SPECIFICATION – E28
CONTENTS
SPECIFICATION – E28
1.00.00 This section furnishes the Purchaser’s minimum requirements of electrical laboratory &
testing equipments. The bidder shall include any other equipment considered
necessary for the satisfactory maintenance of electrical system of the thermal power
plant and associated 400 kV/230KV GIS switchyard and other systems in the power
plant:-
68 Transformer Winding
resistance meter
0 – 10 A. 1
0 – 40 A (with multirange
1
selection)
69 CT/PT Analyzer with 1
demagnetizer
70 Decade Capacitor Box 1
71 Digital Phase Angle meter 1
72 Computer with printer and 1
furniture.
Refer C&I specification for
technical details of PC
73 Loading Transformer with 1
variac – 0-230 V, Output
1200A
74 a) Test Bench 2
The test instrument / kits shall be of latest version with nessary calibration certificate.
The detail specification for the above instrument is given in clause 2.00.00
(Bidder to submit detailed specification, the make & model of the instrument for each item
with the bid)
The detail specifications for the test instruments are given below. The bidder shall
submit make, model number and data sheets along with the bid.
• Battery life: 3500 tests should be possible assuming each test take 5 s with
6 x 1.5V cells
• The Insulation Tester should be supplied with Lead set with carry case.
Heavy Duty Battery Operated Insulation Resistance tester (10 KV Megger) For Automatic
P.I., DAR, Step Voltage and Dielectric Discharge Test.
1)Technical Requirement
• Voltage selection – 50V to 1KV in 10V steps, 1KV to 10KV in 25 V steps
• Instrument should be Mains and Battery operated.
• Rated resistance 10 KΩ to 35 TΩ.
• Instrument should display direct reading of voltage across the test piece when the
test is in progress.
• Instrument should display leakage measurement.
• Short Circuit current 5 mA @ 10 kV
• Instrument should have Breakdown or ‘Burn’ mode
• Interference Rejection should be up to a maximum 4 mA
• Analog/digital display with backlit
Measurement Range
1.Insulation resistance range
• Digital display 10 KΩ to 35 TΩ.
• Current Measurement ….nA to 5 mA
• Capacitance Measurement 10 nF to 50 µF
• Test time should be selectable from 1 second to 99 minutes
• Capacitor Charging time should be < 3.0 Seconds per μF at 5mA
• Capacitor discharge time should be < 250 milli Seconds per μF to discharge from
10000V to 50 V
• Instrument should have high voltage warning display when input voltage across the
terminal is above 50V.
• Accuracy : +/- 5% upto 2 T ohm
• Power supply -Mains Input voltage: 85-260 V, 50Hz.
Type
The instrument should performs automatic tests and measure Insulation Resistance,
current, capacitance, Polarizations Index, Step voltage tests, DAR & Dielectric Discharge.
Instrument should display direct reading of voltage across the test piece, PI
value, and Dielectric discharge Value
The DD value is defined as (mAV-1F-1):
The tester shall be suitable for D.C. battery operation and AC mains operation. The D.C.
batteries should be rechargeable with the 230 Volts A.C. supply. Contractor shall supply
the necessary accessories for this purpose. The ratings of D.C. batteries shall be indicated
in the offer.
• USB and RS232 port and software if any for download of digital data to a computer
and directly to the printer should be possible. Real Time down load to computer
should be possible. Instrument should have atleast 32 kB on board memory. Data
storage should include voltage, test time, leakage current, resistance, PI, DAR, DD,
capacitance and time constant.
• Instrument should have high voltage warning display when input voltage across the
terminal is above 50V.
• Digital and software filter should be available in the instrument to remove induced
noise.
1. Robust Analog multimeter with center-pole movement with 37.5 uA full scale deflection
5. Operator protection should be provided with Fuse protection on all functions and ranges
6. Sensitive cutout should be provided with very positive latching action and should be
triggered by the meter movement itself when there is any overload
8. For negative polarity of the measurements, the deflection of the meter movement should
be reverseable simply by pressing another push button
9. Required Specifications:
Response Time : Typically 1 second to full scale Manetic field effect
Flash Test : 7 kV AC rms
Overload protection : High speed electromechanical cut out with a
fuse on the two lower resistance ranges and
one in series with the ‘common’ terminal
Fuses : 1 A Cermaic HBC, 10A Ceramic HBC
Safety : EN61010-1(1993) CAT III, 250V d.c., 500V a.c.
EMC : In accordance with IEC 61326 incl Amendment
No.1
Power Supply : 1.5V cell (1 no), 15V battery (1 no ) with
Battery Adapter
Ranges
D.C.Voltage : 100 mV/3V/10V/30V/100V/300V/600V/1000V
Decibels : - 10 to + 55 dB using a.c. voltage scale
Resistance : 0 to 2 k ohm / 0 to 200 k ohm / 0 to 20 M ohm
A.C.Voltage : 3V/10V/30V/100V/300V/600V/1000V
D.C.Current : 50 uA/300 uA/1mA/10mA/100mA/1A/10A
A.C.Current : 10mA/100mA/1A/10A
Insulation Resistance : Upto 200MΩ using ohms scale&extl 150Vd.c.
supply
Sensitivity
D.C.Voltage (all ranges) : 20000 ohm / V
A.C.Voltage (3V range) : 100 ohm / V
A.C.Voltage (10V range) : 1000 ohm / V
A.C.Voltage (30V range on wards) : 2000 ohm / V
Accuracy
D.C. Voltage and Current ranges : +/- 1% of full scale deflection
A.C. Voltage and Current ranges : +/- 2% of full scale deflection @ 50 Hz
Resistance : +/- 5% of reading at centre scale
The Instrument should be supplied with 2 x 1m plug in leads, 2 x insulated crocodile clips,
2 x test probes, 2 x spring hook probes and Batteries.
• 4000 counts Large clear LCD display with at least 25 mm character height and
Backlight
• Data Hold
• Fully Auto – Ranging
• Simple to operate
• MAX/MIN feature
• Battery and fuse compartment should be accessed by a separate back cover
• IEC 61010, EN61010-2-32 compliant
• Should be suitable for applications to CAT III 600V
• 9V Battery power supply, Low Battery Indication, Auto-off function
• Should have automatic ( - ) negative polarity indication, Overrange indication
• Weight should not exceed 400 grams
• Should have provision for a bench stand with built-in stand as well as
• extending round 180o to act as a hanging bracket
Required Specifications:
DC Voltage
Ranges : 400.0 mV, 4.000V, 40.00V, 400.0V,600V with a resolution of 0.1
mV in 400.0 mV range with an accuracy of +0.5% of rdg in 400.0
mV range
Input Impdedance : 7.8 M ohm
Maximum Input : 1000V d.c.
AC Voltage
Ranges : 4.000V, 40.00V, 400.0V,1000V with a resolution of 1 mV in
4.000 V range and 100 mV resolution in 400.0V range with an
accuracy of +1% of reading
Input Impedance : 7.8 M ohm
Maximum Input : 1000V r.m.s.
DC Current
Ranges : 400.0 uA, 4000 uA, 40.00mA, 400.0mA,10A with a resolution of
0.1 uA in 400.0 uA range with an accuracy of +1% of rdg upto
400.0 mA
Overload protection : 0.5A / 1000V and 10A/1000V Fuse
Maximum Input : 4000 uA dc on uA range, 400 mA dc on mA range, 10A dc on
10A range
AC Current
Ranges : 400.0 uA, 4000 uA, 40.00mA, 400.0mA,10A with a resolution of
0.1 uA in 400.0 uA range with an accuracy of +1.5% of rdg
Upto 400.0 mA
Should be provided with Diode Test, Audible continuity feature with fast continuity buzzer,
Integral stand/hanger, Probe holder, Tough Rubber armoured case.
The Mulitmeter should be supplied with test leads and probes
Current ; 0/ 100A
Current ; 0/ 2.5/5A
Current ; 0/ 7.5/75 A
2. Voltage measurement :
AC True RMS or dc with maximum overload of 1000V with an accuracy of +/- 1% of rdg and
resolution of 100 mV and crest factor of 6 for V<1000V peak
Input Impedance : 1 M ohm
3. Resistance, continuity and diode testing :
Resistance ranges : 400 ohm, 4 k ohm with resolution of 0.1 ohm and +/- 1% of rdg
Input protection , resistance and diode test to 600V dc or sine wave
4. Frequency response (Measurements and analogue output)’
A.C. only True RMS Voltage and current : 15 Hz to 1 kHz
dc TRMS Current : dc + 15 Hz to 1 kHz
dc Voltage and current : dc only
Range : 0-30mA/300mA/30A/300A
Accuracy : ±5%
Resolution : 0,1 A
Range : 0-199,9A
Accuracy : ±2%
Voltage : 0-150/300/600V
Voltage : 0-125/250/500V
Type : Digital
Cycles ; 40/50/60
9. Environment
11. Optics
The Optical Scanning Assembly shall have adjustable sensitivity, modulated visible light
output, with a 10-segment bar-graph display of reflected intensity. It shall be capable of
operation in reflect mode, LCD, LED and infrared detection.
13. Fully automatic operation : Easy-to-use Windows® 95, 98, 2000, ME, NT or
XP based software simplifies setup and reduces
testing time.
16. Meters with Turtle® installed : The system also easily tests watthour meters with
installed Turtle® made by Hunt Technologies®. No
need to take the Turtle® out of operation
Sl.no.13 Digital Tachometer
Sl.no.14 Timer
Type : Electronic
Accuracy : 0.01%
Technical Requirements
• 0.1μΩ to 999.9mΩ with 0.1 μΩ best resolution
• Accuracy: Resistance: ± Better than 1% from 100μΩ to 100mΩ
• Instrument should have Auto, continuous & normal operating modes of operation
• Large menu driven LCD Display
• Instrument should Weighs less than 15 kg and should be a Portable unit, designed for field
use in a rugged case
• Instrument should have on board Keyboard for entering data. On board memory for up to
300 tests, with test information. RS232 port for data download to computer
• Current selection should be programmable through keypad on face of the instrument for
better resolution.
• Supplied complete with 5 m test leads and download software Optional 10 & 15 m leads
• The instrument should meet all the safety requirement as per IEC61010 Category II, 300V
Phase to earth and EMC compliance EN61326 annex A (heavy industrial).
• Instrument should be rated to IP54 for taking on site.
Range
Voltage : 0 to 150V
Current: 0 to 100A
Humidity range
1. The system is to be used on all power transformers viz. Generating step up transformers,
auto transformers, etc. for early warning of the developing fault conditions that could lead
to equipment failures and unscheduled outages. The system shall be a continuous, on-
line, intelligent moisture and gas-in-oil monitoring system for evaluating dangerous
conditions, bubbling temperature and aging rate. The system shall be light weight and field
mountable. It is to warn the personnel when the diagnostic or remedial actions are needed.
The system shall provide assistance in decision making process for keeping the
equipment on-line or removing from service.
2. The system is to read on-line the composite values of gases in ppm generated by faults in
the transformers. It shall also monitor the moisture level in the transformers. The system
shall have four 4-20mA inputs (or outputs) for possible connection to other sensors such
as temperature or load current. Five dry contacts shall also be available.
4. The system shall respond to relative humidity in oil (%), Hydrogren (H2), Carbon Monoxide
(CO), Acetylene (C2H2), Etylene (C2H4). The system shall have a Gas-permeable
membrane and combustible gas detector and a thin film ca[acitive sensor for moisture.
Sampling method shall be via flooded port with 1.5 inch NPT male threads.
5. Required Specifications:-
. Measurement Range :
Gas - 0 – 2000 ppm (volume/volume, H2 equivalent)
Moisture - 0 – 100 % RH
Accuracy
Moisture - ± 2% RH
Gas - ± 10% of reading ± 25 ppm (H2 equivalent) at 35 deg.C set
point.
Gas Relative Sensitivity:
H2 - 100% of concentration
CO - 18 ± 3% of concentration
C2H2 - 8 ± 2% of concentration
C2H4 - 1.5 ± 0.5% of concentration
Response Time:
Moisture - 5 minutes sensor response (90% of step change)
Gas - 10 minutes sensor response time (90%) of step change
6. The electronic unit shall be microprocessor based unit and shall be operating on real time
basis with menu driven interface. It shall have the following functions:-
7. Gas level, hourly trend and daily trend readings, gas level, gas trends alarms, moisture
level (with oil temperature), hourly average and daily average reading, moisture level and
moisture average alarms, fail alarm, history logging, periodic sensor test, calibration,
configuration and self test, networking, remote control via controller (optional modem),
remote embedded software upgrading.
8. RS232 port shall be provided for the user to select either local laptop connection during
installation or service connection to the controller. Backlit liquid crystal display (LCD) shall
be provided. A keypad with 8 keys shall be provided. 5 dry alarm contacts shall be
provided for outputs allocated as follows:- gas and moisture high, high-high and fail alarm
contacts. One NO and one NC contacts (C type) per alarm shall be provided. 4 analog
outputs shall also be provided.
9. The sensor and the electronic unit shall be housed in a NEMA 4X (IP66) type of an
enclosure. Optional finned high temperature adaptor for oil temperatures up to 105 deg. C
shall be provided. The system shall be able to handle the oil pressure of 0 – 700 kPa (0 –
100 psiG) with no vacuum allowed. The system shall work on 80 – 260 V AC, 50 Hz. It
shall meet IEC 255-4, 801-2, 801-4 and IEEE C37.90 standards
Required Specification
1. Input Power : 220/240 V AC, 50 Hz operation.
2. Output Current : 120 kV Models: 5 mA for 5 min; 2 mA Continuous
When using external 240/120-volt step-down voltage
transformers, the ratings may be used as given for 120 volt
input.
3. Ammeter
Ranges : 0 to 19.9 mA
0 to 199 mA
0 to 1.99 mA
0 to 5 mA
5. Voltmeter
Resolution : To 100 V over entire range
Accuracy : ±(2% of reading + 100 V)
Ripple : Less than 2% on capacitive samples at continuous rated
Output
6. Temperature Range
Operating : -20 to +130° F (-30 to +55° C)
Required Specification
1. Output voltage : 0 to 250V ,2A 50/60-Hz operation,
0 to 125 V ,2A, 50/60-Hz operation,
2. Current Range : 0-2000A,Resolution 1 A
6. Temperature Range
Operating : 0°C to 40°C (32 to104°F)
Storage : -20 to +60° F (-40 to +140°F)
7 . Relative Humidity Range
Operating : 90% RH at 40°C (104°F)
Storage : 93% RH at 40°C (104°F)
8. Supply Voltage : 220V/240V +6% -10%, 50HZ
9. Display : LCD
Phase : Single
Current ; 0-30A/100A
Phase : Three
Current ; 0-30A/100A
Sl.no.23. Rheostat
• The Instrument shall be suitable for testing all types of relays (both static and
electromagnetic type). Shall be portable and handy for easy transportation to be carried by
one person. The equipment shall be capable of working satisfactorily in hot and saline
climate. It must be dust and vermin proof and corrosion free. It must withstand the shock
and vibration during transportation.
• The equipment shall be designed to operate under the adverse conditions of external
influences like Electrostatic discharge, Magnetic field, E.M field induction, E.M. HF field,
R.E. interference, Input waveform distortion and harmonics, Input voltage and frequency
variation.
• The instrument shall be able to generate A/C voltage and current at different frequencies
and phase angles to be suitable for all types of testing of relays (both Static and EM type).
The kit shall have df/dt facility (i.e. frequency variation with respect to time). The kit shall
also generate D.C output as required for the relays. The kit shall also have analog inputs
for measurement of AC/DC current and voltages.
• The instrument shall be capable of being operated both, either through a computer or
manually (Without a Computer). A knob on the front panel of the equipment shall be
provided for the manual operation with all parameters to be displayed on the on-board
digital display.
• All generators for voltage outputs and current outputs shall be continuously and
independently adjustable in amplitude and phase with auto-ranging.
• Apart from self-calibration (Software), the system shall also be provided with a calibration
box as an independent external means of calibration.
• A Laptop computer pre-loaded with the easy to use relay testing software shall also be
provided for a fully automatic operation of the relay testing set. All hardware and software
shall be mentioned separately.
• The unit must be able to generate at least 15A (3 – phase) by itself and upto 30A (3 –
phase) in conjunction with a current amplifier.
It shall have 4 voltage outputs and 3 current outputs. All seven generators shall be
continuously and independently adjustable in amplitude and phase with auto ranging.
Technical Requirements:
1. Input to the Equipment
2. Basic unit
Voltage Outputs
4 phase AC : 4 x 0 – 150V
1 phase AC (L-L) : 2 x 0 – 300V
D.C (L-N) : ±180V
It shall also be possible to get the output of 0 – 300 V by interconnections.
3. Power
3 phase AC : 3 x 82 VA at 150 V
1 phase AC (L-L) : 1 x 140 VA at 300 V
DC (L-N) : 87 W
4.Current Outputs
3 phase AC : 3 x 15 A
1 phase AC : 1 x 45 A
DC (L-N) : 15 A.
Accuracy : ±0.3% of range
5. POWER
3 phase AC : 3 x 87 VA
1 phase AC : 1 x 250 VA
DC (L-N) : 3 x 87 W
6. Frequency Output
Range
Continuous Signals : 0 – 2000 Hz
Transient Signals : 0 – 3.5 K Hz.
Resolution SW : 1 m Hz.
HW : 250 μ Hz.
.Accuracy : ± 1ppm
Power : 75 W
Portable secondary injection test kits of reputed make having the following facilities:
Range
Current : 0 to 50A, AC
Range : 0-600V
The unit shall be a stand alone for field installation on a transformer valve. It shall
continuously monitor the moisture in the transformer oil and the temperature on the
transformer oil at the sampling point. The system shall detect the following:-
a) Ingress of moisture in the transformers (through the breathing system and bushing
seals)
The system shall have a sensor and the electronic unit housed in an enclosure.
Technical Requirements:
1. Sensor
The sensor shall contain a thin film capacitive type moisture sensor and a thin film Platinum
RTD type temperature sensor. The sensor shall have a 1.5” NPT male threads to be mounted
on the transformer valve.
2. Sensor ranges
Sensor operating ranges:-
Moisture : 0 – 100% relative saturation
Temperature : -40 to 150 deg. C
Accuracy
Moisture : ± 2% (absolute) @ 25 deg C
Repeatability
Moisture : ± 1% (absolute) @ 25 deg. C
Response Time : 2hrs in oil (with valve and fitting) at 80% of the step
function
3. Electronic unit
Analog outputs : Non-isolated, 4-20mA
Maximum load per output: 300 ohms at 24v DC
Digital display : 8 digit green LED
4. Enclosure
Stainless Steel enclosure, standard NEMA 4x type (IP66)
Wiring access shall be available.
• A sensor that shall measure the moisture and the temperature of the oil
• Two non-isolated analog outputs shall be available for measuring the relative humidity
of the
• oil and the temperature of the oil at the sampling point
• Terminal blocks shall be supplied to connect the power supply and the analog outputs
• High intensity display for temperature, %RH and ppm shall be available.
EMI/RFI/ESD compatibility: Shall meet the IEEE C37.90; IEC 255-4; and EN 55011,
61000-4-2, 61000-4-3, 61000-4-4, 61000-4-6 and 61010-1 standards
Environmental Tests : Shall meet the standards IEC 682-1 Ad, 682-2 Bd, 682-3 Ca, and
EN 60255-21-1
Range : 0 to 30 V DC
• Instrument should be provided with dual display mode for simultaneous reading of
numerical L/C/R values and Dissipation Factor / Quality Factor of any capacitive or
inductive measurement.
• Instrument should be provided with ‘auto power off’ and should have provision to select
auto range or manual mode. Should be provided with Dual-Frequency mode (120 Hz., and
1 kHz.,) and should be capable of measuring transformers, electrolytic/ceramic capacitors,
standard LCR componentsInstrument should be equipped with Parallel / Series Mode and
should show all the measured values in series or parallel equivalent circuits. (Parallel
mode for capacitance and resistance measurements and the series mode for inductance
measurements)
• Instrument should also be equipped with Tolerance mode for component sorting. The
tolerance modes should be 1 %, 5 %, and 10 % for the Inductance, Capacitance and
Resistance functions respectively.
• Provision should be there for automatic storage of the values into memory while testing
abatch of similar components. Calculations should be performed and indicate the
maximum value, the minimum value and the average value of the batch of components.
• Provision to calibrate the meter internally at both the upper and lower limits of each
range. Should be able to calibrate externally to compensate for connector residues
present while using test leads.
Relative mode should be available to store the reference value.
6. Capacitance Range : 1 nF, 10 nF, 100 nF, 1 µF, 10 µF, 100 µF, 1 mF, 10
mF
7. Accuracy
Inductance : ±0.7%+(Lx/10000)% at 1 H, 10 H
• The infrared thermal imaging and measurement system shall be based on microbolometer
technology. The system shall be lightweight, hand-held with on-board battery. It shall
include a single lens (standard) of 24º lens.
• The system shall have an interpolating electronic Zoom function in steps of 2, 4, and 8. It
shall provide color infrared image display on LCD viewfinder and on external display. The
system shall have the capability of automatically recognizing the lens and calibrating the
system for new lens. The system shall also have facility to see the visual image which
shall automatically be associated with thermal image. An LCD 4” display with in-built
remote control shall also have to be provided. The system shall have a laser pointing
facility also. A flash lamp for proper visual image display in dark conditions shall also be
provided.
• The system shall have the capability to record and store upto 50 images in inbuilt Flash
memory and up to 500 images on a removable PC card depending on the card memory
capacity. A provision to record voice and pre-defined text on each image file shall also be
provided. Voice recording via Bluetooth and predefined text via IR port on each image file
shall be provided.
• The system shall be able to display the temperature reading on any point on the screen
using 10 movable cursors with an auto – spot feature for maximum or minimum
temperatures in the whole image. 14-bit digital image storage shall be possible.
Radiometric image recording at the rate between 25Hz and 0.5Hz allowing recording of
clips between 24 sec. and 20 min. recording time shall be available. Play back facility of
infrared images shall also be available in the camera. Image gallery facility shall be
available for easy reviewing and recalling of stored images.
• The System shall also have at least two programmable keys, which can be programmed
as direct function keys.
Technical Requirements:
The other minimum specifications of the system (but not limited to) are: -
Array.
6. Accuracy : + 2º C
14. It shall be possible to control the system functions with minimum keys.
15. Automatic reading of center cross - point temperature shall be possible. The cross - point
shall be movable over the entire image.
16. Dual colour isotherm either as solid or transparent, Area and Difference Temperature
(different between two cursors), horizontal or vertical profile mode functions shall be
available.
17. Auto or manual Level and span adjustment facility shall be available. Also auto level and
span adjustment facility based on histogram equalization shall also be available.
20. It shall be possible to store the image in a full dynamic 14-bit format.
21. It shall be possible to freeze the image and store a single image or multiple images either
continuously or periodically.
22. Customer defined color scale utilization shall be possible and a minimum of 10 color scales
shall be available.
23. Reflected ambient temperature correction facility shall also have to be provided.
24. The system shall have Firewire, USB, RS 232 and infrared port for downloading all the image
and data into PC directly from the camera and the necessary accessories shall have to be
provided for doing so.
25. Profile and setting storage for multiple users shall be available.
ANALYZING SOFTWARE
The software for report generation and analysis shall also be supplied. It shall be OLE
compliant. Report formation wizard and templates shall be available for easy and fast report
formation. Histogram, Formula, Zoom and profile tools shall be available. It shall also be
possible to insert a visual image (photo) in the report. It shall also be possible to insert logos in
the report. A marker function shall be available. It shall be possible to create table in the report
with cells being defined as field or test cells. The field cells shall be directly connected to the
data on the IR images. It shall also be possible to insert a text object. AVI Creation shall be
possible. Drag and drop facility for easy report generation shall be available. Conversion of the
report in PDF format shall be possible.
1. GENERAL
The Portable Cable Fault Locator shall be a self-contained unit capable to detect condition and
fault of under ground distribution and transmission power cable that comprising of
(a) Surge Generator
(b) DC Tester/ Burner
(c) Arc Reflection Filter,
(d) Surge Pulse Coupler and
(e) Voltage Decay as one package according to the technical specifications stipulated in this
tender documents.
The instruments should provide the following fault location techniques:
• Time Domain Reflectometry
• Arc Reflection
• Differential Arc Reflection
• Surge Pulse Reflection
• Voltage Decay
2. Mode Selections
Surge, Proof/Burn, Ground & Arc Reflection
3. Test Technique.
Test technique should be based on differential Arc Reflection so as to eliminate unwanted and
confusing reflections leaving only the location of fault. This Differential Arc Reflection
Technique should be possible without a need to use extra channel or healthy phase. The
Differential Arc Reflection Analysis systems should work on Windows operating software with
Touch screen interface for ease of use.
All the four systems i.e dc/tester burner, surge generator, Arc Reflection Filter and Radar
coupling should be integrated into one package/unit for ease of use.
The unit shall be versatile, capable supportive to locate faults in a wide variety of power
distribution cable networks through modern, integrated coupling for multiple cable testing and
fault locating technologies to reduce the fault location time. The unit shall be complete in all
respect with all the necessary items, accessories and test techniques and shall be ideal to
ensure its maximum performance to detect faults or conditions for short, medium or long under
ground distribution cable networks alone the roadside of a busy cosmopolitan city.
The unit should be compact and rugged in construction to endure years of hard and rough
field use. The unit shall have the capability to deliver high adequate energy output that is
necessary to ascertain easily the condition and break down faults in cable, joints and
terminations and long cable circuits. The unit shall have to be fitted with necessary wheel kits
for its convenient transportation in the uneven roads and rough working environment. The
dimension, construction and the features of the unit shall be user friendly and suitable to
operate under the conditions that are as follows :
6. Safety
The unit shall have all the facilities to ensure highest possible safety standard during its
Operation. Maintenance and preservation. Some of the major points that the unit shall have
are as follows: -
• Convenient length and adequate size insulated high voltage output cable
• Interlock for zero start voltage
• Provision for external interlock
• Lamps indicate high voltage
• Automatic discharge and grounding upon shut down
• Redundant ground connection
• Circuit breakers for the input power overload protection
• Shall have easier pinpointing of difficult faults
• Strong surge at lower voltage to minimize cable stress
• High energy to test longer cables
• Easy instrument interface to reduce the training time.
• Meters should remain active even when power is off
• Visible mechanical inter grounding system confirms grounding of cable & capacitor
• Detachable cable reel assemblies should be available
7. Voltage Output
(a) Surge Mode :
0 to 8 KV @ 1500 Joules
0 to 16 KV @ 1500 Joules
0 to 32 KV @ 1500 Joules
(b) Surge Interval : 2 to 10 sec. Variable, 5 S full charge
(c) DC mode : Built-in DC timer - 0 to 60 Minutes
(d) Burn current capability should delivers up to 500 mA to condition stubborn faults or splice
failures.
(e) Polarity : with respect to ground- Negative
8. Current Output
(a) DC Mode : 0-500mA Burn Current
(b) Duty Cycle : continuous
9 Energy
(a) Stored Energy : Min. 1500 Joules constant energy at all voltage range.
10 Metering
(a) Kilovolt meter : 0 to 40 kV(min)
(b) Milliam-meter : 0 to 500 mA
Instrument should have Built-in DC test timer — zero to 60 minute timer for
automated DC proof tests
Required Specification
1. The portable equipment shall measure and record a circuit breaker timing cycle including
closing and opening of the main contacts, resistive contacts and auxiliary contacts.
2. The equipment shall be intended to use in high voltage substations (230 kV & 400 kV) .
The equipment shall also be capable for finding opening and closing time of the close or
trip circuit which carry DC voltage upto 250V.
3. The equipment shall be expandable modular concept and upto 48 + 48 time measuring
channels. The equipment shall be stand lone and it shall have one tool box for all breaker
testing and shall be capable to perform offline and online measurements. The equipment
shall have analog and digital transducers to make contact travel measurements and also it
shall have calibration module for stable accuracy. The timing channels shall be
galvinically isolated and allow measurement of resistive contacts and series connected
breaker chambers with out disconnection.
4. The system shall have provision to expand upto 48 time measuring channels. A built in
program shall permit easy selection of different sequences of breaker control pulses. The
time delay between pulses shall be easily set by manual control. The program unit shall be
suitable for the control of trip / close coil currents up to 25A.
5. The software existing in the system shall have predefined templates to perform automatic
testing and it shall have active interference suppression while testing in high voltage
switchyards. The equipment shall have integrated static contact resistance measurement
facility and it shall also measure automatically the coil voltage, current and auxiliary
contacts. The equipment shall be capable to produce enhanced reports, assessment and
archiving of results.
7. All accessories necessary for satisfactory operation and testing of the breaker shall be
provided.
8. The analyzer shall have adequate memory to store at least 10 readings for later recall and
review. There shall be facility to connect the system to the computer link, which will help to
store all the results on a storage device for the comparison at a later stage. The analyzer
shall have automatic transducer calibration facilities.
9. For good resolution a sampling frequency of 40kHz (min) shall be provided. The analyzer
shall provide data on over travel and penetration of the contacts along with the capability
for continuous long term monitoring (online) of a circuit breaker.
Range : 50-100ppm
Range : up to 400KV
Required Specification
1. The detector shall supply high voltage detectors suitable for detecting the presence of high
voltages with complete operator safety. Typical requirements are as follows:
• They shall have built in checking circuits to ensure the equipment is operating satisfactory
and produce clear visible and audible signal.
• They shall have stable operating ranges with no switching required to pre set the voltage
levels.
• The equipments shall be insensitive to induced voltages to ensure no wrong indications
will occur.
• A suitable tester shall be provided to check for satisfactory condition of the insulated stick.
• The equipment shall be light for case of use, typically 0.5 kg.
These shall be suitable for comparison of phases and detection of voltage on 11,000 volt
systems and suitable for outdoor use. Their voltage graduated readings shall be completely
legible and precise.
3. They shall be provided with sticks of suitable length, typically 1.25 m long, and interconnected
by suitable insulated flexible leads which will provide an operating distance of 2.5 meters. The
phase testers shall be complete with built-in check to ensure they are operating satisfactorily.
Means of checking the insulation of the sticks shall also be provided. The equipment shall be
light, typically 1.2 kg, and be housed in a non-metal case.
4 Each detector / phasing sticks shall be supplied with a suitable insulation / condition tester.
Required Specification
12. Computer Software : software should be included for data storage, report
printout, and download of data to a PC.
13. Following Optional accessories should be offered along with the instrument
a) Calibration Standard
12. Should have facility for operator to enter the ratio of the transformer and all of its taps. This
allows the operator to know immediately when a tap is outside the acceptable limits. It should
also have facility to enter pass/fail limit so problem taps can be easily flagged.
Range : Provision for 6 phase current output to test the differential relays
Current : 6 x 0-12.5A
3 x 0-25A
1 x 0-75A
Voltage : 4 x 300V
1 x 600V
Frequency ; 10 to 1000Hz
• The system is to measure and evaluate the characteristic PD quantity "apparent charge"
according to IEC 60270. It shall be computer based and shall have phase resolved PD -
data acquisition, storage, analyzing and post processing features.
• The system shall record and store the magnitude of the apparent charge, the phase
position and the event-time of each PD signal and simultaneously. The system shall be
monitoring continuously in real time mode. It shall be possible to visualize and analyze the
stored PD data without any loss of information.
• The sensitivity range shall be from 1 pico Coulomb (pC) to 100,000 pC (auto-ranging 0-93
dB). It shall have 30MHz wideband pre-amplifier for fault location. Double pulse resolution
of 10 us shall be available. The system shall have minimal superposition error and single
pulse recognition capability upto 100KHz pulse repetition rate shall be possible. A PD
database shall be available for easier fault recognition
Required Specifications:-
Hardware Equipment:
1. 19" - 3 HU plug-in
6. Software-Protection-Adapter (SPA)
The system shall be supplied with all the sensors for PD fault detection on Transformers,
Generators and Motors.
The instrument must measure contact resistance of high current circuit breakers and other
transmission element with high precision and suited for testing in high inductive fields.
• Instrument shall have Auto, continuous & normal operating modes of operation.
• Instrument shall weigh less than 15 kg and shall be a Portable unit, designed for field
use in a rugged case.
• Instrument shall have on board Keyboard for entering data. On board memory for up to
300 tests, with test information. RS232 port for data download to computer.
• Current selection shall be programmable through keypad on face of the instrument for
better resolution.
1. The equipment shall be suitable to measure capacitance and tan delta of EHV class
transformer windings, condenser bushings, shunt reactor winding and other electrical
equipments on site upto 10KV and Line frequency (50Hz) automatically without a need to
balance the bridge.
2. The equipment shall comply with the requirements laid down in internationally acceptable
standard.The test set should meets the requirements of both the IEC-1010 and the CE
mark specifications. The test set also should meets the shock and vibration requirements
of the ASTM D999.75 standard.
3. The equipment shall be complete with measuring bridge, HV power supply unit, Internal
SF6 gas filled standard reference capacitor, connecting cables, Printer and all other
accessories required for measurement of capacitance, tan delta automatically.
4. Instrument should be able to record and stores sets of test results for retrieval and analysis
with date and time stamped. Stored results should be easily transferred to a PC. RS-232
serial interface for downloading the test results to a PC.
Bar code wand and PC software should be provided for recording an alphanumeric test
identification in the field.
5. Instrument should Includes a battery/line operated printer for a hard copy of the test results
on site without a need to download onto a computer
6. The test set should be microprocessor based and should be able to be operated
independently without the need for a dedicate PC. Data Storage facility should be
available
7. Equipment Specification
7.1 Portable Capacitance & tan delta measuring bridge for EHV class transformer,
condenser bushing etc.
Voltage Selection : 0 to 12 KV, 10V resolution
Test Range
Capacitance : 1 pF to 1 .1 micro-farads, 0.01pF maximum
resolution
Tan delta range : 0 to 200%, 0.01% maximum resolution
Instrument should have Open-ground detector to ensure proper grounding before test.
All necessary inter-connecting cables & other accessories required during the
measurement shall also be included in the scope of supply. All high voltage points shall
be provided with interlocked facility for complete safety of the equipment and the
operating personnel.
7.8 Safety Qualifications The test set meets the requirements of both the IEC-1010 and the
CE mark specifications. The test set also meets the shock and vibration requirements of
the ASTM D999.75 standard.
7.9 Instrument should meet EN50081/2 EMC, Vibration & low voltage directives requirements
The Tan delta should come in two units, Control and power supply and the total weight
including control and power unit should not exceed 65Kg for ease of transportation.
7.10 Maintenance Test Data Management Software
• Suitable software should be provided for Data trending, predictive failure analysis
and database management.
• Software should have built-in information processing for equation calculations,
temperature and humidity correction factors and charting historical results, stored
in software or imported from other party’s proprietary database software.
• Users should be able to create new forms or customize forms and report
generation should be possible.
• Software should be able to import previous test data from other
manufacturer/sources
• Test instrument control and data acquisition should be possible from software for
complete automation.
The offered system shall be a norm-compliant (IEC 61000-4-30, Class A) and 3rd party certified
field instrument. The instrument shall be dust- and splash-proof (IP 65), with a high performance
that meets these demands. It shall have remote communication which can download the measure
data and re-configure the unit from the office without going to the location where it is installed. It
shall have no moving parts and measures all parameters in national and international norms like
the EN 50160, and captures disturbances, like transients, sags and swells simultaneously.
Required Specification
1. Voltage Inputs
2. Current Inputs
1. The instrument should be lightweight, portable and operate on live DC Battery Banks
without any down time.
2. The instrument should be able to measure impedance and dc voltage values on Lead-acid
as well as Nickle-Cadnium Cells upto 7000 Ah capacity.
3. The Impedance calculations should be automatic. The equipment should have On-board
Pass/Warning/ Fail Indication based on the type of interpretation of readings.
4. The equipment should also have a inbuilt printer to print this data.
4.1 The equipment should be capable of storing more than 2000 sets of readings
in up to 300 tests (cell impedance, cell voltage and interconnecting strap
resistance).
4.2 Equipment should be able to measure large battery systems having 275Vdc
across the output
5. Receiver Voltage Range and Resolution : 1 to 2.500 V dc, 1mV resolution
2.5 to 25.00 V dc, 10mV resolution
6. Receiver Impedance Range and Resolution : 0 to 1.000mΩ, 1μΩ resolution
1 to 10.00mΩ, 10μΩ resolution
10 to 100.0 mΩ, 0.1 μΩ resolution
7. Transmitter supply voltage : 100 to 120V, 50 Hz ; 210 to 250V, 50 Hz
8. Transmitter output current : 10A nominal
9. Display : Digital LCD meter
10. Receiver accuracy : +/- 0.3% of rdg (ac impedance),
1. The Instrument should be manually balanced instrument and capable to identify, track
and locate ground faults in ungrounded DC Battery systems – on line.
2. The instrument should be provided with digital display of voltage and current signal
amplitudes
3. The instrument should be operable in high electrical noise environment with the
provision to adjust the strength of test current.
4. Bridge measurement of fault resistance and system capacitance should be possible with
the instrument
5. Charging system should be soft start to prevent sensitive relay tripping
6. The instrument should be immune to distributed noise.
7. The Instrument’s fault resistance measurement range should be from 1 ohm to 100 k
ohm
8. The Instrument should comprises of a Transmitter that operates on mains and a
portable, convenient, hand-held receiver that operates on battery
9. The transmitter should be capable of determining fault magnitude and severity before
tracking the fault.
10. The measured readings should not be affected by any presence of ac ripple or dc current
up to 15 amperes
11. Receiver should have gain control for optimal resolution
12. The transmitter should be caster-mounted for easy portability and should incorporate a
resistance and capacitance bridge
13. It should be possible to null out the system capacitance from the measurement to
prevent erroneous readings on the receiver
14. Separate 3-digit LCD meters for volts and current on Transmitter should be provided with
an accuracy of +/- 5%
15. Digital meter display up to 1.999 with three gain selections should be available on
Receiver
16. Required Specifications:
a) Power Supply : 240V ac, 50 Hz, 200 VA max (Transmitter), 1 x
9V alkaline battery (Receiver)
b) Battery life time of Receiver : Upto approx. 40 hrs continuous
usage
c) Source Voltage : 0 to 50V rms (should be variable)
d) Source Current : 0 to 2A rms (Load dependent)
e) Source Frequency : 20 Hz +/- 2%
f) Fault resistance : 1 to 399 kW at 50V;
bridge accuracy can be +/- 10%
g) Line Capacitance : 0.01 to 11.1 uF;
bridge accuracy can be +/- 20%
h) Temperature range : 0 to 40 deg C (operating),
-20 to +55 deg C (storage)
The contractor shall set up and handover fully furnished electrical lab with all the test
instruments, tools, work bench and furniture.
4.00.00 Transformer Oil Testing Lab and Transformer Oil Filtration Plant
The bidder shall include in their scope the supply of one Transformer Oil Testing Lab
equipment and Oil Filtration Plant to facilitate regular testing of oil samples taken from
the transformers.
One (1) no. Stream Line Oil Filter Machine of 6000 Ltr./Hr. capacity with four (4) nos.
portable Oil Tank each of suitable capacity considering the maximum transformer
size of 200MVA
6000 LPH High Vacuum Transformer Oil Filtration Plant, mounted on spring chassis
supported by 4 (four) Pneumatic Tyres, capable of performing function of removing
solid particle, water, gases etc. from transformer oils. The plant can also be used for
filling oil in to the transformer (assembled) at rated capacity of 6000 LPH. It shall be
capable of re-circulating hot oil in degassed, filtered condition through the transformer.
The plant shall be equipped with oil inlet pump (gear pump), oil discharge pump
(centrifugal pump), Vacuum Pump (1st stage roots pump), Rotating Oil sealed pump,
2nd stage Roots (booster) Pump, Air compressor (for edge filter cleaning), water
circulating pump, heaters, thermostat, pressure gauges, electrical control panel, 2 nos.
of 40 meters high temp. nitrile rubber oil hose, etc. & properly illuminated and shall be
provided with all requisite accessories for achieving the following performance :
The specification for portable 1000 gallons / hr oil filtration plant shall be same as
mentioned in clause 4.01.00
A GRINDING MACHINES
B GENERAL EQUIPMENT
TOOLS
4. Work benches - 3
5. Fitter vice - 2
C WELDING MACHINES
2. Soldering irons - 2
3. Brazing hearth - 1
4 Bearing pulley - 1
NOTE:
Any other standard Tools & Facility revised for Electrical workshop are to be supplied.