Calibration Procedure
Calibration, Level Measurement October 9, 2015

Flow Indicator
JUMO UK Flow Products

How to calibrate the level instrument with DP type Capillary Seal sensors

The use of capillary with fluid inside will the make us to have nice and careful calculation to find
what is the range between 0% – 100%.  Below is some examples how to find calibrated range
for many possible position of the DP type Capillary Seal Level transmitter.

The information given is: H = 100 Inch (Center to Center), Process SG Liquid = 1, h = 50
Inch, SG fill fluid = 1.2. What is the calibrated range? what is the required URV and LRV?
for cases below:

1. The first case (atmospheric) is as follows:

To  find  a  range  of  0%  ­100%  level  of  process  fluid  with  DP  Type  Level  value  corresponding
instrument is as follows:

0% ­> Under these conditions the fill fluid in the capillary has put pressure on the sensor even
though the tank is empty.  DP  received  by  the  sensor  is  equal  to  or  50  h  InFillFluid  InFillFluid
which has SG = 1.2. To make it dimensionless InH2O then 50 InFillFluid converted = 50 x 1.2 =
60 InH2O.

http://instrumentationtools.com/dp­diaphragm­capillary­seal­level­instrument­calibration­procedure/ 1/4
3/5/2016 DP Diaphragm Capillary Seal Level instrument Calibration Procedure | Instrumentation Tools

100% ­> In this condition experienced DP sensor is of (process fluid) + (fill fluid).  The pressure
sensor is received (100 InH2O) + (60 InH2O) = 160 InH2O.

Calibrated range is 60 InH2O to 160 InH2O.

2. The second case (atmospheric) is as follows:

To  find  a  range  of  0%  ­100%  level  of  process  fluid  with  DP  Type  Level  value  corresponding
instrument is as follows:

0% ­> Under conditions of process liquid tank is empty, the sensor will receive the DP negative
because it is higher than the tapping point kapilary (Zero Elevation). Is this a vacuum condition
because of pressure disuck or aspirated? I do not think so. DP nagative as head h and the level
of  process  liquid  H  will  push  each  other  in  opposite  directions.  The  higher  level  of  process
liquid,  the  higher  the  pressure  that  is  otherwise  against  the  head  h.  H  Head  pressure  is  50
InFillFluid = 60 InH2O but negative or – 60 InH2O.

100%  ­>  In  this  condition  experienced  DP  sensor  is  on  the  process  pressure  fluid­  pressure
fluid fill. The pressure sensor is received (100 InH2O) – (60 InH2O) = 40 InH2O.

InH2O calibrated range is ­60 to 40 InH2O.

3. The case of the third (closed tank roof) is as follows:

To  find  a  range  of  0%  ­100%  level  of  process  fluid  with  DP  Type  Level  value  corresponding
instrument is as follows:

0% ­> Under these conditions the fill fluid in the capillary has put pressure on the sensor from
both  sides  even  though  the  tank  is  empty.  Pressure  received  by  the  sensors  of  Hi  ­side
(tapping point below) amounted h InFillFluid or 50 InFillFluid which has SG = 1.2. To make it
dimensionless InH2O then 50 InFillFluid converted into 50 x 1.2 =  60 InH2O of the Hi­side.  Lo

http://instrumentationtools.com/dp­diaphragm­capillary­seal­level­instrument­calibration­procedure/ 2/4
3/5/2016 DP Diaphragm Capillary Seal Level instrument Calibration Procedure | Instrumentation Tools

received  pressure  sensor  ­side(tapping  point  above)  is  equal  to  H  +  h  InFillFluid  or  150
InFillFluid which has SG = 1.2. To make it dimensionless InH2O then 150 InFillFluid converted
into 150 x 1.2 =  180 InH2O. Wah both sides put pressure yes yes although the tank is empty?
DP when the level of 0% is obtained by subtracting the pressure (Hi­side) – (Lo­side).  Level
0% = (60 InH2O) – (180 InH2O) = – 120 InH2O. You know if, in the tank already contained gas
or vapor then with the Hi and Lo­side tapping point then by subtracting each method (remember
DP = difference) is the pressure of gas / vapor on the surface of the liquid will cancel out all by
itself.

100%  ­>  In  this  condition  experienced  DP  sensor  is  of  (process  fluid  pressure)  +  (Hi  fill  fluid
pressure)  –  (Lo  pressure  fluid  fill).  DP  received  sensor  is  (100  InH2O)  +  (60  InH2O)  –  (180
InH2O) =  ­20 InH2O.  Gas  or  Vapor  pressure  above  the  liquid  does  not  need  to  be  taken  into
account because it will cancel out the Hi and Lo side by itself.

Range is calibrated ­120 to ­20 InH2O InH2O.

4. The case of the four (closed tank roof) is as follows:

To  find  a  range  of  0%  ­100%  level  of  process  fluid  with  DP  Type  Level  value  corresponding
instrument is as follows:

0% ­> Under these conditions the fill fluid in the capillary has put pressure on the sensor from
both  sides  even  though  the  tank  is  empty.  Pressure  received  by  the  sensors  of  Hi  ­side
(tapping  point  below)  amounted  h  InFillFluid  or  50  InFillFluid  which  has  SG  =  1.2,  but
negative.  To  make  it  dimensionless  InH2O  then  converted  InFillFluid  ­50  to  ­50  x  1.2  =  –  60
InH2O of the Hi­side.  Lo received pressure sensor ­side  (tapping point above) amounted Hh
InFillFluid  or  50  InFillFluid  which  has  SG  =  1.2.  To  make  it  dimensionless  InH2O  then  50
InFillFluid converted into 50 x 1.2 =  60 InH2O.  Wah both sides put pressure yes yes although
the tank is empty? DP when the level of 0% is obtained by subtracting the pressure (Hi­side) –
(Lo­side). DP on Level 0% = (­60 InH2O) – (60 InH2O) = – 120 InH2O. You know if, in the tank
already contained gas or vapor then with the Hi and Lo­side tapping point then by subtracting
each method (remember DP = difference) is the pressure of gas / vapor on the surface of the
liquid will cancel out all by itself.

100%  ­>  In  this  condition  experienced  DP  sensor  is  on  (pressure  process  fluid)  –  (Hi  fill  fluid
pressure)  –  (Lo  pressure  fluid  fill).  DP  received  sensor  is  (100  InH2O)  –  (60  InH2O)  –  (60
InH2O) =  ­20InH2O.  Gas  or  Vapor  pressure  above  the  liquid  does  not  need  to  be  taken  into
account because it will cancel out the Hi and Lo side by itself.

http://instrumentationtools.com/dp­diaphragm­capillary­seal­level­instrument­calibration­procedure/ 3/4
3/5/2016 DP Diaphragm Capillary Seal Level instrument Calibration Procedure | Instrumentation Tools

Range is calibrated ­120 to ­20 InH2O InH2O.

Also Read: Level Indicators Working Principle

Instrumentation Search terms:

diaphragm type lt in closed tank
do capillary filled dp level transmitters shift urv and lrv?
instruments tools and lrv urv ranges method
level measurements on vacuum
what is procedure to calibrate both side capillary lt

POSTED BY S BHARADWAJ REDDY