You are on page 1of 5

EWDC 222

release 01.00
07-2000/ Eng

Controller for Refrigerating Units cod. 9IS22002

“COMPRESSOR” LED : LED associated to selected value is stored through


USER INTERFACE the state of the compressor relay. It is on confirmation (pressing buttons UP and
Instrument frontlet when the compressor is powered on, it DOWN at the same time) or
blinks in the case of protection or automatically not pressing the same
blocked power-on. buttons for at least 10 seconds.
“DEFROST” LED: LED associated to the
state of the defrost relay. It is in the case DEFROST CYCLE MANUAL POWER ON
of the automated defrost and it blinks in (UP BUTTON)
the case of the manual defrost. It is possible to manually power on the
“ALARM” LED : It is on in the case of a defrost cycle by pressing the button UP
probe error, alarm high/low temperature. for at least 7 seconds. The led associated
BUTTON USE It blinks in the case of a silenced alarm. to the function will immediately be
“SET/PRG” LED: LED associated to the switched on blinking.
Buttons and programming menu state of the parameter and Setpoint It is possible to enable the manual
programming. It is on in the case of the defrost cycle only through the instrument
Button Description Function
Setpoint display. It blinks in the case of when in the main displaying phase (i.e.
UP It scrolls
parameters the parameter programming: when displaying the room probe
down, it temperature). When the instrument is
increases LED processing the parameters programming
values. When
keeping LED Associated Details
or is under setpoint displaying, it will not
pressed, the symbol be possible to enable such a function.
increase is Defrost It is constantly on
faster during automatic
SET/DOWN It scrolls
DIPLAYING PROBE VALUES
defrost, it blinks
parameters during manual The instrument provides two input ports
down, it defrost for probes to regulate the temperature
decreased Compressor It is constantly on
values. When and control defrost.
when the
keeping compressor is The inlet of the unit has two probes to
pressed, the powered on, it adjust the temperature and control
decrease is blinks in the case
faster
defrost. From the main status (cell
of protection or
blocked power-on
temperature display), simultaneously
Setpoint press buttons UP and SET/DOWN to
set
It is constantly on
during the access the probe display mode. The two
Buttons and associated functions Setpoint display, it
probes are respectively identified with
blinks in the
Button Description Function parameter label CPP for cell probe and EPP for the
UP It enables the programming evaporator.
manual defrost mode Label CPP is displayed when you access
(press the alarm It is constantly on
button for at
the probe display mode. To move within
when the alarm is
least 5 on, it blinks when the window, perform the operations
seconds) the alarm is described here below.
SET/DOWN Access to the silenced 1. Button UP - enables to select one of
display and
Setpoint the two probes. It displays
programming alternatively labels CPP and EPP
UP-SET/DOWN It accesses to DISPLAY AND PROGRAMMING THE every time it is pressed;
together the probe
SETPOINT VALUE (SET/DOWN 2. Button SET/DOWN – enables to
display window
BUTTON) display the temperature value
When pressing and releasing the associated to the displayed label. If
SET/DOWN button, the Setpoint value is the button is pressed once more,
displayed and the LED (Setpoint) switches returns to the previous probe label;
on. 3. Buttons UP-SET/DOWN together –
To modify the value, press the UP or returns to the main status.
DOWN buttons within 10 seconds. The
EWDC 222 Rel. 01.00 07- 2000 / Eng 1/5
Parameter description table
ALARM SILENCING

Parameter Description
Only in the case the instrument is in the
diF Setpoint intervention differential. In the case of defrost applications, the differential must be normal display function.
set to positive values: the compressor will stop when the programmed Setpoint value is It is possible to silence an alarm by
reached (on the adjusting probe information) to restart when the temperature value accounts
simply pressing one of the UP or
for the Setpoint value added the differential value. Note: the value 0 can not be programmed.
LSE Lower Setpoint. Generally it is set to the minimum value which the probe can measure. SET/DOWN buttons. The LED associated
HSE Higher Setpoint. with the function will start blinking.
rEF Control Mode. Set to H, the compressor regulation algorithm enables a warm operation, when
set to C, it enables a cold operation. KEYBOARD BLOCK
Ont Compressor ON time when the probe fails.
OFt Compressor OFF time when the probe fails Through the special programming of the
dOn Power-on delay. LOC parameter, it is possible to disable
dOF Delay after power-off. Between the relay power-on and the next power-on, it is necessary that the instrument keyboard thus avoiding
the specified time elapses.
dbi Delays between power-on. Between two compressor power-on, it is necessary that the
any function or parameter undesired
specified time elapses. change.
OdO Delay time output since the instrument power on or the voltage cut out.
dtY Defrost type selection. ACCESS PASSWORD TO THE
0= electric defost,
1= hot gas (reverse cycle) defost,
PARAMETER PROGRAMMING
2 = Free (compressor off) It is possible to set an instrument
dit Interval between defrost cycles. In hour or in minutes according to the dtU password to access the parameter
dtU Unit of measure for defrosting interval/duration
programming phase. To program (or
dCt Selection of the interval defrost counting mode.
0 Compressor operating hours modify) the password, it is simply enough
1 Instrument power-on hours to enter the PAS parameter and program
2 Compressor power-off a value between 1 and 250 (when
dOH Defrost off-set hours.
dEt Defrost endurance time, In hours or minutes according to the dtU
programming the value 0, the password is
dSt Defrost Stop temperature. Defrost ends when this temperature is reached. disabled). It is possible to only enable the
dPO Defrost regulation algorithm enabling request during power on password when out from the parameter
dri Such a parameter allows to decide whether the defrost interval counting must be reset or not programming phase. When the password
during the manual defrost request
is enabled and a parameter programming
dt drainage time. In minutes
AFd Alarm/fans set differential phase access is demanded, the PAS label
Att HAL and LAL parameter interpretation mode. is displayed. Press the buttons UP and
0= it interprets values in absolute mode (which do not refer to the Setpoint) SET/DOWN at the same time to enter the
1= it interprets values as relating to the Setpoint
password programming, which can be
LAL Lower temperature alarm. The temperature value which, when overcome, will lead to the
alarm enabling and signalling modified by means of buttons UP AND
HAL Higher temperature alarm. The temperature value which, when overcome, will lead to the SET/DOWN.
alarm enabling and signalling If the password is correct, by pressimg
PAO Alarm cut out when the instrument is switched on
the button UP and SET/DOWN at the
dAO Alarm cut out after defrost
tAO Delay time from the temperature alarm signalling same time, you will able to enter into the
LOC Keyboard block. It is still possible to enter the programming parameters and change such a prameter Programming Phase. If the
parameter state thus allowing to enable the keyboard. N=it does not block, y=it blocks password is wrong the device prompts
PAS Password. See Access Password to Parameter Programming section
the label PAS to enter it again.
ndt Temperature display format. 0n=whole numbers only, y=decimals
CAL Calibration. Positive or negative temperature offset which is added to the value which the
temperature thermal setting probe reads before being displayed and used throughout the PARAMETER PROGRAMMING
adjusting It is possible to enter the parameter
LdL Higher probe value which can be displayed on the display
programming by pressing the button UP
HdL Lower probe value which can be displayed on the display
and SET/DOWN at the same time for at
dLc Display mode during defrost
0= it displays temperature read by the room probe least 5 seconds. The label of the first
1= it displays temperature read by the room probe when starting defrost parameter will be displayed. LED SET will
2= it displays the “deF” label during defrost blink during the entire programming
dro Select °C or °F to display temperature read by the room probe. 0=°C, 1=°F
mode. To move to the other parameters,
rEL Instrument release. Read only
tAb Reserved. Read only
press UP or SET/DOWN. To display the
parameter value, press the two buttons at
the same time. To change it, press the UP
or the SET/DOWN buttons.
Storing of the selected value is only
possible through confirmation, pressing
buttons UP and SET/DOWN at the same
time or automatically avoiding pressing
the two buttons for 10 seconds about. In

EWDC 222 Rel. 01.00 07- 2000 / Eng 2/5


Parameter table: features the latter case, you exit the programming
parameter function, going back to the
Parameter Description Range Default Measure unit
Differential 0.1..30 2 °C/°F
main displaying mode.
diF
LSE Lower Set -67..HSE -50 °C/°F When the failed defrost probe condition
HSE Higher Set LSE..302 50 °C/°F ceases, adjustment can be resumed
rEF Control mode H/C C Flag normally. If a defrost was in progress, it
Ont On time (compressor) 0..250 0 Minutes can be completed as soon as the end
Oft OFF time (compressor) 0..250 0 Minutes defrost temperature is reached.
dOn Power-on delay 0..250 0 Seconds
dOF Delay after power-off 0..250 0 Minutes TEMPERATURE ALARM
dbi Delay between power-on 0..250 0 Minutes
The error mode depends on values at the
OdO Delay output from power 0..250 0 Minutes
on
HAL, LAL and Att parameters level. In the
dtY Defrost interval selection. 0..2 0 Flag case of Att=absolute, the error depends
dit Defrost interval mode 0..250 6 Hours/Minutes on the overcoming of one of the two
dtU Unit of measure for 0..1 0 Flag values entered at the HAL and LAL
defrosting parameter level. In the case of
interval/duration
Att=relative, HAL and LAL parameter are
dCt Defrost counting mode 0..2 1 Flag
Defrost offset hour 0..250 0 Minutes
read as offset in comparison with the
dOH
Defrost Endurance time 1..250 30 Minutes (dtU=H)
SetPoint.
dEt
Seconds(dtU=P) The error occurs at the overcoming of
dSt Defrost Stop time -67..302 8 °C/°F the values obtained by the algebraic sum
dPO Defrost (at) Power On n..Y n Flag between the SetPoint value and the value
dri Defrost reset interval n..Y Y Flag setup by those parameters. When one of
dt drainage time 0..250 0 Minutes
the alarm conditions is detected, if not
Afd Alarm differential 1..30 2 °C/°F
during the alarm cut off (see parameter
Att Alarm temperature mode 0..1 0 Flag
tAO), the LED associated with the
LAL Lower Alarm -67..HAL -50 °C/°F
function switches on. When such an
HAL Higher alarm LAL...302 50 °C/°F
Power on alarm override 0..10 2 Hours
alarm is detected, the actual differential
PAO
Defrost alarm override 0..999 0 Minutes
temperature control is not affected.
dAO
tAO Temperature alarm 0..999 0 Minutes

LOC
override
(keyboard) lock n..Y n Flag
MECHANICAL MOUNT
PAS Password 0..250 0 Number
The instrument was designed to be
ndt Display mode number n..y Y n/Y
assembled to the frontlet. Drill a hole,
CAL Calibration -30..30 0 °C/°F
29x71mm and fix the instrument by
LdL Lower display Limit -67..HdL -50 °C/°F
means of the special supplied bracket.
HdL Higher display Limit LdL..302 110 °C/°F
The admitted room temperature range
dLc Display Lock 0..2 0 Flag
Selection °C or °F 0..1 0 Flag
for a current instrument power on varies
dro
rEL Release firmware 0..999 / Number between -5 and 60 °C.
tAb Table of parameters 0..999 / Number Avoid assembling the instrument in moist
and/or dirty places. It must be power on
in ordinary or normally polluted places.
♦ E1: failed room cell; fixed display. Ventilate the area next to the instrument
♦ E2: failed defrost probe. This display cooling vents.
PARAMETERS alternates with the temperature
Parameters are visible in two different display at intervals of two seconds. ELECTRICAL
tables (Parameter description table) The room probe error state leads to:
which describes the parameter function 1. The E1 code displayed on the display CONNECTIONS
and while the second table (Parameter and the alarm LED is enabled.
The instrument exhibit screw terminal
features table) provides for a list of the 2. Compressor power on as specified
blocks to connect electrical cables,
specific features of each parameter. by parameters Ont and Oft
section max. 2.5 mm² (as for the power
3. Maximum or minimum alarm
contacts, a unique wire per terminal).
regulation algorithm disabling.
Adjust and service the electrical
DIAGNOSTICS The defrost probe error causes:
connection, when the machine is opened
1. the E2 code to be displayed and the
only.
alarm LED to be enabled
PROBE ALARM Check that the power supply voltage
2. the defrost to end due to a time-out
Alarms depending on possible failures are complies with the instrument demanded
condition
displayed on the instrument display by power supply voltage.
means of the following symbols.
EWDC 222 Rel. 01.00 07- 2000 / Eng 3/5
EWDC 222 connection diagram

LIABILITY AND
RESIDUAL RISKS
Invensys Climate Controls s.p.a. is not
liable for possible damages depending
on:
• Installation/operation different from
what prescribed and, more precisely
different from safety regulations in
existing standards and/or described
in the present operating instructions;
• Operation on boards which do not
provide for the necessary protection
against electric shocks, water and
dust under the specified assembly
standards;
• Operation on boards which
dangerous elements can be easily
accessed on without any special tool;
• Tempering and/or any product
change;
• Installation/operation on boards
which do not comply with
regulations and standards in force.

probe extension from an electro- as a control instrument, type 1B action


DISCLAIMER
magnetical compatibility viewpoint: pay according to the automated power on
the due attention to cabling). features; as a Class A instrument The present brochure entirely and sole
No insulation is present between voltage according to the software class and belongs to Invensys Climate Controls
circuit, relay and probe(s) contact wires, structure. s.p.a. which forbids any reproduction
so the instrument generally has not and spreading different from what
extremely low safety voltage wires. FORBIDDEN USE specifically authorised by Invensys
Relays outputs are voltage–free. Any possible use difference from what Climate Controls s.p.a. itself.
prescribed is totally forbidden. The brochure was edited paying the
Supplied relay contact are functional and necessary due attention, however
OPERATING Invensys Climate Controls s.p.a. is not
they can fail (as they are controlled by an
INSTRUCTIONS electronics, they can undergo short liable for damages depending on the use
circuits or remain opened). It is therefore of the brochure itself.
PROPER USE important that protection devices The same applies to any person or
For safety reasons, the control instrument demanded by the regulations or company involved in editing and
must be always installed and used demanded by evident safety reasons publishing such an operating mode.
according to the specific instructions must be supplied outside the instrument. Invensys Climate Controls s.p.a.
provided by the manufacturer. More reserves itself the right to change such an
precisely, under normal conditions, any operating instruction with no notice at
element under dangerous voltage must all.
be accessed. The instrument must be
protected from water and dust and it
must only be accessed by simply using
TECHNICAL DATA
the specific tool, with the exception of Frontlet protection: IP65
the frontlet. The instrument is suitable to Unit: plastic resin PC+ABS, VO extinction
be assembled inside a domestic appliance degree
and/or similar in the case of conditioning. Sizes: Frontlet 76x34mm, 58mm deep
Its safety was controlled according to the Assembly: to the frontlet by means of a
European reference harmonised drilling template 29x71mm
Standards. Display and LED: 3 displays and 7
It is classified as an electronic automated segments with decimal point
control instrument to be independently Room temperature: 25°C (Min. -5°C, Max
assembled according to its construction, 60°C)
EWDC 222 Rel. 01.00 07- 2000 / Eng 4/5
Room moist (non-condensing): 30% (Min.
10°C, Max 90°C)
Storage temperature: 25°C (Min. –30°C,
Max 75°C)
Storage moist (non-condensing): 30%
(Min. 10°C, Max 90°C)
Analogue inputs: 2 probes reinforced
insulation
Digital outputs: 1 relay 15A 1hp 250V~ , 1
relay 8A SPDT 250V~
Accuracy: better than 0.5% at the end
scale
Resolution: 0.1 °C or 1°C
Power supply: 230 V~/12V~/c ±10%,
Power supply frequency 50/60 Hz
Absorbed power: 1W max.

EWDC 222 Rel. 01.00 07- 2000 / Eng 5/5