APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES372793733 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES426690999 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES741229056 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES214694648 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES806010039 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES262814163 Scan Code
CHAPTER 3 CHAPTER 6 CHAPTER 7
USE AND OCCUPANCY CLASSIFICATION TYPES OF CONSTRUCTION
FIRE-RESISTANTANCE-RATED CONSTRUCTION
SECTION BC 302 ARC Architecture + Design Studio
CLASSIFICATION
Proposed/ Provided:
Occupancy Class: Residential: Group R-2
R&O Engineering P.C.
CHAPTER 5
GENERAL BUILDING HEIGHTS AND AREAS; SEPARATION OF OCCUPANCIES
SECTION BC 509
INCIDENTAL USES
509.1 General. Incidental uses listed in Table 509 and located within single occupancy or mixed occupancy buildings shall comply
with the provisions of this section. Incidental uses are ancillary functions associated with a given occupancy that generally pose a
greater level of risk to that occupancy and are limited to those uses listed in Table 509.
Exception: Incidental uses within and serving a dwelling unit are not required to comply with his section.
CHAPTER 8
INTERIOR FINISHES
CHAPTER 12
INTERIOR ENVIRONMENT
1206.2.1 Rear yard access for multiple dwellings. For multiple dwellings, there shall be direct access from the street to every
rear yard through a noncombustible 2-hourfire-resistance-rated passage either in a direct line or through a court, except that the
passage may be 1-hour fire-resistance-rated for dwellings not exceeding three stories in height and occupied by not more than
two families on any story. Such passage shall be at least 36 inches (914 mm) in clear width and 7 feet (2134 mm) in height.
Exceptions: No such passage shall be required for:
1.Buildings of Type IA or IB construction.
2.Buildings not exceeding three stories in height, and occupied by not more than one family on any story nor more
than three families in all.
3. Buildings not exceeding two stories in height, and occupied by not more than two families on any story nor more than four
families in all.
Roxane Tsirigotis, RA
Proposed/ Provided:
Building shall be of Construction Class IB
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES708341382 Scan Code
GENERAL: GENERAL: DIMENSIONING:
ARC Architecture + Design Studio
1. THE PROPOSED WORK ON THIS PLAN SHALL COMPLY WITH THE 2014 NEW YORK CITY BUILDING CODE 16. CONTRACTOR TO COORDINATE ALL EQUIPMENT BASE AND HOUSEKEEPING PADS WITH 1. ALL WALLS ARE ORTHOGONAL TO THE PROPERTY LINES UNLESS OTHERWISE NOTED. THE
REQUIREMENTS. MECHANICAL, PLUMBING AND ELECTRICAL CONTRACTORS. EQUIPMENT BASES AND HOUSEKEEPING CONTRACTOR SHALL BE KNOWLEDGEABLE OF WHICH PROPERTY LINE DETERMINES THE
PADS TO BE A MINIMUM OF 4" HIGH UNLESS OTHERWISE NOTED. PROVIDE ONE LAYER OF WWF 6X6XW4 ORIENTATION OF EACH WALL, AND SHALL NOTIFY THE ARCHITECT OF ANY CONDITIONS REQUIRING
2. THE GENERAL CONTRACTOR SHALL OBTAIN CONSTRUCTION PERMIT AND PAY ALL REQUIRED FEES WELDED WIRE FABRIC MINIMUM, TO BE INSTALLED BENEATH THE FULL PROJECTED AREA OF CLARIFICATION BEFORE PROCEEDING WITH THE WORK.
TO THE D.O.B. BASED ON THE PROPOSED WORK OF THIS DRAWING FROM NEW YORK CITY BUILDING EQUIPMENT. R&O Engineering P.C.
DEPARTMENT PRIOR TO START OF WORK. 2. PARTITIONS ARE DIMENSIONED TO THE UNFINISHED FACE OF THE WALL UNLESS OTHERWISE
17. CONCRETE PADS AND MOUNTINGS IN MECHANICAL SPACES SHALL BE COORDINATED WITH NOTED.
3. ALL ELECTRICAL WORK BEING PERFORMED SHALL BE BY A LICENSED ELECTRICIAN IN ELECTRICAL AND PLUMBING CONTRACTORS.
3. ALL DIMENSIONS SHALL HAVE PREFERENCE OVER SCALE.
ACCORDANCE WITH NEW YORK CITY ELECTRICAL CODE., AND SHALL BE REQUIRED TO OBTAIN ALL
REQUIRED SIGN-OFFS AND CERTIFICATE OF COMPLETIONS FROM THE B.E.C. 18. CONTRACTOR TO COORDINATE ALL MECHANICAL AND ELECTRICAL FLOOR AND WALL SLEEVES AND Bicaluro Associates P.C.
ALL MECHANICAL SHAFTS WITH MECHANICAL, PLUMBING, FIRE-PROTECTION, ELECTRICAL, 4. ALL DIMENSIONS SHALL BE VERIFIED IN THE FIELD BEFORE PROCEEDING TO WITH THE WORK. THE
ARCHITECT SHALL BE NOTIFIED OF ANY CORRECTIONS.
4. ALL PLUMBING WORK SHALL BE PERFORMED BY A LICENSED PLUMBER IN ACCORDANCE WITH THE STRUCTURAL AND ARCHITECTURAL DRAWINGS.
NEW YORK CITY BUILDING CODE AND INSPECTION REQUIREMENTS. HE SHALL BE RESPONSIBLE TO
OBTAIN ALL REQUIRED PLUMBING SIGN-OFFS AND INSPECTIONS FROM THE DEPARTMENT OF 19. PROVIDE ACCESS PANELS AS APPLICABLE AND AS REQUIRED FOR MECHANICAL EQUIPMENT. ALL 5. DOOR OPENINGS ARE GENERALLY DIMENSIONED TO CENTERLINE OF OPENING. DOOR OPENINGS
BUILDING'S PLUMBING DIVISION. ACCESS PANELS SHALL BE CONCEALED, AND LOCATIONS SHALL BE REVIEWED WITH THE ARCHITECT THAT ARE NOT DIMENSIONALLY LOCATED ARE TO BE CENTERED BETWEEN WALLS OR POSITIONED
PRIOR TO PROCEEDING. WITH ONE JAMB AGAINST AND ADJACENT WALL OR COLUMN AS SHOWN ON THE PLANS AND/OR
5. DIMENSIONS ON THE SITE PRIOR TO START OF WORK. HE SHALL NOTIFY THE ARCHITECT/ENGINEER DETERMINED FROM THE DETAILS.
OF RECORD ANY DISCREPANCIES AND/OR CHANGE OF LAYOUT BETWEEN THE FIELD CONDITIONS 20. PORTABLE FIRE EXTINGUISHERS LOCATED ON THE DRAWINGS SHALL RECEIVE APPROVAL OF FIRE
AND THIS DRAWING(S) IMMEDIATELY. FAILURE TO DO SO WILL INDICATE THE GENERAL CONTRACTOR'S DEPARTMENT PRIOR TO INSTALLATION. 6. WHEN UNDIMENSIONED PARTITIONS APPEAR IN CONJUNCTION WITH DOOR OPENINGS THE DOOR
ACCEPTANCE OF THIS DRAWING(S) AND WILL TAKE FULL RESPONSIBILITY FOR SAID WORK BEING WIDTH AND DOOR FRAME DETAILS DETERMINE THE LOCATION OF THE ADJACENT WALLS AND
PERFORMED. 21. DRAWINGS SHALL NOT BE SCALED, USE INDICATED DIMENSIONS ONLY. FRAMES.
6. THE TERMS "GENERAL CONTRACTOR", "GEN. CONTRACTOR", "GEN CONTR.", AND "G.C." SHALL BE 22. ALL STRUCTURAL ELEMENTS WHICH DO NOT REQUIRE FIREPROOFING SHALL BE FIELD PAINTED.
UNDERSTOOD TO BE THE SAME UNLESS SPECIFICALLY NOTED OTHERWISE.
23. ALL EXTERIOR HANDRAILS AND EXTERIOR EXPOSED METAL SHALL BE GALVANIZED AND PAINTED
7. THE OWNER SHALL RETAIN THE SERVICES OF A LICENSED ARCHITECT/ENGINEER FOR ALL REQUIRED UNLESS NOTED OTHERWISE.
CONTROLLED INSPECTIONS. PARTITION NOTES:
24. ALL EXTERIOR DOORS SHALL PREVENT AIR LEAKAGE/INFILTRATION AROUND THEIR PERIMETER
8. THE GENERAL CONTRACTOR SHALL OBTAIN SIGN-OFF FROM THE DEPARTMENT OF BUILDING WHEN IN A CLOSED POSITION. 1. DEFLECTION FOR ALL PARTITIONS SHALL NOT EXCEED 1/240TH OF THE SPAN MAXIMUM FOR
AFTER COMPLETION OF WORK. TYPICAL GYPSUM PARTITIONS, OR 1/360 FOR WOOD-CLAD PARTITIONS, OR STONE-CLAD PARTITION
25. ALL EXTERIOR JOINTS AROUND WINDOW AND DOOR FRAMES, BETWEEN WALLS AND FOUNDATIONS, SYSTEMS.
9. TOP OF ARCHITECTURAL FINISH OF FIRST FLOOR SEATING ELEVATION=0'-0" FOR THE PURPOSES OF BETWEEN WALLS AND ROOFS, AND BETWEEN WALLS AND PANELS AT PENETRATION OF UTILITIES
THESE CONTRACT DOCUMENTS. THROUGH THE ENVELOPE SHALL BE SEALED, CAULKED OR WEATHER STRIPPED TO PREVENT AIR 2. WATER RESISTANT DRYWALL (FOR THE FULL HEIGHT OF THE PARTITION CONSTRUCTION) SHALL BE
LEAKAGE/INFILTRATION. USED IN TOILETS, SHOWERS, SERVICE ROOMS, ETC. USE STANDARD GYPSUM BOARD FOR CEILING
10. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL BE KNOWLEDGEABLE OF CONDITIONS CONSTRUCTION.
THEREON. HE SHALL INVESTIGATE, VERIFY AND BE RESPONSIBLE FOR ALL CONDITIONS OF THE 26. ALL EXTERIOR SOFFITS SHALL BE CONSTRUCTED WITH RIGID GALVANIZED METAL FRAME
PROJECT AND SHALL NOTIFY THE OWNER OF ANY CONDITIONS REQUIRING MODIFICATIONS BEFORE MEMBERS AND SHALL RESIST UPLIFTING WIND LOADS OF 1.5 TIMES THE WIND PRESSURE DIAGRAM. 3. PENETRATIONS: COORDINATE WITH MECHANICAL CONTRACTOR FOR OPENINGS REQUIRED FOR
PROCEEDING WITH THE WORK. RETURN AIR IN FULL HEIGHT PARTITIONS.
27. ALL EXTERIOR SOFFITS SHALL BE INSTALLED TO PROVIDE A 'U' VALUE OF 0.09 SHALL HAVE A
11. REFER TO STRUCTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR ADDITIONAL VAPOR BARRIER AND SHALL BE PROPERLY SEALED AGAINST AIR INFILTRATION. 4. PROVIDE LATERAL BRACING TO STRUCTURE ABOVE FINISHED CEILINGS FOR PARTITIONS
GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. ALL NOTES ARE TO BE REVISED AND APPLIED TO EXCEEDING UNSUPPORTED HEIGHTS INDICATED ON DRAWINGS.
RELATED BUILDING COMPONENTS. 28. ALL DISSIMILAR METALS SHALL BE EFFECTIVELY ISOLATED FROM EACH OTHER TO AVOID
MOLECULAR BREAKDOWN. 5. PROVIDE HORIZONTAL CONTROL JOINTS AT 12'-0' O.C. IN THE VERTICAL DIRECTION UNLESS
12. NOTES APPEAR ON VARIOUS SHEETS FOR DIFFERENT SYSTEMS AND MATERIALS. SHEETS ARE TO NOTED OTHERWISE.
BE REVIEWED AND NOTES ON ANY ONE SHEET ARE TO BE APPLIED ON RELATED DRAWINGS AND 29. ALL DIMENSIONS ARE FROM FINISH TO FINISH, UNLESS OTHERWISE NOTED.
DETAILS. 6. PROVIDE CONTROL JOINTS IN GYPSUM WALLBOARD CONSTRUCTION SUCH THAT PARTITION OR
30. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL CONDITIONS AND FURRING RUNS DO NOT EXCEED 30', AND CEILING DIMENSIONS DO NOT EXCEED 50' IN EITHER
13. DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE DETAILED. WHERE SPECIFIED MATERIALS THE PROPOSED CONSTRUCTION AREA. THE CONTRACTOR SHALL DESIGN AND INSTALL ALL DIRECTION WITH PERIMETER RELIEF OR 30' WITHOUT PERIMETER RELIEF.
DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE DETERMINED, CONSULT THE ARCHITECT ADEQUATE SHORING AND BRACING FOR ALL STRUCTURAL AND REMOVAL TASKS. THE CONTRACTOR
BEFORE PROCEEDING WITH THE WORK. SHALL HAVE SOLE RESPONSIBILITY FOR ANY DAMAGE OR INJURIES CAUSED BY OR DURING THE 7. PROVIDE VERTICAL CONTROL JOINTS WITH SEALANT IN MASONRY WALLS AS SHOWN IN
EXECUTION OF WORK. DRAWINGS WITH MAXIMUM SPACING OF 25'-0'.
14. ALL ELEVATOR AND STAIR OPENINGS SHALL BE CERTIFIED BY THE ELEVATOR SUBCONTRACTOR
PRIOR TO FORMING. REQUIRED MODIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE 31. THE CONTRACTOR SHALL REPLACE AND REPAIR MISSING, BROKEN SIDEWALK, CURB, OR 8. COMPLETELY SEAL WITH ACOUSTICAL SEALANT HEADS, BASES, AND ENDS, PLUS ALL
ARCHITECT FOR APPROVAL PRIOR TO FORMING. ROADWAY DAMAGE DURING CONSTRUCTION AS DIRECTED BY THE BOROUGH PENETRATIONS (INCLUDING BUT NOT LIMITED TO MECHANICAL, ELECTRICAL, AND PLUMBING WORK).
15. REFER TO CERTIFIED MECHANICAL AND ELECTRICAL CONTRACTOR'S DRAWINGS AND 9. PROVIDE SOUND BLANKETS AS INDICATED.
MANUFACTURER'S TEMPLATE DRAWINGS FOR ALL MECHANICAL AND ELECTRICAL EQUIPMENT
SUPPORTS, BOLT SETTING TEMPLATES, ISOLATIONS, SPRING ISOLATION,ETC, NOT SHOWN ON THE
DRAWINGS.
3. ALL RATED PARTITIONS SHALL RUN PAST STRUCTURAL BEAMS, TO THE UNDERSIDE OF 2. INTERIOR FLOOR FINISH SHALL BE TESTED IN ACCORDANCE TO NFPA 253. WOOD FINISH FLOORING
STRUCTURAL SLAB. WHERE THE PARTITIONS TERMINATE TO THE UNDERSIDE OF STRUCTURAL IS PERMITTED TO BE ATTACHED DIRECTLY TO THE EMBEDDED OR FIREBLOCKED WOOD SLEEPERS
BEAMS, THE STRUCTURAL BEAMS SHALL HAVE ADDITIONAL SPRAYED-ON FIREPROOFING TO ACHIEVE AND SHALL BE PERMITTED WHERE CEMENTED DIRECTLY TO THE TOP SURFACE OF APPROVED
AN AREA SEPARATION RATING EQUAL TO THAT OF THE PARTITION RATING, IF REQUIRED. FIRE-RESISTANCE REATED CONSTRUCTION OR DIRECTLY TO A WOOD SUBFLOOR ATTACHED TO
SLEEPERS AS PROVIDED IN SECITON 804.4.1.
4. SPACE BETWEEN SLAB AND EXTERIOR WALL AND ALL OPENINGS IN THE FLOOR SLABS INCLUDING
SPACES BETWEEN DUCTS, CONDUIT, PIPING, ETC., (EXCEPT WHEN COMPLETELY ENCLOSED BY FIRE 3. ALL DECORATIONS AND TRIM SHALL COMPLY WITHT HE REQUIREMENTS OF THE NEW YORK CITY
RATED CONSTRUCTION), SHALL BE SAFED- OFF(FILLED) WITH APPROVED SAFING MATERIAL TO FIRE CODE.
MAINTAIN FIRE RATING CONTINUITY OF THE FLOOR CONSTRUCTION. ALL JOINTS OF ANY ELEMENT OF
CONSTRUCTION SHALL BE TIGHT AND PREVENT THE PASSAGE OF SMOKE OR FLAME.
5. WHERE MASONRY WALLS AT INTERIOR LOT LINES ARE BROKEN TO ACCOMMODATE STRUCTURE
THEREBY REDUCING THE FIRE RATING OF THE WALL AT THE STRUCTURE, THEN THE STRUCTURE
SHALL BE FIREPROOFED AT THE REQUIRED WALL RATING.
6. ALL FIRE RESISTIVE (LABELED) FIRE DOORS SHALL HAVE THE APPROPRIATE LABELS AFFIXED TO
BOTH DOOR AND FRAME.
7. A FINISH OR FIRE RATING INDICATION ON A WALL SHALL MEAN THE ENTIRE LENGTH OF WALL IS TO
BE FINISHED OR FIRE RATED AS INDICATED.
8. ALL PIPING, DUCTS, ETC., THAT PENETRATE FLOOR SLABS SHALL BE INSTALLED IN A MANNER THAT Roxane Tsirigotis, RA
WILL PRESERVE THE FIRE RESISTIVE AND STRUCTURAL INTEGRITY OF THE BUILDING.
9. WHERE INTERIOR FINISH MATERIALS ARE SPACED (FURRED) FROM THEIR SUPPORTING MEMBERS, APPROVED
Under Directive 2 of 1975
THE CONCEALED SPACES CREATED SHALL BE FIRE STOPPED AS REQUIRED BY CODE. Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES568870367 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES474721892 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES609069543 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
EQUIPMENT
PERMITTED
IN SHADED
AREA
(A) BACK WALL (B) SIDEWALL (C) ELONGATED
WALL-HUNG (URINAL)
ALTERNATE NOTES:
1. 1'-6" DIMENSIONS @ TOILETS IS 1'-4 21"
DOOR LOCATION
FOR RESIDENTIAL USE, (J2), TYPICAL
METAL STUDS @ 12" O.C.
20 GA. STEEL
(WALL MOUNTED W.C.)
(FLOOR MOUNTED W.C.)
ANCHOR PLATE PAN
HEAD SCREW
NOTES:
1. 1'-6"
(WALL MOUNTED W.C.)
DIMENSIONS @
(FLOOR MOUNTED W.C.) (WALL MOUNTED W.C.)
(FLOOR MOUNTED W.C.) TOILETS IS 1'-4 21" GYPSUM WALLBOARD
42" MIN. LATCH APPROACH ONLY, FOR RESIDENTIAL
ALL OTHER APPROACHES 48" MIN. USE, (J2), TYPICAL
GRAB BAR TO BE
INSTALLED WHERE
MIDDLE OF ROW END OF ROW
INDICATED ON PLANS.
42" MIN. LIATCH APPROACH ONLY, ALL
INTERNATIONAL ACCESSIBILITY SYMBOL
OTHER APPROACHES 48" MIN.
RAISED (IF BOTH CLOSER AND
LATCH ARE PROVIDED) Lobby
PULL SIDE
HANDICAPPED ACCESS NOTES:
PUSH SIDE
1. DOORS SHALL BE CAPABLE OF OPENING AT LEAST 90
DEGREES AND SHALL BE SO MOUNTED THAT CLEAR
WIDTH OF DOORWAY IS NOT AT LEAST 32 INCHES.
2. LATCHING AND LOCKING DOORS THAT ARE HAND
ACTIVATED AND WHICH ARE IN A PATH OF TRAVEL
SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER
TYPE HARDWARE.
3. MAXIMUM EFFORT TO OPERATE FIRE DOORS SHALL
PROPORTIONS BE 15 LBS. AT OTHER INTERIOR DOORS MAXIMUM
INTERNATIONAL INTERNATIONAL SYMBOL
(A) FRONT APPOACH, PULL SIDE (B) FRONT APPOACH, PUSH SIDE EFFORT TO OPERATE SHALL BE 5 LBS. (A) WALKING PANELS (B) WALKING
INTERNATIONAL TDD SYMBOL OF ACCESS FOR PROTRUDING OBJECTS
4. FLOOR, RAMP, AND TREAD SURFACES SHALL BE SLIP PARALLEL TO A WALL PERPENDICULAR TO A
ACCESSIBILITY SYMBOL HEARING EMPAIRED
RESISTANT. WALL
5. EMERGENCY WARNING SYSTEMS SHALL ACTIVATE A
MEANS OF WARNING THE HEARING IMPAIRED,
FLASHING VISUAL WARNING SHALL HAVE A
PULL SIDE PULL SIDE
6. THRESHOLDS SHALL NOT BE MORE THAN 21" HIGHER
THAN ADJACENT FLOOR OR LANDING, LEVEL CHANGE
NOTE:
THE AUTOMATIC DOOR REOPENING BETWEEN 41" AND 21" SHALL BE BEVELED WITH SLOPE NO
SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE)
DEVICE IA ACTIVATED IF AN OBJECT GREATER THAN 1:2.
SHALL BE MINIMUM 3" HIGH AND PLACED ON BOTH JAMBS
PASSES THROUGH EITHER LINE A
AT EACH FLOOR ENTRANCE OR LINE B. LINE A & B REPRESENT ELEVATOR CAR CONTROL PANEL
THE VERTICAL LOCATIONS OF THE 7. CENTER OF ALARM PULL BOXES SHALL BE 4'-0" A.F.F.
DOOR REOPENING DEVICE NOT HALL CALL BUTTONS (C) HINGE APPROACH, PULL SIDE (D) HINGE APPROACH, PULL SIDE
REQUIRING CONTACT RAISED FLOOR DESIGNATIONS (A) CLEAR FLOOR SPACE (B) HIGH AND LOW SIDE (C) MAX. SIDE SPACE
(PARALLEL APPROACH) REACH LIMITS OVER OBSTRUCTION
AUTOMATIC REOPENING DEVICE (IF BOTH CLOSER AND
LATCH ARE PROVIDED)
LATCH PROVIDED)
7 8
PROVIDED)
(48" MIN IF BOTH
CLOSER IS
NUMERAL HEIGHT
(48" MIN IF
PROVIDED)
CLOSER IS
CL
(54" MIN IF
PUSH SIDE
5 6
CL
3 4
MAIN ENTRY FLOOR
1 2
54" MAX FOR SIDE
72" MIN.
L
C
60"
APPROACH
DOOR OPEN
L
35" MIN.
C
42"
(A) SHELVES (B) CLOSETS (C) FORWARD REACH LIMIT
5"
EMERGENCY STOP
OCTAGON SYMBOL
STRAGE SHELVES AND CLOSETS
SHALL BE RAISED HOISTWAY & ELEVATOR ENTRANCE AND CONTROLS (E) HINGE APPROACH, PUSH SIDE (F) LATCH APPROACH, PULL SIDE (G) LATCH APPOACH, PUSH SIDE
BUT THE X IS NOT
THRESHOLD
TO 1 1/2" 1 1/2" 1-1/4" 1/2" MAX.
TO 1-1/2"
RAMP SURFACE
1-1/4" TO
X = RAMP LENGTH
(HORIZONTAL PROJECTION OR RUN) Roxane Tsirigotis, RA
LANDING LANDING
5'-0" MIN. 30'-0" MAXIMUM RUN 5'-0" MIN. NOTES:
HANDRAIL GRAB BAR GRAB BAR HANDRAIL HANDRAIL
BOTTOM LANDING
1. 1/2" MAXIMUM TOTAL HEIGHT WITH 1/4" MAXIMUM VERTICAL CHANGE AT EDGE.
NOTE: APPROVED
SLOPE = Y:X, WHERE X IS A LEVEL PLANE. 2. 1 : 2 SLOPED BEVEL REQUIRED IF LEVEL CHANGE IS OVER 1/4" VERTICAL LEVEL CHANGE. Under Directive 2 of 1975
ADJUSTIBLE
SINK SECTION
ARC Architecture + Design Studio
WALL CABINETS TO BE
ADJUSTABLE SO THAT HEIGHT
OF LOWEST SHELF TO BE
WORK SECTION
48" A.F.F. WHEN CONVERTED R&O Engineering P.C.
WORK SECTION
TO ACCESSIBLE KITCHEN.
ADJUSTIBLE
PROVIDE REQUIRED WALL REINFORCEMENT
SINK SECTION
ADJUSTIBLE
ADJUSTIBLE
FOR POSSIBLE FUTURE RELOCATION.
Bicaluro Associates P.C.
SUGGESTED FLEXIBLE
REMOVABLE
REMOVABLE SUPPLY LINES
BASE CABINETS BASE CABINETS
SUGGESTED SLIP JOINT IN
TAIL PIECE
ADAPTABLE KITCHENETTE
(MIN. PERMISSIBLE SIZE)
ADAPTABLE KITCHEN ADAPTABLE KITCHEN
LOWERABLE WORK SURFACE LOWERABLE SINK COUNTER
LOWERABLE WALL CABINETS
ADAPTABLE BATHROOM
MINIMUM SIZE SIDE APPROACH
ADAPTABLE ADAPTABLE
TYPE B TOILET TOILET
HEAD END
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES692485209 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES318455966 Scan Code
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES882302052 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES760134050 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
ARC Architecture + Design Studio
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES599841443 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES449536243 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
O
O
O P O P
Bicaluro Associates P.C.
P P
O
O O
O
O S
O S
O
O
O
O P O P
P P
P
P
P
O
O O
O O
O
O S
O S
O
P
P P
P P
P P
P
5 6 6
O P
P P
O P P
6 O P
O P
O
Roxane Tsirigotis, RA
O
O
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES095671701 Scan Code
CHAPTER 6
TYPES OF CONSTRUCTION
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
CHAPTER 7
FIRE-RESISTANTANCE-RATED CONSTRUCTION
CHAPTER 8
INTERIOR FINISHES
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES044120702 Scan Code
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES169445783 Scan Code
1. UL DESIGNS ARE BASED UPON THE TEST METHOD AND ACCEPTANCE CRITERIA IN
ANSI/UL263 (ASTM E119), "FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS"
2. REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS FOR FASTENING AND
FINISHING REQUIREMENTS.
3. ALL DIMENSIONS ON PLANS ARE TO FINISH UNLESS OTHERWISE NOTED.
ARC Architecture + Design Studio
4. ALL PARTITIONS WITH ACOUSTIC INSULATION SHALL HAVE PERIMETER CAULKING AS
PER MANUFACTURERS RECOMMENDATION AS NECESSARY TO MAINTAIN THE
PRESCRIBED STC RATING.
5. USE MOISTURE RESISTANT GWB IN ALL TOILETS, AT WALLS & CEILING R&O Engineering P.C.
6. ALL FIRE RATED PARTITIONS SHALL HAVE U.L. APPROVAL NO. ALL FIRE RATED
PARTITIONS SHALL EXTEND TO UNDERSIDE OF STRUCTURE.
7. ALL PARTITIONS TO SUPPORT WALL MOUNTED CABINETS SHALL HAVE 20 GAUGE
METAL STUDS SPACED AS RECOMMENDED BY THE MANUFACTURER. PROVIDE Bicaluro Associates P.C.
PLYWOOD BACKING OR STEEL STRAPS BETWEEN STUDS IN WALLS TO SUPPORT
CABINETS, GRAB BARS AND OTHER EQUIPMENT.
8. ALL PARTITIONS TO BE TAPED, SPACKLED AND PAINTED PER FINISH SCHEDULE.
9. ELECTRICAL AND SERVICE OUTLETS FOR ADJACENT ROOMS ARE TO BE POSITIONED
MINIMUM 24 INCHES APART AND IN SEPARATE STUD SPACES.
10. USE 20 GA. DOUBLE METAL STUDS AT ALL DOOR JAMBS IN BOX SHAPED
CONFIGURATION
11. USE 20 GA. METAL STUDS AT WINDOW JAMBS, SILLS & HEADS
12. FRAME DRYWALL PARTITIONS AROUND DUCT, PIPE & STRUCTURAL PENETRATIONS.
DO NOT FRAME DRYWALL TO PENETRATIONS. PROVIDE FIRESTOPPING
CORRESPONDING TO PARTITION RATING AS REQUIRED.
13. ALL TOP AND BOTTOM METAL STUD RUNNERS AT ALL EXTERIOR WALL ARE TO BE
SET IN A FULL BED OF SEALANT - TYPICAL
14. STAGGER JOINTS WHERE DOUBLE LAYERS OF GWB SHEATHING IS REQUIRED
15. CARPENTER TO COORDINATE WET WALL PARTITIONS WITH PLUMBER AND ALLOW
FOR FURRING OF PARTITIONS AS REQUIRED FOR PLUMBING
16. CARPENTER TO ALLOW FURRING OUT PARTITIONS OR USING WIDER STUDS AS
REQUIRED TO INSTALL FIRE EXTINGUISHER CABINETS, ELECTRICAL PANELS AND
OTHER WALL MOUNTED DEVICES
(III) INSTALLATION SHALL COMPLY WITH THE FOLLOWING:
(A) STUDS SHALL BE MINIMUM 3-½ INCH (89 MM) DEPTH COLD-FORMED STEEL FRAMING, AT
LEAST 33 MILS THICK (20 GAUGE).
(B) VERTICAL STUDS SHALL BE SPACED AT A MAXIMUM DISTANCE OF 24 INCHES (610 MM), ON
CENTER.
(C) RUNNERS SHALL BE SECURELY ATTACHED AT THE FLOOR AND CEILING TO STRUCTURAL
ELEMENT MEMBERS AND SHALL COMPLY WITH THE STRUCTURAL REQUIREMENTS OF THE
BUILDING CODE.
(D) WALL BOARDS SHALL BE ATTACHED WITH NO. 8 SELF-DRILLING BUGLE-HEAD SCREWS, 12
INCHES (305 MM), ON CENTER MAXIMUM, WITH A MINIMUM DEPTH OF ⅝ INCH (16 MM)
PENETRATION INTO THE WALL CAVITY.
(E) JOINTS BETWEEN ADJOINING SHEETS OF WALL BOARD SHALL BE STAGGERED FROM BASE
LAYER WITH FACE PANEL LAYER.
Roxane Tsirigotis, RA
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES885689625 Scan Code
§24-01 CONSTRUCTION AND MAINTENANCE OF REFUSE CHUTES AND REFUSE ROOMS.
(A) REFUSE CHUTE ENCLOSURES. REFUSE CHUTES USED FOR CONVEYANCE OF GARBAGE AND RUBBISH FROM UPPER FLOORS OF A BUILDING TO A CELLAR ARC Architecture + Design Studio
OR OTHER LOCATION SHALL BE CONSTRUCTED WITH AN ENCLOSURE OF BRICK MASONRY AT LEAST EIGHT INCHES IN THICKNESS OR OF REINFORCED
CONCRETE AT LEAST SIX INCHES IN THICKNESS, EXCEPT AS OTHERWISE PROVIDED IN THIS SECTION.
(B) HEIGHT AND SERVICE OPENINGS. REFUSE CHUTES SHALL EXTEND FROM THE REFUSE COLLECTION ROOM TO A HEIGHT OF AT LEAST SIX FEET ABOVE THE
ROOF. A SPARK ARRESTOR SHALL BE PROVIDED AT THE TOP OF THE CHUTE ABOVE THE ROOF. SERVICE OPENINGS INTO THE CHUTE SHALL BE EQUIPPED
WITH APPROVED SELF-CLOSING HOPPERS SO CONSTRUCTED THAT THE CHUTE IS CLOSED OFF WHILE THE HOPPER IS BEING LOADED AND SO THAT NO PART
WILL PROJECT INTO THE CHUTE. THE AREA OF SERVICE OPENING SHALL NOT EXCEED ONE THIRD THE AREA OF THE CHUTE. HOPPER DOORS SHALL HAVE A R&O Engineering P.C.
FIRE RESISTIVE RATING OF AT LEAST ONE HOUR, UNLESS SEPARATED FROM THE CORRIDOR BY A FIREPROOF, SELF-CLOSING DOOR IN WHICH CASE THEY
SHALL BE CONSTRUCTED OF INCOMBUSTIBLE MATERIAL .
(C) EXISTING FLUES AND REFUSE CHUTES . FLUES FOR EXISTING INCINERATORS MAY BE USED FOR REFUSE CHUTES PROVIDED SUCH FLUES ARE IN GOOD
CONDITION AND PROVIDED THE FLUES COMPLY WITH THE PROVISIONS OF SUBDIVISIONS (A) AND (B) OF THIS SECTION. EXISTING REFUSE CHUTES MAY BE
CONTINUED IN USE PROVIDED THEY CONFORM TO THE PROVISIONS OF SUBDIVISIONS (A) AND (B) OF THIS SECTION, EXCEPT THAT EXISTING REFUSE CHUTES Bicaluro Associates P.C.
OF OTHER CONSTRUCTION, WHICH HAVE BEEN APPROVED BY THE DEPARTMENT MAY BE RETAINED.
(D) REFUSE CHUTES IN NEW CONSTRUCTION . WHERE REFUSE COMPACTING SYSTEMS ARE REQUIRED HEREAFTER IN NEW CONSTRUCTION, REFUSE CHUTES
SHALL BE REQUIRED FOR CONVEYANCE OF GARBAGE AND RUBBISH TO REFUSE COLLECTION ROOMS, EXCEPT THAT REFUSE CHUTES WILL NOT BE REQUIRED
IN CLASS A MULTIPLE DWELLINGS WHICH ARE FOUR STORIES OR LESS IN HEIGHT. REFUSE CHUTES ERECTED HEREAFTER IN NEW CONSTRUCTION SHALL BE
OF A TYPE APPROVED BY THE BOARD OR SHALL COMPLY WITH THE REQUIREMENTS OF SUBDIVISIONS (A) AND (B) OF THIS SECTION. CHUTES SHALL BE
CONSTRUCTED STRAIGHT AND PLUMB, WITHOUT PROJECTIONS OF ANY KIND WITHIN THE CHUTE. REFUSE CHUTES SHALL HAVE AN INSIDE DIMENSION OF AT
LEAST TWENTY-FOUR INCHES FOR THE FULL HEIGHT OF THE CHUTE. ALL CHUTES SHALL BE SUPPORTED ON FIREPROOF CONSTRUCTION HAVING AT LEAST A
THREE HOUR RESISTIVE RATING.
(E) REFUSE COLLECTION ROOMS . A REFUSE COLLECTION ROOM SHALL BE PROVIDED AT THE BOTTOM OF ALL CHUTES AT THE CELLAR OR LOWEST STORY
LEVEL TO RECEIVE THE REFUSE. SUCH ROOMS SHALL BE ENCLOSED WITH WALLS AND ROOFS CONSTRUCTED OF MATERIAL HAVING A MINIMUM FIRE
RESISTIVE RATING OF THREE HOURS, EXCEPT THAT GYPSUM MASONRY MAY NOT BE USED FOR SUCH ENCLOSURE WALLS. OPENINGS TO SUCH ROOMS SHALL
BE PROVIDED WITH FIREPROOF, SELF-CLOSING DOORS HAVING A MINIMUM FIRE RESISTIVE RATING OF ONE AND ONE-HALF HOURS. IT SHALL BE UNLAWFUL TO
KEEP SUCH DOORS OPEN. REFUSE CHUTES SHALL EXTEND TO THE UNDERSIDE OF THE ROOF OF THE REFUSE ROOM OR LOWER. ROOFS SHALL BE AT LEAST
SIX INCHES AWAY FROM COMBUSTIBLE FLOOR OR WALL CONSTRUCTION. REFUSE ROOMS SHALL BE USED ONLY FOR RECEIPT OF REFUSE AND FOR REFUSE
COMPACTING EQUIPMENT. REFUSE ROOMS SHALL BE PROVIDED WITH SUFFICIENT SPRINKLERS TO SPRINKLE ALL PARTS OF THE ROOM, WITH AT LEAST TWO
SPRINKLER HEADS PROVIDED AND WITH SPRINKLERS SO SEPARATED AS TO SPRINKLE A MAXIMUM AREA OF THE ROOM WHEN ONE OF THE SPRINKLERS IS
BLOCKED OR NOT OPERATING. A HOSE CONNECTION SHALL BE PROVIDED WITHIN THE REFUSE ROOM. EXISTING REFUSE ROOMS AND INCINERATOR ROOMS
THAT HAVE BEEN APPROVED BY THE DEPARTMENT FOR SUCH USE MAY BE RETAINED AS APPROVED.
(F) COLLECTION ROOM FLOORS. THE FLOOR WITHIN THE ROOM FOR THE COLLECTION OF REFUSE SHALL BE CONSTRUCTED OF CONCRETE AND SHALL BE
SLOPED TO A FLOOR DRAIN WITHIN THE ROOM CONNECTED TO THE HOUSE DRAIN. THE DRAIN SHALL BE PROVIDED WITH A PROTECTIVE SCREEN TO RETAIN
SOLID MATERIAL. FLOOR DRAIN TRAPS SHALL BE READILY ACCESSIBLE FOR CLEANING.
(G) USE OF EXISTING COMBUSTION CHAMBERS. EXISTING INCINERATOR COMBUSTION CHAMBERS MAY BE USED IN WHOLE OR IN PART AS REFUSE
COLLECTING ROOMS FOR COLLECTION OF REFUSE AND FOR COMPACTING EQUIPMENT PROVIDED THE GRATES ARE REMOVED AND PROVIDED THEY COMPLY
WITH THE PROVISIONS OF SUBDIVISION (E) OF THIS SECTION.
(H) SPRINKLER OPERATION AND WATER SUPPLY . SPRINKLERS SHALL BE DESIGNED TO OPERATE AUTOMATICALLY AT A TEMPERATURE NOT EXCEEDING ONE
HUNDRED SIXTY-FIVE DEGREES FAHRENHEIT. THEY MAY BE ELECTRICALLY CONTROLLED PROVIDED SUCH SPRINKLERS ARE APPROVED BY THE BOARD OF
STANDARDS AND APPEALS. SPRINKLERS MAY BE CONNECTED TO THE COLD WATER SUPPLY OF THE BUILDING AT THE POINT WHERE SUCH SERVICE ENTERS
THE BUILDING OR AT THE BASE OF A WATER SUPPLY RISER PROVIDED THE PIPING OF SUCH SERVICE OR RISER IS OF ADEQUATE SIZE. NO CONNECTIONS,
EXCEPT THOSE FOR SPRINKLERS, SHALL BE MADE TO THE SPRINKLER PIPING
.
(I) HOPPERS, CUT OFF DOORS AND COMPACTORS. A HOPPER AND CUT OFF DOOR SHALL BE PROVIDED AT THE BOTTOM OF THE REFUSE CHUTE TO REGULATE
AND GUIDE THE FLOW OF REFUSE INTO CONTAINERS. WHERE COMPACTORS ARE INSTALLED SO THAT THE REFUSE FLOWS DIRECTLY INTO THE COMPACTING
EQUIPMENT, THE EQUIPMENT MAY BE USED IN PLACE OF THE HOPPER AND CUT OFF DOOR. COMPACTING EQUIPMENT SHALL BE ARRANGED TO OPERATE
AUTOMATICALLY WHEN THE LEVEL OF RUBBISH IS NOT HIGHER THAN THREE FEET BELOW THE LOWEST DOOR.
COMPACTORS SHALL BE LOCATED ENTIRELY WITHIN THE ENCLOSURE OF THE REFUSE ROOM AND FORMER COMBUSTION CHAMBER WHERE THE LATTER IS
RETAINED, EXCEPT THAT MOTORS, PUMPS AND CONTROLS MAY BE INSTALLED IN ADJACENT ROOMS.
WHERE REFUSE IS REMOVED MANUALLY, THE REFUSE SHALL BE REMOVED WITH SUFFICIENT FREQUENCY SO THAT IT WILL AT NO TIME EXTEND LESS THAN
THREE FEET BELOW THE LEVEL OF THE LOWEST HOPPER DOOR OPENING INTO THE CHUTE.
(J) NUMBER OF SPRINKLER HEADS. SUFFICIENT SPRINKLERS SHALL BE INSTALLED IN THE REFUSE ROOM AND FORMER COMBUSTION CHAMBER TO PROVIDE
SPRINKLER COVERAGE FOR THE ENTIRE AREA OF EACH UNIT.
(1) ADEQUATE LIGHTING SHALL BE PROVIDED IN REFUSE ROOMS.
(2) REFUSE CHUTES, REFUSE ROOMS, HOPPERS AND ALL PARTS OF THE REFUSE COLLECTING SYSTEM SHALL BE MAINTAINED IN A CLEAN AND SANITARY
CONDITION AT ALL TIMES, FREE OF VERMIN, ODORS AND DEFECTS, AND SHALL BE MAINTAINED IN GOOD OPERATING CONDITION. FUSED SPRINKLER HEADS
SHALL BE REPLACED PROMPTLY.
(3) THE OWNER SHALL ESTABLISH A PROGRAM TO ENSURE THAT THE REFUSE CHUTE AND THE REFUSE ROOM AND APPURTENANCES WILL BE TREATED AS
OFTEN AS MAY BE NECESSARY TO PREVENT INFESTATION WITH INSECTS OR RODENTS. THE OWNER SHALL MAINTAIN A RECORD OF SUCH TREATMENTS
WHICH SHALL BE AVAILABLE AT ALL TIMES FOR INSPECTION BY THE DEPARTMENT.
(K) THESE RULES SHALL APPLY ONLY TO REFUSE CHUTES IN NEW CONSTRUCTION AND TO REFUSE CHUTES RESULTING FROM THE CONVERSION OF EXISTING
INCINERATOR FLUES AND TO EXISTING REFUSE CHUTES.
(L) COLLECTION AND DISPOSAL OF REFUSE WITHIN PREMISES. THE COLLECTION AND DISPOSAL OF REFUSE WITHIN ANY BUILDING OR ON ANY PREMISES
SHALL BE PERFORMED AS DEEMED NECESSARY TO PROVIDE FOR THE SAFETY, HEALTH AND WELL BEING OF THE OCCUPANTS OF BUILDINGS AND OF THE
PUBLIC. THE CONSTRUCTION, OPERATION, MAINTENANCE, CLEANLINESS AND SANITATION OF REFUSE CHUTES AND REFUSE ROOMS AND EXTERMINATION
TREATMENT FOR INSECTS AND RODENTS, AND THE KEEPING OF RECORDS OF SUCH TREATMENTS FOR REFUSE CHUTES AND REFUSE ROOMS SHALL BE IN
ACCORDANCE WITH REGULATIONS ESTABLISHED BY THIS DEPARTMENT IN CONSULTATION WITH THE DEPARTMENT OF HEALTH.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES249121247 Scan Code
ARC Architecture + Design Studio
6'-0" 6'-0" 9'-0" 8'-0"
3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 5'-0" 3'-0" R&O Engineering P.C.
Bicaluro Associates P.C.
7'-0"
7'-0"
7'-0"
7'-0"
7'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
2'-6"
2'-6"
2'-6"
2'-6"
2'-6"
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
8'-0" 8'-0" 8'-0"
3'-0" 5'-0" 5'-0" 3'-0" 5'-0" 3'-0" 3'-0" 2'-10"
7'-0"
7'-0"
7'-0"
7'-0"
7'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
2'-6"
2'-6"
2'-6"
2'-6"
2'-6"
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
3'-0"
5'-0"
4'-0"
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
DEPT OF BLDGS321192801 Job Number ES914372885 Scan Code
ARC Architecture + Design Studio
3'-0"
1. PROVIDE ADAPTABLE FRAMES
FOR FUTURE OUTSWINGING
SAMPLE WINDOW SPEC - FINAL SELECTION MUST NOT EXCEED INPUTTED COMCHECK VALUES: U-FACTOR 0.38 AND SHGC 0.40 (ADA) BATHROOM DOORS
THROUGHOUT.
PROVIDE 2'X2' 24 GA. 2. ALL DOORS IN FIRE RATED R&O Engineering P.C.
STEEL PLATE BEHIND PARTITIONS SHALL BE FIRE
GYP. BD. AT STRIKE RATED, AND HAVE CLOSERS
7'-0"
SIDE OF DOORS FOR AND LATCH
ALL ENTRY DOORS OF 3. * DENOTES 1 1/2 HR. FIRE
5'-0"
APARTMENTS @ PROTECED SELF-CLOSING
A.F.F.
Bicaluro Associates P.C.
3'-2"
METAL STUD WALLS. 4. DOOR OPENING FORCE FOR
DOORS OTHER THAN FPSC
DOORS SHALL BE 5 LBS
MAXIMUM AS PER ANSI A
117.1-2003
5. ALL APARTMENT ENTRY &
STAIR DOORS & FRAMES
2'-8" 2'-10" SHALL BE APPROVED IN
1ST FLOOR
ACCORDANCE WITH UL 1784
FOR SMOKE AND DRAFT
CONTROL AND SHALL BE
LABELED FOR 1 1/2 HOUR
RATED SELF CLOSING AND
BEAR THE LETTER "S".
7'-0"
7'-0"
A.F.F.
A.F.F.
3'-2"
3'-2"
7'-0"
7'-0"
A.F.F.
3'-2"
7'-0"
SAMPLE DOOR SPEC - FINAL SELECTION MUST NOT EXCEED INPUTTED COMCHECK VALUES: U-FACTOR 0.38 AND SHGC 0.40
A.F.F.
3'-2"
EXIT DOORS ASSOCIATED WITH THE BUILDING THERMAL ENVELOPE TO HAVE MAXIMUM U-FACTOR
OF 0.61
7'-0"
REMARKS: DOOR W/ AUTOMATIC DOOR OPENER AND OCCUPANCY SENSOR TO MAINTAIN
A.F.F.
3'-2"
DOOR IN OPEN POSITION WHILE THE ROOM IS OCCUPIED. DOOR MUST RETURN TO CLOSED
POSITION IF THE ROOM IS NOT OCCUPIED OR IN CASE OF POWER FAILURE.
3'-0"
7'-0"
A.F.F.
3'-2"
2'-10"
7'-0"
A.F.F.
3'-2"
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES610103549 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES601215181 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES229165462 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES586446170 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES096741013 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES755043363 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES378977618 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES345035208 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES167988734 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES915572677 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES929389221 Scan Code
ARC Architecture + Design Studio
ENERGY CODE COMPLIANCE STATEMENT
TO THE BEST OF MY KNOWLEDGE, BELIEF AND PROFESSIONAL
JUDGEMENT, ALL WORK UNDER THIS APPLICATION IS IN R&O Engineering P.C.
COMPLIANCE WITH THE 2014 NYC ENERGY CONSERVATION
CODE, CHAPTER C4.
NOTE:
THIS PROJECT REQUIRES COMMISSIONING AND A Bicaluro Associates P.C.
PRELIMINARY COMMISSIONING REPORT CERTIFICATION WILL
BE PROVIDED PRIOR TO SIGN-OFF
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES031403206 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
ENERGY ANALYSIS
D.S.
11 OF 12
EN-200.00
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES523776363 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
COMCHECK CERTIFICATE
OF COMPLIANCE
D.S.
11 OF 12
EN-201.00
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES831410898 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
GENERAL NOTES, VENTILATION
REQUIREMENTS & SYMBOLS
D.S.
1 OF 12
M-100.00
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES628102821 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
CELLAR & 1ST
FLOOR PLANS
D.S.
2 OF 12
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
M-101.00
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES682822459 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
2ND THRU 6TH
FLOOR PLANS
D.S.
3 OF 12
M-102.00
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES861791371 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
7TH FLOOR AND ROOF
PLANS
D.S.
4 OF 12
M-103.00
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES383471119 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
BULKHEAD
PLAN AND DETAILS
D.S.
5 OF 12
M-104.00
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES841076452 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
AIR FLOW DIAGRAM
D.S.
6 OF 12
M-105.00
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES428465793 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
EQUIPMENT SCHEDULES
D.S.
7 OF 12
M-106.00
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES215956207 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
HEAT PUMP SPLIT UNITS
D.S.
8 OF 12
M-107.00
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES333649449 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
DETAILS
D.S.
9 OF 12
M-108.00
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES522633798 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
MECHANICAL SYSTEMS
SPECIFICATIONS
D.S.
10 OF 12
M-109.00
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES597975870 Scan Code
GENERAL NOTES NEW YORK CITY BUILDING DEPARTMENT PLUMBING NOTES PLUMBING INSTALLATION CRITERIA
PIPE MATERIAL SCHEDULE
SANITARY DRAINAGE PIPING (S)
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
PIPING INSULATION SCHEDULE
NOTES:
OPEN GARDEN
BUSHWICK AVENUE
KENT
MYRTLE AVE
PLUMBING
NOTES & ABBREVIATIONS
PLUMBING FIXTURE CONNECTION SCHEDULE
PLUMBING APPLIANCE CONNECTION SCHEDULE
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES007925091 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
PLUMBING
CELLAR AND 1ST FL PLANS
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
1 2
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES343822015 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
3 4
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES611081115 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
PLUMBING
7TH FL & ROOF PLANS
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
5 6
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES815253328 Scan Code
MECHANICAL ROOM
ROOF
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
7TH FL
6TH FL.
5TH FL.
4TH FL.
3RD FL.
2ND FL.
1ST FL.
PLUMBING
SANITARY RISER DIAGRAM
CELLAR
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES745356408 Scan Code
ARC Architecture + Design Studio
ROOF
R&O Engineering P.C.
Bicaluro Associates P.C.
7TH FL
6TH FL.
5TH FL.
4TH FL.
3RD FL.
PLUMBING
DOMESTIC WATER
RISER DIAGRAM
1ST FL.
CELLAR
DEPT OF BLDGS321192801 Job Number ES617848328 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
ROOF ROOF
Bicaluro Associates P.C.
7TH FL 7TH FL
6TH FL. 6TH FL.
PLUMBING
GAS AND STORM
RISER DIAGRAMS
CELLAR CELLAR
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
1 2
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES691774301 Scan Code
FINISHED WALL
ARC Architecture + Design Studio
FIN. FL.
*
1/2" COMBINATION
MPT BRASS SWEAT
R&O Engineering P.C.
CONNECTION
42" 2" DRAIN
HANGER
(SEE NOTE #2) Bicaluro Associates P.C.
6" MAX.
TYP.
FINISHED FLOOR
PLUMBING
DETAILS
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES791458776 Scan Code
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
PLUMBING
SPECIFICATIONS
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES148321259 Scan Code
R&O Engineering P.C.
Bicaluro Associates P.C.
ROOF
EL: 71'-6"
7TH FL.
EL: 61'-6"
6TH FL.
EL: 51'-6"
5TH FL.
EL: 41'-6"
4TH FL.
FOR SPRINKLER WORK ONLY EL: 31'-6"
3RD FL.
EL: 21'-6"
OPEN GARDEN
2ND FL.
EL: 11'-6"
HYDRAULIC CALCULATIONS
A NUMBER IN TRIANGLE REPRESENT A NODE-NO WATER
1ST FL.
BUSHWICK AVENUE
DISCHARGE
A NUMBER IN A CIRCLE REPRESENT A SPRINKLER HEAD EL: 0'-0"
LOCATION
KENT
SPRINKLER
NOTES & ABBREVIATIONS
CELLAR
MYRTLE AVE Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES523118249 Scan Code
R&O Engineering P.C.
Bicaluro Associates P.C.
PLUMBING
CELLAR AND 1ST FL PLANS
APPROVED
Under Directive 2 of 1975
DEPT OF BLDGS321192801 Job Number ES179672783 Scan Code
ARC Architecture + Design Studio
FOR SPRINKLER WORK ONLY
R&O Engineering P.C.
Bicaluro Associates P.C.
SPRINKLER
2ND & TYP 3-6 FL PLANS
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
3 4
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES597649142 Scan Code
ARC Architecture + Design Studio
FOR SPRINKLER WORK ONLY
R&O Engineering P.C.
Bicaluro Associates P.C.
SPRINKLER
7TH & ROOF FL PLANS
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
5 6
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES457876026 Scan Code
SPRINKLER SPECIFICATIONS
ARC Architecture + Design Studio
R&O Engineering P.C.
Bicaluro Associates P.C.
SPRINKLER
SPECS & DETAILS
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES677125923 Scan Code
MISCELLANEOUS NOTES:
GENERAL NOTES: CONTROLLED INSPECTION NOTES:
FOUNDATION NOTES:
LOADING SCHEDULE
16-51
GENERAL NOTES
Roxane Tsirigotis, RA
C
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES808643777 Scan Code
ABBREVIATIONS: LEGEND:
GENERAL NOTES
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES388830226 Scan Code
1
B
1
1 OVERCUT SECTION
SCALE: 1/4" = 1'-0"
D
GENERAL NOTES:
A A
C C
B B
A A
D D 16-51
SHORING AND
UNDERPINNING
C C
PLAN
B B
A A
B SECTION - B
SCALE: 1/2" = 1'-0"
A
UNDERPINNING SEQUENCE OF WORK:
C SECTION -
SCALE: 1/2" = 1'-0"
TYPICAL UNDERPINING
PIT PLAN
SECTIONS &
D TYP. SECTION - UNDERPINNING PIT DETAILS
SCALE: 1/2" = 1'-0"
ISOMETRIC VIEW
OF TYPICAL SHORING
N.T.S.
Roxane Tsirigotis, RA
A VIEW APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
SCALE: 1/2" = 1'-0"
DEPT OF BLDGS321192801 Job Number ES238473980 Scan Code
FOUNDATION
PLAN
Roxane Tsirigotis, RA
FOUNDATION PLAN
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
OPTION 2
SECTION A-A
16-51
@ BUTTRESS @ INTERSECTION @ INSIDE CORNER
FOUNDATION
BOX-OUT OPENING THRU FOUNDATION WALL
SECTIONS &
@ OUTSIDE CORNER HORIZONTAL SECTION SHOWING DETAIL DETAILS
WATERPROOFED SLEEVE THRU WALL
OF PLACING WALL REINFORCEMENT
W/ WATERPROOFING
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES867629589 Scan Code
3 WALL SECTION
SCALE: 1/2" = 1'-0"
1 WALL SECTION
SCALE: 1/2" = 1'-0"
2/S-202
16-51
FOUNDATION
SECTIONS &
DETAILS
4 CONC PIER
SCALE: 1/2" = 1'-0"
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES528552471 Scan Code
1 EDGE OF SLAB
REINFORCEMENT
(TYP.)
2 EDGE OF SLAB
REINFORCEMENT
@ STAIRS
16-51
Roxane Tsirigotis, RA
Date: 04/17/2017
WITH CELLAR WALLS WITH 1ST FLOOR WALLS
SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0"
DEPT OF BLDGS321192801 Job Number ES520557328 Scan Code
1 EDGE OF SLAB
REINFORCEMENT
(TYP.)
2 EDGE OF SLAB
REINFORCEMENT
@ STAIRS
16-51
Roxane Tsirigotis, RA
3RD TO 5TH FLOOR FRAMING PLAN 6TH FLOOR FRAMING PLAN APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
WITH 2ND TO 4TH FLOOR WALLS WITH 5TH FLOOR WALLS
SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0"
DEPT OF BLDGS321192801 Job Number ES466939326 Scan Code
Roxane Tsirigotis, RA
BULKHEAD ROOF
7TH FLOOR FRAMING PLAN ROOF FRAMING PLAN APPROVED
Under Directive 2 of 1975 FRAMING PLAN
WITH 6TH FLOOR WALLS WITH 7TH FLOOR WALLS Date: 04/17/2017
COLUMN DETAILS
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES421377433 Scan Code
16-51
SECTIONS &
DETAILS
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
16-51
SECTIONS &
DETAILS
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES825313819 Scan Code
SECTIONS &
DETAILS
Roxane Tsirigotis, RA
APPROVED
Under Directive 2 of 1975
Date: 04/17/2017
DEPT OF BLDGS321192801 Job Number ES799487003 Scan Code
SW1 SHEAR WALL SCHEDULE SW3 SHEAR WALL SCHEDULE SWA SHEAR WALL SCHEDULE
SECTIONS &
SW2 SHEAR WALL SCHEDULE SWB SHEAR WALL SCHEDULE
DETAILS
Roxane Tsirigotis, RA