Contents
1. Specifications
2. Dimensions
3. Center of gravity
4. Piping diagram
5. Wiring diagram
6. Electrical current characteristics
7. Sensible capacity table
8. Fan characteristics
9. Sound data
10. Accessories
1
+00E15-3F1_01EN.book Page 2 Tuesday, March 22, 2016 4:10 PM
MMK-AP___3H2UL E15-3F1
1. Specifications
Air intake grille and side panel Moon white (Munsell 2.5GY9.0/0.5)
Unit lbs 33 33 33 33 33 33
Total weight
Packed unit lbs 42 42 42 42 42 42
Fan unit Standard air flow (High/Mid/Low) cfm 340/270/230 350/280/230 350/280/230 490/390/320 490/390/320 600/440/340
Motor W 30 30 30 30 30 30
Sound pressure level (High/Mid/Low) (*1) dB(A) 36/32.5/30 39/34/30 39/34/30 43/38/34.5 43/38/34.5 47.5/40.5/35
Note
(*1) The actual values in an external operating environment are generally higher than the indicated values due to the contribution from ambient
noise.
2
+00E15-3F1_01EN.book Page 3 Tuesday, March 22, 2016 4:10 PM
E15-3F1 MMK-AP___3H2UL
2. Dimensions
MMK-AP0073H2UL, AP0093H2UL, AP0123H2UL, AP0153H2UL, AP0183H2UL, AP0243H2UL
41.3"(1050)
CAUTION
Connecting pipe cannot be connected to
the right side of the indoor unit when
conduit pipe is used.
When connecting pipe is connected on
the left or bottom of the indoor unit,
connect the conduit pipe on other side.
2.9"(73.5)
12.6"(320)
2.0"(50) 2.0"(50)
0.3"(7)
0.3"(7)
Heat exchanger Knock out system
Knock out system
2.0"(50)
Unit: in (mm)
6.2"(157)
Knock out system 2.8" 3.1"
(72) (78)
6.4"(163)
Hole for power supply cable 1.6"(40) 3.2"
Refrigerant connecting pipe (Liquid) 12.3" (0.49 m) (82) 0.9"(26)
Installation plate hanger Refrigerant pipe connecting port (Liquid) B
Refrigerant connecting pipe (Gas) 13.4" (0.34 m) Remote control holder
Drain hose 19.7"(0.5 m)
Refrigerant pipe connecting port (Gas) A
B C
12.6"(316)
1.6"(40)
1.6"(40)
Distance Comments
A 2.0"(50) or more
Hanger Hanger B 33.5"(850) or more For exchange of cross flow fan
6.0" 4.3"
1.9"(47) 8.5"(215.5) 10.3"(262.5) 10.3"(262.5) (153.5) (109) C 6.7"(170) or more
Installation plate
Unit:in (mm)
Model MMK- A B
3
+00E15-3F1_01EN.book Page 4 Tuesday, March 22, 2016 4:10 PM
MMK-AP___3H2UL E15-3F1
3. Center of gravity
4. Piping diagram
Strainer
Capillary Tube
Pulse
Motor
Valve
Sensor
Fan
Sensor (TCJ)
(TC2)
Sensor
(TC1)
㹋 Fan Motor
Sensor
(TA)
4
5.
E15-3F1
B
A
5
䣙䣊䣋 䣄䣎䣍
䣎䢳 䣎䢴
Control P.C board for indoor unit
䢪䣙䣊䣋䢫
Power Supply WIRED REMOTE
208/230-1-60 FLOW SELECTOR UNIT
(Sold separately) CONTROL
(Sold Separately)
MMK-AP0073H2UL, AP0093H2UL, AP0123H2UL, AP0153H2UL, AP0183H2UL, AP0243H2UL
MMK-AP___3H2UL
+00E15-3F1_01EN.book Page 6 Tuesday, March 22, 2016 4:10 PM
MMK-AP___3H2UL E15-3F1
6
+00E15-3F1_01EN.book Page 7 Tuesday, March 22, 2016 4:10 PM
E15-3F1 MMK-AP___3H2UL
High Wall type (MMK-AP___3H2UL) TC: Total capacity [Btu/h] SHC: Sensible capacity [Btu/h]
7
+00E15-3F1_01EN.book Page 8 Tuesday, March 22, 2016 4:10 PM
MMK-AP___3H2UL E15-3F1
High Wall type (MMK-AP___3H2UL) TC: Total capacity [Btu/h] SHC: Sensible capacity [Btu/h]
8
+00E15-3F1_01EN.book Page 9 Tuesday, March 22, 2016 4:10 PM
E15-3F1 MMK-AP___3H2UL
8. Fan characteristics
9
+00E15-3F1_01EN.book Page 10 Tuesday, March 22, 2016 4:10 PM
MMK-AP___3H2UL E15-3F1
9. Sound data
3.28 ft
(1 m)
3.28 ft
(1 m)
Microphone
MMK-AP0073H2UL MMK-AP0093H2UL/
Sound pressure H-M-L AP0123H2UL Sound pressure H-M-L
level (dB (A)) 36-32.5-30 level (dB (A)) 39-34-30
90 90
H H
M M
80 80
L L
Octave band sound pressure level (dB)
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 20 Audibility limits of
Audibility limits of NC-20
NC-20 continuous white level
continuous white level
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
MMK-AP0153H2UL/ MMK-AP0243H2UL
AP0183H2UL Sound pressure H-M-L Sound pressure H-M-L
level (dB (A)) 43-38-34.5 level (dB (A)) 47.5-40.5-35
90 90
H H
M M
80 80
L L
Octave band sound pressure level (dB)
70 NC-70 70 NC-70
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
10
+00E15-3F1_01EN.book Page 11 Tuesday, March 22, 2016 4:10 PM
E15-3F1 MMK-AP___3H2UL
10. Accessories
Remote control
• Louver setting
• Clock
WH-L15SE
• Timer function
- ON/OFF timer (10 min. step)
- Everyday timer
- Sleep timer
- COMFORT SLEEP timer
• High power mode
• QUIET mode
• One-touch pre-set memory
• A/B temperature display switching
11