Professional Documents
Culture Documents
Technical Bulletin
LIT-12011524
Software Release 5.2
Issued May 13, 2011
Supersedes October 4, 2010
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
What’s New. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
NAE/NIE Update Tool Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Quick Start Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Flowchart of Update Decision Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Main Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Descriptions of the Columns in Main Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Login Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Reset Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Advanced Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Configuring the Windows Firewall for Windows 7 OS . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Installing the NAE/NIE Update Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Extracting the Disk Images from the Image DVD/CD to Your Computer . . . . . . . . . . . 36
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
General Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Advanced Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Stand-Alone NAE Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Hardware Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Connecting the NAE to the Ethernet Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Document Introduction
This document:
• defines prerequisites of and describes how to install the NAE/NIE Update Tool
• provides instructions for updating software disk images of Network
Automation Engines (NAEs), Network Integration Engines (NIEs), and
Network Control Engines (NCEs) to any supported Metasys® system software
release. (For additional system upgrade details, see Related Documentation.)
• describes the migration process from a Network Control Module (NCM) 45-2
to an NAE45-2, which is considered an image update on an NAE45
Note: In this document, unless otherwise noted, NAE refers to all NAE35,
NAE45, NAE55, NIE55, and NIE59 models; all NCE25 models; and all
NCM 45x0-2s migrating to NAE45s. This document does not apply to the
NAE85/NIE85 engines.
What’s New
The Release 5.2 NAE/NIE Update Tool can update redesigned NxE55xx-2
engines. See Characteristics for additional considerations.
The Release 5.2 NAE/NIE Update Tool can run on the same computer at the same
time as the Release 5.2 NxE Information and Configuration Tool.
Related Documentation
Table 1 contains literature related to the NAE/NIE Update Tool and the upgrade
process.
Table 1: NAE/NIE Update Tool Related Documentation
For Information On See Document LIT or Part Number
Complete Upgrade Process ADS, ADX, and SCT Installation and LIT-12011521
Upgrade Instructions Wizard1
Network and Information Technology Network and IT Guidance for the BAS LIT-12011279
(IT) Considerations Professional Technical Bulletin
NAE Configuration and NAE Date and NAE Commissioning Guide LIT-1201519
Time Management
NCE25 Configuration and Field NCE Technical Bulletin LIT-12011267
Equipment Controller (FEC) Upgrades
NCM45x0-2 Migration and the NCM NCM45x0-2 Network Control Module LIT-12011176
Update Utility Commissioning Guide
Serial Printer Destination Delivery NAE Commissioning Guide LIT-1201519
Agent (DDA)
ToggleTunnel or ChangeModel ToggleTunnel and ChangeModel LIT-12011531
Technical Bulletin
5. Select a wired Ethernet adapter that has a non-zero IP address and click OK.
Note: If all Ethernet adapters listed have zero addresses (0.0.0.0), click OK,
exit the NAE/NIE Update Tool, and enable at least one Ethernet
connection. Then, restart the tool.
The main screen of the NAE/NIE Update Tool appears (Figure 2).
Figure 2: NAE/NIE Update Tool - Main Screen
6. If you retained the target file from an earlier version of the NAE/NIE Update
Tool that contains your NAE targets, load it now with File > Load Target File.
The old file is saved for you when you upgrade the NAE/NIE Update Tool
from an earlier version. See Installing the NAE/NIE Update Tool. If not, add
the NAEs that you want to update, using the Test Login Before Update
function for each NAE to help you fill in some of the required configuration
settings.
7. Select the disk image for each device and select Enable in the Status field.
(Disk images are available on product DVD/CD.) You can select multiple disk
images using the Shift + Click or Ctrl + Click key combinations, then either
select Edit from the NAE/NIE/NCE menu or right-click and select Edit.
Note: See Extracting the Disk Images from the Image DVD/CD to Your
Computer on page 36 and Preparing the Computer and NAE on page
37 for information regarding NxE55xx-2 disk images.
8. Verify that your Ethernet connection is currently active and shows a status of
connected.
No Yes
No Yes
No Yes
Terms
DHCP
Dynamic Host Configuration Protocol. A set of communications rules that
allows a Network Administrator to automatically assign Internet Protocol (IP)
addresses as needed when NAEs and other devices are plugged into a network;
it enables dynamic IP network configuration and IP addressing.
HTTP
Hypertext Transfer Protocol. One of two possible technologies that the NAE/
NIE Update Tool uses to update an NAE disk image. The HTTP method is
used to update NAEs across different subnets.
To restore the NCM45-2 code to the unit, use the NCM Update Utility. If the
NAE45-2 was not originally an NCM45-2, you cannot migrate it to an NCM45-2.
System Requirements
The NAE/NIE Update Tool requires the following:
• 1 GB of free space on the hard disk
• One of the following Microsoft Windows operating systems:
• Windows 7 OS (Professional, Enterprise, and Ultimate editions; 32-bit
only) and Microsoft Internet Information Services (IIS) Version 7.5
Note: To install the NAE/NIE Update Tool on a computer with the
Windows 7 OS, IIS must be configured properly. Refer to the Installing
IIS Version 7.5 and ASP.NET for Windows 7 OS section in the ADS,
ADX, and SCT Installation and Upgrade Instructions Wizard Content
(LIT-12011331) for detailed information on setting up IIS. If an ADS or
SCT is installed on a computer with the Windows 7 OS, IIS is already
configured properly for the NAE/NIE Update Tool.
Note: To use the NAE/NIE Update Tool with Windows 7 OS, see
Configuring the Windows Firewall for Windows 7 OS.
• Windows XP® Professional OS with Service Pack SP3 (32-bit) and IIS 5.1
• Windows Server 2003 R2 OS (32-bit) with SP2 and IIS 6.0
• Windows Server 2008 OS (32-bit) with SP1 and IIS 7.0
• Windows Server 2008 R2 OS (64-bit) with IIS 7.5
• An external power adapter to an AC power source. We recommend that you do
not run the NAE/NIE Update Tool computer on battery power during the
update process. If the low battery message appears, you cannot see it because it
appears behind the NAE/NIE Update Tool screen.
• Active connection to the facility’s network
Main Screen
The Main screen of the NAE/NIE Update Tool (Figure 4) comprises these areas:
• Menu Options - provides various tool selections
• Target List - indicates the NAEs that are configured for updates
• Split Screen Adjuster - resizes the amount of window space given to the device
list and the Diagnostic Log window
• Diagnostic Log Window - chronologically lists events that occur during each
update
Each NAE that is configured for an update is listed All columns can be sorted for easy
here. Any order and any combination of NAE models grouping; for example, all NAE45s can be
and release levels is acceptable. grouped and selected for update together.
Clicking the Start Update(s) button begins the update
process for all selected NAEs Release 4.1 or higher.
Manual resets are required to begin updating NAEs
at Release 4.0 or earlier.
Menu Options
Target List
Split Screen
Adjuster
Diagnostic
Log Window
Messages regarding the update process Click the Details cell to display a
appear here. More detailed information window that lists more details about the
appears when you enable Advanced mode. update. These details save
The contents of this window are saved automatically when you close the tool.
automatically when you exit the tool.
1. Waiting, Updating, and Resetting text are shown in black color; OK text is shown in green; and Error text is shown
in red.
Characteristics
The NAE/NIE Update Tool has the following characteristics:
• You must use a Release 5.2 NAE/NIE Update Tool to update NxE55xx-2
engines; you cannot update NxE55xx-2 engines with a Release 5.1 or earlier
version of the NAE/NIE Update Tool.
• The NAE/NIE Update Tool can update NAEs at different image releases. For
example, you can update one NAE45 to Release 5.2 and another to
Release 5.0. If you need to downgrade an NAE from Release 5.2, 5.1, or 5.0 to
an earlier release, the update must be performed over the same subnet or
performed using the stand-alone method. See Stand-Alone NAE Update.
• You can select up to 50 devices to update at a time (Release 4.1 or later), but
you can only update 20 devices simultaneously. NAEs from older releases can
also be included in the 50-device count. The remaining devices are queued to
start as soon as the other devices have completed.
• For NAEs currently at Release 4.1 or later, you can begin the update without
restarting the device manually. For NAEs at Release 4.0 or earlier, a manual
restart is still required. For instructions, see Updating an NAE or Migrating an
NCM45-2.
• Before you start an NAE update, you can verify the device is accessible by
logging into the NAE from the NAE/NIE Update Tool using the Test Login
procedure. See Testing Login before Updating NAE. An added benefit to this
test is the retrieval of the MAC Address (if the HTTP update method is
selected) or the verification of the IP address information (if Enable DHCP is
not selected). If the retrieved IP Address information is different from the
current configuration, the tool provides the option of updating these values to
match.
IP address space size1 Number of addresses that the tool can assign. The base address plus this address
space cannot exceed the subnet specified by the IP address mask. If any
specified number is incorrect, a Default IP Space Error dialog box displays when
you click OK. The default for this field is 254.
Description (NAE55/NIE55) Name to identify this NAE55/NIE55
Disk image (NAE55/NIE55) Disk image to download to this NAE55/NIE55.
Note: After you select a disk image file from the Select disk image dialog box for
NxE55 models (Figure 6), the disk image file extensions are not displayed
in this field. The disk image file extension for NxE55xx-2 models (.dn2) is
different than the disk image file extension for NxE55xx-0 and NxE55xx-1
models (.dsk).
Description (NAE45/35/ Name to identify this NAE45/35/NCE25
NCE25)
Disk image (NAE45/35/ Disk image to download to this NAE45/35/NCE25 (.rgz file)
NCE25)
Update Process To Use Type of process the tool uses to update the device. To update NAEs at Release
4.0 or earlier, select either PXE Only or PXE or HTTP. To update NAEs at
Release 4.1 or later, select HTTP Only or PXE or HTTP.
1. Use these parameters only when using the PXE stand-alone update method. See Stand-Alone NAE Update.
Figure 7 shows the Select Disk Image dialog box that is displayed when you
attempt to edit the default setting for multiple NxE55-x engines and the list of
engines includes both NxE55-0/1 and NxE55-2 engines.
Figure 7: Select Disk Image Dialog Box When Editing Multiple NxE55 Engines
Including Both NxE55-0/1 and NxE55-2 Engines
Timeouts Tab
The Timeouts tab (Figure 11) allows you to specify various wait times that the tool
uses for PXE and HTTP updates.
Figure 11: Timeouts Tab
1. The Update Reset Time for NxE55xx-2 engines is fixed and does not require any adjustment.
Advanced Mode
Advanced mode is enabled when you select the Advanced Mode option from
the Options menu. In Advanced mode, the log shows details of every operation
that occurs during the update, including every DHCP discovery message on the
network. The information shown in the log window for a particular device also
appears in the Details window for that device.
Figure 15: Diagnostic Log Window for Advanced Mode
FIG:N40-tmelne
Establishing Transferring Files Metasys Writing Attributes Completed
Communication (script, bin, rgz) Installing and Reset*
* If you did not specify a Site Director, one less reboot is necessary, decreasing this time by
about 2 minutes.
FIG:N40-tmelne2
Establishing Transferring Files Metasys Writing Attributes Completed
Communication (img, script, bin, rgz) Installing and Reset*
* If you did not specify a Site Director, one less reboot is necessary, decreasing this time by
about 2 minutes.
FIG:N50-tmelne
Establishing Transferring Files Metasys Writing Attributes Completed
Communication ( tbosloader, script, .dn2) Installing and Reset*
* Note: The Writing Attributes and Reset times shown here represent the typical times
when there is no fixed IP address and a Site Director is not specified
.
Detailed Procedures
If you are planning to install the NAE/NIE Update Tool on a computer running the
Windows XP Professional OS or Windows Server 2003 OS, go directly to
Installing the NAE/NIE Update Tool. If you are using a computer with Windows 7
OS you need to configure the firewall to allow network communication between
the computer running the NAE/NIE Update Tool and the supervisory engines.
Follow the Windows firewall configuration procedures before installing the NAE/
NIE Update Tool.
3. In the left pane of the window, click Advanced Settings. The Windows
Firewall with Advanced Security window appears (Figure 20).
4. In the left pane, click Inbound Rules. The Inbound Rules pane appears
(Figure 21).
Figure 21: Windows Firewall - Inbound Rules
5. In the Inbound Rules pane, select World Wide Web Services (HTTP Traffic-
In).
6. In the Actions pane, select Enable Rule. The World Wide Web Services (HTTP
Traffic-In) Inbound Rule is enabled.
7. In the Actions pane for World Wide Web Services (HTTP Traffic-In), select
Properties. The Properties window appears (Figure 22).
8. In the General tab of the World Wide Web Services (HTTP Traffic-In)
Properties window, select Enabled and select the Allow the Connection option.
9. Click OK to save this change.
10. Close all windows.
11. Go to Installing the NAE/NIE Update Tool.
Note: If the computer has the Windows 7 OS and IIS is not configured
properly, the following error message appears and the installation stops
(Figure 24). Refer to the Installing IIS Version 7.5 and ASP.NET for
Windows 7 OS section in the ADS, ADX, and SCT Installation and
Upgrade Instructions Wizard Content (LIT-12011331) for details on
configuring IIS for Windows 7 OS.
Figure 24: Error Message When Window 7 OS
IIS Is Not Configured Properly Prior to Installation
3. Click Install. The Installation Complete screen appears (Figure 26) when the
NAE/NIE Update Tool is installed successfully in the C:\NAEUpdateTool
folder on the computer.
Figure 26: Installation Complete Screen
3. For each zipped file, click Unzip to extract the file contents to
C:\NAEUpdateTool\tftpfiles.
4. Click Close on the dialog box when the extraction is complete.
5. Go to Preparing the Computer and NAE.
Figure 30: Add New Update Target Dialog Box Contents (NAE55 Example)
4. Specify the information for the Target device to be updated as follows (Figure 31).
6. Select the name of the disk image under the File section. See Figure 33.
7. Specify values in the Enable DHCP or Fixed IP Address Information section. See Figure 34.
10. Specify the login information for the NAE if the HTTP process is used or you wish to test logging into the
device. See Figure 37. Also see Testing Login before Updating NAE.
11. After you have entered all necessary fields, click OK to save. The NAE is now ready for the update. Go to
Updating NAE Targets.
If login is successful, the message Login succeeded appears in the dialog box.
If login is not successful, the message reads Login failed. The Details portion
of the dialog box indicates a reason for the failure. You can try again, this time
specifying the current Host Name or IP Address of the device in the field next
to the Test Login Before Update button. If login is successful, but the MTU
setting is not correct for NAE55/NIE55 devices, the message in Figure 39
appears:
Figure 39: Warning Message Indicating Incorrect MTU Setting
If DHCP is not enabled for the device, the NAE/NIE Update Tool retrieves the
IP Address and MAC Address from the device during the login process. The
tool verifies that these retrieved addresses match the IP and MAC Addresses
given on the Edit update target dialog box (Figure 41).
If during the login process the Host Name, MAC address, or any fixed IP
address field as read is different from what is configured in the NAE/NIE
Update Tool, you are presented with a Warning box asking if you want to
replace the configured values. Figure 40 shows an example. Click Yes to
match the values to ensure a successful update.
6. For each NAE that is currently at Release 4.1 or later, highlight the NAE in the
Target list and press the Update Device button. The NAE receives the request
and the update begins. If any of the selected NAEs is not Enabled for an
update, a user message appears, indicating this device is not to be updated.
For an NAE that is currently at Release 4.0 or earlier, instead of highlighting it
and pressing the Update Device button, perform a software reset of the device
from the Site Management Portal UI: right-click the NAE on the Navigation
tree and select Commands > Reset Device.
The NAE/NIE Update Tool detects the NAE restart and begins the update. The
log portion of the screen shows the update progress (Figure 42). An Update
Complete message in the log indicates a successful update. If any errors occur,
see Troubleshooting.
Note: During the entire update process, make sure you do not exit from the
NAE/NIE Update Tool or turn off power to the NAE. Doing so could
adversely affect the update process.
For a summary of the stages that the NAE goes through, see NAE35/NAE45/
NCE25 Update Stages and Timeline and NAE55/NIE55 Update Stages and
Timeline.
Note: The example in Figure 42 shows the typical update messages you can
expect, but it does not match the set of messages you may receive. Any
messages that contain the words via host and an IP address indicate the
address of the device being updated.
7. When the Status column for the NAE indicates Completed, log on to the
newly updated NAE using the IP address displayed in the log portion of the
tool. See the following:
• Verify that the time, time zone, and date of the NAE matches what is
expected. The NAE/NIE Update Tool does not set the device’s time zone.
If you specified an ADS in the Target window, the NAE receives the
appropriate time zone and date information from the ADS. If you did not
specify an ADS, you may need to download the NAE with this
information.
• You can change the NAE Host Name from its current setting, unless you
made this change before you started the update; see Figure 31.
• You must change the NAE IP address if you are using static IP addressing,
unless you made this change before you started the update; see Figure 34.
Note: These adjustments are required to make sure the SCT can communicate
with the newly updated NAE.
Troubleshooting
Generally, the fact that an NAE communicates with the Site Director and displays
an Online status in the Site Management Portal UI does not guarantee that you can
update this NAE with the NAE/NIE Update Tool over the network. Site Director
communication is performed with the robustness of the operating system. The
NAE/NIE Update Tool update process, however, updates the device’s operating
system and employs a more primitive level of communication that does not include
lengthened timeouts and full error handling.
If a problem occurs during an update, click the Details button (Figure 4) to show a
list of all operations performed. This information helps with problem diagnosis.
Retrying a failed update usually works, but if still unsuccessful, try to update the
NAE using the stand-alone method. See Stand-Alone NAE Update.
For more information, use Table 15 in General Troubleshooting to troubleshoot
problems with the NAE/NIE Update Tool. If you are unable to resolve problems
using the entries in this table, see Advanced Troubleshooting.
Advanced Troubleshooting
Note: The steps in this section assume advanced knowledge of troubleshooting
procedures. If you use Table 15 and are unsure how to follow the steps in
this section, contact technical support.
If Table 15 does not resolve your problem, use the following steps based on the
controller you are using:
NAE55-1, NAE55-2, NIE55-1, and NIE55-2: The boards of these NxE55 engines
have an external Video Graphics Array (VGA) connection that can be used to
determine what is happening in the controller. Attempt the following:
a. Locate a spare monitor (Liquid Crystal Display [LCD] or Cathode Ray
Tube [CRT]).
b. Remove the plastic cover on the NAE.
c. Attach the monitor cable to the NAE.
d. Try updating the NAE again, noting what appears on the monitor during
the update process.
If the messages that appear during the update do not help you resolve the
problem, contact technical support and report your findings.
Hardware Requirements
The following hardware is required for connecting to all supported NxEs:
• 2 RJ45 Ethernet patch cables
Note: Do not use a crossover cable.
• 1 FS10x 10/100 Netgear® switch (for example, FS105NA Netgear 5 Port
10/100) or 1 W-Linx 5-port 10/100 Mini Hub (Universal Serial Bus [USB])
E63746 or 1 Netgear 5 Port 10/100 Desktop switch (model FS605) connected
to your computer
Note: NxE55xx-2 engines can connect at 10/100/1,000 Mbps. To connect to
an NxE55xx-2 engine at 1,000 Mbps (1 Gbps), requires a
GS108 Netgear 10/100/1,000 switch. This switch can also be used with
all of the other supported NxEs.
Note: Do not use any other switch, hub, or dual-speed hub.
Make sure the Ethernet cables are patch (straight through) cables. To verify that
you have a patch cable, use a cable tester. If you do not have a cable tester, visually
inspect the cables by holding both ends of the cable either tab up or tab down. The
order of the colors/terminations at both ends of a patch cable should be identical.
See Figure 43 and Table 17 for an example of an Ethernet patch cable.
White/Green
Green
White/Brown
Brown
White/Orange
Orange
Blue
White/Blue
FIG:ptch
White/Green
Green
White/Brown
Brown
Orange
White/Orange
Blue
White/Blue
Note: The colors of your cable do not need to match the colors in Figure 43 and
Table 17. The important characteristic of a patch cable is that the color
pairs do not change position between the ends of the cable.
Table 17: Detail for Patch Cable Wiring
RJ45 Pin Number Colors Wiring Diagram
1 White/Orange
2 Orange
3 White/Green
4 Blue
5 White/Blue
6 Green
7 White/Brown
8 Brown
FIG:naiupdt
Ethernet Switch
Laptop Computer
NAE55
NAE/NIE Update Tool
4. Verify that the 10/LINK or 100/1000LINK LED on the NAE and Ethernet
switch are lit to confirm connectivity between the computer and the NAE via
the Ethernet switch.
Note: NxE55xx-2 engines can connect at 10, 100, or 1,000 Mbps. Connecting
at 1,000 Mbps requires a 1,000 Mbps capable Ethernet switch. See
Hardware Requirements for required switch. The 100/1000 LINK LED
flashes green for 100 Mbps connections and yellow for 1,000 Mbps
connections.
5. Verify that the Local Area Connection for the Ethernet connection to the NAE
is enabled and all other network connections (including wireless connections)
are disabled:
a. On the Control Panel, select Network Connections or Network and Dialup
Connections.
b. Verify that the Local Area Connection for the Ethernet connection to the
NAE is enabled. All other connections should be Disabled or
Disconnected. To disable or enable a connection, right-click the connection
and choose from the menu.
6. Verify the computer has a valid IP address:
a. On the Start menu, select Run.
b. Type cmd, and click OK.
c. At the command prompt, type ipconfig and press Enter. If the computer IP
address is all 0s, wait several minutes. Repeat ipconfig until the address is
established.
7. Proceed with the update. See Adding NAE Update Targets.
c. Highlight the local area connection that the NAE/NIE Update Tool uses.
Right-click and select Properties. The Local Area Connection Properties
dialog box appears.
d. Select Internet Protocol (TCP/IP) and click OK. The Internet Protocol
(TCP/IP) Properties dialog box appears.
Figure 47: TCP/IP Properties Dialog Box
e. If the computer is currently using a static IP address, write down all of the
information in this dialog box (Figure 47). You need this data in the later
step.
j. Add each compatible address from Step a. You need to specify each
address individually. If you added all three IP addresses, the Advanced
TCP/IP Settings dialog box should resemble Figure 51.
Figure 51: New TCP/IP Settings
k. Click the DNS tab and delete any listed DNS server addresses. Click OK.
The Local Area Connection Properties dialog box appears.
5. Add the NAEs to the NAE/NIE Update Tool and start the updates as usual.
6. After you updated the NAEs, start the SCT and download the devices.
7. After you have updated and verified all NAEs, change your Ethernet adapter
settings back to what you recorded in Step e.
8. Reattach the computer to the corporate network.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.