Three point bending (3PB) tests were carried out using 150×150×600 mm notched
prismatic beams. The tests configuration can be seen in Figure A.1, the setup is similar to
that proposed by RILEM (2000a) recommendations; the only difference is that a 450 mm
span was used instead of 500 mm. The test was controlled by means of the crack mouth
opening displacement (CMOD) through a clip gage extensometer (± 2.5 mm span and 10
mm gauge length) and the deflection measured by an LVDT mounted on a rigid frame
(Figure A.1).
Load
25 mm
150 mm deep notch
75 450 mm 75
The notation used in the study is presented in Table A.1 and is in accordance with
the following designation:
N1, N2 = Mix notations
3PB-P = Three point bending test on a plain concrete 150×150×600 mm beam with a 25
mm deep notch.
- A.2 -
Flexural Test Data
3PB-20= Three point bending test on a 150×150×600 mm SFRC beam with a 25 mm deep
notch. The concrete had 20 kg/m3 of steel fibres.
3PB-40= Three point bending test on a 150×150×600 mm SFRC beam with a 25 mm deep
notch. The concrete had 40 kg/m3 of steel fibres.
The last number in the specimen notation denotes the trial.
In total, 18 beams were tested under three point bending. All tests were stable
along the entire pre- and post-peak response. A typical state of the crack after the test can
be seen in Figure A.2 for the150 case of a HSC beam with 20 kg/m3 of steel fibres.
- A.3 -
Annex A
The following figures present the load-deflection and load-CMOD responses for all
the specimens tested. The responses are plotted up to 3000 µm and the inset presents the
initial response up to 250 µm. For each specimen, the relation between deflection and
CMOD is also plotted. Tables summarise the mean values of the parameters calculated
from the flexure test. The limit of proportionality, fct,fl , is obtained as:
3.Fu .L
fct,fl =
2.b.h sp2
The crack mouth opening displacement at the limit of proportionality has been
denoted as CMODpeak.
- A.4 -
Flexural Test Data
(a) (b)
15 15
N1-3PBDEFLP-1 N1-3PBCMODP-1
10 10
Load (kN)
5 5
0 0
0 100 200 300 400 500 0 100 200 300 400 500
Deflection (µm) CMOD (µm)
(c)
500
N1-3PB-P-1
400
ffct,fl = 3.71 MPa
Deflection (µm)
300
CMODpeak= 30 µm
200
100
0
0 100 200 300 400 500
CMOD (µm)
Figure A.3. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.5 -
Annex A
(a) (b)
15 15
N1-3PBDEFLP-2 N1-3PBCMODP-2
10 10
Load (kN)
5 5
0 0
0 100 200 300 400 0 100 200 300 400
Deflection (µm) CMOD (µm)
(c)
400
N1-3PB-P-2
CMODpeak= 30 µm
200
100
0
0 100 200 300 400
CMOD (µm)
Figure A.4. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.6 -
Flexural Test Data
(a) (b)
20 20
N1-3PBDEFLP-3 N1-3PBCMODP-3
15 15
Load (kN)
10 10
5 5
0 0
0 50 100 150 200 250 300 350 0 50 100 150 200 250 300 350
Deflection (µm) CMOD (µm)
(c)
350
N1-3PB-P-3
300
CMODpeak= 23 µm 200
150
100
50
0
0 50 100 150 200 250 300 350
CMOD (µm)
Figure A.5. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.7 -
Annex A
(a) (b)
15 15
N1-3PBDEFL20-1 N1-3PBCMOD20-1
10 10
Load (kN)
15 15
Load (kN)
Load (kN)
5 5
0 0
0 250 0 250
Deflection (µm) CMOD (µm)
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 4.04 MPa
Deflection (µm)
2000
CMODpeak= 23 µm 0
1500 0 250
CMOD (µm)
1000
500
N1-3PB-20-1
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.6. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.8 -
Flexural Test Data
(a) (b)
15 15
15 15
Load (kN)
Load (kN)
10 10
0
Load (kN)
0
0 250 0 250
Deflection (µm) CMOD (µm)
5 5
N1-3PBDEFL20-2 N1-3PBCMOD20-2
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 3.85 MPa
Deflection (µm)
2000
CMODpeak= 21 µm 0
1500 0 250
CMOD (µm)
1000
500
N1-3PB-20-2
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.7. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.9 -
Annex A
(a) (b)
15 15
N1-3PBDEFL20-3 N1-3PBCMOD20-3
10 10
Load (kN)
15 15
Load (kN)
Load (kN)
5 5
0 0
0 250 0 250
Deflection (µm) CMOD (µm)
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 4.06 MPa
Deflection (µm)
2000
CMODpeak= 31 µm 0
0 250
1500 CMOD (µm)
1000
500
N1-3PB-20-3
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.8. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.10 -
Flexural Test Data
(a) (b)
20 20
N1-3PBDEFL40-1 N1-3PBCMOD40-1
15 15
Load (kN)
10 20 10 20
Load (kN)
Load (kN)
5 5
0 0
0 250 0 250
Deflection (µm) CMOD (µm)
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 4.18 MPa
Deflection (µm)
2000
CMODpeak= 43 µm 0
1500 0 250
CMOD (µm)
1000
500
N1-3PB-40-1
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.9. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.11 -
Annex A
(a) (b)
20 20
N1-3PBDEFL40-2 N1-3PBCMOD40-2
15 15
Load (kN)
10 10
20 20
Load (kN)
Load (kN)
5 5
0 0
0 250 0 250
Deflection (µm) CMOD (µm)
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 4.17 MPa
Deflection (µm)
2000
CMODpeak= 27 µm 0
0 250
1500 CMOD (µm)
1000
500
N1-3PB-40-2
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.10. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.12 -
Flexural Test Data
(a) (b)
20 20
N2-3PBDEFLP-1 N2-3PBCMODP-1
15 15
Load (kN)
10 10
5 5
0 0
0 50 100 150 200 0 50 100 150 200
Deflection (µm) CMOD (µm)
(c)
200
N2-3PBCMODP-1
CMODpeak= 20 µm
100
50
0
0 50 100 150 200
CMOD (µm)
Figure A.11. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.13 -
Annex A
(a) (b)
15 15
N2-3PBDEFLP-2 N2-3PBCMODP-2
10 10
Load (kN)
5 5
0 0
0 50 100 150 200 250 0 50 100 150 200 250
Deflection (µm) CMOD (µm)
(c)
250
N2-3PBCMODP-2
200
ffct,fl = 3.68 MPa
Deflection (µm)
150
CMODpeak= 16 µm
100
50
0
0 50 100 150 200 250
CMOD (µm)
Figure A.12. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.14 -
Flexural Test Data
(a) (b)
15 15
N2-3PBDEFLP-3 N2-3PBCMODP-3
10 10
Load (kN)
5 5
0 0
0 50 100 150 200 250 0 50 100 150 200 250
Deflection (µm) CMOD (µm)
(c)
250
N2-3PBCMODP-3
200
ffct,fl = 4.09 MPa
Deflection (µm)
150
CMODpeak= 11 µm
100
50
0
0 50 100 150 200 250
CMOD (µm)
Figure A.13. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.15 -
Annex A
(a) (b)
25 25
N2-3PBDEFL20-1 N2-3PBCMOD20-1
20 20
Load (kN)
15 15
25 25
10 10
Load (kN)
Load (kN)
5 5
0 0
0 250 0 250
Deflection (µm) CMOD (µm)
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 3.87 MPa
Deflection (µm)
2000
CMODpeak= 27 µm 0
0 250
1500 CMOD (µm)
1000
500
N2-3PBCMOD20-1
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.14. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.16 -
Flexural Test Data
(a) (b)
25 25
N2-3PBDEFL20-2 N2-3PBCMOD20-2
20 20
Load (kN)
15 15
25 25
10 10
Load (kN)
Load (kN)
5 5
0 0
0 250 0 250
Deflection (µm) CMOD (µm)
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 4.03 MPa
Deflection (µm)
2000
0
CMODpeak= 26 µm 0
CMOD (µm)
250
1500
1000
500
N2-3PBCMOD20-2
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.15. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.17 -
Annex A
(a) (b)
20 20
N2-3PBDEFL20-3 N2-3PBCMOD20-3
15 15
Load (kN)
10 10
20 20
Load (kN)
Load (kN)
5 5
0 0
0 250 0 250
Deflection (µm) CMOD (µm)
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 3.91 MPa
Deflection (µm)
2000
CMODpeak= 20 µm 0
0 250
1500 CMOD (µm)
1000
500
N2-3PBCMOD20-3
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.16. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.18 -
Flexural Test Data
(a) (b)
25 N2-3PBDEFL40-1 25 N2-3PBCMOD40-1
20 20
Load (kN)
15 15
25 25
Load (kN)
Load (kN)
10 10
5 5
0 0
0 250 0 250
Deflection (µm) CMOD (µm)
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 5.30 MPa
Deflection (µm)
2000
CMODpeak= 18 µm 0
0 250
1500 CMOD (µm)
1000
500
N2-3PB-40-1
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.17. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.19 -
Annex A
(a) (b)
35 35
N2-3PBDEFL40-2 N2-3PBCMOD40-2
30 30
25 25
Load (kN)
20 20
35 35
15 15
Load (kN)
Load (kN)
10 10
5 0 5 0
0 250 0 250
Deflection (µm) CMOD (µm)
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 5.45 MPa
Deflection (µm)
2000
CMODpeak= 24 µm 0
0 250
1500 CMOD (µm)
1000
500
N2-3PB-40-1
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.18. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.20 -
Flexural Test Data
(a) (b)
40 40
N2-3PBDEFL40-3 N2-3PBCMOD40-3
35 35
30 30
25 25
Load (kN)
20 20
40 40
Load (kN)
Load (kN)
15 15
10 10
0 0
5 0 250 5 0 250
Deflection (µm) CMOD (µm)
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Deflection (µm) CMOD (µm)
(c)
3000
250
Deflection (µm)
2500
ffct,fl = 4.77 MPa
Deflection (µm)
2000
CMODpeak= 25 µm 0
0 250
1500 CMOD (µm)
1000
500
N2-3PB-40-3
0
0 500 1000 1500 2000 2500 3000
CMOD (µm)
Figure A.19. (a) Load-deflection, (b) load-CMOD responses and (c) deflection-CMOD curves
- A.21 -