FWA 130V: Electrical Characteristics
FWA 130V: Electrical Characteristics
Electrical Characteristics
Total Clearing I2t Arc Voltage Power Losses
The total clearing I2t at rated voltage and This curve gives the peak arc voltage, Watts loss at rated current is given in
at power factor of 15% are given in the U L , which may appear across the fuse the electrical characteristics. The curve
electrical characteristics. For other volt- during its operation as a function of the allows the calculation of the power loss-
ages, the clearing I2t is found by multi- applied working voltage, E g , (RMS) at a es at load currents lower than the rated
plying by correction factor, K , given as power factor of 15%. current . The correction factor, K p , is
a function of applied working voltage, given as a function of the RMS load cur-
E g , (RMS). rent, Ib , in % of the rated current .
1.5 1.0
K Kp
UL 0.8
1.0 0.6
300 0.5
0.4
0.5
200 0.3
0.3 0.2
0.2 100
Eg
Eg Ib
0.15 0.1
26 65 104 130 50 100 150 30 40 50 60 70 80 90 100%
Dimensions
Fig. 1: 1000-3000 Amp Range Fig. 2: 4000 Amp Range
1.875 1.875
B C B C
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition
uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications.
Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves
the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all pos-
sible applications.