Date: 23 April 2012

PCS7 V8.0

Section: OS Download

Prepared by: Bilal Moolla

Subject: An Error occurred while downloading to the target system

The project could not be opened

The SQL server cannot access database. Please check access rights.

Contents
Background information ............................................................................................................................... 2
Engineering Station ................................................................................................................................... 2
Server ........................................................................................................................................................ 2
Error .............................................................................................................................................................. 3
How to overcome the error .......................................................................................................................... 4
Take a note of the following settings on the Server OS station ............................................................... 4
Folder Sharing ....................................................................................................................................... 4
Station Configuration Editor problems before change (With both Mac and IP) .................................. 8
Station Configuration Editor Resolution (With only Mac (ISO)) ......................................................... 10
Take a note of the following settings on the Engineering station .......................................................... 18

Prepared by Bilal Moolla Page 1 of 28


Background information
A project using PCS7 V8.0 is created on one network (WORKGROUP). AS and OS connected in one
network (WORKGROUP)

Engineering Station
Windows 2008 Server SR2

PCS7 V8.0

PC Name: FOEWS

CP1623 Ethernet card

Server
Windows 2008 Server SR2

PCS7 V8.0

PC Name: FOSVR1A

Prepared by Bilal Moolla Page 2 of 28


CP1623 Ethernet card

Error
An Error occurred while downloading to the target system

The project could not be opened

The SQL server cannot access database. Please check access rights.

This problem occurs while downloading to the SERVER from the Engineering Station.

Prepared by Bilal Moolla Page 3 of 28


How to overcome the error

Take a note of the following settings on the Server OS station

Folder Sharing

Sharing and access


permissions.

Prepared by Bilal Moolla Page 4 of 28


Sharing and access
permissions.

Prepared by Bilal Moolla Page 5 of 28


Add users to the group folder’s
permission and Allow full control

Prepared by Bilal Moolla Page 6 of 28


Add users to the group folder’s
permission and Allow full control

Prepared by Bilal Moolla Page 7 of 28


Station Configuration Editor problems before change (With both Mac and IP)

Prepared by Bilal Moolla Page 8 of 28


Prepared by Bilal Moolla Page 9 of 28
The NDIS IP address must be the same as the network adaptor IP address.

You cannot have the same address on Industrial Ethernet and NDIS

Pinging the engineering station from the Server.

This problem occurs when you have TCP and ISO assigned in your hardware configuration. You cannot
have a MAC and TCP/IP running at the same time with the CP1623 card.

You will notice that you cannot ping the engineering station after the download.

Station Configuration Editor Resolution (With only Mac (ISO))

After removing the TCP/IP setting in the hardware configuration on the Engineering station recompile in
netpro. And make a note of the XBD file for Importing.

Prepared by Bilal Moolla Page 10 of 28


Import Station

Delete the components in Netpro and import the XDB file from the Engineering station.

Disable all other adaptors

Prepared by Bilal Moolla Page 11 of 28


Disable other network adaptors temporarily

Change the IP address so that the NDIS and the Industrial Ethernet IP addresses are different to resolve
this conflict.

Prepared by Bilal Moolla Page 12 of 28


Temprary Change of IP Address

Prepared by Bilal Moolla Page 13 of 28


Make the NDIS IP address the IP address of the Server and Industrial Ethernet IP address anything else,
but there nust not be any conflicting addresses.

Conflict Resolved. Now you should beable to


ping the engineering station

Now will beable to ping the Engineering station for import.

Prepared by Bilal Moolla Page 14 of 28


Notice your Configuration editor changes as follows

At this stage we will use import station

Prepared by Bilal Moolla Page 15 of 28


Select the correct XDB file from your
engineering station over the network.

New Imported file

Prepared by Bilal Moolla Page 16 of 28


We are now communicating using MAC addresses.

Prepared by Bilal Moolla Page 17 of 28


Take a note of the following settings on the Engineering station

Set up the IP addresses for each PC in the CP Card (Network Adaptor Settings).

You have to change the hardware configuration and remove the IP settings with a CP card. You cannot
have both MAC and TCP together.

Disable IP
Protocol

Prepared by Bilal Moolla Page 18 of 28


Select the WinCC Application and create a
Connection to the PLC. Also make sure the
configured computer name in the project
matches the Actual Server Name.

Prepared by Bilal Moolla Page 19 of 28


Select the winCC
Application and create a
Connection to the PLC

Prepared by Bilal Moolla Page 20 of 28


Save and compile your netpro.

This is not going to work.


You will have to import
the XDB file as explained
below.

Prepared by Bilal Moolla Page 21 of 28


Prepared by Bilal Moolla Page 22 of 28
Good idea to make the
names identical

Prepared by Bilal Moolla Page 23 of 28


Make a note of the path
where the XDB file is saved
on the engineering station

Prepared by Bilal Moolla Page 24 of 28


Compile the OS Server

Remember the path of the .XBD file on the engineering station because you are going to import this file
“Take a
from the server's station configuration editor. At this stage you should refer to the section

note of the following settings on the Server OS station”

Prepared by Bilal Moolla Page 25 of 28


Make sure you can see all
your PC nodes in Simatic
Shell

Then download to the Server from the engineering station after having a look at the server settings.

Now you should be able to download the OS with out problems.