NR Electric Co., Ltd.

Overview

Applications
PCS-9691 provides a cost-effective protection & LEDs, programmable logics. And it is easy to assign
control solution for distribution system. The relay offers any binary input and output signal to the internal logic
extensive protection, control, monitoring and measuring circuits via PCS-Explorer.
functions in one enclosed unit. The relay is suitable for
• Two Ethernet ports (one optical and one RJ-
the application in solidly grounded, impedance grounded,
45) and one RS-485 port are provided for remote
Peterson coil grounded or ungrounded networks. The
communication. The protocol supports IEC 61850
hardware is designed for the installation in distribution
(Ethernet), IEC 60870-5-103 (RS-485), MODBUS
cabinets.
(Ethernet and RS-485) and DNP3.0 (Ethernet and
• The draw-out structure is adopted in the hardware RS-485).
design to achieve convenient maintenance without • Time synchronization with IRIG-B or pulse-per-second
opening the cabinet door. (PPS) is provided based on the differential-level
• Operating temperature: –40° to +70°C (for LCD –20° interface (three-wire: sync+, sync- and shield).
to +70°C) • Fourteen configurable 3-color LEDs, two fixed LEDs
• Combined 1/5A current inputs are integrated. and four button LEDs are provided for indication.

• Wide-range power supply is integrated with24– • The relay can be configured, set and commissioned
250Vdc, or 110–240Vac via PCS-Explorer assistant tool.

• The CT terminals are automatically short-circuited • External wirings and size are designed for easy
when the relay is drawn out. replacement of an existing relay.

• Four current inputs, four voltage inputs, fifteen binary • Both 50Hz & 60Hz are supported in this relay.
inputs and eight binary outputs are supported by the • 10 setting groups are supported for various operating
relay. Two binary outputs provide one NC contact and scenarios.
one NO contact.
• Enhanced screw terminals are employed for AC
• The relay integrates the full flexibility including voltage/current, binary input and binary output.
configurable binary inputs/outputs, self-definable

Read more on the web


www.nrec.com 1
NR Electric Co., Ltd.

Figure 1 Function diagram of PCS-9691

Read more on the web


www.nrec.com 2
NR Electric Co., Ltd.

Features
• High-setting and low-setting elements are provided for • Up to six stages of neutral/ground(zero sequence)
Restricted Earth Fault protection (REF). CT saturation overcurrent protection are integrated. Four stages can
detection element is integrated for the blocking of low- be controlled by directional element and harmonic
setting REF. The CT ratio compensation is provided blocking element.
to eliminate the unbalance due to CT ratio.
• 12 IDMT curves are integrated: five IEC curves
• Six-stage over- & under- frequency protections and (short time inverse, standard inverse, very inverse,
four-stage change-of-frequency (df/dt) are integrated extremely inverse, long time inverse), six IEEE/
to implement load shedding and other control ANSI curves (short time inverse, moderately inverse,
schemes. The over- & under- frequency protection inverse, very inverse, extremely inverse, long time
is controlled by voltage element to avoid the mal- inverse) and one self-defined curve.
operation due to short-circuit faults.
• Self-adaptive polarized voltage is employed for
• Cold load pickup logic is integrated to automatically directional element to avoid the mal-operation due to
increase the setting of phase overcurrent and zero the close-in severe three-phase faults. The memorized
sequence overcurrent protections to improve the voltage or measured voltage is automatically selected
adaptability for various loads. according to different scenario.
• Fault locator function is integrated for the post-fault • Independent phase overcurrent element and zero
checking and maintenance. sequence overcurrent element are employed for the
Switch-Onto-Fault (SOTF) logic to achieve the high-
• Dead zone protection is integrated to clear the faults
speed tripping.
between the CT coil and the circuit breaker.
• Phase-ground voltage or phase-phase voltage can be
• Directional power element is provided for the reverse
selected for overvoltage and undervoltage protections.
power protection or forward power protection.
Selective 1-phase (‘OR’ logic) and 3-phase (‘AND’
• Thermal model based on IEC60255-8 standard logic) modes are supported.
is integrated for thermal overload protection. The
• Up to 13th harmonics are measured for power quality
fundamental current and 2nd to 7th harmonics are
monitoring.
utilized for thermal accumulation.
• Four self-definable buttons are provided in the
• Broken conduct protection can be automatically
faceplate for easy control and maintenance. The
blocked for a very short time to avoid the mal-
button can be set as the remote/local, lock/unlock,
operation due to the circuit breaker switching.
open/close for the circuit breaker control.
• Up to six stages of phase overcurrent protection
• Powerful disturbance recording function is
are provided for various applications. Four stages
integrated in the relay for after-fault analysis. Up
can be controlled by directional element, harmonic
to 64 disturbance reports can be stored in non-
blocking element and voltage element (phase-phase
volatile memory. Each report includes 5-cycle pre-
undervoltage or negative sequence overvoltage)
fault waveform and 100-cycle to 416-cycle post-fault
waveform.

Read more on the web


www.nrec.com 3
NR Electric Co., Ltd.

Functions
• Protections • Control
-- Six-stage phase overcurrent protection(50/51P) -- Remote/Local control
-- Four-stage directional phase overcurrent protection -- Lock/unlock logic
(67P) -- Faceplate control button
-- Six-stage neutral/ground overcurrent
• Monitoring
protection(50/51N, 50/51G)
-- Tripping circuit supervision (TCS)
-- Four-stage directional neutral/ground overcurrent
protection(67N/G) -- Voltage transformer supervision (VTS)

-- Two-stage negative-sequence overcurrent -- Current transformer supervision (CTS)


protection (46) -- Circuit breaker status monitoring
-- Thermal overload protection for alarm/trip (49) -- Self supervision
-- Broken conduct detection (46BC) • Measurement
-- Breaker failure element (50BF) -- Current: Ia, Ib, Ic, In
-- Dead zone protection (50DZ) -- Voltage: Va, Vb, Vc, Vsync, Vn, Vab, Vbc, Vca
-- Undercurrent protection (37) -- Sequence current/voltage: I1, I2, 3I0, V1, V2, 3V0
-- Restricted earth fault protection (64REF) -- Frequency: f
-- Two-stage phase-ground or phase-phase -- Angle: Va^Vb, Vb^Vc, Vc^Va, Ia^Ib, Ib^Ic, Ic^Ia,
undervoltage protection (27) Va^Ia, Vb^Iv, Vc^Ic, V0^I0,Vab^Vsync,
-- Two-stage phase-ground or phase-phase -- Power: P, Q
overvoltage protection (59)
-- Energy: kWh IN/OUT, kVarh IN/OUT
-- Two-stage ground overvoltage protection (59G)
-- Power factor: Cos
-- One-stage negative sequence overvoltage
-- Harmonics: up to 13th
protection (47)
-- Four-stage under-frequency protection (81U) • Communication

-- Over-frequency protection (81O) -- Front-panel RJ-45 commissioning port

-- Frequency rate-of-change protection (81R) -- Two rear Ethernet ports with IEC 61850, DNP 3.0
LAN and MODBUS TCP (One optical and one RJ-
-- Directional power protection (32)
45)
-- Four-shot three-pole auto-reclosing (79)
-- One rear RS-485 port with IEC 60870-5-103,
-- Synchronism check for manual closing and auto- MODBUS and DNP 3.0 serial
reclosing (25)
• Recording
-- Switch onto fault logic (SOTF)
-- 1024 SOE
-- Cold load pickup logic (CLP)
-- 1024 supervision alarm records
-- Mechanical protection (MR)
-- 1024 control records
-- Fault location (FL)
-- 1024 user log records
-- Voltage and current drift auto adjustment

Read more on the web


www.nrec.com 4
NR Electric Co., Ltd.

-- 64 protectioneventsummaries-fault type and trip


data, including time of tripping Flexibility
-- 64 fault and disturbance oscillograms with 5-cycle • 15 configurable binary inputs, 8 configurable binary
pre-fault and 100-cycle to 416-cycle post-fault outputs
waveform
• Programmable logics
• Clock Synchronization
• 4 configurable pushbuttons
-- Clock message via serial communication, or SNTP
via Ethernet • 14 configurable 3-color LEDs (green, yellow, red)
-- Differential level interface for IRIG-B or pulse-per-
second (PPS)
Front-Panel HMI
• Setting Group • Four programmable pushbuttons with indication LEDs
(Default: Close, Open, Lock/Unlock, Remote/Control)
-- 10 setting groups
-- Switching of setting groups via configured binary • Two fixed LEDs and fourteen user-programmable
input, Menu and remote communication LEDs

• Maintenance Mode • LCD to display measured values, calculated values, I/


O status, device status, and configuration parameters
-- Directly control outputs via Menuwithout current/
voltage injection

Technical Data
Power Supply
Standard IEC60255-11: 2008
Rated voltage 24/30/48Vdc, 110/125Vdc, 220/250Vdc, 110~240Vac
Variation DC: 80% ~ 120%, AC: 80% ~ 110%
Permissible ripple voltage Max 15% of the rated voltage (DC power supply)
Burden <10W @ Quiescent condition; <15W @ Operating condition

Analog Current Input Ratings


Phase rotation ABC
Rated frequency (fn) 50Hz, 60Hz
Nominal range fn ± 5Hz
Application object For protection and measurement
Rated current (In) 1A 5A
Linear to 30×In 30×In
continuously 4×In 4 ×In
Thermal for 10s 30×In 30×In
withstand
capability for 1s 100×In 100×In
for half a cycle 250×In 250×In
Burden (@ In) < 0.15VA/phase < 0.25VA/phase

Read more on the web


www.nrec.com 5
NR Electric Co., Ltd.

Analog Voltage Input Ratings


Phase rotation ABC
Rated frequency (fn) 50Hz, 60Hz
Nominal range fn ± 5Hz
Rated voltage (Un) 100V ~ 130V (phase-to-phase voltage)
Linear to 130V
continuously 130V
Thermal
withstand 10s 200V
capability
1s 250V
Burden < 0.10VA/phase

Binary Input
Binary input number Up to 15
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.93mA 2.29mA 2.92mA 3.19mA 3.15mA 3.430mA 3.63mA
Pickup voltage 55% ~ 70% rated voltage
“ON” value voltage 70% ~ 120% rated voltage
“OFF” value voltage < 50% rated voltage
Maximum permitted voltage 120% rated voltage
High voltage withstand 2000Vac, 2800Vdc
Resolving time for logic input < 1ms

Binary Output
Item Tripping output Signal output
Binary output number Up to 6 Up to 4
Output model Potential-free contact
Max system voltage 440 VAC, 300 VDC
Voltage across open contact 1000V RMS for 1mi
Continuous carry 8.0A @ 250Vac; 8.0A @ 30Vdc
Short duration current 6A for 3000ms; 15A for 500ms
5A @ 48Vdc, L/R=7ms
Breaking capacity 2A @ 110Vdc, L/R=7ms
1A @ 220Vdc, L/R=7ms
Pickup time < 15ms
Dropout time < 5ms
Bounce time 1ms
loaded contact 30,000 operations minimum
Durability
unloaded contact 20,000,000 operations minimum

Read more on the web


www.nrec.com 6
NR Electric Co., Ltd.

Mechanical Specifications
Mounting way Flush mounted
Weight per device Approx. 5.5kg
Local control panel Small control module: a 240×160-dot LCD, 13 keys and 20 LED indicators
Display language Optional: Chinese, English
Housing material Aluminum
Housing color Silver grey
Location of terminals Rear panel of the device
Front side: IP51
Protection class IEC60225-1: 2009 Rear side, connection terminals: IP30
Other Sides: IP50

Ambient Temperature and Humidity


Standard IEC60225-1: 2009
Operating temperature range -40°C ~ +70°C (for the LCD -20°C ~ +70°C)
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Altitude <3000m

Communication Interfaces
Communication Ports for RTU/SCADA
Medium Parameters
Port number 1 or 2
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 100Base-TX
Electrical
Transmission distance <100m
IEC60870-5-103:1997, IEC61850,
Protocol
DNP3.0 etc.
Ethernet Safety level Isolation to ELV level
Port number 0 or 1
Connector type LC
Transmission rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical fiber type Multi-mode
Wavelength 1310nm
Transmission distance <2000m
IEC60870-5-103:1997, IEC61850,
Protocol
DNP3.0 etc.

Read more on the web


www.nrec.com 7
NR Electric Co., Ltd.

Medium Parameters
Port number 1
Baud rate 4800 ~ 115200bps
Transmission distance <500m @ 4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997, DNP3.0, ModBus etc.
Safety level Isolation to ELV level

Serial Port for Time Synchronization


Medium Parameters
Port number 1
Transmission distance <500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level

Ethernet Port for Test


Medium Parameters
Port number 1
Connector type RJ-45
Electrical Ethernet Transmission rate 100Mbits/s
(in front panel) Transmission standard 100Base-TX
Transmission distance <100m
Safety level Isolation to ELV level

Type Test
Environmental Tests
Dry cold test IEC60068-2-1: 2007, 16h at -25°C
Dry heat test IEC60068-2-2: 2007, 16h at +55°C
Damp heat test IEC60068-2-78: 2001, 10 days, 93%RH, +55°C
Cyclic temperature with IEC60068-2-30: 2005, six (12+12hours) cycles, 95%RH,
humidity test low temperature +25°C, high temperature +55°C

Electrical Tests
Dielectric test IEC60255-27: 2005, test voltage: 2kV, 50Hz, 1min
IEC60255-5: 2000, test voltage: 5kV, unipolar impulses,
Impulse voltage test
waveform 1.2/50μs, source energy 0.5J
Overvoltage category IEC60255-5: 2000, Class III
Insulation measurement IEC60255-5: 2000, insulation resistance >100MΩ @ 500Vdc
Pollution degree IEC60225-1: 2009, Class II

Read more on the web


www.nrec.com 8
NR Electric Co., Ltd.

Electromagnetic Compatibility
IEC 60255-22-1: 2007 IEEE C37.90.1-2002
1MHz burst disturbance test Common mode: Class III2.5kV Common mode: 2.5kV
Differential mode: Class III1.0kV Differential mode: 2.5kV
IEC60255-22-2: 2008 Class IV IEEE C37.90.3-2001
Electrostatic discharge test For contact discharge: 8kV For contact discharge: 8kV
For air discharge: 15kV For air discharge: 15kV
IEC 60255-22-3: 2007 Class III IEEE C37.90.2-2004
Frequency sweep 20V/m (rms,
Frequency sweep
unmodulated)
Radiated amplitude-modulated
Amplitude-modulated
10V/m (rms), f=80~1000MHz
f=80~1000MHz
Spot frequency 20V/m (rms,
Radio frequency interference tests Spot frequency
unmodulated)
Radiated amplitude-modulated
Radiated amplitude-modulated
10V/m(rms),
f=80MHz/160MHz/380MHz/450MHz/900
f=80MHz/160MHz/450MHz/900MHz
MHz;
Radiated pulse-modulated
Radiated pulse-modulated
10V/m (rms), f=900MHz
f=900MHz
IEC 60255-22-4:2008 IEEE C37.90.1-2002
Power supply, I/O, Earth: Class IV, 4kV,
Power supply, I/O: 4kV, 2.5kHz, 5/50ns
Fast transient disturbance tests 2.5kHz, 5/50ns
Communication terminals: Class IV, 2kV, Communication terminals: 2kV, 2.5kHz,
5kHz, 5/50ns 5/50ns
IEC 60255-22-5:2008
Power supply, AC input, I/O port: Class IV,1.2/50us
Surge immunity test
Common mode: 4kV
Differential mode: 2kV
Conducted RF Electromagnetic IEC 60255-22-6:2001
Disturbance Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Power Frequency Magnetic Field IEC 61000-4-8:2001
Immunity Class V, 100A/m for 1min, 1000A/m for 3s
IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
Class V, 6.4/16μs, 1000A/m for 3s
Damped oscillatory magnetic field IEC 61000-4-10:2001
immunity Class V, 100kHz &1MHz–100A/m
Auxiliary power supply IEC 60255-11: 2008
performance
- Voltage dips Up to 200ms for dips to 40% of rated voltage without reset
- Voltage short interruptions 30ms for interruption without rebooting

Read more on the web


www.nrec.com 9
NR Electric Co., Ltd.

Mechanical Tests
Vibration test IEC60255-21-1:1988, Class I
Shock test IEC60255-21-2:1988, Class I
Bump test IEC60255-21-2:1988, Class I
Seismic test IEC60255-21-3:1988, Class I

Mechanical Installation
• This relay is made of a single layer 4U height 6" chassis with 2 connectors on its rear panel. The following figure
shows the dimensions of this relay for reference in mounting.

Dimensions and cut-out in the cubicle (unit: mm)

Read more on the web


www.nrec.com 10
PCS-9691 Technical Data Sheet

NR Electric Co., Ltd. NR Electric Power Automation Factory NR Electric Power Electronics Co., Ltd.
NR Engineering Co., Ltd.
99 Shengtai Road, Nanjing 211106, China 328 Wuyi Road, Changzhou 213025, China
69 Suyuan Avenue, Nanjing 211102, China Tel: +86 25 87178911 Tel: +86 519 88408565
Tel: +86 25 8717 8888 Fax:+86 25 52100511 Fax: +86 519 88408576
Fax: +86 25 8717 8999
E-mail: NRsales@nrec.com
NRservices@nrec.com
Website: www.nreccom

NR Electric International Co., Ltd. PT NR Electric Jakarta NR Energy Solutions India Pvt. Ltd.

Unit C, 7/F, Ford Glory Plaza, 37-39 Wing Hong Unit I, 2nd Floor, Tower Menara Prima, Jl Plot No.89, Panvel Industrial, Co-operative
Street, Cheung Sha Wan Kowloon, Hong Kong Lingkar Mega Kuningan Blok 6.2, Indonesia Estate, Ltd, Panvel. Dist. Raigad – 410206
Tel: + 852 23703773 Tel: +62 2157948606 Maharashtra, India

Fax: + 852 27439555 Fax: +62 2157948608 Tel: + 91 22 27452317


Fax: +91 22 27452319
Email: international@nrec.com Email: indonesia@nrec.com
Email: india@nrec.com

NR Electric USA LLC NR Electric Nigeria Co., Ltd. NR Electric Participações Ltda

11 Orchard Road, Suite 104, Lake Forest, A5, Salatu royal estate, Aminu kano crecent, Avenida Brigadeiro Luis Antônio, 2466 -
CA 92630 Wuse II. Abuja, Nigeria conjunto 73, São Paulo, Brasil.

Tel: +1 949 305 7789 Tel: + 234 806 3881005 Tel: + 55 21 96932-0300

Fax: +1 949 305 7763 Email: nigeria@nrec.com Email: brazil@nrec.com

Email: usa@nrec.com

Copyright © NR Electric 2016.03 All rights reserved

You might also like