PRODUCT DATA
OPERATION IN IP NETWORKS
When operating EagleAX in IP networks, either private
(e.g., VPN) networks must be used or protection against
the open Internet (e.g., by means of external firewalls)
must be ensured. See "Network Security."
FEATURES
• Reduced total installed cost: Existing standard
Ethernet/LAN infrastructure is used for
communication between EagleAX controllers, 3rd-
APPLICATION party BACnet® controllers, and BACnet® front-ends.
Costs are further reduced by the flexible and optional
EagleAX is a BACnet-compliant heating, ventilation, air use of Panel Bus I/Os (which allow manual override
conditioning (HVAC) building controller supported by independent of the controller, thus obviating the need
WEBs-AX Niagara framework, specifically tuned for Plant for external switches) and of onboard I/Os.
controllers.
Panel Bus I/Os allow for wiring lengths of up to 800 m,
It provides unparalleled energy efficiency through the use thus obviating the need to lay wire from field devices all
of a vast HVAC Application Library. the way back to the controller.
• Reduced life cycle cost: EagleAX supports the highly
EagleAX enables uniform graphical operation, control,
reliable Panel Bus I/O modules, which allow for
data logging, alarming, scheduling, and network
plugging and replacing without any need for re-wiring
management functions for HVAC and non-HVAC
or engineering, thus minimizing system down-time.
applications. Through its integrated web server, it allows
real-time access to all information through web-based
The Panel Bus is polarity-insensitive, thus reducing
graphical views.
potential wiring errors. Furthermore, Panel Bus I/O
EagleAX supports full remote engineering, including modules allow the predefinition of output safety
changes to the control program and the graphical user positions, ensuring safe operation even if
interface. This greatly supports reduction of life cycle and communication with EagleAX is disrupted.
maintenance cost. • Universal operation: Via Internet browser, EagleAX can
be operated from any place, from any PC and/or mobile
device connected to the (EagleAX) network! An
integrated web-server allows local and remote
operation by standard browsers.
Contents
APPLICATION ............................................................................................. 1
OPERATION IN IP NETWORKS ............................................................ 1
FEATURES ................................................................................................... 1
OPERATOR INTERFACE ......................................................................... 2
COMMUNICATION PROTOCOLS ....................................................... 2
BUS AND PORT CONNECTIONS ........................................................ 3
NETWORK SECURITY ............................................................................. 4
CONTROLLER SPECIFICATIONS ....................................................... 5
MODELS ....................................................................................................... 7
DIMENSIONS ............................................................................................. 8
31-00126-01
WEB-EAGLEAX26 CONTROLLER
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further
information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone
directory).
2. Honeywell Customer Care
1985 Douglas Drive North
Golden Valley, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China,
Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
31-00126—01 2
WEB-EAGLEAX26 CONTROLLER
BIAS
END
MID
RS232
GND1
GND2
485-2+
485-1+
485-1-
485-2-
GND
UI10
BI1
UI1
BI2
UI9
UI2
UI7
UI8
BI3
BI4
UI3
UI4
UI5
UI6
RS485-1
With the optional IF-LON2, a Free Topology Transceiver
(FTT-10A or FT-X1) allows a communication speed of 78
Kbaud. Max. cable lengths are 320 m to 2,200 m, J1 J8
24V-0
GND
BO1
AO1
24V~
BO2
BO3
BO6
BO7
BO8
AO2
AO3
BO4
BO5
AO4
IN7
IN8
IN5
IN6
IN4
IN
node object, plus application-specific LONWORKS objects. 1 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Modbus 9 M36759
Optionally, the two onboard RS485 interfaces can be used
(even simultaneously) for communication via Modbus RTU. Fig. 3. Top view (shown: model with onboard I/Os).
Modbus TCP communication is supported via the onboard
Ethernet RJ45 interface. See also EagleAX - Installation &
Commissioning Instructions for details. 1 8
MID
BIAS
END
Panel Bus
Optionally, one or both of the onboard RS485 interfaces J1 J8
CONNECTIONS
WARNING
Risk of electric shock or equipment damage!
WARNING It is prohibited to connect any of the RJ45 sockets
of the EagleAX Controller to a so-called PoE-
Risk of electric shock or equipment damage!
enabled device ("Power over Ethernet").
Do not touch any live parts in the cabinet!
Disconnect the power supply before making
connections to or removing connections from Modbus Connection
terminals of the EagleAX Controller or Panel Bus
I/O modules. The EagleAX controller can function as a Modbus
Do not reconnect the power supply until you have Master/Slave.
completed installation. For Modbus RTU, the RS485 wiring rules must be followed.
It is prohibited to power the EagleAX Controller with
the same transformer used to power other
controllers or devices.
Observe the rules regarding electrostatic discharge.
3 31-00126—01
WEB-EAGLEAX26 CONTROLLER
XX
MODBUS MODBUS MODBUS
WARNING
MASTER SLAVE SLAVE
NETWORK SECURITY
Honeywell hereby expressly states that the EagleAX is not
inherently protected against cyber attacks from the
MODBUS MODBUS MODBUS Internet and that it is therefore intended solely for use in
SLAVE SLAVE SLAVE
private, protected networks.
MODBUS
SLAVE
M36762
Unprotected Internet connections can expose the EagleAX
to cyber attacks from third parties who can then damage it
Fig. 6. Prohibited Modbus wiring topology (example). and connected facility components or cause them to
malfunction, or who can misuse it for illegal purposes for
Cables which the operator may then be held liable.
See section "EIA 485 Cable Specifications" in EagleAX When directly connected to the Internet, the EagleAX
Controller - Installation & Commissioning Instructions. automatically becomes a potential target for cyber attacks.
Corresponding protective measures are therefore essential
Use shielded, twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8. if safe and reliable operation is to be ensured.
You must use three wires: If it is not necessary for the EagleAX to be accessible from
• One wire for D1 = Modbus + the Internet, the EagleAX should be isolated from the
• One wire for D0 = Modbus - Internet via a suitable firewall.
• One wire for the signal common
If it is necessary for the EagleAX to be accessible from the
When using one pair for D1 and D0 and one wire of another Internet (e.g., in order to perform remote maintenance), the
pair for the signal common, CAT5 cable may also be used. use of a coded VPN connection is indispensable. Suitable
VPN routers are available from numerous third-party
For connection details, see EagleAX Controller - manufacturers in a wide variety of designs, for operation at
Installation & Commissioning Instructions. 230 V or 24 V.
31-00126—01 4
WEB-EAGLEAX26 CONTROLLER
5 31-00126—01
WEB-EAGLEAX26 CONTROLLER
31-00126—01 6
WEB-EAGLEAX26 CONTROLLER
MODELS
WEB-EAGLEAX26: with 26 onboard I/Os
NOTE: The maximum permitted number of Honeywell Panel Bus points is 400. The maximum recommended number of
integrated points is 400. The maximum recommended number of total points is 400.
For more details on the licenses, please refer to the Release Bulletin.
7 31-00126—01
WEB-EAGLEAX26 CONTROLLER
DIMENSIONS
2-15/64 (58)
8-29/64 (216) 1-61/64 (50)
24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
BIAS
END
MID
RS232
GND1
GND2
485-2+
485-1+
485-1-
485-2-
GND
UI10
BI1
UI1
BI2
UI9
UI2
UI7
UI8
BI3
UI3
UI6
BI4
UI4
UI5
RS485-1
J1 J8
1-25/32 4-21/64
(45) (147)
L1 L2 Tx Rx
GND
BO1
AO1
BO2
BO7
BO8
AO2
BO3
BO6
AO3
BO4
BO5
AO4
24V-0
24V~
IN7
IN8
IN5
IN6
IN4
IN
1 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Fig. 7. EagleAX Controller (shown: model with onboard I/Os), dimensions (in mm).
J8
J1
5-51/64
(147)
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or
modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any
liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.