You are on page 1of 12

Subsection 1.

3
Air-Fuel Ratio

The ratio of combustion air to fuel is


INDEX OF MEASURES
the most important adjustment on a boiler.
1.3.1 Optimize the air-fuel ratio.
You can often improve efficiency
significantly by keeping the air-fuel ratio 1.3.2 Install automatic air-fuel
optimized. The Measures in this Subsection mixture controls.
optimize the air-fuel ratio, improve air-fuel 1.3.3 Adjust and repair air-fuel ratio controls.
controls, and correct defects in the controls.
RELATED MEASURES
• Subsection 1.2, for methods of measuring
combustion efficiency
• Measure 1.4.4, installing burners that require less
excess air
• Measures 1.9.1 ff, adjustment of fuel oil viscosity
to maintain proper air-fuel ratio

© D. R. Wulfinghoff 1999. All Rights Reserved.


60 1. BOILER PLANT
RATINGS
MEASURE 1.3.1 Optimize the air-fuel ratio. New Facilities Retrofit O&M

B
Air-fuel ratio is by far the most important routine SUMMARY
adjustment that is made to boilers. Of all the adjustments The most important routine adjustment for
that plant operators can make, it has the greatest boilers. Has a major effect on efficiency,
influence on efficiency. Furthermore, failure to set the maintenance, and pollution. The trick is to
air-fuel ratio properly can create serious maintenance
set the air-fuel ratio as close to optimum as
and environmental problems.
possible, while avoiding insufficient air.
If you have automatic combustion controls,
adjusting the air-fuel ratio is easy. Using the methods SELECTION SCORECARD
explained in Measure 1.2.1, measure combustion Savings Potential ...................
efficiency while setting the combustion controls to the
optimum air-fuel ratio. The combustion controls will Rate of Return .......................
then maintain this ratio under all load conditions. Reliability ...............................
Adjusting the air-fuel ratio is not much more difficult
if you have burners that fire at one or more fixed firing Initiation .................................
rates. On the other hand, adjusting modulating burners
can be tedious.
The basic steps are described here. See the burner Efficiency Loss from Incorrect Air-Fuel Ratio
maintenance manual for details of how to adjust your Efficiency suffers from too much air, and from too
particular model of burner. little. Efficiency declines rapidly as the amount of air is
reduced below the point of best efficiency. Efficiency
The Optimum Air-Fuel Ratio declines much more slowly above the point of best
A perfect boiler would use just enough air to burn efficiency. This is because insufficient air and excess
all the fuel completely, with no oxygen left over in the air waste energy in two different ways.
flue gas. (The ratio of air to fuel that achieves this ideal With insufficient air, efficiency falls primarily
result is called a “stoichiometric mixture” by chemists because combustion is incomplete. The incompletely
and advanced boiler people.) With real boilers, burned portion of the fuel is being thrown away through
achieving reasonably complete combustion requires a the flue, taking along its unused energy.
certain amount of air in excess of the stoichiometric ratio. With excess air, the fuel is being burned almost
The excess air is needed to ensure that all the fuel comes completely, but a portion of the combustion energy is
in contact with sufficient oxygen for complete wasted in heating the excess air. The heated excess air
combustion within the flame area. is carried through the boiler as useless baggage. Also,
The minimum amount of excess air that is necessary mixing the combustion gases with excess air lowers the
for clean combustion depends on the type of fuel and temperature of the gases, which reduces heat transfer.
on the type of burner. Table 1 in Measure 1.4.4 lists See the effect in the graph of Figure 1 in Measure 1.2.1.
typical ranges of excess air for different fuels and burner If the amount of excess air is extreme, the large
types. More excess air is needed for fuels that are heavier volume of cool air can quench the combustion process,
and dirtier. Also, burners in smaller equipment tend to causing fuel to be burned incompletely. However, this
have substantially higher excess air requirements. effect does not become significant until efficiency has
Modern, high-efficiency burners minimize the amount already been lowered drastically by the previous effect.
of excess air required. The best modern burners do a
much better job of preparing the fuel for combustion Other Problems Caused by Insufficient Air
and of bringing the proper amount of air into the To repeat, insufficient air wastes much more energy
combustion zone. than an equal percentage of excess air. In addition,
The design of the boiler’s combustion chamber may insufficient air causes these problems:
also affect the excess air requirement. The design of • air pollution. For any hydrocarbon fuel (gas, oil,
the combustion chamber becomes an issue in existing coal, wood, peat, etc.), the end products of complete
boilers if you plan to retrofit a new burner. combustion are carbon dioxide and water, along
Determine the optimum air-fuel ratio for each of with a small amount of additional compounds that
your boilers individually, using the tests recommended may be formed from other substances in the fuel.
below.

ENERGY EFFICIENCY MANUAL


1.3 AIR-FUEL RATIO 61
The combustion process is complex, and includes For example, burning petroleum with insufficient air
a myriad of intermediate organic compounds, produces dense black smoke, while an extreme amount
especially with oil and solid fuels. Many of these of excess air produces dense white smoke.
partially burned combustion products are noxious
compounds that comprise an air pollution problem General Procedure for Adjusting Air-Fuel Ratio
if they escape unburned. If the air-fuel ratio is too Adjusting the air-fuel ratio consists of testing the
low, the chain of combustion reactions is combustion efficiency of the boiler and adjusting the
incomplete, greatly increasing the emission of air-fuel ratio until you find the optimum air-fuel ratio.
pollutants. Measure 1.2.1 gives the details of the tools you need to
• fireside fouling. With insufficient air, some of the measure the air-fuel ratio. In summary, the test sequence
products of incomplete combustion adhere to the is:
heat transfer surfaces in the form of soot. Soot is a • Set the air-fuel ratio by using the oxygen test.
porous material that is mostly carbon, combined • Refine the adjustment by setting carbon monoxide.
with other products of incomplete combustion that As you reduce excess air and get close to the point
tend to be sticky. Its porous nature makes it an of optimum efficiency, the carbon monoxide in the
effective insulator, resisting the flow of heat from flue gas will start to rise rapidly. This rapid increase
the combustion gases to the boiler water. Even occurs at about 200 to 400 parts per million carbon
small amounts of soot can significantly reduce monoxide, with most fuels. Set the air-fuel ratio
efficiency. Soot accumulates rapidly when there is just short of this rapid rise.
too little air for complete combustion. You will not be able to set the carbon monoxide
• explosion hazard. When combustion is incomplete, level properly if there is a defect in the boiler that
the unburned fuel components make the flue gas causes incomplete combustion. In such cases, the
potentially explosive. If the gases reach a part of amount of carbon monoxide remains high near the
the boiler or flue where they can be mixed with optimum air-fuel ratio. In fact, this condition is a
additional air (for example, above an atmospheric reliable indication of trouble. Typical causes of
flue damper), they could explode if ignited. high carbon monoxide are a fouled burner or an
• flame instability. Flame stability can be a problem improper flame pattern that allows the flame to
when pushing the limits of low excess air with contact a combustion chamber surface.
conventional burners. Minimizing excess air can • With dirty fuels, conduct a smoke test. Add air as
produce noticeable pulsations in the flame. This necessary to reduce soot and smoke to acceptable
can become dangerous if the flame is briefly levels. Use a smoke test if the fuels used produce
extinguished and then re-ignites. This problem can too much soot and smoke even at low carbon
occur with some burners even though the amount monoxide concentrations. Dirty fuels require
of air still exceeds the stoichiometric ratio. With additional excess air to burn up combustible
such burners, the most direct solution is to replace material that is embedded in inorganic particles that
them with burners that are designed to operate with are released when the fuel is burned.
low excess air. See Measure 1.4.2 for this Measure. • Repeat the oxygen test and check it with a separate
Insufficient air creates highly visible smoke and it carbon dioxide test. The oxygen test is based on
deposits soot that requires hard work to remove, so boiler some assumptions (spelled out in Measure 1.2.1)
operators tend to avoid insufficient air. They may carry that break down under certain conditions, so it is a
this to the extreme of carrying far too much excess air. good idea to check it with a test of a different type.
If the carbon dioxide test does not correlate to the
Incomplete Combustion Caused by Extreme Excess Air oxygen test, there is something wrong with either
When excess air is carried to an extreme, it cools the test or the boiler. If you find that you cannot
the gases enough to prevent complete combustion. The reduce excess air without producing excessive
amount of excess air that will cause incomplete smoke or carbon monoxide, the problem is probably
combustion depends on the type of fuel, the burner in the boiler. Either the burners need cleaning or
design, and the firebox conditions. The main problems there is an equipment defect in the boiler, the flue,
caused by having too much excess air are inefficiency, or the air delivery system.
air pollution, and fireside fouling. The procedure for adjusting the burner assembly or
The compounds that form in excess air are different the air-fuel controls differs from one unit to another.
from the compounds that form when there is insufficient The only reliable guide is the burner manufacturer’s
air. You can see this easily by observing the smoke. instructions. Follow the instructions exactly.

© D. R. Wulfinghoff 1999. All Rights Reserved.


62 1. BOILER PLANT

air. If the maintenance of the plant is competent and


energetic, it is probably not necessary to add more than
a few percent of excess air to account for these factors.
In plants with less sophisticated controls, and in plants
that are not monitored closely, you may have to widen
the margin of excess air. But don’t overdo it.
Even with automatic air-fuel controls, it may be
desirable to add a small margin of excess air. The
amount depends on the accuracy of the controls. You
will get a feeling for the right amount of excess air from
regular combustion efficiency testing and from
monitoring the trend of fireside fouling.

How to Adjust the Air-Fuel Ratio Mechanically


If you do not have automatic combustion controls,
you need to set the air-fuel ratio by making mechanical
adjustments to the burners or the control linkages. You
need the burner manufacturer’s maintenance manual and
WESINC
the latest service bulletins to show you precisely what
Fig. 1 Atmospheric gas burner The primary air to each
to do. There may be critical adjustments that do not
venturi is adjusted on this furnace by rotating a plate with holes
in it. As you can see, the settings are random, wasting energy seem important from their appearance. If you are not
and increasing air pollution. sure that you have all the information you need, call the
factory. Details matter, so don’t try to fake it.
Also, you should have a combustion efficiency tester
for this job that provides a continuous, instantaneous
readout. (See Measure 1.2.1 for tips on selecting the
equipment.)
It helps to have two persons doing this work,
especially if the burner adjustments are not close to the
point where the flue gas sample is taken for the
combustion efficiency tests. One person stays at the
WESINC
boiler breeching with the test equipment and calls out
Fig. 2 Another atmospheric gas burner On this furnace, the readings, while the other person adjusts the burner.
the primary air for each venturi is adjusted by a disk that moves Try to hold the boiler load as steady as possible
along a threaded rod, providing fine adjustment. during the adjustments. If the burner operates at different
firing rates, you may have to set the air-fuel ratio for
Use a Little Additional Excess Air to Allow for each firing rate at different times, as the load changes.
Changing Conditions If the load on the boiler plant is light, it is practically
You can set the air-fuel ratio with almost perfect impossible to set the fuel-air ratio for high firing rates.
precision by using the methods just described. However, Do not create a load by warming up a cold boiler,
the air-fuel ratio can wander after it is set, from these because this would produce erroneous efficiency
causes: readings and air-fuel settings.
• changes in atmospheric conditions Atmospheric Gas Burners
• imperfect calibration of throttling burners across Most atmospheric gas burners have two sources of
the load range air, “primary” air and “secondary” air. Primary air enters
• wear of mechanical linkages the venturi and mixes with the fuel there. Secondary
• friction in pneumatic actuators air enters around the outside of the burner, and mixes
• fouling of sensors in automatic combustion controls with the flame at the burner.
• burner fouling In packaged boilers where the burner is an integral
part of the boiler, there is usually no adjustment for
• differences in fuel composition between batches
secondary air. In such boilers, setting the air-fuel ratio
• changes in fuel oil or gas pressure involves little more than changing the position of a
• changes in fuel oil temperature. shutter that controls the flow of primary air. Figures 1
With mechanical air-fuel controls, these factors and 2 show two examples.
make it advisable to provide an additional margin of In contrast, generic burners designed for retrofit
excess air to avoid the problems caused by insufficient installations have a separate adjustment for secondary

ENERGY EFFICIENCY MANUAL


1.3 AIR-FUEL RATIO 63
air, and the proper secondary air setting is important in more cams to depress plunger-type fuel valves. Figure 3
such installations. See Measure 1.4.2 for more about shows a typical jackshaft arrangement for a dual-fuel
atmospheric burners. boiler, and Figure 4 shows a detail of a typical cam.
You may find that the primary air setting has little The air-fuel linkages are normally adjusted at the
effect on boiler efficiency or on the excess air factory, with little provision to make it easy to adjust
requirement. But, the primary air setting may seriously them in the field. For example, the typical fuel
affect the carbon monoxide concentration in the flue adjustment cam has a shape that is set by adjusting a
gas. Therefore, test for carbon monoxide when setting large number of screws. This makes it tedious to adjust
atmospheric burners. the air-fuel ratio.
Modulating Burners
Modulating burners with mechanical air-fuel
controls typically have a single control motor that moves
in response to the boiler’s output pressure or temperature.
The control motor has a linkage connected to an air
control, which typically is a damper. The motor also
has linkage to the fuel control, which is a valve of some
kind. If the burner can burn more than one type of fuel,
there is a separate linkage for each type of fuel.
The control linkages are non-linear, which means
that a certain amount of motion in the air control linkage
does not produce the same relative change as the motion
in the fuel linkage. To compensate for this, the fuel
linkage typically has an adjustable cam, which makes
the fuel flow proportional to the air flow.
Boilers with mechanically modulating burners
commonly link the air and fuel controls with a common
shaft, called a “jackshaft.” The load control motor drives
the jackshaft. The jackshaft typically has an arm that
drives a linkage to the air damper, and it has one or

WESINC
Fig. 3 Typical jackshaft air-fuel control The jackshaft is
mounted horizontally, moved by the control motor on the upper WESINC
left. A cam on the left end of the jackshaft controls a fuel oil Fig. 4 Typical cam on jackshaft air-fuel linkage The shape
valve, and a cam on the right end of the shaft controls a gas of the cam determines the air-fuel ratio at all boiler loads. The
valve. An arm to the left of the shaft’s center support moves shape can be adjusted by turning the screws that you see
the combustion air damper. The air-fuel ratio depends on the between the cam body and the curved spring that rides on the
relative positions of these mechanical linkages. plunger. This is a tedious job.

© D. R. Wulfinghoff 1999. All Rights Reserved.


64 1. BOILER PLANT

The procedure consists of holding the firing rate


steady, measuring the efficiency, performing the pressure-fired boiler burning a variety of fuels may have
necessary adjustment to the air-fuel ratio, and repeating a noticeable drift in air-fuel ratio over a period of days
the sequence until the point of best efficiency is found. or weeks.
Then, repeat this process for the next increment of load.
The number of adjustments depends on the design of Adjust Flue Draft First
the mechanism that controls air and fuel. With a variable Adjust the flue draft before you set the air-fuel ratio.
cam, you have to change the boiler loading in small The principles of flue draft and the methods of adjusting
increments that allow you to set each of the adjustment it are explained in Measure 1.5.3.
screws. Regardless of the linkage design, make the ECONOMICS
adjustments at sufficiently close intervals to keep the
boiler efficient at all loads. SAVINGS POTENTIAL: 1 to 10 percent of fuel cost,
typically.
It may be difficult to hold the boiler output steady
at each percentage of load as you make the adjustments. COST: The cost of efficiency test equipment is covered
If you have more than one boiler, you can shift the load in Measure 1.2.1. The amount of labor required to set
between boilers by changing the relative pressure or air-fuel ratio can be less than one man-hour for a boiler
temperature settings of the boilers. You can use three with a single-stage burner, to several man-days for a
people for this job. One adjusts the boiler load, another boiler with throttling burners and difficulty in maintaining
performs the combustion efficiency tests and calls out a steady load.
the readings, and the third adjusts the air-fuel controls. PAYBACK PERIOD: Immediate, to one year.
After you go through this exercise, you will
understand the advantages of combustion air “trim” TRAPS & TRICKS
systems, which adjust the air-fuel ratio automatically SKILLS: Adjusting air-fuel ratio requires two skills,
and continuously. See Measure 1.3.2 for details. efficiency testing and setting the boiler’s air-fuel controls.
How Often Should You Adjust the Air-Fuel See Measure 1.2.4 about the former. Make sure that
Ratio? the person adjusting the boiler knows how to do it
Inspect the air-fuel ratio on a periodic basis. With correctly.
mechanical air-fuel controls, the ratio drifts because of TEST EQUIPMENT: The right test equipment makes
the factors discussed previously. You need less excess the work much easier. See Measure 1.2.1 about
air as a safety factor if you test and adjust the air-fuel selecting test equipment.
ratio more often. BOILER CONDITION: You can’t set the air-fuel ratio
The appropriate interval between settings depends properly if the boiler’s controls are sloppy or defective.
on the type of boiler and the type of fuel. A simple gas- See Measure 1.3.3 about maintenance.
fired boiler with atmospheric burners may hold its
SCHEDULING: Repeat the procedure periodically.
efficiency for years without adjustment and with
Make sure that you have an effective method of
minimal maintenance. On the other hand, a large
scheduling it.

ENERGY EFFICIENCY MANUAL


1.3 AIR-FUEL RATIO 65
RATINGS
MEASURE 1.3.2 Install automatic air-fuel New Facilities Retrofit O&M

mixture controls.
A C
Automatic air-fuel controls provide the ultimate in SUMMARY
efficiency by continuously monitoring the flue gas
Keeps the air-fuel ratio optimum. Available
composition and readjusting the air-fuel ratio. These
controls are common on larger boilers. You can retrofit with a wide range of features and prices.
them to existing boilers. Economical for larger boilers. May not be
Environmental regulation of boiler operation has worth the additional maintenance and failure
expanded enormously in recent years, and continues to modes in smaller boilers.
expand. If you decide to install automatic air-fuel SELECTION SCORECARD
controls, consider the effect of regulation on the
Savings Potential ...................
capabilities that the controls should have. Try to satisfy
foreseeable environmental regulations as well as Rate of Return, New Facilities
maximizing efficiency.
Rate of Return, Retrofit .........
The simplest type of automatic air-fuel control is
an “oxygen trim” system. Oxygen trim systems typically Reliability ...............................
sense only oxygen in the flue gases. The output of the Ease of Retrofit ......................
oxygen trim system is a small adjustment in the air-fuel
ratio to move the measured oxygen content in the desired
direction. Figure 1 shows the control box for a typical Potential Savings
oxygen trim system. The improvement in efficiency that you can expect
At the other extreme are complex air-fuel control from automatic air-fuel control system varies widely
systems for large boilers that measure a variety of flue from one boiler plant to another. As an example, a boiler
gases and combustion conditions. Virtually all of these burning heavy oil might have an optimum excess air of
use flue gas oxygen as the primary measurement. They 15%. In this boiler, increasing the excess air to 30%
may also sense carbon monoxide, nitrogen oxides, other would cause an efficiency loss of one percent. In some
gases, and smoke. Such systems provide accurate plants, excess air may drift from 15% to 30% under
control of boiler output, precise control of air-fuel ratio, realistic operating conditions. Therefore, you may be
and control of various functions related to plant able to save about one percent of fuel energy percent in
emissions, such as stack gas recirculation and scrubbing. such a plant. In plants where maintenance has been
neglected, the saving may be as high as several percent
of the fuel input.
On the other hand, a well maintained boiler that
burns natural gas of stable characteristics may benefit
little from automatic air-fuel adjustment. In this case, a
simple mechanical linkage that regulates the air-fuel
ratio may keep efficiency optimized within close
tolerances. With such a boiler, the efficiency
improvement would typically be only a fraction of one
percent.
Take the claims of efficiency improvements made
by combustion control manufacturers with a grain of
salt. Before-and-after comparisons, even if they are
monitored by a disinterested party, may be misleading.
Much of the improvement that is measured when a trim
system is installed may actually result from the cleaning
and tune-up that occurs along with the installation.

Most Favorable Applications


Larger boilers are candidates for automatic air-fuel
controls because small differences in efficiency can
Cleaver-Brooks
produce large differences in absolute energy
Fig. 1 Oxygen trim control consumption. For example, a boiler that produces 100

© D. R. Wulfinghoff 1999. All Rights Reserved.


66 1. BOILER PLANT

million BTU’s per hour of steam for 3,000 hours per provides a reliable average flue gas temperature.
year while burning heavy oil at $1.00 per gallon has an Be careful to prevent outside air from mixing with
annual fuel cost of approximately $2,500,000. the flue gas sample. See Measure 1.2.1 for more
Improving efficiency by one half of one percent would about this.
save approximately $12,000 per year. • analysis hardware and logic circuitry. This usually
An automatic air-fuel control system is more comes in a single box. If the sensor output is
valuable if the factors that affect the air-fuel ratio are electrical (for example, from a zirconium oxide
subject to change. Some of the conditions that can cause oxygen sensor), the box can be installed almost
the air-fuel ratio to drift are listed in Measure 1.3.1, anywhere. If gas samples are conveyed to the box
above. through tubing, install the box within a specified
Boilers that burn solid fuels or heavy oils need to distance from the sampling point.
adjust the air-fuel ratio continually to account for • displays. You should install gauges or recorders
changes in fuel characteristics, such as the content of that display gas content, efficiency, etc. Install them
carbon, hydrogen, oxygen, sulfur, moisture, and dirt. where they are mostly likely to be monitored by
With coal, these factors can change as fuel is brought in the operators.
from different parts of the coal pile. With oil, they can • actuators. Actuators translate the output signal of
change as different strata of oil are tapped from the tanks. the combustion control system to motion of the fuel
Automatic air-fuel controls correct for drift, valves and air dampers. Retrofitting actuators on a
hysteresis, and non-linearity in control linkages. For preexisting control system can be challenging,
example, where pneumatic actuators are used to control unless the retrofit system is custom designed for
the fuel valves and/or fan dampers, friction in the the particular boiler.
actuators and linkages can cause errors in the air-fuel With boilers that use a common mechanical linkage
ratio. Linkage geometry in modulating burners is to control both air and fuel, the usual practice is to
typically non-linear, and requires tedious adjustments insert a variable-length link in a part of the original
of cams to compensate. Automatic controls can eliminate linkage that controls either the air or the fuel. The
the need to adjust for these factors. trim system works by controlling the length of the
variable link.
Staff Skill and Control Reliability Larger boilers typically use pneumatic, electric
To a certain extent, automatic air-fuel controls can analog, or digital signals to control the motion of
compensate for deficient maintenance. In particular, it separate actuators on the fuel valve and fan control.
can compensate for lack of tuning and for looseness in With such controls, you have to match the output
the controls. However, automatic combustion controls signals of the combustion control system with the
are not a proper substitute for skills, salary, and signals needed by the actuators. For example, if
supervision. Installing a complex control system in an the original controls move the fuel and air actuators
environment with poor maintenance trades continuing with 3-to-15 PSI air pressure, the trim system must
poor efficiency for the possibility of much worse have pneumatic outputs in this range. Alternatively,
efficiency if the control system fails. you can change the actuators.
By the same token, you need controls that are • failure alarms. To repeat, the control system should
especially reliable in plants that are not continuously test itself continuously. If a failure occurs, or if the
monitored by skilled operators. This situation is air-fuel ratio gets out of the designated range, the
common in non-industrial facilities, where the boiler controls should indicate an alarm. Make the alarm
plant is often treated as an inscrutable nuisance. able to get attention, in a manner appropriate to the
Any automatic combustion control should staffing. For example, if the boiler plant is not
continuously self-test, and it should sound an alarm if it staffed continuously, have the alarm trigger a loud
senses failure or an out-of-range condition. horn, or automatically dial the telephone of the
appropriate manager, or whatever is needed to
System Components and Installation Issues initiate immediate repairs.
Automatic air-fuel mixture controls vary in
complexity, control accuracy, and versatility. Their How to Select Air-Fuel Controls
performance depends on their installation as well as their Air-fuel control systems differ widely in cost and
components. These are the basic components, and some in the range of features that they offer. Here are the
important issues to consider in installing them: main features to consider when shopping for a system.
• flue gas probe(s) or sensor(s). The mechanics of What is Sensed
installing sensors is usually easy. Be sure that the Sensing the oxygen content of the flue gas provides
location where you install the sensor(s) provides a the most direct and accurate indication of combustion
representative sampling of flue gases, and that it

ENERGY EFFICIENCY MANUAL


1.3 AIR-FUEL RATIO 67
efficiency. The least sophisticated combustion air trim by the gas. This is done with polarizing filters
systems measure only oxygen, and these systems are similar to polarized sunglasses.
called “oxygen trim” systems. Unburned combustibles can be measured directly
More sophisticated combustion air trim systems with catalytic units that work by burning up the
adjust the oxygen concentration by sensing unburned combustibles and measuring the heat produced. In order
combustibles. These systems typically sense carbon for this type of sensor to work, there must be some
monoxide as an indicator of unburned combustibles. oxygen in the flue gas. Unburned combustibles can also
Carbon monoxide plays this role because it is the second be measured with flame ionization detectors.
from the last combustion product in the long chain of Smoke opacity, which may indicate both
reactions by which the carbon in petroleum or other combustible and non-combustible particulate matter, is
complex fuels is converted to carbon dioxide. Hydrogen usually sensed by measuring the absorption of a beam
is sometimes used as an indicator of unburned of light in the flue.
combustibles, but this practice is limited to specialized Flue gases that are not directly related to combustion
applications. efficiency, such as nitrogen and sulfur oxides, are
Smoke density, or opacity, is commonly used as a measured with a variety of technologies. For example,
separate indicator of unburned combustibles when oxides of nitrogen can be sensed by chemiluminescence,
burning dirty fuels, like heavy oil or coal. A separate which is the emission of certain wavelengths of light
indicator is desirable because carbon monoxide does when nitrogen oxides undergo specific chemical
not correlate well to the concentration of large unburned reactions. Sulfur oxides and chlorine can be detected
particulate matter in the flue gases. Monitoring smoke with polarized light sensing. And so forth.
opacity is necessary in its own right because visible With some types of sensors, one type of gas may
smoke may be an environmental or public relations issue. register as another. For example, hydrogen and
Still another approach is measuring total unburned hydrogen sulfide register as carbon monoxide on some
combustibles, using one of the sensor types described electrochemical carbon monoxide sensors. Guard
below. At the present time, this approach is uncommon against such cross readings if the flue gases contain large
in smaller boilers. concentrations of combustion products other than carbon
The combustion air trim system may also have to dioxide and water vapor.
control other gases not directly related to efficiency. Sensor technology is a rich and growing field.
Environmental laws restrict emission of nitrogen oxides Check the latest offerings when selecting a system. The
and sulfur oxides from larger boilers. Specialized best types for air-fuel control will probably change with
boilers, such as refuse burners, may have to control other time as existing sensor types evolve and new types are
flue gas constituents, such as chlorine and mercury. Such discovered.
gases are controlled by boiler design and by the addition Sensor Calibration
of specialized equipment, such as flue gas scrubbers and
flue gas recirculators. The operation of such equipment The sensors used in combustion air controls are
affects combustion air control. exposed continuously to the harsh environment of the
flue. This causes the output of the sensors to drift. If
Sensor Types not corrected, sensor drift causes serious inaccuracy in
Oxygen is commonly measured with a zirconium control. The only solution to drift is recalibrating the
oxide sensor. This is a solid state device that develops a sensors at appropriate intervals. Some types of sensors
voltage in response to a difference in oxygen can be recalibrated with the boiler in operation, and
concentration across two sides. others cannot be. Sensor accuracy is important, so get
Carbon monoxide is measured with a variety of sensors that can be recalibrated while the boiler is
devices, including: operating.
• electrochemical cells, which produce electric Even if the sensors can be calibrated during boiler
current when carbon monoxide is involved in operation, you may have to manually initiate a
specific chemical reactions calibration cycle. This has the disadvantage that the
• infrared absorption detectors, which send a beam procedure can be neglected, but it has the advantage of
of infrared light through the flue gas. The light is reminding operators of the need for checking the
tuned to an oscillation frequency of the carbon condition of sensors. Automatic recalibration cannot
monoxide molecule, which causes carbon repair a sensor that becomes defective.
monoxide to absorb and scatter the light. Oxygen sensors have the important advantage that
• polarization detectors, which function by sending they can be calibrated using ambient air. The atmosphere
a beam of polarized light through the flue gas, and contains a fixed percentage of oxygen, so the sensor
measuring rotation of the direction of polarization can be calibrated by diverting boiler room air into the
sensor while it remains in place. Most zirconium oxide

© D. R. Wulfinghoff 1999. All Rights Reserved.


68 1. BOILER PLANT

sensors used in combustion control systems include this and the fuel valve are connected by a common
feature. mechanical linkage. This type of fail-safe limit is not
Carbon monoxide sensors that use the principles of possible with control systems in which the air and fuel
infrared absorption or polarization can be calibrated are controlled separately by pneumatic, electrical, or
continuously by using reference beams of light. Sensors electronic signals.
that use electrochemical cells must be recalibrated Alarms
periodically by passing calibration gases through the The controls should have effective alarms to alert
sensor. operators of any undesirable condition, especially a
Instruments that need calibration gases require you failure of the combustion control system or an excess
to keep a stock of the appropriate gases on hand. Also, of undesirable gases in the flue.
using calibration gases requires more skill.
Displays and Data Logging
Smoke opacity sensors can be recalibrated
The control system should include convenient
continuously by using a reference light beam.
displays of all the measurements being taken, such as
Sensors for gases that are not directly related to percentage of gas concentration and flue temperature.
combustion efficiency operate on a variety of principles. If you can afford it, get data logging equipment to record
Some of them can be continuously recalibrated, and and analyze long-term trends in the measurements.
some cannot be.
Some systems display derived values, such as
Ability to Change the Air-Fuel Ratio with Load percent efficiency and boiler load. Understand which
The simplest oxygen trim systems establish a outputs are being measured directly, and which are
constant percentage of oxygen at all boiler loads. A derived. For example, percent carbon dioxide may be
constant oxygen percentage is less than optimum calculated from the measured percent oxygen and the
because it allows the percentage of unburned fuel flue temperature. Such a derived value is dubious and
products to rise at lower loads. (This occurs because can be misleading. Boiler load indications may be
the combustion zone is smaller and cooler at low loads, derived from stack temperature. Such a load indication
requiring more oxygen to ensure complete combustion.) is only approximate, because other factors can affect
The appropriate variation in oxygen content with flue temperature.
load depends on the fuel and the boiler design. For this The output of the combustion control system must
reason, most oxygen trim systems include provision to be matched to the input of the recording and analysis
manually adjust the amount of excess oxygen at different equipment. There are a variety of signal conventions,
boiler loads. This is called “characterization” of the such as 4-to-20 milliamperes or 0-to-100 millivolts. If
controls. Do it when the controls are installed, and when the combustion control system includes integral data
sensor elements are replaced. logging, you don’t have to worry about this.
More sophisticated combustion air trim systems Actuator Connections
eliminate the need for manual characterization of excess It can be tricky to make the mechanical connections
air by sensing unburned fuel components in addition to to the existing air-fuel control system. Select a system
sensing oxygen. Even so, complex systems may still that makes this job as easy as possible.
have a manual characterization capability to allow for
control of smoke or environmental pollutants. PID Control Characteristics
It is difficult to maintain control of the air-fuel ratio
Multi-Fuel Capability
when the boiler load fluctuates rapidly, as occurs in many
In boilers that burn more than one type of fuel, applications. To achieve accurate tracking, sophisticated
account for the fact that the optimum air-fuel ratio differs control systems have special features to reduce error,
from one fuel to another. Heavier and dirtier fuels eliminate overshoot, and prevent oscillations. These are
require more excess air than gaseous or light fuels. usually called “proportional-integral-derivative” (PID)
Therefore, get automatic air-fuel controls that provide control characteristics. See Reference Note 37, Control
separate characterization for each fuel burned. Characteristics, for details.
Failure Modes and Overrides
Combustion controls will fail occasionally. For this ECONOMICS
reason, the system should have a reliable self-test feature,
and it should respond to failures by reverting to a fail- SAVINGS POTENTIAL: 0.2 to 3 percent of fuel
safe setting. Typically, the fail-safe setting is a fixed consumption.
percentage of excess oxygen. COST: A simple oxygen trim system for a boiler that
A particularly reliable method of fail-safe control uses a mechanical linkage for control of air-fuel ratio
is to have mechanical stops in the control linkages so may cost less than $10,000. Installing a complex state-
that high and low limits in the air-fuel ratio cannot be of-the-art control system for a large boiler may cost
exceeded. Such stops are possible only if the air damper several hundred thousand dollars.

ENERGY EFFICIENCY MANUAL


1.3 AIR-FUEL RATIO 69
PAYBACK PERIOD: Several years or longer. INSTALLATION: Follow installation instructions
precisely. The details matter.
TRAPS & TRICKS MAINTENANCE: Be prepared to perform repetitive
SELECTING THE EQUIPMENT: Get equipment that is maintenance, such as replacing sensors. This requires
well proven. Be sure to match the features of the control effective training and supervision. Alternatively, arrange
system to the characteristics of your boilers. for maintenance to be done by the manufacturer or a
qualified service representative. Schedule periodic tests
of the equipment.

RATINGS
MEASURE 1.3.3 Adjust and repair air-fuel New Facilities Retrofit O&M

ratio controls.
A
The air-fuel control system needs maintenance on SUMMARY
a regular basis. The mechanical components that control Basic maintenance that keeps the air-fuel
air and fuel are continually moving in response to load
controls working properly.
changes. Something as simple as a loose connection
can cause a major error in the air-fuel ratio. Combustion SELECTION SCORECARD
control systems have sensors that are exposed to hot Savings Potential ...................
flue gases, so they require periodic calibration and
replacement. Rate of Return .......................
Reliability ...............................
Looseness in Mechanical Linkages
The air and fuel controls of most boilers have some Ease of Initiation ....................
mechanical linkages. Most small and medium sized
boilers control the air-fuel ratio entirely with mechanical such as slotted sheetmetal control arms, are unbelievably
linkages, which may include a rotating shaft, one or more flimsy. Linkages are often adjusted with ordinary nuts,
bellcranks, pushrods, and an adjustable cam. These which are virtually certain to work loose in time.
linkages are simple, accessible, and easy to understand. Improve such features wherever you can. For example,
Figure 1 shows a typical example. if your linkages have slotted control arms, install friction
This is fortunate, because the adjustment of the washers on each side of the slot, and use an all-metal
linkages is critical. Even a small amount of play may stop nut.
cause significant inefficiency because fuel and air
controls typically have a small range of movement. Fuel
valves are usually the most sensitive element. For
example, movement of a millimeter in a plunger-type
fuel valve may cause a significant change in fuel flow.
Air-fuel linkages have a number of wear points and
opportunities for components to come loose. To discover
play in a control linkage, hold one end of the linkage in
a fixed position. Then, grasp the linkage at various
places and attempt to move it while feeling for looseness.
Inspect each bearing and joint in the linkage as you do
this. If there is enough play in the linkage to allow any
significant amount of motion, repair the linkage or
tighten it. Replace all worn components.
Industrial Combustion
Unfortunately, many burners have air-fuel linkages Fig. 1 Typical dual-fuel burner assembly All the linkages
made of cheap stamped parts, so they are vulnerable to that control the air-fuel ratio of this burner are easily accessible
wear and working loose. Some common components, for inspection, adjustment, and repair.

© D. R. Wulfinghoff 1999. All Rights Reserved.


70 1. BOILER PLANT

Mechanical Components of Combustion Air More sophisticated combustion control systems


Trim Controls operate by sensing other flue gases in addition to oxygen,
In air-fuel controls that have combustion air trim such as carbon monoxide. Sensors for other gases
systems (covered in Measure 1.3.2), the trim system can typically require frequent replacement. Also, calibration
compensate for wear in the mechanical components up of the sensors may require more elaborate procedures
to a point. But don’t rely on this. When the movement than for calibrating oxygen sensors. Some types of
of the linkage reverses direction, the slack in the control sensors require calibration gases for recalibration. These
linkage must be taken up in the reverse direction to get are gases that have a known percentage of the type of
the air-fuel ratio back within limits. Such control gas that is being measured in the flue.
reversals may occur frequently, and the hammering that Test, maintain, and calibrate sensors using the
they produce in the linkage aggravates the looseness. manufacturer’s procedures. Calibrate often enough to
Beyond a certain point, looseness in the control system avoid substantial drift in control accuracy.
can trigger major control oscillations so that the air-fuel
ratio never stabilizes. For this reason, keep your Upgrading
combustion control systems just as tight as mechanical The technology of air-fuel controls has been
air-fuel controls. advancing rapidly. Newer equipment may be
significantly superior to older combustion control
Sensors in Combustion Control Systems installations, justifying upgrading. See Measure 1.3.2
Combustion control systems continuously readjust for the features of newer equipment.
the air-fuel ratio by sensing the combustion products in
the flue gases. When they function properly, automatic ECONOMICS
combustion controls provide the ultimate in efficiency.
However, their accuracy depends on proper operation SAVINGS POTENTIAL: Up to 10 percent of fuel cost,
and calibration of their gas sensors and associated in extreme cases. The potential for savings is
circuitry. proportional to the opportunity for error in the air-fuel
controls.
The combustion gas sensors are the most vulnerable
element of automatic air-fuel control systems. Most COST: Minor. The cost of efficiency testing to re-adjust
combustion control systems operate by sensing oxygen the air-fuel ratio is covered in Measure 1.3.1.
with a zirconium oxide element. Zirconium oxide PAYBACK PERIOD: Immediate.
elements are more tolerant of the flue environment than
other types of sensors, but they eventually foul. The TRAPS & TRICKS
sensor typically must be replaced every year or two. SKILLS: Basic repair of loose linkages is easy. However,
Between replacements, the sensor and associated you have to recalibrate mechanical air-fuel controls after
instrumentation require periodic recalibration. This may you repair them. See Measure 1.3.1 for details.
be done automatically by the control system, or an
operator may have to initiate a recalibration cycle. SCHEDULING: This activity needs to be repeated
Oxygen sensors typically are recalibrated with ambient periodically. Include this in your maintenance scheduling
air, which contains a known quantity of oxygen. system.

ENERGY EFFICIENCY MANUAL

You might also like