You are on page 1of 3

A STUDY ON GENERATOR RUNNING AT LOW FREQUENCY, LOW SPEED, UNDER

produced by the synchronous generator will


EXCITATION AND REVERSE
increase.POWER

Prepared by
Saleh Ebn Sharif
EEE, BUET

A synchronous electrical machine is intended to So, fuel equals torque, and torque equals
be operated at a constant speed (synchronous amperes, and varying amperes varies the power
speed). When the generator rotor is rotated, produced by the generator. So, to make more
the magnetic flux of the generator rotor induces power, increase the fuel flow-rate. To make less
a voltage in the generator stator windings-- power, decrease the fuel flow-rate.
called the generator terminal voltage.
Again, to have a constant terminal voltage, the
When the speed of the generator rotor is generator rotor magnetic field must be held
constant (or at rated) and the excitation is constant. And the exciter controls the strength
constant, the generator terminal voltage will be of the generator rotor magnetic field. So, that
constant, or stable. The magnitude of the means the exciter will normally operate at a
generator terminal voltage is a function of the relatively constant, stable, output to maintain a
strength of the magnetic field of the generator relatively constant, stable generator terminal
rotor-since the generator rotor is being rotated voltage.
at a constant speed: synchronous speed.
When Rotor rotates, its segments passes
The exciter controls the strength of the rotor through north and South Pole and voltages
magnetic field, and the strength of the rotor induced through a complete cycle. The
magnetic field controls the magnitude of the frequency of generator depends on two factors.
generator terminal voltage. Mathematically,
Voltage is proportional to rate of flux change in  The speed at which the rotor rotates
within magnetic field
winding.
 The number of stator poles that creates
Again, to have a constant terminal voltage, the the magnetic field
generator rotor magnetic field must be held
F = PN/ 60;
constant. And the exciter controls the strength
P = number of poles
of the generator rotor magnetic field. So, that N= Rotational Speed in RMS
means the exciter will normally operate at a
relatively constant, stable, output to maintain a
relatively constant, stable generator terminal Low freq operation due to the prime mover
voltage. running slow could be caused by a governor
fault, fuel supply or a steam supply issues. Now,
If torque being applied to the generator rotor is Effects of running generator on low frequency
increased, the amperes flowing in the generator can be analyzed into two scenarios.
stator will increase. And, when the generator
stator amperes increase, then the power being
power system as well as generators will loss
synchronism with grid. So, Fuel pressure drop
MULTIPLE GENERATORS CONNECTED IN leads to low speed of prime mover and
SINGLE BUS: alternator causing under excitation of generator
causing loss of excitation of generator. Loss of
Low speed of paralleled generators causes the
excitation causes the generator to draw
slower generator to give up its load to the other
(absorb) lots of reactive power from the grid in
generators. If speed is reduced enough the
an effort to maintain the magnetic field in the
generator will become motorized and draw
air gap. The Reverse Power Relay ( or loss of
current from the bus. A reverse power relay is
excitation ) monitors the amount of real power
supposed to trip a motorized generator off of
that is flowing from the generator; it is there to
the bus.
ensure that a loss of fuel, steam, water, etc.
In any case it is possible to have additional does not cause the generator to run as a motor.
generators trip off line due to being overloaded
The real danger is to a fully loaded machine
as the slow generator is not taking its share of
under high demand conditions. Here there is a
the electrical load. The sudden loss of one or
very real probability of your machine slipping
more generators off of a bus can result in a
poles (losing synchronization) with the grid, not
progressive failure ending in a blackout.
because it over speeds (it shouldn't unless there
are governor and/or control valve problems),
but because as the field decays the magnetic
SINGLE GENERATOR CONNECTED IN field in the air gap will ultimately become too
SINGLE BUS: weak to couple the power from the prime
mover to the grid (think of a viscous coupling as
Low speed operation (low freq) can cause over the fluid leaks out). If it does slip poles then the
heating of the generator. Air circulation and reverse power relay might act as the grid tries
cooling within the generator box is reduced. to pull the rotor back into synchronization, but
Low frequency operation of the electrical bus if the field has weakened significantly then
reduces the reactance of motors causing an there won't be any 'poles" for the air gap flux to
increase in current demand. Lower speed also align with.
reduces the amount of voltage produced, the
automatic regulator will increase field current If your generator is a significant portion of the
to the field winding in an attempt to maintain overall load then there may be a system
bus voltage. If the regulator cannot maintain transient stability problem. If it is lightly loaded
voltage then low bus voltage results further then it might continue operating until the
increasing current demands of the connected operator notices that his field current is too
loads. low, there's no power being produced, there's a
lot of VARs/current flowing into the machine,
These overheating factors combine and the the power factor meter is reading much too
amount and rate of overheating is directly low, the fuel flow is lower than expected, etc,
proportional to the amount and time of etc., or any combination of them. Some of this
reduced speed operation. As system is unstable will depend upon the type of governor and the
due to low frequency, harmonics will increase in
mode that it is in, so overspeeding, though
unlikely, can't be ruled out.

When the excitation is lost and the generator


remains connected to the grid and prime mover
continues to supply power, the generator starts
acting as "Induction generator". It no more
remains a "synchronous generator". It draws
excitation current from the grid and runs at
some "slip". The control room will notice rise in
speed of this particular set (other sets running
at synchronous speed). The slip value depends
on various parameters of the generator (various
reactances etc.) and the amount of load
delivered by this set. The stator current would
exceed its rated value (assuming that it is
supplying its rated load at that moment) as it
would be the vectorial sum of load current and
the excitation current drawn from the grid. As
the generator is not running at synchronous
speed, the rotor direct axis and quadrature axis
would be cutting stator field axis. As the two
axes reactances are different, the currents and
the reactance drop would fluctuate at slip
frequency. This in turn will make fluctuation in
the terminal voltage of the generator. The final
value of this fluctuation will depend on the grid
strength and its parameters. What percentage
of grip capacity is the generator under question
will decide the amount of fluctuation in grid
voltage.

Ultimately which parameter causes the tripping


of the set will be decided by generator and the
grid parameters. But if allowed to run as
induction generator, then generator will be
damaged due to excessive stator current. The
power station accessories (various motors etc.)
may trip due to fluctuation in grid voltage.

You might also like