Professional Documents
Culture Documents
CONTENTS
© 2002
1
OPEN WEB, LONGSPAN, AND DEEP LONGSPAN STEEL JOISTS, AND JOIST GIRDERS
2002 REVISIONS
2
OPEN WEB, LONGSPAN, AND DEEP LONGSPAN STEEL JOISTS, AND JOIST GIRDERS
3
OPEN WEB, LONGSPAN, AND DEEP LONGSPAN STEEL JOISTS, AND JOIST GIRDERS
4
FIRE-RESISTANCE RATINGS WITH STEEL JOISTS
Hundreds of fire tests on steel joist-supported assemblies The following procedure may be used to substitute the
have been conducted at nationally recognized testing labo- proper K-Series Joist for any S-, J-, and/or H-Series Joist
ratories in accordance with ASTM Standard E119, ANSI listed in a U.L. design assembly.
A2.1/UL 263, and NFPA 251. Because of practical loading 1. Determine the uniform load per foot the joist is required
restrictions and limitations of furnace dimensions, the vast to support.
majority of these tests were run using lightweight joists –
2. Select a design from the U.L. “Fire Resistance
normally from 8 inches to 14 inches deep. This practice
Directory” that matches the building construction and
was advantageous in that it established the minimum
has the required fire rating.
acceptable joists at the shallow and lightweight end of the
joist load tables. 3. a) Floor Assemblies: x x x x x x x x x x x x x x x x
Adjust the design load per foot calculated in step
The specified minimum size joist as listed in Underwriters
#1 for any required reduction in stress level by
Laboratories (U.L.) Fire Resistance Designs is the joist
multiplying the load by a factor of 30 ksi (207MPa)
which combines the required minimum depth and minimum
divided by the specified stress level, i.e. [30/24
weight per foot. Joists, of the same series, which meet, or
(207/165), 30/22 (207/152) etc.].
exceed the specified minimums may be used provided the
accessories are compatible. The dimension from the bot- b) Roof Assemblies: x x x x x x x x x x x x x x x x
tom chord of joists to the ceiling, whether given or calculat- Adjust the design load per foot calculated in step
ed, is a minimum. #1 by multiplying by the factor of 30/26 (207/179),
or a greater factor if the particular assembly
K-Series Joists, LH Series Joists and Joist Girders
design requires a lessor stress level.
specified in floor- or roof-ceiling assemblies, shall be
designed and manufactured in accordance with the Steel 4. Enter the K-Series Economy Table and select the prop-
Joist Institute’s Specifications adopted November 4, 1985, er joist for the calculated load requirement.
revised to May 1, 2000. 5. Insure that the K-Series Joist selected has a depth and
Many of U.L.’s Fire Rated Assemblies now specifically list load table weight per foot equal to, or greater than, the
K-Series Joists. When a K-Series Joist is specified in a S-, J- and/or H-Series joist listed in the U.L. Design.
particular U.L. assembly the K-Series Joist shall have its Joists used in roof assemblies must have a minimum
design stress limited only if the assembly specifically limits depth of 10 inches (254mm).
the design stress of the K-Series Joist. So that the proper K-Series Joist can be selected for U.L.
K-Series Joists may be substituted for S-, J-, and/or H- Designs not presently containing a K-Series designation
Series Joists specified in U.L. floor-, or roof-ceiling designs the weights of various S-, J-, and H-Series Joists used in
as follows: the U.L. Fire Resistance Designs are listed below:
Floor-Ceiling Assemblies:
Load Table Load Table
K-Series Steel Joists of equal or greater depth weight Joist Joist
Weight Weight
Designation Designation
per foot may be substituted for any S-, J-, and/or H- lbs./ft. lbs./ft.
Series Joist in any floor-ceiling design which employs 8S2 4.0 14J5 7.3
a structural concrete floor and suspended membrane 10S3 5.0 14J7 9.7
ceiling.
8J2 4.2 8H2 4.2
Roof-Ceiling Assemblies:
10J2 4.2 8H3 5.0
K-Series Steel Joists of equal or greater depth and 10J3 4.8 10H2 4.2
weight per foot may be substituted for any S-, J-, 10J4 6.0 10H3 5.0
and/or H-Series Joists in any roof-ceiling design with 12J2 4.5 10H4 6.1
the following restrictions: 12J3 5.1 12H4 6.2
12J4 6.0 12H5 7.1
a) Minimum Nominal Depth = 10 inches (254mm)
12J5 7.0
b) Maximum Tensile Stress = 26 KSI (179 MPa) 12J6 8.1
Any stress limitation specified in a U.L. floor or roof fire
rated assembly containing S, J and/or H Series Joists shall
remain applicable when a K-Series Joist is substituted.
Also, certain U.L. assembly designs contain restrictions
regarding minimum allowable joist member sizes, areas of
steel, and/or bridging material sizes. These restrictions
remain applicable when a K-Series Joist is substituted and
it is the responsibility of the specifying professional to list all
such restrictions on the contract drawings.
5
FIRE-RESISTANCE RATINGS WITH STEEL JOISTS
FLOOR-CEILING ASSEMBLIES WITH MEMBRANE PROTECTION
CONCRETE FLOOR
FORM DECK
STEEL JOIST
MEMBRANE
PROTECTION
Primary Support
Restrained Type of Concrete Minimum Maximum Member U. L.
Assembly Protection Joist Size Joist Spacing Min. Depth & Wt. Design
Rating System Thickness See Note #3 & #4 See Note #2 See Note #3 Number
Above Deck Type
20G @14.0 plf.
NW 10K1 72" Min. Area Top & G256
Exposed 2 1/2 " Bottom Chord
1 Hr. 1.12 Sq. Inch
Grid
LW, NW 12K1, 18LH02 Unrestricted ---
D216
Sprayed 2 1/2 " LW, NW 16K6 Unrestricted 20G @20.0 plf. G801
Fiber Min. 3/4" dia. web
MEMBRANE MEMBRANE
PROTECTION PROTECTION
Primary Support
Restrained Type of Built Up Roof Minimum Maximum U. L. Design
Member
Assembly Protection Joist Size Joist Spacing Number
Rating System Type of Metal Deck Min. Depth & Wt.
See Note #3 & #4
Insulation Min. Size See Note #3
26 Ga. 10K1 48" 20G @ 20.00 plf. P211
22 Ga. 12K3 72" 20G @ 13.0 plf. or P214
28 Ga. 12K3 48" W8x18
Rigid 22 Ga. 12K1 72" 20G P225
Insulation
24 Ga. 12K3 48" ----- P227
7
FIRE-RESISTANT RATINGS WITH STEEL JOISTS
ROOF-CEILING ASSEMBLIES WITH DIRECT APPLIED PROTECTION
FIRE FIRE
PROTECTION PROTECTION
NOTES:
1. The UNDERWRITERS LABORATORY FIRE RESIS- 4. Some U.L. Fire Assembly Designs stipulate an allow-
TANCE DIRECTORY lists hundreds of assemblies able maximum joist design stress level less than the 30
and their fire ratings. As a convenience a selected ksi (207MPa) used in the K-Series Joist Specifications.
number of assemblies are listed on 3 preceding pages. It is the responsibility of the specifying professional to
This listing is intended as a guide only and the speci- apply the proper stress level reductions (if required)
fying professional must refer to the U.L. Directory for when selecting Joists and/or Joist Girders.
complete design information.
To adjust the stress level of K-Series Joists or Joist
2. The maximum joist spacing shown for Floor-Ceiling Girders multiply the design load by the required factor
Assemblies may be increased from the spacing listed [30/26 (207/179), 30/24 (207/165), 30/22 (207/1520)],
in the U.L. Directory to a maximum of 48 inches on and then using this increased load, select a Joist or
center, provided the floor slab meets the structural Joist Girder from the load and/or weight tables.
requirements and the spacing of hanger wires sup-
5. Some U.L. Roof-Ceiling Design assemblies using
porting the ceiling is not increased.
direct applied protection limit the spacing of the joists
3. Some U.L. Design Assemblies stipulate minimum size for certain types and gages of metal decking - refer to
materials for Steel Joist and Joist Girder components, the U.L. Directory for this information.
and/or bridging. It is the responsibility of the specifying
professional to show all special requirements on the
Structural Drawings.