Professional Documents
Culture Documents
3
Air-Fuel Ratio
B
Air-fuel ratio is by far the most important routine SUMMARY
adjustment that is made to boilers. Of all the adjustments The most important routine adjustment for
that plant operators can make, it has the greatest boilers. Has a major effect on efficiency,
influence on efficiency. Furthermore, failure to set the maintenance, and pollution. The trick is to
air-fuel ratio properly can create serious maintenance
set the air-fuel ratio as close to optimum as
and environmental problems.
possible, while avoiding insufficient air.
If you have automatic combustion controls,
adjusting the air-fuel ratio is easy. Using the methods SELECTION SCORECARD
explained in Measure 1.2.1, measure combustion Savings Potential ...................
efficiency while setting the combustion controls to the
optimum air-fuel ratio. The combustion controls will Rate of Return .......................
then maintain this ratio under all load conditions. Reliability ...............................
Adjusting the air-fuel ratio is not much more difficult
if you have burners that fire at one or more fixed firing Initiation .................................
rates. On the other hand, adjusting modulating burners
can be tedious.
The basic steps are described here. See the burner Efficiency Loss from Incorrect Air-Fuel Ratio
maintenance manual for details of how to adjust your Efficiency suffers from too much air, and from too
particular model of burner. little. Efficiency declines rapidly as the amount of air is
reduced below the point of best efficiency. Efficiency
The Optimum Air-Fuel Ratio declines much more slowly above the point of best
A perfect boiler would use just enough air to burn efficiency. This is because insufficient air and excess
all the fuel completely, with no oxygen left over in the air waste energy in two different ways.
flue gas. (The ratio of air to fuel that achieves this ideal With insufficient air, efficiency falls primarily
result is called a “stoichiometric mixture” by chemists because combustion is incomplete. The incompletely
and advanced boiler people.) With real boilers, burned portion of the fuel is being thrown away through
achieving reasonably complete combustion requires a the flue, taking along its unused energy.
certain amount of air in excess of the stoichiometric ratio. With excess air, the fuel is being burned almost
The excess air is needed to ensure that all the fuel comes completely, but a portion of the combustion energy is
in contact with sufficient oxygen for complete wasted in heating the excess air. The heated excess air
combustion within the flame area. is carried through the boiler as useless baggage. Also,
The minimum amount of excess air that is necessary mixing the combustion gases with excess air lowers the
for clean combustion depends on the type of fuel and temperature of the gases, which reduces heat transfer.
on the type of burner. Table 1 in Measure 1.4.4 lists See the effect in the graph of Figure 1 in Measure 1.2.1.
typical ranges of excess air for different fuels and burner If the amount of excess air is extreme, the large
types. More excess air is needed for fuels that are heavier volume of cool air can quench the combustion process,
and dirtier. Also, burners in smaller equipment tend to causing fuel to be burned incompletely. However, this
have substantially higher excess air requirements. effect does not become significant until efficiency has
Modern, high-efficiency burners minimize the amount already been lowered drastically by the previous effect.
of excess air required. The best modern burners do a
much better job of preparing the fuel for combustion Other Problems Caused by Insufficient Air
and of bringing the proper amount of air into the To repeat, insufficient air wastes much more energy
combustion zone. than an equal percentage of excess air. In addition,
The design of the boiler’s combustion chamber may insufficient air causes these problems:
also affect the excess air requirement. The design of • air pollution. For any hydrocarbon fuel (gas, oil,
the combustion chamber becomes an issue in existing coal, wood, peat, etc.), the end products of complete
boilers if you plan to retrofit a new burner. combustion are carbon dioxide and water, along
Determine the optimum air-fuel ratio for each of with a small amount of additional compounds that
your boilers individually, using the tests recommended may be formed from other substances in the fuel.
below.
WESINC
Fig. 3 Typical jackshaft air-fuel control The jackshaft is
mounted horizontally, moved by the control motor on the upper WESINC
left. A cam on the left end of the jackshaft controls a fuel oil Fig. 4 Typical cam on jackshaft air-fuel linkage The shape
valve, and a cam on the right end of the shaft controls a gas of the cam determines the air-fuel ratio at all boiler loads. The
valve. An arm to the left of the shaft’s center support moves shape can be adjusted by turning the screws that you see
the combustion air damper. The air-fuel ratio depends on the between the cam body and the curved spring that rides on the
relative positions of these mechanical linkages. plunger. This is a tedious job.
mixture controls.
A C
Automatic air-fuel controls provide the ultimate in SUMMARY
efficiency by continuously monitoring the flue gas
Keeps the air-fuel ratio optimum. Available
composition and readjusting the air-fuel ratio. These
controls are common on larger boilers. You can retrofit with a wide range of features and prices.
them to existing boilers. Economical for larger boilers. May not be
Environmental regulation of boiler operation has worth the additional maintenance and failure
expanded enormously in recent years, and continues to modes in smaller boilers.
expand. If you decide to install automatic air-fuel SELECTION SCORECARD
controls, consider the effect of regulation on the
Savings Potential ...................
capabilities that the controls should have. Try to satisfy
foreseeable environmental regulations as well as Rate of Return, New Facilities
maximizing efficiency.
Rate of Return, Retrofit .........
The simplest type of automatic air-fuel control is
an “oxygen trim” system. Oxygen trim systems typically Reliability ...............................
sense only oxygen in the flue gases. The output of the Ease of Retrofit ......................
oxygen trim system is a small adjustment in the air-fuel
ratio to move the measured oxygen content in the desired
direction. Figure 1 shows the control box for a typical Potential Savings
oxygen trim system. The improvement in efficiency that you can expect
At the other extreme are complex air-fuel control from automatic air-fuel control system varies widely
systems for large boilers that measure a variety of flue from one boiler plant to another. As an example, a boiler
gases and combustion conditions. Virtually all of these burning heavy oil might have an optimum excess air of
use flue gas oxygen as the primary measurement. They 15%. In this boiler, increasing the excess air to 30%
may also sense carbon monoxide, nitrogen oxides, other would cause an efficiency loss of one percent. In some
gases, and smoke. Such systems provide accurate plants, excess air may drift from 15% to 30% under
control of boiler output, precise control of air-fuel ratio, realistic operating conditions. Therefore, you may be
and control of various functions related to plant able to save about one percent of fuel energy percent in
emissions, such as stack gas recirculation and scrubbing. such a plant. In plants where maintenance has been
neglected, the saving may be as high as several percent
of the fuel input.
On the other hand, a well maintained boiler that
burns natural gas of stable characteristics may benefit
little from automatic air-fuel adjustment. In this case, a
simple mechanical linkage that regulates the air-fuel
ratio may keep efficiency optimized within close
tolerances. With such a boiler, the efficiency
improvement would typically be only a fraction of one
percent.
Take the claims of efficiency improvements made
by combustion control manufacturers with a grain of
salt. Before-and-after comparisons, even if they are
monitored by a disinterested party, may be misleading.
Much of the improvement that is measured when a trim
system is installed may actually result from the cleaning
and tune-up that occurs along with the installation.
million BTU’s per hour of steam for 3,000 hours per provides a reliable average flue gas temperature.
year while burning heavy oil at $1.00 per gallon has an Be careful to prevent outside air from mixing with
annual fuel cost of approximately $2,500,000. the flue gas sample. See Measure 1.2.1 for more
Improving efficiency by one half of one percent would about this.
save approximately $12,000 per year. • analysis hardware and logic circuitry. This usually
An automatic air-fuel control system is more comes in a single box. If the sensor output is
valuable if the factors that affect the air-fuel ratio are electrical (for example, from a zirconium oxide
subject to change. Some of the conditions that can cause oxygen sensor), the box can be installed almost
the air-fuel ratio to drift are listed in Measure 1.3.1, anywhere. If gas samples are conveyed to the box
above. through tubing, install the box within a specified
Boilers that burn solid fuels or heavy oils need to distance from the sampling point.
adjust the air-fuel ratio continually to account for • displays. You should install gauges or recorders
changes in fuel characteristics, such as the content of that display gas content, efficiency, etc. Install them
carbon, hydrogen, oxygen, sulfur, moisture, and dirt. where they are mostly likely to be monitored by
With coal, these factors can change as fuel is brought in the operators.
from different parts of the coal pile. With oil, they can • actuators. Actuators translate the output signal of
change as different strata of oil are tapped from the tanks. the combustion control system to motion of the fuel
Automatic air-fuel controls correct for drift, valves and air dampers. Retrofitting actuators on a
hysteresis, and non-linearity in control linkages. For preexisting control system can be challenging,
example, where pneumatic actuators are used to control unless the retrofit system is custom designed for
the fuel valves and/or fan dampers, friction in the the particular boiler.
actuators and linkages can cause errors in the air-fuel With boilers that use a common mechanical linkage
ratio. Linkage geometry in modulating burners is to control both air and fuel, the usual practice is to
typically non-linear, and requires tedious adjustments insert a variable-length link in a part of the original
of cams to compensate. Automatic controls can eliminate linkage that controls either the air or the fuel. The
the need to adjust for these factors. trim system works by controlling the length of the
variable link.
Staff Skill and Control Reliability Larger boilers typically use pneumatic, electric
To a certain extent, automatic air-fuel controls can analog, or digital signals to control the motion of
compensate for deficient maintenance. In particular, it separate actuators on the fuel valve and fan control.
can compensate for lack of tuning and for looseness in With such controls, you have to match the output
the controls. However, automatic combustion controls signals of the combustion control system with the
are not a proper substitute for skills, salary, and signals needed by the actuators. For example, if
supervision. Installing a complex control system in an the original controls move the fuel and air actuators
environment with poor maintenance trades continuing with 3-to-15 PSI air pressure, the trim system must
poor efficiency for the possibility of much worse have pneumatic outputs in this range. Alternatively,
efficiency if the control system fails. you can change the actuators.
By the same token, you need controls that are • failure alarms. To repeat, the control system should
especially reliable in plants that are not continuously test itself continuously. If a failure occurs, or if the
monitored by skilled operators. This situation is air-fuel ratio gets out of the designated range, the
common in non-industrial facilities, where the boiler controls should indicate an alarm. Make the alarm
plant is often treated as an inscrutable nuisance. able to get attention, in a manner appropriate to the
Any automatic combustion control should staffing. For example, if the boiler plant is not
continuously self-test, and it should sound an alarm if it staffed continuously, have the alarm trigger a loud
senses failure or an out-of-range condition. horn, or automatically dial the telephone of the
appropriate manager, or whatever is needed to
System Components and Installation Issues initiate immediate repairs.
Automatic air-fuel mixture controls vary in
complexity, control accuracy, and versatility. Their How to Select Air-Fuel Controls
performance depends on their installation as well as their Air-fuel control systems differ widely in cost and
components. These are the basic components, and some in the range of features that they offer. Here are the
important issues to consider in installing them: main features to consider when shopping for a system.
• flue gas probe(s) or sensor(s). The mechanics of What is Sensed
installing sensors is usually easy. Be sure that the Sensing the oxygen content of the flue gas provides
location where you install the sensor(s) provides a the most direct and accurate indication of combustion
representative sampling of flue gases, and that it
sensors used in combustion control systems include this and the fuel valve are connected by a common
feature. mechanical linkage. This type of fail-safe limit is not
Carbon monoxide sensors that use the principles of possible with control systems in which the air and fuel
infrared absorption or polarization can be calibrated are controlled separately by pneumatic, electrical, or
continuously by using reference beams of light. Sensors electronic signals.
that use electrochemical cells must be recalibrated Alarms
periodically by passing calibration gases through the The controls should have effective alarms to alert
sensor. operators of any undesirable condition, especially a
Instruments that need calibration gases require you failure of the combustion control system or an excess
to keep a stock of the appropriate gases on hand. Also, of undesirable gases in the flue.
using calibration gases requires more skill.
Displays and Data Logging
Smoke opacity sensors can be recalibrated
The control system should include convenient
continuously by using a reference light beam.
displays of all the measurements being taken, such as
Sensors for gases that are not directly related to percentage of gas concentration and flue temperature.
combustion efficiency operate on a variety of principles. If you can afford it, get data logging equipment to record
Some of them can be continuously recalibrated, and and analyze long-term trends in the measurements.
some cannot be.
Some systems display derived values, such as
Ability to Change the Air-Fuel Ratio with Load percent efficiency and boiler load. Understand which
The simplest oxygen trim systems establish a outputs are being measured directly, and which are
constant percentage of oxygen at all boiler loads. A derived. For example, percent carbon dioxide may be
constant oxygen percentage is less than optimum calculated from the measured percent oxygen and the
because it allows the percentage of unburned fuel flue temperature. Such a derived value is dubious and
products to rise at lower loads. (This occurs because can be misleading. Boiler load indications may be
the combustion zone is smaller and cooler at low loads, derived from stack temperature. Such a load indication
requiring more oxygen to ensure complete combustion.) is only approximate, because other factors can affect
The appropriate variation in oxygen content with flue temperature.
load depends on the fuel and the boiler design. For this The output of the combustion control system must
reason, most oxygen trim systems include provision to be matched to the input of the recording and analysis
manually adjust the amount of excess oxygen at different equipment. There are a variety of signal conventions,
boiler loads. This is called “characterization” of the such as 4-to-20 milliamperes or 0-to-100 millivolts. If
controls. Do it when the controls are installed, and when the combustion control system includes integral data
sensor elements are replaced. logging, you don’t have to worry about this.
More sophisticated combustion air trim systems Actuator Connections
eliminate the need for manual characterization of excess It can be tricky to make the mechanical connections
air by sensing unburned fuel components in addition to to the existing air-fuel control system. Select a system
sensing oxygen. Even so, complex systems may still that makes this job as easy as possible.
have a manual characterization capability to allow for
control of smoke or environmental pollutants. PID Control Characteristics
It is difficult to maintain control of the air-fuel ratio
Multi-Fuel Capability
when the boiler load fluctuates rapidly, as occurs in many
In boilers that burn more than one type of fuel, applications. To achieve accurate tracking, sophisticated
account for the fact that the optimum air-fuel ratio differs control systems have special features to reduce error,
from one fuel to another. Heavier and dirtier fuels eliminate overshoot, and prevent oscillations. These are
require more excess air than gaseous or light fuels. usually called “proportional-integral-derivative” (PID)
Therefore, get automatic air-fuel controls that provide control characteristics. See Reference Note 37, Control
separate characterization for each fuel burned. Characteristics, for details.
Failure Modes and Overrides
Combustion controls will fail occasionally. For this ECONOMICS
reason, the system should have a reliable self-test feature,
and it should respond to failures by reverting to a fail- SAVINGS POTENTIAL: 0.2 to 3 percent of fuel
safe setting. Typically, the fail-safe setting is a fixed consumption.
percentage of excess oxygen. COST: A simple oxygen trim system for a boiler that
A particularly reliable method of fail-safe control uses a mechanical linkage for control of air-fuel ratio
is to have mechanical stops in the control linkages so may cost less than $10,000. Installing a complex state-
that high and low limits in the air-fuel ratio cannot be of-the-art control system for a large boiler may cost
exceeded. Such stops are possible only if the air damper several hundred thousand dollars.
RATINGS
MEASURE 1.3.3 Adjust and repair air-fuel New Facilities Retrofit O&M
ratio controls.
A
The air-fuel control system needs maintenance on SUMMARY
a regular basis. The mechanical components that control Basic maintenance that keeps the air-fuel
air and fuel are continually moving in response to load
controls working properly.
changes. Something as simple as a loose connection
can cause a major error in the air-fuel ratio. Combustion SELECTION SCORECARD
control systems have sensors that are exposed to hot Savings Potential ...................
flue gases, so they require periodic calibration and
replacement. Rate of Return .......................
Reliability ...............................
Looseness in Mechanical Linkages
The air and fuel controls of most boilers have some Ease of Initiation ....................
mechanical linkages. Most small and medium sized
boilers control the air-fuel ratio entirely with mechanical such as slotted sheetmetal control arms, are unbelievably
linkages, which may include a rotating shaft, one or more flimsy. Linkages are often adjusted with ordinary nuts,
bellcranks, pushrods, and an adjustable cam. These which are virtually certain to work loose in time.
linkages are simple, accessible, and easy to understand. Improve such features wherever you can. For example,
Figure 1 shows a typical example. if your linkages have slotted control arms, install friction
This is fortunate, because the adjustment of the washers on each side of the slot, and use an all-metal
linkages is critical. Even a small amount of play may stop nut.
cause significant inefficiency because fuel and air
controls typically have a small range of movement. Fuel
valves are usually the most sensitive element. For
example, movement of a millimeter in a plunger-type
fuel valve may cause a significant change in fuel flow.
Air-fuel linkages have a number of wear points and
opportunities for components to come loose. To discover
play in a control linkage, hold one end of the linkage in
a fixed position. Then, grasp the linkage at various
places and attempt to move it while feeling for looseness.
Inspect each bearing and joint in the linkage as you do
this. If there is enough play in the linkage to allow any
significant amount of motion, repair the linkage or
tighten it. Replace all worn components.
Industrial Combustion
Unfortunately, many burners have air-fuel linkages Fig. 1 Typical dual-fuel burner assembly All the linkages
made of cheap stamped parts, so they are vulnerable to that control the air-fuel ratio of this burner are easily accessible
wear and working loose. Some common components, for inspection, adjustment, and repair.