GA Linear
Bar Grille
ASLI GA is a type of grille made up of 2 sets of air foil
blades with the horizontal blade in front and vertical set
air foil blade behind.
Features Accessories
• The horizontal blades are fixed meanwhile the vertical air foil blade is adjustable. G1 Opposed blade damper.
• The grille will come in more sections for blade length that is more than 500mm.
• Approximately 60% free area when blades are fully open.
Pitch
Standard Size A B D
Model
WxH Duct Size Wall Size Face Size
400 x 150
450 x 150 W+10 W+15 W+48
GA-A
500 x 150 H+10 H+15 H+48
500 x 250
60
G1 Sectional View
600 x 300 Throw Ceiling 5.3 - 9.5 6.5 - 10.8 7.9 - 12.1 9.0 - 13.2 10.2 - 14.3 11.0 - 15.6 12.0 - 16.9
0.18
700 x 250 (m)
Wall 8.5 - 15.2 10.7 - 16.9 12.7 - 18.3 14.2 - 19.8 15.2 - 21.3 16.2 - 22.5 16.9 - 23.8
NC - 21 25 31 35 38 40
CMH 1405 1755 2105 2457 2808 3160 3510
650 x 300 Throw Ceiling 5.8 - 10.1 7.3 - 11.4 8.7 - 12.6 9.7 - 13.9 10.8 - 15.1 11.7 - 16.4 12.6 - 17.6
0.195
550 x 350 (m) Wall 9.1 - 15.8 11.2 - 17.2 13.2 - 19.0 14.7 - 20.7 15.8 - 22.1 16.8 - 23.5 17.7 - 24.9
NC - 21 25 31 35 38 40
CMH 1512 1890 5568 2646 3024 3402 3780
700 x 300 Throw Ceiling 6.1 - 10.6 7.8 - 11.8 9.3 - 13.1 10.3 - 14.5 11.3 - 15.9 12.3 - 17.2 13.3 - 18.5
0.21
1000 x 200 (m) Wall 9.6 - 16.5 11.6 - 18.1 14.0 - 19.7 15.3 - 21.5 16.6 - 23.3 17.5 - 24.5 18.7 - 26.0
NC - 21 26 31 35 38 41
CMH 1620 2025 2430 2835 3240 3645 4050
750 x 300 Throw Ceiling 6.5 - 11.1 8.3 - 12.5 9.6 - 13.8 11.0 - 15.5 12.2 - 16.9 13.3 - 18.2 14.2 - 19.8
0.225
900 x 250 (m) Wall 10.0 - 17.1 12.1 - 18.6 14.5 - 20.5 16.0 - 22.4 17.2 - 24.0 18.0 - 25.6 19.3 - 26.9
NC - 22 26 31 36 39 41
CMH 1728 2160 2592 3024 3456 3888 4320
Throw Ceiling 6.7 - 11.4 8.5 - 13.0 10.2 - 14.3 11.4 - 16.0 12.5 - 17.7 13.6 - 19.2 14.7 - 20.4
0.24 850 x 300
(m) Wall 10.2 - 17.5 12.5 - 19.5 14.8 - 21.1 16.6 - 23.1 17.6 - 24.7 18.6 - 26.3 19.9 - 27.7
NC - 22 26 32 36 39 41
CMH 1836 2295 2754 3213 3672 4130 4590
Throw Ceiling 6.9 - 11.8 8.6 - 13.4 10.4 - 15.0 11.6 - 16.6 12.9 - 18.2 14.3 - 20.0 15.1 - 21.1
0.255 850 x 300
(m) Wall 10.4 - 18.0 12.9 - 20.0 15.2 - 21.9 17.3 - 23.8 18.2 - 25.5 19.3 - 27.0 20.5 - 28.5
NC - 22 27 32 36 39 41
CMH 1944 2430 2915 3402 3888 4374 4860
Throw Ceiling 7.0 - 12.3 8.9 - 14.0 10.7 - 15.7 21.1 - 17.4 13.3 - 19.1 14.7 - 20.6 15.5 - 21.7
0.27 900 x 300
(m) Wall 10.5 - 18.4 13.0 - 20.6 15.6 - 22.6 17.5 - 24.5 18.7 - 26.5 19.6 - 27.9 21.0 - 29.3
NC - 22 27 32 36 39 42
CMH 2160 2700 3240 3780 4320 4860 5400
Throw Ceiling 7.3 - 12.9 9.3 - 14.8 11.3 - 16.9 13.0 - 18.4 14.2 - 20.2 15.5 - 21.7 16.6 - 23.0
0.3 1000 x 300
(m) Wall 11.0 - 19.5 13.6 - 21.7 16.4 - 24.0 18.6 - 26.0 19.9 - 27.2 21.0 - 29.5 22.5 - 31.1
NC - 23 28 32 37 40 43
CMH 2304 2880 3456 4032 4608 5184 5760
Throw Ceiling 7.5 - 13.2 9.5 - 15.2 11.5 - 17.5 13.3 - 19.4 14.4 - 21.4 15.8 - 22.1 17.0 - 23.7
0.32 800 x 400
(m) Wall 11.4 - 19.9 14.1 - 22.2 16.7 - 24.7 18.9 - 26.9 20.2 - 28.7 21.7 - 30.5 23.0 - 32.0
NC - 23 28 32 37 40 43
• Throw is based on terminal velocities of 0.5 m/s - 0.25 m/s respectively.
• NC value is based on a room absorption of 10 dB, re 10-12 watts.
• Dash (-) in space indicates NC value less than 20.
GA Order Code
Model Materials Accessories W H
GA A G1 N350 150