Hydro-dyanmic force Value Unit
Hydrodynamic force 259.42 kN Towards D/s
Moment 972.84 kN-m Clockwise

Value Unit
Net vertical forces
25802.45 kN Downward
Resisting moment
377104.93 kN-m Anti-clock wise

Overturning Moment
171402.21 kN-m Clockwise

Net Moment
205702.72 kN-m Anti-clock wise

Check for sliding

+ CA
V Tan φ
F =
H
V = Net Vertical force 25802.45 kN
H = Net Horizontal Force 6781.09 kN
Coeff. of Internal Friction of the
Tan φ = 0.58
material

C = Cohesion of the material at the 0.00


Plane Cons. kN/m2

A = Area under consideration for 193.20


cohesion m2
F = Factor of Safety against sliding 2.20 >1.3 Safe

Check for stress Value Unit


Distance of resultant from point A
X = ∑M/∑V 7.97 m
Eccentricity e = L/2-X 0.65 m
L/6 2.88 m Compression

Bearing pressure(kN/m2) Point A 163.88 ∑V*(1±6*e/L)


Bearing pressure(kN/m2) Point B 103.23 B*L

Allowable bearing pressure 172.5 kN/m2 Safe


Case-2 (Horizontal Seismic force towards D/s & Vertical seismic force downward)

Calculation due to Self Weight Value Unit


B 11.20 m
L 17.25 m
Self weight of the structure 36932.09 kN Downward
CG from point A(horizontal distance) 8.76 m

Moment due to Self weight Anti-clockwise


323596.19 kN-m

Water inside power intake Value Unit


CG from point A(Horizontal distance) 6.60 m
CG from point A(Vertical distance) 4.26 m

Weight of water inside power intake Downward


1839.43 kN
Moment Anti-clockwise
12140.26 kN-m
Horizontal seismic force 91.97 kN Toward D/s
Moment 391.80 kN-m Clockwise
Vertical seismic force 61.31 kN Downward
Moment Anti-clockwise
404.68 kN-m

Water near power intake Value Unit


CG from point A(Horizontal distance) 15.52 m
CG from point A(Vertical distance) 5.94 m
Weight of water near power intake 2665.49 kN
Moment 41368.48 kN-m
Horizontal seismic force 133.27 kN Toward D/s
Moment 791.65 kN-m Clockwise
Vertical seismic force 88.85 kN Downward
Moment 1378.95 kN-m Anti-clockwise

Uplift water force Value Unit 17.25 m


CG from point A(Horizontal distance) 9.32 m 91.57 55.98
Uplift water force 14253.33 kN Upward
Moment 132841.04 kN-m Clockwise

Horizontal seismic force Value Unit


CG from point A(Vertical distance) 5.32 m
Horizontal seismic force 1846.60 kN Toward D/s
Moment 9817.80 kN-m Clockwise

Vertical seismic force Value Unit

CG from point A(Horizontal distance)


8.76 m
Vertical seismic force 1231.07 kN Downward
Moment 10786.54 kN-m Anti-clockwise
0
Hydrostatic force Value Unit
CG from point A(Horizontal distance) 3.15 m
Hydrostatic force 4449.82 kN Toward D/s
Moment 14016.92 kN-m Clockwise 9m

Hydro-dyanmic force Value Unit 88.29


Hydrodynamic force 259.42 kN Toward D/s
Moment 972.84 kN-m Clockwise

Value Unit
Net vertical forces
28564.92 kN Downward
Resisting Moment 389675.10 kN-m Anti-clock wise
Overturning Moment 158832.05 kN-m Clockwise

Net Moment 230843.05 kN-m


Anti-clock wise

Check for sliding

+ CA
V Tan φ
F =
H

V = Net Vertical force 28564.92 kN


H = Net Horizontal Force 6781.09 kN
Coeff. of Internal Friction of the
Tan φ = material 0.58
Cohesion of the material at the
C = Plane Cons. 0.00 kN/m2

A = Area under consideration for 193.20


cohesion m2
F = Factor of Safety against sliding 2.43 >1.3 Safe

Check for stress Value Unit


Distance of resultant from point A X = ∑M/∑V 8.08 m
Eccentricity e = L/2-X 0.54 m
L/6 2.88 m Compression

Bearing pressure(kN/m2) Point A 175.81 ∑V*(1±6*e/L)


Bearing pressure(kN/m2) Point B 119.89 B*L

Allowable bearing pressure 172.50 kN/m2


Unsafe
Case-3 (Horizontal Seismic force towards U/s & Vertical seismic force downward)

Calculation due to Self Weight Value Unit


B 11.20 m
L 17.25 m
Self weight of the structure 36932.09 kN Downward
CG from point A(horizontal distance) 8.76 m
Moment due to Self weight Anti-clockwise
323596.19 kN-m

Water inside power intake Value Unit


CG from point A(Horizontal distance) 6.60 m
CG from point A(Vertical distance) 4.26 m
Weight of water inside power intake 1839.43 kN Downward

Moment kN-m Anti-clockwise


12140.26

Horizontal seismic force kN Towards U/s


91.97

Moment kN-m Anti-clockwise


391.80
Vertical seismic force 61.31 kN Downward

Moment 404.68 kN-m Anti-clockwise

Water near power intake Value Unit


CG from point A(Horizontal distance) 15.52 m
CG from point A(Vertical distance) 5.94 m
Weight of water near power intake 2665.49 kN Downward

Moment Anti-clockwise
41368.48 kN-m

Horizontal seismic force Towards U/s


133.27 kN

Moment Anti-clockwise
791.65 kN-m
Vertical seismic force 88.85 kN Downward

Moment Anti-clockwise
1378.95 kN-m

17.25 m
Uplift water force Value Unit 91.57 55.98
CG from point A(Horizontal distance)
9.32 m
Uplift water force 14253.33 kN Upward
Moment 132841.04 kN-m Clockwise

Horizontal seismic force Value Unit


CG from point A(Vertical distance) 5.32 m
Horizontal seismic force 1846.60 kN Towards U/s
Moment Anti-clockwise
9817.80 kN-m
Vertical seismic force Value Unit
CG from point A(Horizontal distance)
8.76 m
Vertical seismic force 1231.07 kN Downward
Moment Anti-clockwise
10786.54 kN-m

Hydrostatic force Value Unit 0


CG from point A(Horizontal distance) 3.15 m
Hydrostatic force 4449.82 kN Towards D/s 9m
Moment 14016.92 kN-m Clockwise

88.29
Hydro-dyanmic force Value Unit

Hydrodynamic force
259.42 kN Towards D/s
Moment 972.84 kN-m Clockwise

Value Unit
Net vertical forces
28564.92 kN Downward
Resisting Moment
400676.34 kN-m Anti-clock wise
Overturning Moment 147830.80 kN-m Clockwise

Net Moment
252845.55 kN-m Anti-clock wise

Check for sliding

+ CA
V Tan
F =
H

V = Net Vertical force 28564.92 kN


H = Net HorizontalForce 2637.39 kN
Coeff. of Internal Friction of the
Tan φ = material 0.58
Cohesion of the material at the
C = Plane Cons. 0.00 kN/m2
Area under consideration for
A = 193.20 m2
cohesion
F = Factor of Safety against sliding 6.25 >1.3 Safe

Check for stress Value Unit


Distance of resultant from point A
X = ∑M/∑V 8.85 m
Eccentricity e = L/2-X -0.23 m
L/6 2.88 m Compression

Bearing pressure(kN/m2) Point A 136.20 ∑V*(1±6*e/L)


Bearing pressure(kN/m2) Point B 159.51 B*L

Allowable bearing pressure 172.50 kN/m2 Safe


Case-4 (Horizontal Seismic force towards U/s & Vertical seismic force upward)

Calculation due to Self Weight Value Unit


B 11.20 m
L 17.25 m
Self weight of the structure 36932.09 kN Downward
CG from point A(horizontal distance) 8.76 m
Moment due to Self weight Anti-clockwise
323596.19 kN-m

Water inside power intake Value Unit


CG from point A(Horizontal distance) 6.60 m
CG from point A(Vertical distance) 4.26 m
Weight of water inside power intake 1839.43 kN Downward
Moment Anti-clockwise
12140.26 kN-m

Horizontal seismic force


91.97 kN Towards U/s
Moment Anti-clockwise
391.80 kN-m
Upward
Vertical seismic force
61.31 kN Clockwise
Moment 404.68 kN-m Clockwise

Water near power intake Value Unit


CG from point A(Horizontal distance)
15.52 m
CG from point A(Vertical distance) 5.94 m
Weight of water near power intake 2665.49 kN Downward

Moment Anti-clockwise
41368.48 kN-m

Horizontal seismic force Towards U/s


133.27 kN

Moment Anti-clockwise
791.65 kN-m
Vertical seismic force 88.85 kN Upward
Moment 1378.95 kN-m Clockwise

Uplift water force Value Unit 17.25 m


CG from point A(Horizontal distance)
9.32 m
Uplift water force 14253.33 kN Upward
Moment 132841.04 kN-m Clockwise 91.57 55.98

Horizontal seismic force Value Unit

CG from point A(Vertical distance)


5.32 m

Horizontal seismic force Towards U/s


1846.60 kN

Moment 9817.80 kN-m Anti-clockwise


Vertical seismic force Value Unit
CG from point A(Horizontal distance) 8.76 m
Vertical seismic force 1231.07 kN Upward
Moment 10786.54 kN-m Clockwise

0
Hydrostatic force Value Unit
CG from point A(Horizontal distance)
3.15 m
Hydrostatic force 4449.82 kN Towards D/s 9m
Moment 14016.92 kN-m Clockwise

Hydro-dyanmic force Value Unit 88.29

Hydrodynamic force kN Towards D/s


259.42
Moment 972.84 kN-m Clockwise

Net vertical forces 25802.45 kN Downward


Resisting Moment kN-m
388106.18 Anti-clock wise
Overturning Moment 160400.96 kN-m Clockwise
Net Moment 227705.22 kN-m
Anti-clock wise

Check for sliding

V Tan φ + CA

F =

V = Net Vertical force 25802.45 kN


H = Net Horizontal Force 2637.39 kN
Coeff. of Internal Friction of the
Tan φ = 0.58
material
Cohesion of the material at the
C = 0.00
Plane Cons. kN/m2
Area under consideration for
A = 193.20
cohesion m2
F = Factor of Safety against sliding 5.64 >1.3 Safe

Check for stress Value Unit


Distance of resultant from point A
X = ∑M/∑V 8.82 m
Eccentricity e = L/2-X -0.20 m
L/6 2.88 m Compression

Bearing pressure(kN/m2) Point A 124.26 ∑V*(1±6*e/L)


Bearing pressure(kN/m2) Point B 142.84 B*L

Allowable bearing pressure 172.50 kN/m2 Safe


Load Combination 5 : (Flood condition)

Case-1

Calculation due to Self Weight Value Unit


B 11.20 m
L 17.25 m
Self weight of the structure
Downward
36932.09 kN
CG from point A(horizontal distance)

8.76 m
Moment due to Self weight Anti-
323596.19 kN-m clockwise

Water inside power intake Value Unit


CG from point A(Horizontal distance) 11.55 m
Weight of water inside power intake Downward
710.59 kN
Moment Anti-
8207.28 kN-m clockwise

Water near power intake Value Unit


CG from point A(Horizontal distance) 14.45 m
Weight of water near power intake 6630.78 kN Downward
Anti-
Moment
95814.70 kN-m clockwise

Uplift water force Value Unit


CG from point A(Horizontal distance) 9.15 m 17.25
Uplift water force(Upward) 20172.01 kN 123.53
Moment 184573.91 kN-m Clockwise

Hydrostatic force Value Unit 0


CG from point A(Horizontal distance)
4.88 m
Hydrostatic force 11077.30 kN Towards D/S
Moment 54094.12 kN-m Clockwise 139.30

Net vertical forces Value Unit


24101.44 kN Downward
Resisting Moment Anti-clock
427618.17 kN-m wise
Overturning moment 238668.03 kN-m Clockwise
Anti-clock
Net Moment
188950.14 kN-m wise

Check for sliding

+ CA
V Tan φ
F =
H

V Net Vertical force = 24101.44 kN


H Net horizontal force = 11077.30 kN
Tan φ Coeff. of Internal Friction of the material = 0.58
C Cohesion of the material at the Plane Cons. = 0.00 kN/m2
A Area under consideration for cohesion = 193.20 m2
F Factor of Safety against sliding = 1.26 >1.1
Check for stress Value Unit

Distance of resultant from point A X = ∑M/∑V 7.84 m


Eccentricity e = L/2-X 0.79 m
L/6 2.88 m

Bearing pressure(kN/m2) Point A 158.82 ∑V*(1±6*e/L)


Bearing pressure(kN/m2) Point B 90.68 B*L

Allowable bearing pressure 225.00 kN/m2

Limit of resultant location


Location of
Resultant force is
resultant force 7.84 m
within the base
from point A
m
85.29

14.2 m

Safe
Compression

Safe