You are on page 1of 12

Construction and Building Materials 176 (2018) 470–481

Contents lists available at ScienceDirect

Construction and Building Materials


journal homepage: www.elsevier.com/locate/conbuildmat

Performance of concrete beams reinforced with basalt fibre composite


rebar
Jason Duic a, Sara Kenno b, Sreekanta Das a,⇑
a
Department of Civil and Environmental Engineering, University of Windsor, Windsor, ON N9B 3P4, Canada
b
MEDA Limited, 1575 Lauzon Rd, Windsor, ON N8S 3N4, Canada

h i g h l i g h t s

 Presents application of a green alternative BFRP rebar in concrete beams.


 Discusses effectiveness of BFRP-concrete beams.
 BFRP-beams exhibited acceptable deformability compared to regular beams.
 Cracking moments and Vc in BFRP-concrete beams were found to be less.
 Recommends developing BFRP bent rebar to eliminate shear failure.

a r t i c l e i n f o a b s t r a c t

Article history: Basalt fibre reinforced polymer (BFRP) rebar is an emerging green construction material. In this research,
Received 20 August 2017 performance of concrete beams reinforced with BFRP rebar has been evaluated. Full-scale tests on eight
Received in revised form 24 April 2018 large-scale concrete beam specimens reinforced with either BFRP rebars or steel rebars were undertaken.
Accepted 25 April 2018
The test data were analysed to evaluate the performance of BFRP rebar reinforced concrete beams in
shear and flexure. It was found that at a low reinforcement ratio, BFRP rebar reinforced beams exhibited
more flexural and shear cracking than counterpart steel rebar reinforced concrete beams. It was also
Keywords:
found that BFRP reinforced beams exhibited acceptable deformability according to CSA S6-14. Cracking
Basalt rebar
BFRP
moments were found to be 30–50% higher for steel rebar reinforced specimens, compared to BFRP rebar
Reinforced concrete beam reinforced specimens. The study also found that shear failure can govern the design of BFRP rebar rein-
Shear forced concrete beams containing BFRP stirrups, and that Vc is 30–40% less for BFRP reinforced beams.
Flexure The CSA S806-12 standard was found to be conservative in predicting Vc. However, ACI 440.1-15 standard
Deformability was found to be unconservative, but in some cases accurately predicted Vc.
Ó 2018 Elsevier Ltd. All rights reserved.

1. Introduction reinforced polymer (AFRP) rebars. Each type of FRP rebar has its
advantages and disadvantages in terms of its mechanical proper-
Corrosion of steel rebar is inevitable in traditional steel- ties, durability properties, and cost. Among the three, GFRP rebar
reinforced concrete structures. With the heavy use of deicing salt is probably the most popular choice for building and other con-
in cold climates, this problem is a more serious concern for durabil- structions due to its relatively low cost with respect to CFRP and
ity of steel rebar reinforced concrete (RC) structures and structural AFRP rebars. In recent years, various forms of products made of
elements. Hence, the use of fibre-reinforced polymer (FRP) rebar as basalt fibres such as basalt fibre-reinforced polymer (BFRP) rebar,
an alternative reinforcement has been gaining popularity in fabrics, meshes, and chopped fibres (Fig. 1) are made available
addressing this issue. FRP rebars are corrosion resistant and chem- for various civil engineering construction applications. Basalt fibres
ically inert. Presently, there are three types of FRP rebar recom- are made of volcanic rock called basalt and hence, BFRP products
mended by design standards: carbon fibre-reinforced polymer are a greener alternative than other FRP products.
(CFRP), glass fibre-reinforced polymer (GFRP), and aramid fibre- Sim et al. (2005) [1] conducted mechanical and durability tests
on basalt fibres and compared them to glass and carbon fibres. The
study found that basalt fibre performed better than both glass and
⇑ Corresponding author.
carbon fibres in accelerated weathering and temperature testing.
E-mail addresses: duicj@uwindsor.ca (J. Duic), sdas@uwindsor.ca (S. Das).

https://doi.org/10.1016/j.conbuildmat.2018.04.208
0950-0618/Ó 2018 Elsevier Ltd. All rights reserved.
J. Duic et al. / Construction and Building Materials 176 (2018) 470–481 471

(a) Mesh (top and bottom left), fabric


(top right), fibres (bottom right)

(b) Rebar in various sizes


Fig. 1. Various basalt fibre products.

BFRP rebars have been shown to have an ultimate strength of the ultimate strength. In line with this, ACI 440.1R-15 [11] requires
about twice that of conventional reinforcing steel rebar. Serbescu that FRP stirrup strength be reduced using the factor: 0.05rb/db +
et al. (2015) [2] studied the effect of weathering on BFRP rebars 0.3.
and found that these rebars exhibit good strength retention in Hence, the literature review found that a few studies were
accelerated weathering conditions of heat and alkalinity. Bond undertaken to understand the behaviour of BFRP reinforced RC
durability has been shown to be excellent among BFRP rebars, beams. However, none of these studies compared the behaviour
and showed higher bond strength than GFRP rebar [3]. Nonethe- of BFRP RC beam with the behaviour of steel rebar RC beams. Fur-
less, all three FRPs show excellent resistance to electrochemical ther, previous researches used 8 mm or lesser diameter BFRP
corrosion. rebars as flexural reinforcement and hence, in these studies, the
Many studies have been conducted on FRP reinforced concrete, scale factor was ignored. Therefore, the current study was designed
with much of the research focused on the applications of CFRP and carefully to eliminate scale factor induced error and to determine
GFRP rebars. FRP rebar has demonstrated successful application as the behaviour of BFRP reinforced concrete beams and compare that
both flexural and shear reinforcement in various reinforced con- with similar steel reinforced concrete beams. The research was
crete structural elements including RC beams [4–7]. However, only completed using experimental methods.
very limited research has been conducted on the feasibility of BFRP
rebar as a reinforcing material to replace traditional steel rebar.
Recent studies have shown that BFRP reinforced RC beams with 2. Experimental procedure
sufficient shear resistance can undergo a flexural mode of failure,
and the failure is often initiated by crushing of concrete [8–10]. 2.1. Test specimens
Both American standard, ACI 440.1R-15 [11] and Canadian stan-
dard, CSA 806-12 [12] specify that FRP reinforced elements should This study consisted of eight full-scale reinforced concrete (RC)
fail by crushing of concrete in flexure. Beams can be made to fail in beam specimens. The beam specimens were 275 mm wide, 500
a flexural tension manner initiated by rupture of the longitudinal mm deep, and 3200 mm long and made with concrete that had a
BFRP bars, if the reinforcement ratio is sufficiently low [9,10]. target strength of 35 MPa. Ready mix concrete from a local supplier
However, when insufficient shear reinforcement is provided, BFRP was used to cast the beam specimens. Table 1 presents the differ-
reinforced concrete beams can undergo shear failure instead of ent specimens tested and parameters studied. As shown in the
flexural failure [9]. table, the test specimens consist of steel and BFRP rebar RC beams.
Tomlinson and Fam (2014) [9] and Issa et al. (2015) [13] found The test parameters studied were: two different reinforcement
that even if bent BFRP shear reinforcement was provided, shear materials, two flexural reinforcement ratios, and the presence or
failure still occurred due to rupture of the BFRP bars at the bend. absence of shear reinforcement. The naming of the beam speci-
Thus, shear failure is still a problem that can govern the design mens is intended to reflect their main attributes. The first letter
of BFRP reinforced concrete beams. Additionally, many types of of the name indicates if the beam specimen was made of steel
FRPs, including BFRP, are currently manufactured with thermoset- rebar (S) or BFRP rebar (B). The next one is a number which repre-
ting resins, and thus, cannot be reheated and bent to the desired sents the reinforcement ratio (0.41% and 0.83%). The last letter rep-
shape, further limiting the use of BFRP as shear reinforcement resents if the beam specimen had shear reinforcement (Y) or not
[14]. Hence, Tomlinson and Fam (2014) [9] and Ovitigala et al. (N). Hence, specimen S41Y is a RC beam specimen made of steel
(2015) [8] used steel stirrups in some of their specimens to avoid rebar (S) with reinforcement ratio of 0.41% and this beam specimen
shear failure and to ensure flexural failure, and thus, this did not had shear reinforcement (Y).
solve the problem of shear reinforcement made of BFRP rebar. The beam specimens in Table 1 are divided in two phases,
Bentz et al. (2010) [5] studied the effect of reinforcement ratio namely I and II. Four beam specimens were built and tested in each
on large GFRP reinforced concrete members. The study concluded phase. Flexural reinforcement ratios in these two phases are differ-
that the behaviour is similar to that of steel reinforced concrete ent. The reinforcement ratios of the Phase I and II beam specimens
beams. It is a well-known, however, that bent FRP reinforcement were 0.41% and 0.83%, respectively, producing sections having
tends to be dramatically weaker at the bend due to stress concen- reinforcement ratios approximately equal to and twice the FRP bal-
trations [14]. This weakness has been shown to be as high as 54% of anced reinforcement ratio [11,12,15,16], respectively. Stirrups
472 J. Duic et al. / Construction and Building Materials 176 (2018) 470–481

Table 1
Test matrix.

Phase Specimen ID q (%) qb (%) q/qb Longitudinal Rebar Stirrup f’c (STD) (MPa) Ef (STD) or Es (GPa) fy or ffu (STD) (MPa)
* *
I S41Y 0.41 3.35 (3.79) 0.12 (0.11) 10 M Steel Bent Steel 41 (3.73) 200 440
S41N –
y y
B41Y 0.38 (0.45) 1.08 (0.91) 10 mm BFRP Straight BFRP 38 (2.59) 54 (3.25) 943 (14.25)
B41N –
II S83Y 0.83 3.35 (3.79)* 0.24 (0.22)* 15 M Steel Bent Steel 41 (2.14) 200 430
S83N –
B83Y 0.38 (0.47)y 2.18 (1.77)y 15 mm BFRP Straight BFRP 51 (2.08) 986 (12.19)
B83N –
*
ACI 318–14 [15] (CSA A23.3–14) [16].
y
ACI 440.1R-15 [11] (CSA S806-12) [12].
1 mm = 0.039 in.
1 MPa = 0.15 ksi.

were removed from two specimens in each phase to determine the


concrete contribution (Vc) to the total shear resistance (Vr). The
individual material properties for each beam are also summarized
in the table.
Beam specimens without shear reinforcement were constructed
with just four stirrups outside of the shear span and this was done
to hold the rebar cages together. The rebar cages were tied using
traditional steel ties for steel cages and plastic cable ties for BFRP
cages. BFRP stirrups were cut as single straight legs with no bends
or hooks and were offset in the longitudinal direction to make a (a) S-series (b) B-series
square shape as can be seen in Figs. 2 and 3. It is worth noting that
the BFRP rebars are manufactured with thermosetting resin and Fig. 3. Beam cross-sections.
hence, a straight BFRP rebar cannot be bent with heat application
to make a bent stirrup. Further, pre-manufactured bent stirrups
are not available in the market. Hence, in the current study straight The steel used for this study was 400 grade. Tensile tests on the
legs with no bends or hooks were used as stirrups. Fig. 3 shows the steel reinforcement were conducted in accordance with ASTM
cross section of the beams with shear reinforcement. A clear cover A370-14 [19]. The measured yield strengths are shown in Table 1,
of 30 mm was used. Vertical spacing of 30 mm was provided alongside the FRP rupture strengths for BFRP reinforced beams.
between layers of longitudinal rebar. Fig. 4 shows the elevation Fig. 6 shows a typical stress-strain plot for the 10 mm (0.4 in) BFRP
of the beam specimens constructed with and without stirrups. and 10 M steel rebar used in this study. ASTM C39-15 [20] was fol-
The beams were cast in a lab setting, and allowed to cure in room lowed to determine the concrete compressive strengths (Table 1).
temperature for a minimum of 28 days before testing.
2.2. Test procedure

2.1.1. Material properties Each beam specimen was simply supported and tested in 4-
Tensile properties of the BFRP rebar were determined in accor- point bending as shown in Fig. 7. The beam spanned 3000 mm
dance with ASTM D7205-11 [17]. Digital image correlation (DIC) (118.1 in) and was supported by a roller between two plates at
technique was used to measure the strain over approximately one end and a knife edge between two plates at the other end.
100 mm gauge length, as required by the standard. VIC-2D soft- Bending load was applied to the top of the beam through the
ware [18] was used to determine the strain in the specimen spreader steel beam creating a constant moment region of 1000
(Fig. 5). The virtual extensometer showed a strain of approximately mm (39.4 in). Load was measured using three load cells: one
0.022 (2.2%) prior to rupture. Table 2 shows a summary of the ten- attached to the loading actuator, and two on the bottom under
sile properties of the BFRP rebar used for this investigation. the supports. Displacements were measured using four linear

(a) Steel rebar cage (b) BFRP rebar cage


Fig. 2. Rebar cages.
J. Duic et al. / Construction and Building Materials 176 (2018) 470–481 473

3. Test results and discussion

This section discusses the results of this investigation in terms


of the crack pattern, load-deflection response, deformability,
load-strain response, ultimate capacity, and mode of failure. The
effect of steel versus BFRP shear and flexural reinforcement at
two different reinforcement ratios are characterised and discussed
in terms of these parameters.
(a) With stirrups (Y)
3.1. Crack pattern

During loading, flexural cracks began to form in the extreme


tension fibres of concrete in the constant moment region, and
propagated up towards the compression face as the load increased.
As the load increased further, shear cracks began to form in both
shear spans and propagated from the bottom face of the beam
diagonally up towards the top supports. Fig. 8 shows the crack pat-
(b) Without stirrups (N)
terns and shear crack angles for Phase I and II beams. Shear crack
Fig. 4. Beam elevations. angles were noted only for beams that failed in shear. Among
Phase I beams, it is clear that beams reinforced with BFRP rebar
(B-series) experienced a higher number of flexural tensile cracks
than the steel rebar reinforced beams (S-series), possibly due to
the low stiffness of BFRP rebar. The cracks in B-series beams
showed significant branching near the location of the reinforce-
ment (bottom third of the beams). However, the number and spac-
ing of flexural cracks above the mid-depth of the beam in the
constant moment region were similar in both B- and S-series
beams. Cracking in the shear span was also observed among all
Phase I beams. Shear crack angle varied from 47 to 57 degrees
among B-series beams, whereas cracks in the shear span in the
S-series beams with stirrups (S41Y) were much steeper. B-series
beams also experienced significantly larger number of shear cracks
than the S-series beams and the shear cracks in the BFRP beams
spread closer to the end support.
Among Phase II beams, similar patterns were observed to that
of the Phase I beams. Flexural cracks formed in the constant
moment region and the number of cracks in all the beams was sim-
(a) BFRP rebar tensile test setup (b) BFRP rebar DIC
ilar. However, the B-series beams in Phase II did not exhibit the sig-
Fig. 5. BFRP rebar tension test and DIC setup. nificant branching in the lower third of the beam, perhaps due to
the increased reinforcement ratio. The shear crack angle in the
B83N specimen was slightly steeper than that of the S83N speci-
men. However, specimen B83Y experienced a much steeper shear
variable differential transformers (LVDTs). One LVDT was with the crack angle. The number of shear cracks in the two BFRP reinforced
loading actuator and thus, it measured the vertical displacement at specimens (B83Y and B83N) was less than the similar S-series
mid-span from the top of the beam specimen. Three other LVDTs specimens (S83Y and S83N). The B-series specimens exhibited
were placed underneath the beam and measured the vertical dis- shear cracking closer to the supports.
placement of the beam at the quarter, half, and three quarter
points along the span (Fig. 7). 3.2. Load-Deflection behaviour
Strain gauges were placed on the reinforcing rebars at the mid-
span on the longitudinal tension rebars, as well as on stirrups in The load versus mid-span deflection response of Phase I and II
the shear span on each side. Fig. 4 shows the locations of the strain beams are show in Fig. 9a and 9b, respectively. A distinct difference
gauges placed on both layers of tension rebars (eT) and on the stir- in the shape of the load-displacement plots for S- and B-series
rups (es). All test data were acquired through a computerised data beams exists. Both S- and B-series beams exhibited similar pre-
acquisition system. The beam specimens were loaded using dis- cracking load-deflection behaviour. However, post-cracking load-
placement control method. Loading was continued until either a deflection behaviours of these two beams were notably different.
shear failure or a flexural compression failure was observed. As can be observed in Fig. 9, after cracking, the stiffness in

Table 2
BFRP rebar tensile properties.

Bar size (mm) Ultimate Load (kN) Ultimate Stress, ffu (MPa) Ultimate Strain, efu (%) Modulus of Elasticity, Ef (GPa)
10 107 943 1.67 54
15 152 986 1.96 51

1 mm = 0.039 in.
1 kN = 0.22 kip.
1 MPa = 0.15 ksi.
474 J. Duic et al. / Construction and Building Materials 176 (2018) 470–481

1000 1000
140 140
900 900
120 120
800 800

700 100 700 100


Stress (MPa)

Stress (ksi)
600 600
80 80
500 500

400 60 400 60

300 300
40 40
200 200
10 mm BFRP Rebar 10 mm BFRP Rebar
20 20
100 10M Steel Rebar 100 10M Steel Rebar
0 0 0 0
0 5 10 15 20 25 30 35 0 0.5 1 1.5 2
Strain (%) Strain (%)
(a) Until rupture (b) Until 2% strain
Fig. 6. BFRP and steel rebar constitutive relationships.

Fig. 7. Test setup.

load-deflection behaviour of S-series beams did not reduce much in flexure was similar to that of the elastic loading path. The
whereas the stiffness in the B-series beams reduced considerably. unloading path for beam specimens that failed in shear are not
Among Phase I B-series beams, the ratio of pre-cracking stiffness shown because the unloading path for these beams showed a sud-
to post-cracking stiffness in the load-deformation curve are 4.9 den large drop in load carrying capacity.
and 8.2 for B41N and B41Y, respectively. However, both B-series Both S-series beams in Phase I exhibited larger displacement at
beams of Phase II exhibited a ratio of pre-cracking stiffness to failure than the two B-series beams. However, beam B41Y of B-
post-cracking stiffness of 4.8. Hence, this study shows that stirrups series beams held approximately 50% more load than its S-series
in low flexural reinforcement ratio BFRP beams are effective in counterpart beam, S41Y. Specimen S83Y was the only beam in
increasing the post-cracking stiffness. Phase II to sustain large mid-span deflection at failure. Mid-span
However, after cracking, both B-series beams remained linear deflections of B83N in Phase II was approximately 20% higher than
while, S-series beams remained linear until the steel rebars specimen S83N. However, the beam B83Y showed about half of the
yielded. As expected, yielding of the reinforcement in S-series maximum deflection than the beam S41Y exhibited.
beams caused a plateau in the load carrying capacity and only mar-
ginal load increase occurred thereafter until flexural compression 3.2.1. Service load
failure occurred. In Fig. 9, the unloading path is shown only for Table 3 shows the service loads, Pservice for each beam. The ser-
specimens that experienced a flexural compression mode of fail- vice load in this study is defined as the least of the loads calculated
ure. The slope of the unloading curve for S-series beams that failed using four different criteria: (i) mid-span deflection of L/360
J. Duic et al. / Construction and Building Materials 176 (2018) 470–481 475

Displacement (in)
0 0.5 1 1.5 2 2.5 3
500

100
400
L/360
L/180 80

Load (kip)
Load (kN)
300
60

200
40
S41Y
S41N
100 20
B41Y
B41N
0 0
0 10 20 30 40 50 60 70 80
Displacement (mm)
(a) Phase I beams

Displacement (in)
0 0.5 1 1.5 2 2.5 3
500
L/360
(a) Phase I beams L/180 100
400
80

Load (kip)
Load (kN)
300
60

200
40
S83Y
S83N
100 20
B83Y
B83N
0 0
0 10 20 30 40 50 60 70 80
Displacement (mm)
(b) Phase II beams
Fig. 9. Load-displacement plots.

3.2.2. Deformability
The fundamental mechanical difference between reinforcing
steel and FRP rebar is that FRP rebar does not exhibit yielding,
nor a large amount of ductility or energy absorption prior to rup-
ture. In light of this, the Canadian Highway Bridge Design Code
[22] requires that concrete rectangular flexural elements rein-
(b) Phase II beams forced with FRP satisfy the following requirement.

Fig. 8. Beam crack patterns. Mult wult


J¼ P 4:0 ð1Þ
M c wc

where,
[12,16] and (ii) mid-span deflection of L/180 [12,16], (iii) the ser-
vice strain in steel/FRP [21], and (iv) the maximum sustained load Mult = the ultimate moment capacity of the section
divided by the load factor 1.5 [9]. For all beams, the service strain wult = the curvature at Mult
criterion governed since it produced the most conservative service Mc = the moment corresponding to a maximum concrete com-
load. Service loads thus calculated for the B-series beams of both pressive strain of 0.001
phases ranged from 30 to 60% less than those of the S-series wc = the curvature at Mc
beamsa. This is due to the fact that the stiffness of the BFRP rebar
is about one quarter the stiffness of steel rebar. Thus, the stress The term Mcwc in Equation (1) is simply the product of moment
in the BFRP bar is about 50,000  0.002 = 100 MPa (14.5 ksi), and curvature at service. In lieu of using a strain of 0.001 in con-
whereas the stress in a steel bar would be 200,000  0.0012 = crete, the strain at which concrete is assumed to begin nonlinear-
240 MPa (34.8 ksi). However, if the Pmax/1.5 criterionb is applied, ity, a service strain of 0.002 for FRP rebar and 0.0012 for steel rebar,
the service loads in some B-series beams of Phase I would exceed recommended by Newhook et al. (2002) [21], was used to compute
those of their S-series counterparts. However, this trend is reversed the J-factor in this study. Curvature was calculated from LVDT data.
for Phase II beams and the B-series beams would have service loads Table 4 shows the summary of the J-factors for all the beam
of about 25–50% less than that of their S-series counterparts. specimens.
476 J. Duic et al. / Construction and Building Materials 176 (2018) 470–481

Table 3
Service loads.

Phase Specimen ID Service load using various criteria (kN) Pservice (kN)
at L/360 at L/180 at ea
service Pmax/1.5 b

I S41Y 188.5 206.2 123.4 164.7 123.4


S41N 190.9 202.3 105.8 153.9 105.8
B41Y 116.1 166.7 90.0 200.7 90.0
B41N 94.8 130.3 72.1 106.3 72.1
II S83Y 295.0 368.9 192.8 264.9 192.8
S83N 286.0 373.2 204.6 265.5 204.6
B83Y 155.7 201.1 114.2 201.8 114.2
B83N 141.7 191.7 110.6 192.0 110.6

L/360 = 8.3 mm (0.33 in), L/180 = 16.7 mm (0.66 in).


eservice = 0.0012 for steel, 0.002 for BFRP.
1 kN = 0.22 kip.

The J-factors for S41Y and B41Y are relatively close, due to the 3.4.1. Cracking moments and ultimate moment capacity
increased ultimate moment capacity (by 20%) achieved by speci- As can be found in Table 5, the experimental (shown by E in the
men B41Y, despite having less deflection at failure (see Fig. 9a). table) cracking moments of all beam specimens ranged between 40
Service deflection for specimen B41Y is also about 30% more than and 60 kN-m (29.5–60.0 kip-ft), since it depends primarily on the
that of S41Y (see Table 4). The J–factor of specimen S41N is about gross concrete section, and not the presence of reinforcing bars.
2.6 times higher than that of B41N, primarily due to the substan- Cracking moments from the tests were determined by the load at
tially lower ultimate deflection and lower ultimate load of speci- first crack, or where a noticeable increase in strain was observed
men B41N. The J–factor of S83Y is about 20% higher than that of in the tensile reinforcement, as can be seen in Fig. 10ai and 10bi
B83Y due to both a marginally higher load and ultimate deflection for Phases I and II, respectively. Distinct increases in the strain
capacities exhibited by specimen B83Y. The J–factor for S83N is are noticeable at a load of approximately 100 kN (22.5 kip). In both
about 50% less than that of B83N mostly due to the lower load Phase I and II specimens, the cracking moments of the S-series
capacity at service. beams are 30–50% higher than those of B-series beams. This is
due to the additional contribution of the rebar to the gross cross-
sectional inertia and the difference in stiffness between the two
3.3. Load-Strain response types of rebar. Thus, the test data shows that the contributions of
the rebar area and rebar stiffness influence the cracking moment
The load-strain response obtained from the strain gauges which is currently ignored by the design standards.The experimen-
placed on the tension and shear reinforcement are shown in tal ultimate moment of each beam is also presented in Table 5. All
Fig. 10. Both tension and shear steel reinforcements behaved sim- theoretical calculations (shown by T in Table 5) were performed
ilarly. As can be found in these figures, both tension and shear using CSA A23.3-14 [16] and CSA S806-12 [12], but setting any
strain gauges became noticeably engaged in tension around the material resistance factors equal to one. Ultimate moment capaci-
load that first initiated cracking of the section. However, the ties of steel reinforced beams obtained from the tests are in good
strain values obtained from BFRP reinforcement increased at a agreement with theoretical moment capacities, with theoretical
much faster rate than the strain values obtained from steel rein- values being slightly conservative. Theoretical ultimate moment
forcement. After cracking initiated, the strain in B-series tension capacities of B-series beams ranged between 1.5 and 3 times
reinforcement suddenly increased without any increase in the greater than those obtained experimentally. This is since the BFRP
load. This increase was more pronounced in Phase I beams, which beams did not experience a flexural mode of failure, but rather
agrees with the findings by Issa et al. (2015) [13]. The tension these specimens failed in shear before achieving maximum
strain for specimen B41N is not shown since this strain gauge moment capacity. CSA S806-12 [12] also requires that beams rein-
did not function. forced with FRPs satisfy Mr/Mcr > 1.5 and all B-series beams in this
study satisfied this requirement.
3.4. Ultimate capacity and mode of failure
3.4.2. Ultimate capacity and mode of failure
Table 5 summarizes the ultimate moment and shear capacities Fig. 11 shows the failure of each specimen used in the study.
of the beam specimens and the modes of failure. Among Phase I beams, S41Y experienced a flexural tension mode

Table 4
J–factors.

Phase Specimen ID Pc (kN) Pult (kN) Dc (mm) Dult (mm) J-factor


I S41Y 123.4 247.1 3.4 61.2 36.0
S41N 105.8 230.8 2.9 50.6 38.0
B41Y 90.0 301.0 4.5 39.0 29.0
B41N 72.1 159.5 3.6 24.1 14.8
II S83Y 192.8 397.4 4.8 55.3 23.7
S83N 204.6 398.2 4.7 25.5 10.6
B83Y 114.2 302.7 4.6 31.1 17.9
B83N 110.6 288.0 4.8 31.3 17.0

1 kN = 0.22 kip.
1 mm = 0.039 in.
J. Duic et al. / Construction and Building Materials 176 (2018) 470–481 477

400 500
200 200
40 40
80 100

100 400
20 100 20
300
80
60

Load (kip)

Load (kip)
Load (kN)
Load (kN)

0 0 300 0 0
0 0.025 0 0.025 60
200
40
200
40
S41Y S83Y
100
20 S83N
S41N 100 20
B83Y
B41Y B83N
0 0 0 0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 0 0.2 0.4 0.6 0.8 1 1.2
Strain (%) Strain (%)
(i) Tension rebar strain (i) Tension rebar strain

400 500

80 100
400
300 80
60

Load (kip)
Load (kip)

Load (kN)
300
Load (kN)

60
200
40
200
40

100
20 100 20
S41Y S83Y
B41Y B83Y

0 0 0 0
0 0.04 0.08 0.12 0.16 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14

Strain (%) Strain (%)

(ii) Stirrup strain (ii) Stirrup strain


(a) Phase I beams (b) Phase II beams
Fig. 10. Load-strain response.

of failure followed by flexural compression and S41N experienced contribution of the concrete and stirrups to the total shear resis-
a flexural tension mode of failure followed by shear failure when tance, Vr, of each specimen. The theoretical ACI [11,15] and CSA
mid-span deflection was around 55 mm (2.2 in). However, all B- [12,16] standard predictions of shear capacity, also divided into
series beams in Phase I experienced shear failure. Flexural tension concrete contribution and stirrup contribution, are presented.
modes of failure in S–series beams were evidenced by a plateau in
the load-deformation plots, as well as yielding of the steel flexural
reinforcement, when the strain become greater than 0.002. Flexu- 3.4.3.1. Effect of steel vs BFRP on Vc. Specimens B41Y and B41N both
ral compression modes of failure were observed when the concrete experienced shear failure, and thus the effect of the BFRP stirrups
in the compression zone crushed. In some cases, this happened can be analyzed. The experimental and theoretical shear resistance
more suddenly. Shear failure was always evidenced by the pres- of the concrete section, Vc, is presented in Table 5 for these speci-
ence of a large diagonal crack in the shear span, followed by com- mens. For Phase I B-series beams, the ACI 440.1 [11] standard is
plete separation along the crack and a sudden large drop in load unconservative in predicting Vc, whereas the CSA S806 [12] stan-
capacity. The shear capacity was calculated at the ultimate load dard is conservative. No comparisons can be drawn between the
for each specimen. In Phase I, specimen B41Y carried approxi- S- and B-series shear reinforced beams since both S41Y and S41N
mately 50% more load than its S-series counterpart, S41Y. How- experienced flexural tension failure. However, analysis of the the-
ever, specimen B41N carried 25% less load than S41N. oretical values of Vc indicates that the concrete contribution to
Among Phase II beams, S83Y experienced flexural tension fail- shear for B-series specimens is approximately 40% less than their
ure followed by flexural compression. However, beam S83N exhib- steel counterparts. This is due to lower stiffness of the BFRP rebar
ited flexural tension failure followed by shear failure at around 25 relative to the steel rebar.
mm (1.0 in) of deflection at the mid-span. Both B-series beams in A similar trend can be observed among Phase II B-series beams.
Phase II experienced shear failure at a load 25% less than the ulti- The CSA S806 [12] standard is conservative in predicting Vc, how-
mate capacity of S83Y and S83N. ever, the ACI 440.1 [11] standard predicts a similar shear capacity
to the experimental value. Since specimen S83N experienced shear
3.4.3. Ultimate shear capacity failure, a direct comparison of Vc can be made between B- and S-
The experimental and theoretical shear capacities of the speci- series beams. Table 5 shows that the experimental value of Vc is
mens are presented in Table 5, as well as an analysis showing the approximately 30% less for B-series beams than for S-series beams.
478 J. Duic et al. / Construction and Building Materials 176 (2018) 470–481

Both the ACI 318 [15] and CSA A23.3 [16] standards were very con-

CSAà
predicted Vr
servative in predicting Vc for the steel reinforced beams.

1.1

1.4

1.8

1.8
0.9

0.7


Test/

3.4.3.2. Effect of stirrups on shear capacity. Table 5 presents the steel

ACIy

1.9
0.9
0.9
0.7

0.8
1.0


and FRP stirrup contributions (Vs or Vf) to the shear resistance as
well as comparisons to ACI 440.1 [11], ACI 318 [15], CSA S806

112.3
222.3
107.2
160.3
CSAà

57.9

78.9
– [12], and CSA A23.3 [16] standards. Beams B41Y carried approxi-


mately 50% more load than B41N, which can be attributed to the
Vr (kN)

128.6
161.7
117.1

146.4
103.1
191.0
addition of BFRP stirrups. However, regardless of the addition of
ACIy

stirrups, beam B41Y still failed in shear. The fact that the stirrups


T

did not have any hooks or bend suggests that the reason for the
CSAà
predicted Vs

shear failure is insufficient development. As stated previously,


0.8

0.1




BFRP rebar is currently made with a thermosetting epoxy resin,
Test/

or Vf

ACIy

and thus they cannot be bent without compromising the structural


1.6

0.2



integrity and strength of the BFRP rebar. Further, pre-


manufactured BFRP stirrups are not yet available. Table 5 shows
70.9

7.3




E

the experimental value of Vs or Vf alongside the theoretical predic-


tions of ACI [11,15] and CSA [12,16] standards. Since the ACI [11]
164.5

164.5

128.6
CSAà

91.5
Vs or Vf (kN)

standard indicates that 160% of the theoretical contribution of Vf


0.0

0.0

0.0

0.0

was achieved, and the CSA [12] standard indicates that 80% of Vf
140.8

140.8

was achieved, it can be concluded that, for the Phase I B-series


44.5

44.5
ACIy

0.0

0.0

0.0

0.0

beams, the stirrups were effective in postponing the shear failure,


T

despite the shear failure by debonding/slippage of the stirrups that


CSAà
predicted Vc

occurred due to insufficient development.


1.2
1.4

1.8
1.5
1.8

The B83Y and B83N beams of Phase II both failed in shear, and
Test/

ACIy

at a similar load. The fact that they failed at similar loads highlights
1.9
0.7
0.7

1.0
1.0

the insufficient development and lack of hooks or bends in the rel-


atively short legs of the stirrups, becoming ineffective after a cer-
199.1
144.0
144.0
79.8
79.8

tain load. Analysis of stirrup strains at failure in Fig. 10aii and




E

Fig. 10bii for both B41Y and B83Y confirms this. Stirrups in both
114.1

112.3
107.2

109.8
CSAà

beams experienced a strain of approximately 0.0012 at failure of


68.7
57.9

93.7
78.9

the specimen. The ACI 440.1R-15 [11] standard implicitly limits


Vc (kN)

the strain in the stirrups to 0.004. Table 5 also confirms that the
128.6
128.6
117.1
117.1

146.4
146.4
103.1
103.1
ACIy

effect of the stirrups in the Phase II B-series beams was minimal.


T

The ACI 440.111 and CSA S806 [12] standards show that 20% and
Vr (kN)

10% of the theoretical Vf was achieved. Previous tests by Tomlinson


123.6
115.4

198.7
199.1
151.4
150.7

144.0
79.8

and Fam (2014) [9] and Bentz et al. (2010) [5] have shown that FRP
E

stirrups tend to fail by rupture at the bend. Bentz et al. (2010) [5]
Mr/Mcr

also showed that, if multiple layers of flexural reinforcement are


1.8
1.9
4.6

3.5
3.1
3.6
3.6
2.0

used, the FRP stirrups can be made to rupture away from the bend
E

due to the lack of stress concentrations produced by the shear


176.7
185.6
151.4
150.7

144.0

stress distribution in the cross section. Hence, it may be concluded


91.7
93.6

79.8
Mr (kN-m)

that BFRP rebar as a stirrup material is not realistic yet until a ther-
E

moplastic resin is used in manufacturing BFRP rebar or BFRP stir-


216
216
170
170
304
304
85
85

rups are manufactured with thermosetting resin in the desired


T*

shapes.
38

42
50
50

40
50
60

40
Mcr (kN-

E
m)

44
44
41
41
42
46
46
46
T*

4. Conclusions
S series: CSA A23.3-14 [16]; B series: CSA S806-12 [12].
Py (kN)

S series: ACI 318-14 [15]; B series: ACI 440.1R-15 [11].


183.4
187.2

353.3
371.2
N/A
N/A

N/A
N/A

Based on the results of the test program, the following conclu-


sions are drawn. However, the conclusions may be limited to the
specific test specimens studied.
Pult (kN)

247.1

159.5
397.4
398.2
230.8
301.3

302.7
288.0

1. At the low reinforcement ratio, BFRP reinforced beams exhib-


ited greater number of flexural cracking and shear cracking
tension
tension

tension
tension
Mode of Failure

T = Theoretical; E = Experimental.

than their steel counterparts. At the higher reinforcement


ratios, less shear cracking and slightly steeper shear crack
Flexural
Flexural

Flexural
Flexural
Ultimate capacity analysis.

angles are exhibited by BFRP reinforced beams.


Shear
Shear

Shear
Shear

2. Despite the low elastic modulus and low energy absorption of


1 kN-m = 0.74 kip-ft.
CSA S806-12 [12].

BFRP rebar, BFRP reinforced beams exhibited acceptable


deformability according to CSA S6-14.
Specimen ID

1 kN = 0.22 kip.

3. The cracking moments for S-series concrete beams are approx-


imately 30–50% higher than those of B-series beams. Hence,
B41N

B83N
S41N

S83N
B41Y

B83Y
S41Y

S83Y
Table 5

this study suggests that the contribution of the rebar to the


cracking moment should be in considered.
à
y
*
J. Duic et al. / Construction and Building Materials 176 (2018) 470–481 479

Compression
failure
Slight compression
failure

S41Y S83Y

Shear failure
Shear failure

S41N S83N

Shear failure
Shear failure

B41Y B83Y

Shear failure
Shear failure

B41N B83N
Fig. 11. Specimen failure modes.

4. Although BFRP reinforced beams can be made to fail in flexural 5. Vc is 30–40% less for BFRP reinforced beams. The CSA S806 stan-
tension or flexural compression, shear failure will still govern dard is conservative in predicting Vc, whereas the ACI 440.1
the design of BFRP reinforced concrete beam containing stirrups standard is unconservative, but in some cases accurately pre-
until pre-manufactured BFRP bent stirrups are available. Hence, dicts Vc.
this study found an urgent need for pre-manufactured BFRP
stirrups. The BFRP stirrups in this study were effective in delay-
ing the shear failure for the low reinforcement ratio (q/qb < 1.0). Conflict of interest
Stirrups in BFRP reinforced beams in Phase I was effective in
increasing post-cracking stiffness. None.
480 J. Duic et al. / Construction and Building Materials 176 (2018) 470–481

qffiffiffiffi
Acknowledgements 0
V c ¼ 2k f c bw d (ACI 318)
1
qffiffiffiffiffiffi
0 Vf d
The authors wish to express their appreciation for MEDA Engi- V c ¼ 0:05k/c km kr ðf c Þ3 bw dv , where km ¼ Mf
6 1:0 and
neering & Technical Services for providing technical assistance
kr ¼ 1 þ ðEF qFw Þ (CSA S806)
1
3
necessary for this investigation. The financial assistance for this qffiffiffiffi
0
project was provided by the Natural Sciences and Engineering V c ¼ uc kb f c bw dv (CSA A23.3)
Research Council of Canada. Vf ¼
Af f f v d
, where f f v ¼ 0:004Ef 6 f fb (ACI 440.1)
s
Av f yt d
V s ¼ s (ACI 318)
Appendix A.
V sF ¼ 0:4uF AsF v f Fu dv cot h, where h ¼ 30o þ 7000el and
Mf
The following symbols are used in this paper: þðV f V p Þþ0:5Nf Ap f po
el ¼ dv
2ðEF AF þEp Ap Þ
(CSA S806)
/s Av f y dv cot h
AFRP Aramid Fibre Reinforced Polymer Vs ¼ s
, where h ¼ 35o (CSA A23.3)
BFRP Basalt Fibre Reinforced Polymer
CFRP Carbon Fibre Reinforced Polymer
FRP Fibre Reinforced Polymer References
GFRP Glass Fibre Reinforced Polymer
[1] J. Sim, C. Park, D.Y. Moon, Characteristics of basalt fiber as a strengthening
LVDT Linear Variable Differential Transformer
material for concrete structures, Composites Part B 36 (6–7) (2005) 504–512.
db rebar diameter [2] A. Serbescu, M. Guadagnini, K. Pilakoutas, Mechanical characterization of
Ef modulus of elasticity of FRP basalt FRP rebars and long-term strength predictive model, J. Compos. Constr.
Es modulus of elasticity of steel 19 (2) (2015) 1–13. 04014037.
0 [3] A. Altalmas, A. El Refai, F. Abed, Bond degradation of basalt fibre-reinforced
fc concrete compressive strength polymer (BFRP) bars exposed to accelerated aging conditions, Constr. Build.
ffu rupture strength of FRP Mater. (2015) 162–171.
[4] M.S. Alam, A. Hussein, Experimental investigation on the effect of longitudinal
fy yield stress of steel
reinforcement on shear strength of fibre reinforced polymer reinforced
Mc moment corresponding to a maximum concrete concrete beams, Can. J. Civ. Eng. 38 (3) (2011) 243–251.
compressive strain of 0.001 [5] C.E. Bentz, L. Massam, M.P. Collins, Shear strength of large concrete members
with FRP reinforcement, J. Compos. Constr. ASCE 14 (6) (2010) 637–646.
Mcr cracking moment
[6] A.F. Ashour, Flexural and shear capacities of concrete beams reinforced with
Mr resisting moment GFRP bars, Constr. Build. Mater. 20 (10) (2005) 1005–1015.
Mult ultimate moment capacity of the section [7] M. Theriault, B. Benmokrane, Effects of FRP reinforcement ratio and concrete
Pult ultimate load at failure strength on flexural behavior of concrete beams, J. Compos. Constr. 2 (1)
(1998) 7–16.
Py yield load [8] T. Ovitigala, M.A. Ibrahim, M.A. Issa, Serviceability and ultimate load behavior
rb bend radius of rebar of concrete beam reinforced with basalt fiber-reinforced polymer bars, ACI
Vc concrete contribution to shear resistance Struct. J. 113 (4) (2016) 757–768.
[9] D. Tomlinson, A. Fam, Performance of concrete beams reinforced with basalt
Vf FRP stirrup contribution to shear resistance FRP for flexure and shear, J. Compo. Constr.ASCE 19 (2) (2014) 1–10. 04014036.
Vr shear resistance [10] V.B. Brik IDEA Project 86, in: Advanced Concept Concrete Using Basalt Fiber/BF
Vs steel stirrup contribution to shear resistance Composite Rebar Reinforcement, Transportation Research Board, Washington,
DC, 2003, p. 71.
efu ultimate strain of FRP [11] ACI Committee 440, in: Guide for the Design and Construction of Concrete
es strain in stirrup Reinforced with FRP Bars (ACI 440.1R-15), American Concrete Institute,
eT strain in tension steel Farmington Hills, MI, 2015, p. 44.
q longitudinal reinforcement ratio [12] CAN/CSA S806-12, in: Design and Construction of Building Components with
Fibre Reinforced Polymers, Canadian Standards Association, Mississauga, ON,
qb balanced reinforcement ratio Canada, 2012, p. 206.
qfb balanced FRP reinforcement ratio [13] M.A. Issa, T. Ovitigala, M. Ibrahim, Shear behavior of basalt fibre reinforced
wc curvature at Mc concrete beams with and without basalt FRP stirrups, J. Compos. Constr. 20 (4)
(2015) 1–11. 04015083.
wult curvature at Mult [14] ISIS Canada, in: Reinforcing Concrete Structures with Fibre Reinforced
Polymers, Intelligent Sensing for Innovative Structures, Winnipeg, MA,
Canada, 2007, p. 151.
[15] ACI Committee 318, in: Building Code Requirements for Structural Concrete
(ACI 318-14), American Concrete Institute, Farmington Hills, MI, 2014, p. 465.
Appendix B. [16] CAN/CSA A23.3-14, in: Design of Concrete Structures, Canadian Standards
Association, Mississauga, ON, Canada, 2014, p. 214.
[17] ASTM D7205-11, in: Standard Test Method for Tensile Properties of Fiber
Equations from various codes and standards: Reinforced Polymer Matrix Composite Bars, ASTM Int., West Conshohocken,
PSA, USA, 2011, p. 13.
[18] VIC-2D, web: http://correlatedsolutions.com/vic-2d/, viewed on 17 February
qbal ¼ au1 bFRP1 uf frpc f c  EfrpEefrpc þfec frp (CSA S806)
0
2016, 2016.
0 Ef ecu [19] ASTM A370-14, in: Standard Test Methods and Definitions for Mechanical
qfb ¼ 0:85b1 fffuc Ef ecu þf fu
(ACI 440.1) Testing of Steel Products, ASTM Int., West Conshohocken, PSA, USA, 2014, p.
a1 b1 uc f 0c 50.
qbal ¼ us f y  700
700þf y
(CSA A23.3) [20] ASTM C39-15, in: Standard Test Method for Compressive Strength of
0 Cylindrical Concrete Specimens, ASTM Int., West Conshohocken, PSA, USA,
qb ¼ 0:85b1 ff yc EsEescuecu
(ACI 318)
þf y 2015, p. 7.
qffiffiffiffi [21] J. Newhook, A. Ghali, G. Tadros, Concrete flexural members reinforced with
2f r Ig 0
M cr ¼ where f r ¼ 0:62 f c (ACI 440.1)
h
, fiber reinforced polymer: design for cracking and deformability, Can. J. Civ.
qffiffiffiffi Eng. 29 (1) (2002) 125–134.
I 0
Mcr ¼ f r  yg , where f r ¼ 0:6k f c and k ¼ 1:0 for normal density [22] CAN/CSA S6-14, in: Canadian Highway Bridge Design Code, Canadian
t
Standards Association, Mississauga, ON, Canada, 2014, p. 733.
concrete (CSA S806)
qffiffiffiffi qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
0
V c ¼ 25 f c bw c, where c ¼ kd and k ¼ 2qf nf þ ðqf nf Þ2  qf nf Mr. Jason Duic is a Masters Student at the University of Windsor. He completed his
BASc program at the University of Windsor, Canada. His research interest is rein-
(ACI 440.1) forced concrete structures and rehabilitation of concrete structures with FRP.
J. Duic et al. / Construction and Building Materials 176 (2018) 470–481 481

Dr. Sara Kenno is an Industrial R&D Fellow at MEDA Limited, Windsor, Canada. She Dr. Sreekanta Das is a Professor at the Department of Civil and Environmental
received her PhD from the University of Windsor. Her research interest is the Engineering, University of Windsor, Canada. He received his PhD from University of
development of various BFRP products and materials in building construction Alberta, Canada. His research interests include behaviour of concrete structures and
applications. FRP materials.

You might also like