Design Of Isolated Footing 1 of 3

1 Footing Size Design

Load Pu 765 KN
Design Load P 561 KN

Moment in x dir Mux 50 KN-m


Moment in y dir Muy 0 KN-m

Column size cx 450 mm


cy 230 mm

SBC q 150 KN/sqm

Footing Size required A req 3.74 sqmm

L 2.50 meters
Footing Size Provided
B 2.00 meters
Area Provided A prvd 5.00 meters

Zx 1.67
Zx 2.08

Net upward pressure Nup 132 KNm2

Footing Size OK

2 Slab Design
lx 1.025
ly 0.885

Bending Moment in x dir Mx 104 KN-m


Bending Moment in y dir My 78 KN-m

Concrete fck 30 MPa


Steel fy 500 MPa

Minimum Depth Required dmin 162

Depth Provided D 500 mm


Clear Cover c 50 mm
Effective Cover d' 56 mm
Effective Depth d' 444 mm

Spacing c/c in mm
Area of Steel
12# 16# 20#
551 sqmm 205 c/c 365 c/c 570 c/c
533 sqmm 212 c/c 377 c/c 590 c/c

Minimum Ast required across y direcion

Ast across x direction 12 mm dia @ 125 mm c/c 905 sqmm


Ast across y direction 12 mm dia @ 150 mm c/c 754 sqmm
Design Of Isolated Footing 2 of 3

3 One Way Shear along x direction

Vu1 230 KN
ζv 0.259 MPa

ζc 0.269 MPa
Vc1 239 KN

One Way Shear Check OK

4 One Way Shear along y direction

Vu1 219 KN
ζv 0.197 MPa

ζc 0.265 MPa
Vc1 294 KN

One Way Shear Check OK

5 Two Way Shear


Vu2 872 KN
ζv 0.626 MPa

ks*ζc 1.369 MPa


Vc1 1907 KN

Two Way Shear Check OK


Design Of Isolated Footing 3 of 3

L= 2.50 meters

450

230
B= 2.00 meters

500 mm
200 mm

12 mm dia @ 125 mm c/c 12 mm dia @ 150 mm c/c