Professional Documents
Culture Documents
L-545 Servicemans Manual
L-545 Servicemans Manual
L-545 Servicemans Manual
Serviceman’s
Manual
The LP-Gas
Serviceman’s Manual
RegO®, has prepared this LP-Gas Serviceman’s
Manual for use by installation servicemen and others
requiring a handy reference for field service work.
It deals with subjects that can be useful to field
servicemen striving for greater efficiency and safer
installations. For the more technical problems and
theories, the many texts and manuals concerning the
particular subject should be consulted.
This manual is not intended to conflict with federal,
state, or local ordinances and regulations. These
should be observed at all times.
1
Contents
2
Information About LP-Gas*
Propane Butane
Formula C H C H 3 8 4 10
*Conversion Formula:
Degrees C = (ºF - 32) X 5/9
Degrees F = 9/5 X ºC + 32
4
Installation Planning
6
100 LB. Cylinders
How Many Are Required
“Rule of Thumb” Guide for
Installing 100 Lb. Cylinders
For continuous draws where temperatures may reach
0ºF. Assume the vaporization rate of a 100 lb. cylinder
as approximately 50,000 BTU per hour.
Number of cylinders per side = Total load in BTU
50,000
Example:
Assume total load = 200,000 BTU/hr.
Cylinders per side = 200,000 = 4 cylinders per side
50,000
8
Proper Purging of LP-Gas Containers
The Importance of Purging
A very important step which must not be overlooked by LP-Gas
distributors is the importance of properly purging new LP-Gas
containers. Attention to this important procedure will promote
customer satisfaction and greatly reduce service calls on new
installations. Consider the following:
• Both ASME and DOT specifications require hydrostatic
testing of vessels after fabrication. This is usually done with
water.
• Before charging with propane, the vessel will contain the
normal amount of air.
Both water and air are contaminants
They seriously interfere with proper operation of the system and
the connected appliances. If not removed, they will result in costly
service calls and needless expense far exceeding the nominal cost
of proper purging.
Neutralizing Moisture
Even if a careful inspection (using a flashlight) reveals no visible
moisture, the container must still be neutralized, since dew may
have formed on the walls; additionally, the contained air may have
relative humidity up to 100%.
A rule of thumb for neutralizing moisture in an ASME container
calls for the introduction of at least one pint of genuine absolute
anhydrous methanol* (99.85% pure) for each 100 gal. of water
capacity of the container. On this basis, the minimum volumes for
typical containers would be as shown below:
Minimum Volume
Container Type Methanol Required
{
30 Lb. Pressure Gauge (RegO®
Gauge Adapter No. 2411)
Assembly 1/4” Elbow
POL Connection (RegO® No. 970
13
14
Location of DOT Cylinders
From NFPA 58, Appendix I
Federal, state, and local ordinances and regulations should be observed at all times.
Notes:
1) 5-ft minimum from relief valve in any direction away from exterior source if ignition, openings into direct-vent gas appliances, or mechanical ventilation air intakes.
2) If the cylinder is filled on site from a bulk truck, the filling connection and vent valve must be at least 10 ft from any exterior source of ignition, openings into
direct–vent gas appliances, or mechanical ventilation air intakes.
3) Cylinders installed along side buildings the relief valve discharge must be:
(a) At least 3 ft horizontally away from any building openings that is below level of the relief valve discharge.
(b) For cylinders not filled on site the relief valve discharge must be at least 5 ft from any exterior source of ignition, openings into direct–vent gas appliances, or
mechanical ventilation air intakes.
Reprinted with permission from NFPA 58-2004, Liquefied Petroleum Gas Code, Copyright © 2004, National Fire Protection Association, Quincy, MA 02269.
This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.
Location of Federal, state, and local ordinances and regulations
should be observed at all times.
ASME Containers
From NFPA 58, Appendix I
15
Pipe And Tubing Selection
Use the following simple method to assure the selection
of the correct sizes of piping and tubing for LP-Gas
vapor systems. Piping between the first and second stage
is considered, as well as lower pressure (2 PSIG) piping
between the 2 PSIG second stage or integral twin stage
regulator and the line pressure regulator; and low pressure
(inches of water column) piping between second stage,
single stage, or integral twin stage regulators and appliances.
The information supplied below is from NFPA 54 (National
Fuel Gas Code) Appendix C, and NFPA 58 (Liquefied
Petroleum Gas Code) Chapter 15; it can also be found in
CETP (Certified Employee Training Program) published
by the Propane Education and Research Council “Selecting
Piping and Tubing” module 4.1.8. These illustrations are
for demonstrative purposes, they are not intended for actual
system design.
Instructions:
1. Determine the total gas demand for the system by adding
up the BTU/hr input from the appliance nameplates and
adding demand as appropriate for future appliances.
2. For second stage or integral twin stage piping:
A. Measure length of piping required from outlet of
regulator to the appliance furthest away. No other length
is necessary to do the sizing.
B. Make a simple sketch of the piping, as shown.
C. Determine the capacity to be handled by each section of
piping. For example, the capacity of the line between a
and b must handle the total demand of appliances A, B,
and
C; the capacity of the line from c to d must handle only
appliance B, etc.
16
Pipe And Tubing Selection
D. Using Table 3 select proper size of tubing or pipe for
each section of piping, using values in BTU/hr for the
length determined from step #2-A. If exact length is
not on chart, use next longer length. Do not use any
other length for this purpose! Simply select the size
that shows at least as much capacity as needed for
each piping section.
3. For piping between first and second stage regulators
A. For a simple system with only one second stage regula-
tor, merely measure length of piping required between
outlet of first stage regulator and inlet of second stage
regulator. Select piping or tubing required from Table
1.
B. For systems with multiple second stage regulators,
measure length of piping required to reach the second
stage regulator that is furthest away. Make a simple
sketch, and size each leg of piping using Table 1, 2,
or 3 using values shown in column corresponding to
the length as measured above, same as when handling
second stage piping.
17
Pipe And Tubing Selection
Example 1.
Determine the sizes of piping or tubing required for the
twin-stage LP-Gas installation shown.
18
Pipe And Tubing Selection
Example 2.
Determine the sizes of piping or tubing required for the
two-stage LP-Gas installation shown.
Total first stage piping length = 26 feet; first stage regulator set-
ting is 10psig (use Table 1 or 2 @ 30 feet)
From aa to a, demand = 338,000 BTU/hr; use 1/2” pipe, 1/2” tub-
ing, or 1/2” T plastic pipe.
Total second stage piping length = 58 feet (use Table 3 @ 60 feet)
From a to b, demand = 338,000 BTU/hr; use 1” pipe
From b to c, demand = 138,000 BTU/hr; use 3/4” pipe or 7/8” tub-
ing
From c to d, demand = 100,000 BTU/hr; use 1/2” pipe or 3/4” tubing
From d to e, demand = 35,000 BTU/hr; use 1/2” pipe or 1/2” tubing
From b to f, demand = 200,000 BTU/hr; use 3/4” pipe or 7/8” tub-
ing
From c to g, demand = 38,000 BTU/hr; use 1/2” pipe or 1/2” tubing
From d to h, demand = 65,000 BTU/hr; use 1/2” pipe or 5/8” tubing
19
Pipe And Tubing Selection
Example 3
Determine the sizes of piping or tubing required for the 2
PSI LP-Gas installation shown.
Total first stage piping length = 26 feet; first stage regulator set-
ting is 10psig (use Table 1 or 2 @ 30 feet)
Total 2 PSI Piping Length = 19 ft. (use Table 4 @ 20 ft. or Table
6 @ 20 ft.)
From aa to a, demand = 338,000 BTU
use 3/8” CSST or 1/2” copper tubing or 1/2” pipe
From Regulator a to each appliance:
From a to b, demand = 65,000 BTU; length = 25 ft. (Table 5),
use 1/2” CSST
From a to c, demand = 200,000 BTU; length = 30 ft. (Table 5)
use 3/4” CSST
From a to d, demand = 38,000 BTU; length = 21 ft.* (Table 5)
use 3/8” CSST *use 25 ft. column
From a to e, demand = 35,000 BTU; length = 40 ft. (Table 5)
use 1/2” CSST
20
Table 1 – First Stage Pipe Sizing (Between First and Second Stage Regulators)
10 PSIG Inlet with a 1 PSIG Pressure Drop
Maximum capacity of pipe or tubing, in thousands of BTU/hr or LP-Gas
Length of Pipe or Tubing, Feet
Size of Pipe or Copper
Tubing, Inches 10 20 30 40 50 60 70 80 90 100
⅜” 558 383 309 265 235 213 196 182 171 161
½” 1387 870 700 599 531 481 443 412 386 365
Copper ⅝” 2360 1622 1303 1115 988 896 824 767 719 679
Tubing ¾” 3993 2475 2205 1887 1672 1515 1394 1297 1217 1149
½” 3339 2295 1843 1577 1398 1267 1165 1084 1017 961
(O.D.)
¾” 6982 4799 3854 3298 2923 2649 2437 2267 2127 2009
1” 13153 9040 7259 6213 5507 4989 4590 4270 4007 3785
Pipe Size 1¼” 27004 18560 14904 12756 11306 10244 9424 8767 8226 7770
1½” 40461 27809 22331 19113 16939 15348 14120 13136 12325 11642
2” 77924 53556 43008 36809 32623 29559 27194 25299 23737 22422
Length of Pipe or Tubing, Feet
Size of Pipe or Copper
Tubing, Inches 125 150 175 200 225 250 275 300 350 400
⅜” 142 130 118 111 104 90 89 89 82 76
½” 323 293 269 251 235 222 211 201 185 172
Copper ⅝” 601 546 502 467 438 414 393 375 345 321
Tubing ¾” 1018 923 843 790 740 700 664 634 584 543
½” 852 772 710 660 619 585 556 530 488 454
(O.D.)
¾” 1780 1613 1484 1381 1296 1224 1162 1109 1020 949
1” 3354 3039 2796 2601 2441 2305 2190 2089 1922 1788
Pipe Size 1¼” 6887 6240 5741 5340 5011 4733 4495 4289 3945 3670
1½” 10318 9349 8601 8002 7508 7092 6735 6426 5911 5499
2” 19871 18005 16564 15410 14459 13658 12971 12375 11385 10591
* Total length of piping from outlet of first stage regulator to inlet of second state regulator (or to inlet of second stage regulator furthest away).
Notes: 1) To allow 2 PSIG pressure drop, multiply total gas demand by .707, and use capacities from table.
2) For different first stage pressures, multiply total gas demand by the following factors, and use capacities from table.
Ex: 1,000,000 BTU load at 5 PSI: 1,000,000 (1.12) = 1,200,000 BTU then use chart bases on 1,200,000 BTU
First Stage Pressure PSIG Multiply By
20 .844
15 .912
5 1.120 Data Calculated per NFPA #54 & 58
21
22
Table 2 – First Stage Plastic Tubing Sizing
10 PSIG Inlet with a 1 PSIG Pressure Drop
Maximum capacity of plastic tubing in thousands of BTU/hr of LP-Gas
Size of Plastic Tubing Length of Tubing, Feet*
NPS SDR 10 20 30 40 50 60 70 80 90 100
½ CTS 7.00 1387 954 762 653 578 524 482 448 421 397
½ 9.33 3901 2681 2143 1835 1626 1473 1355 1261 1183 1117
¾ 11.00 7811 5369 4292 3673 3256 2950 2714 2525 2369 2238
1 CTS 11.00 9510 6536 5225 4472 3864 3591 3304 3074 2884 2724
1 11.00 14094 9687 7744 6628 5874 5322 4896 4555 4274 4037
1¼ 10.00 24416 16781 13416 11482 10106 9220 8433 7891 7404 6994
1½ 11.00 - - 20260 17340 15368 13924 12810 11918 11182 10562
2 11.00 66251 45534 36402 31155 27612 25019 23017 21413 20091 18978
23
24
Table 4-Maximum Capacity of CSST
In Thousands of BTU per hour of undiluted LP-Gases
Pressure of 2 psi and a pressure drop of 1 psi (Based on a 1.52 Specific Gravity Gas)*
Length of Pipe or Tubing, Feet
EHD** Flow
Size Designation 10 20 30 40 50 75 80 110 150 200 250 300 400 500
25
26
Table 6 – Copper Tube Sizing or Schedule 40 Pipe Sizing*
In Thousands of BTU per hour of undiluted LP-Gases
2 PSIG inlet with a 1PSIG pressure drop
Size of Pipe or Copper Length of Pipe or Tubing, Feet
Tubing, Inches 10 20 30 40 50 60 70 80 90 100
⅜” 451 310 249 213 189 171 157 146 137 130
½” 1020 701 563 482 427 387 356 331 311 294
Copper ⅝” 1900 1306 1049 898 795 721 663 617 579 547
Tubing ¾” 3215 2210 1774 1519 1346 1219 1122 1044 979 925
(O.D.) ½” 2687 1847 1483 1269 1125 1019 938 872 819 773
¾” 5619 3862 3101 2654 2352 2131 1961 1824 1712 1617
Pipe 1” 10585 7275 5842 5000 4431 4015 3694 3436 3224 3046
Size 1¼” 21731 14936 11994 10265 9098 8243 7584 7055 6620 6253
1½” 32560 22378 17971 15381 13632 12351 11363 10571 9918 9369
2” 62708 43099 34610 29621 26253 23787 21884 20359 19102 18043
Seat Disc
Step 3
Reinstall the inlet nipple and
gasket by turning counterclockwise into
neck of regulator (left hand thread).
Hold the neck of the regulator body Inlet Nipple
secure with a wrench. Tighten the inlet
nipple into the regulator with a second
wrench. Tighten to 35 ft/lbs torque–do
not overtighten. Hold neck of
regulator securely
Be careful not to damage threads. with this wrench
After completing these steps, be sure
system piping is clean and that new pig-
tails are being used.
Reinstall the regulator, check for leaks
and properly check the
system.
per NFPA 58
30
LP-Gas Regulators
Indoor Installation of Regulators
Regulators installed inside a building must have the bonnet vent
piped away. To maintain the large vent capacity relief feature of
the regulator, the vent piping should be at least as large as the vent
opening on the regulator bonnet.
To pipe away the LV4403B or LV5503B regulators, for example,
remove the vent screen from the bonnet vent and install 3/4” pipe
into the bonnet vent threads and pipe to the outside of building.
Install vent protection on the outlet of the pipe away vent line.
To utilize the vent screen and retainer supplied with the regulator,
use a 3/4” NPT 90º elbow. Insert screen into 3/4” F.NPT outlet of
elbow. Thread retainer into outlet at least 1 turn. Install the elbow
with vent screen pointing down. The vent line must be installed in
a manner to prevent the entry of water, insects, or foreign material
that could cause blockage. The discharge opening must be at least
3 feet from any opening below it.
NOTE: Do not use regulators with over 5 PSIG inlet pressure
indoors. Follow all local codes and standards as well as NFPA 54
and 58.
3/4” Elbow
3/4” Elbow
Vent Screen
with supressor 3/4” Pipe
From 1 stage
st
regulator
3/4” Elbow
To appliances
31
LP-Gas Regulators
Selecting LP-Gas Regulators
Type of System Maximum Load Suggested
Regulator
1,500,000 (a) LV3403TR
First Stage in a Two
Stage System LV4403SR Series
2,500,000 (b)
LV4403TR Series
935,000 (c) LV4403B Series
1,600,000 (c) LV5503B4/B6
Second Stage in a
2,300,000 (c) LV5503B8
Two Stage System
9,800,000 LV6503B Series
450,000 LV3403B Series
32
LP-Gas Regulators
Underground Installations
In underground installations the vent tube opening must be above
the maximum water table and kept free from water, insects, and
foreign material. NOTE: if the water mark in the dome of an
underground tank is above the regulator vent tube end or regulator
vent opening, the regulator should be replaced and the situation
corrected.
18
33
LP-Gas Regulators
3. Assume a minimum tank pressure of 15 psig.
4. For these conditions, refer to chart for the LV4403TR Series,
First Stage Regulator, shown below.
5. Find the line on the chart corresponding to the lowest
anticipated winter tank pressure (note that each performance line
corresponds to and is marked with a different inlet pressure in
PSI).
6. Draw a vertical line upward from the point of assumed load
(500,000 BTUs per hour) to intersect with the line correspond-
ing to the lowest tank pressure.
7. Read horizontally from the intersection of these lines to the
delivery pressure at the left side of the chart. In this example the
delivery pressure will be 9.7 psig. Since the delivery pressure
will be 9.7 psig at the maximum load conditions and lowest
anticipated tank pressure, the regulator will be sized properly
for the demand.
34
LP-Gas Regulators
5. Find the line on the chart corresponding to the anticipated inlet
pressure.
6. Draw a vertical line upward from the point of assumed load
(250,000 BTUs per hour) to intersect with the line corresponding
to the lowest inlet pressure.
7. Read horizontally from the intersection of these lines to the
delivery pressure at the left side of the chart. In this example
the delivery pressure will read 10.6” w.c.. Since the delivery
pressure will be 10.6” w.c. at the maximum load condition and
lowest anticipated inlet pressure, the regulator is sized properly
for the demand.
36
Leak Testing the Installation
B. Gauge Adapter Method (High Pressure Testing Procedure)
Step 1. Inspect all connections and appliance valves to be sure
such connections are wrench tight and that all appliance valves are
closed including the pilot valves.
Step 2. Install 2962 high pressure test gauge adapter on the tank
service valve and connect the other end of the gauge adapter to the
pigtail and regulator inlet.
Step 3. Open container valve to allow the system to pressurize
while observing indicated pressure on 300 pound testing gauge.
Step 4. Close service valve tightly. Note pressure reading on the
pressure gauge, then slowly bleed gas between service valve and
gauge adapter, reduce pressure to 10 PSIG less than the original
reading on the gauge and retighten gauge adapter into service valve
or close bleeder port. Note reading on gauge.
If gauge reading remains constant for 3 minutes, it can be
assumed the system is leak tight. If the pressure reading drops,
it indicates a leak somewhere in the high or low pressure piping
system. NOTE: A pressure drop of 15 psig in 10 minutes time
indicates a leak as little as 10 BTU of gas per hour. Check joints
and other possible points of leakage with an approved combustible
gas detector, soap and water, or an equivalent nonflammable
solution. CAUTION: Since some leak test solutions, including
soap and water, may cause corrosion or stress cracking, the piping
should be rinsed with water after testing, unless it is determined
the leak test solution is noncorrosive. Never test with an open
flame. If there is an increase in pressure it indicates the container
valve is not shut off completely. Shut off container valve tightly
and repeat step 4.
Step 5. Disconnect the 2962 test gauge adapter from the service
shut off valve. Reconnect pigtail, tighten and test with soap and
water or an appropriate leak detector solution (refer to caution in
step 4., above).
Step 6. If required, proceed with manometer method steps 2
through 4. Never check for leaks with an open flame.
37
Leak Testing the Installation
C. High Pressure Test Method. For service valves equipped
with a pressure test port.
Step 1. Inspect all connections and appliance valves to be sure
such connections are wrench tight and that all appliance valves are
closed including the pilot valves.
Step 2. Install pressure test gauge on the test port down stream of
the tank service valve seat and up stream of the pigtail and regula-
tor inlet.
Step 3. Open container valve to allow the system to pressurize
while observing indicated pressure on 300 pound testing gauge.
Step 4. Close service valve tightly. Note pressure reading on the
pressure gauge, then slowly bleed gas between service valve and
gauge adapter, reduce pressure to 10 PSIG less than the original
reading on the gauge and retighten gauge adapter into service valve
or close bleeder port. Note reading on gauge.
If gauge reading remains constant for 3 minutes, it can be
assumed the system is leak tight. If the pressure reading drops,
it indicates a leak somewhere in the high or low pressure piping
system. NOTE: A pressure drop of 15 psig in 10 minutes time
indicates a leak as little as 10 BTU of gas per hour. Check joints
and other possible points of leakage with an approved combus-
tible gas detector, soap and water, or an equivalent nonflammable
solution. CAUTION: Since some leak test solutions, including
soap and water, may cause corrosion or stress cracking, the piping
should be rinsed with water after testing, unless it is determined
the leak test solution is noncorrosive. Never test with an open
flame. If there is an increase in pressure it indicates the container
valve is not shut off completely. Shut off container valve tightly
and repeat step 4.
Step 5. Disconnect the test gauge from the service shut off valve or
leave it in place if desired. If gauge is removed plug the opening
and check for leaks with an appropriate leak detector solution (refer
to caution in step 4 above).
Step 6. If required, proceed with manometer method steps 2
through 4. Never check for leaks with an open flame.
38
Leak Testing the Installation
NOTE: After the piping system and appliance connections have
been proven to be leak tight, the air may be purged from lines.
Refer to NPGA Propane Safety and Technical Support Manual
Bulletin T403 and NFPA 54 for more information.
Regulator Delivery Pressure
Check the regulator delivery pressure with approximately half the
total appliance load in use. Your gauge should read 11 inches water
column at the appliance. Adjust regulator if necessary. Following
this, turn on all appliances to make sure that pressure is maintained
at full load. If an excessive pressure drop occurs, inspect line for
“kinks,” “flats,” or other restrictions.
CAUTION: Appliance regulators are installed on most appliances
and may be preset by the manufacturer for flow pressure lower
than 11 inches water column. It is recommended the manometer
or test gauge be installed at a location other than the range orifice
or appliance pressure tap when performing lockup and delivery
pressure checks.
Regulator Lock-up and Leakage
After this, shut off all appliance valves to determine if the regula-
tor has a worn seat or if it has been set too high to compensate for
line losses due to undersize piping. A slight rise in pressure will
occur under these conditions. This is called the “lock-up” pressure.
The lock-up pressure should not exceed 130% of the regulator set
delivery pressure. A quick rise in pressure above this point will
indicate undersize piping.
Continue this same test for 5 minutes or more. If a creeping rise is
noticed in the pressure, the regulator seat is not closing off prop-
erly. Inspect regulator inlet nozzle for dirt, scratches, or dents, and
seat disc for signs of wear. Replace where necessary.
For more information, refer to NFPA 54, Section on Inspection,
Testing and Purging, NPGA Propane Safety and Technical Support
Manual Bulletin 403, “Pressure testing and leak checking LP Gas
piping systems.” For more information on setting single stage regu-
lators, request RegO® Products Technical Guide 107.
39
Proper Use of Excess Flow Valves
The primary purpose of an excess flow valve is to protect against
excessive flow when breakage of pipe lines or hose rupture takes
place. When we refer to breakage or rupture, a clean and complete
separation is assumed. It is obvious that, if the damage is only a
crack or if the piping is crushed at the point of failure, the escaping
flow will be restricted and may or may not pass sufficient vapor or
liquid to cause the excess flow valve to close.
An excess flow valve, while in its normal open position, permits
the flow of liquid or gas in either direction. Flow is controlled in
one direction only. Each excess flow valve is stamped with an
arrow showing the direction in which the flow is controlled. If the
flow in that direction exceeds a predetermined rate the valve
automatically closes. Manufacturers’ catalogs show the closing
flow rating both in terms of liquid and vapor.
Since excess flow valves depend on flow for closure, the line
leading away from the excess flow valve should be large enough
so that it will not excessively restrict the flow. If the pipe run is
unusually long or restricted by numerous elbows, tees, or other
fittings, consideration should be given to the use of larger size pipe
and fittings. Never use a pipe size smaller than that of the excess
flow valve.
It is considered good practice to select an excess flow valve with
a rated closing flow approximately 50% greater than the antici-
pated normal flow. This is important because valves which have a
closing flow very close to the normal flow may chatter or slug
closed when surges in the line occur either during normal operation
or due to the rapid opening of a control valve.
Excess flow valves should be tested and proven at the time of
installation and at periodic intervals not to exceed one year. The
tests should include a simulated break in the line by the quick
opening of a shutoff valve at the farthest possible point in the
piping which the excess flow valve is intended to protect. If the
valve closes under these conditions, it is reasonable to assume that
it will close in the event of accidental breakage of the piping at any
point closer to the excess flow valve.
®
See RegO Products Safety Warning in the L-500 and L-102
Catalogs for important warning information
40
Pressure Relief Valves
Minimum required rate of discharge in cubic feet per minute of
air at 120% of the maximum permitted start to discharge pressure
for safety relief valves to be used on containers other than those
constructed in accordance with Department of Transportation
specification.
41
Pressure Relief Valves
Surface area = Total outside surface area of container in square
feet.
When the surface area is not stamped on the nameplate or when the
marking is not legible, the area can be calculated by using one of
the following formulas:
(1) Cylindrical container with hemispherical heads
Area = Overall length X outside diameter X 3.1416
(2) Cylindrical container with semi-ellipsoidal heads
Area = (Overall length + .3 outside diameter) X outside
diameter X 3.1416
(3) Spherical container
Area = Outside diameter squared X 3.1416
1 2
Turn handwheel counterclock- Remove self tapping screw and
wise as far as possible to assure handwheel.
valve is completely open and
backseated.
43
Repair of the MultiBonnet®
3 4
Holding the lower section of Thread the new upper bon-
the MultiBonnet® in place net packing assembly into
with a wrench, use a second the lower section of the
wrench to remove the upper MultiBonnet®.
bonnet packing assembly.
5 6
Tighten upper packing Reassemble the handwheel
assembly with 50 to 75 inch/ and check valve for leaks.
pounds torque.
44
Flow of LP-Gas Through Fixed Orifices
BTU Per Hour at 11” w.c. at Sea Level
Orifice or Orifice or
Drill Size Propane Butane Drill Size Propane Butane
.008 519 589 51 36,531 41,414
.009 656 744 50 39,842 45,168
.010 812 921 49 43,361 49,157
.011 981 1,112 48 46,983 53,263
.012 1,169 1,326 47 50,088 56,783
80 1,480 1,678 46 53,296 60,420
79 1,708 1,936 45 54,641 61,944
78 2,080 2,358 44 60,229 68,280
77 2,629 2,980 43 64,369 72,973
76 3,249 3,684 42 71,095 80,599
75 3,581 4,059 41 74,924 84,940
74 4,119 4,669 40 78,,029 88,459
73 4,678 5,303 39 80,513 91,215
72 5,081 5,760 38 83,721 94,912
71 5,495 6,230 37 87,860 99,605
70 6,375 7,227 36 92,207 104,532
69 6,934 7,860 35 98,312 111,454
68 7,813 8,858 34 100,175 113,566
67 8,320 9,433 33 103,797 117,672
66 8,848 10,031 32 109,385 124,007
65 9,955 11,286 31 117,043 132,689
64 10,535 11,943 30 134,119 152,046
63 11,125 12,612 29 150,366 170,466
62 11,735 13,304 28 160,301 181,728
61 12,367 14,020 27 168,580 191,144
60 13,008 14,747 26 175,617 199,092
59 13,660 15,486 25 181,619 205,896
58 14,333 16,249 24 187,828 212,935
57 15,026 17,035 23 192,796 218,567
56 17,572 19,921 22 200,350 227,131
55 21,939 24,872 21 205,525 232,997
54 24,630 27,922 20 210,699 238,863
53 28,769 32,615 19 233,945 253,880
52 32,805 37,190 18 233,466 264,673
Reprinted with permission from NFPA 54, National Fuel Gas Code,
Copyright©1999, National Fire Protection Association, Quincy, MA 02269. This
reprinted material is not the complete and official position of the NFPA on the
referenced subject which is represented only by the standard in its entirety.
45
Line Sizing Chart for Liquid Propane
(Based on Pressure Drop of 1 PSI)
To Use Chart
1. Having determined the required flow at point of use, locate this flow in the left
hand column. If this falls between two figures, use the larger of the two.
2. Determine total length of piping required from source to point of use.
3. Read across chart from left (required flow) to right to find the total length
which is equal to or exceeds the distance from source to use.
4. From this point read up to find the correct size of pipe required.
46
Representative Equivalent Lengths of Pipe for Various Valves and Fittings
47
Determining Age of RegO® Products
1960 to 1985 -- Two-Letter Date Code
First letter in date code is the month
A—January G—July
B—February H—August
C— March I—September
D— April J—October
E—May K—November
F—June L—December
Relief valves used on ASME tanks carry a numerical code indicating
month and year such as 1-75 means January, 1975.
1 — January 7 — July
2 — February 8 — August
3 — March 9 — September
4 — April 10 — October
5 — May 11 — November
6 — June 12 — December
Letter in date code Second 2 digits in date code are the year
is the week
91 — 1991 98 — 1998
A — 1st week
92 — 1992 99 — 1999
B — 2nd week
93 — 1993 00 — 2000
C — 3rd week
94 — 1994 01 — 2001
D — 4th week
95 — 1995 etcetera . . .
E — 5th week
96 — 1996
97 — 1997
Example: 6A92 = First week of June, 1992
Converting Volumes of Gas
(CFH to CFH or CFM to CFM)
49
Conversion Units
Multiply By To Obtain
Pressure
Atmospheres 1.0332 kilograms per sq. centimeter
Atmospheres 14.70 pounds per square inch
Atmospheres 407.14 inches water
Grams per sq. centimeter 0.0142 pounds per square inch
Inches of mercury .4912 pounds per square inch
Inches of mercury 1.133 feet of water
Inches of water 0.0361 pounds per square inch
Inches of water 0.0735 inches of mercury
Inches of water 0.5781 ounces per square inch
Inches of water 5.204 pounds per square foot
bar 100 kPa
Kilograms per sq. centimeter 14.22 pounds per square inch
Kilograms per square meter 0.2048 pounds per square foot
Pounds per square inch 0.0680 atmospheres
Pounds per square inch 0.07031 kilograms per sq. centimeter
Pounds per square inch* 6.89 kPa
Pounds per square inch 2.036 inches of mercury
Pounds per square inch 2.307 feet of water
Pounds per square inch .06897 bar
Pounds per square inch 27.67 inches of water
kPa .145 PSI
Length
Centimeters 0.3937 inches
Feet 0.3048 meters
Feet 30.48 centimeters
Feet 304.8 millimeters
Inches 2.540 centimeters
Inches 25.40 millimeters
Kilometer 0.6214 miles
Meters 1.094 yards
Meters 3.281 Feet
Meters 39.37 inches
Miles (nautical) 1,853.0 meters
Miles (statute) 1,609.0 meters
Yards 0.9144 meters
Yards 91.44 centimeters
*Ex. 5 pounds per square inch X (6.89) = 34.45 kPa
50
Conversion Units
Multiply By To Obtain
Volume
Cubic centimeter 0.06103 cubic inch
Cubic feet 7.48 gallons (US)
Cubic feet 28.316 liters
Cubic feet 1728 cubic inches
Cubic feet .03704 cubic yards
Cubic feet .02832 cubic meters
Gallons (Imperial) 1.201 gallons (US)
Gallons (US)* 0.1337 cubic feet
Gallons (US) 0.8326 gallons (Imperial)
Gallons (US) 3.785 liters
Gallons (US) 231 cubic inches
Liters 0.0353 cubic feet
Liters 0.2642 gallons (US)
Liters 1.057 quarts (US)
Liters 2.113 pints (US)
Pints (US) 0.4732 liters
Miscellaneous
BTU 252 calories
Calories 3.968 BTU
Ton (US) 2000 pounds
Kilogram 2.205 pounds
Kilowatt Hour 3412 BTU
Ounces 28.35 grams
Pounds 0.4536 kilograms
Pounds 453.5924 grams
Ton (US) .908 tonne
Therm 100,000 BTU
API Bbls 42 gallons (US)
51
52
53
Manual L-545 Copyright 1962 Revised 1/11
Printed in the USA 11-0111-0862
100 RegO Drive PO Box 247 Elon, NC 27244 USA
Phone (336) 449-7707 Fax (336) 449-6594
54