Master HP UL (65-500)
HP UL
6
VFI
TYPE
ONLINE Tower
The high levels of quality, reliability and technology based entirely on IGBT and
HIGHLIGHTS energy savings offered by the Master HP digital signal processors (DSP), the Master
range of UPS, has been extended to include HP UL range ensures maximum critical load
• High efficiency a UL/CSA Listed, 480 Vac 60 Hz version with protection, with VFI SS 111 classification
ratings from 65 kVA to 500 kVA. (Voltage and Frequency Independent) in
• IGBT-based rectifier IT managers, facility managers, and CTOs accordance with IEC EN 62040-3.
technology are under increasing pressure to reduce This range is designed using a new
downtime and assure that their critical configuration that includes an IGBT
• Compact, reliable and loads are supplied with uninterrupted and sinusoidal input rectifier. Unique in its
high quality power. With this increasingly design, double conversion technology with
robust stringent requirement, Riello UPS has galvanic isolated output guarantees a quality
invested in power solutions that meet strict power supply that is completely protected
• Galvanic isolation demands; a commitment resulting in the from all electrical anomalies at the input.
launch of the Master HP UL range.
• High overload capacity More than just an innovative and Complete galvanic separation
technologically-advanced UPS, it is a leap The Master HP UL UPS features an output
into the future of three-phase technology. isolation transformer on the inverter as part
With its double conversion on-line of the inverter circuit inside the UPS cabinet,
providing galvanic isolation between that generate current harmonics. Master MHT Battery care system: maximum
the load and the battery with improved UL series UPS have zero impact on the power battery care
versatility in system configuration, allowing: supply source, whether it is a utility grid or Master HP UL series UPS include a range of
• Complete UPS output galvanic isolation for generator set: features designed to prolong battery life and
critical infrastructures from the battery DC • Input current distortion < 3% reduce usage by using different recharging
power source; • Input power factor 0.99 methods; deep discharge protection, current
• Two truly separated supply inputs (utility • Power walk-in function that ensures limitation, and voltage compensation based
and bypass), which can be taken from two progressive rectifier start up on ambient temperature.
different power sources (with different • Start-up delay function, to restart the
neutrals); this is particularly well suited rectifiers when mains power is restored if Main features
for parallel systems in order to ensure there are several UPS in the system. • Compact size: e.g.: only 2.330 square
selectivity between the two sources, This provides savings in installation costs via: inches for the Master HP UL 500 kVA
improving the reliability of the entire • A smaller electrical infrastructure. • Reduced weight for transformer based UPS
installation; • Smaller circuit protection devices • Double load protection, both electronic
• No neutral input connection is required at • Less wiring. and galvanic, towards the battery.
the UPS rectifier input stage; this method The entire Master HP UL range is suitable
is particularly favorable in order to prevent Flexibility for use in a wide range of applications.
the transmission of common neutral Master HP UL is suitable for a wide range The Master HP can supply any type of
disturbances via the neutral conductor; of applications including IT and the most load, e.g. servers, controls, lighting,
• No effects to the UPS output performance demanding industrial environments capacitive, switch mode. Power supply
or reduced impact of the inverter power and processes. With several operational reliability and availability are ensured for
components while supplying specific configurations including On-Line, Eco, critical applications by distributed parallel
loads; in addition the inverter transformer Smart Active, Stand By, Frequency Converter configurations of up to 8 units, for redundant
minimizes the impact of third harmonic and Voltage Regulation. A broad range (N+1) or power parallel configurations.
disturbances, prevents the effects of of accessories and options, complex
energy back-feed into the inverter when configurations and system architectures can Advanced supervision
supplying industrial load applications and be achieved to guarantee maximum power The Master HP UPS has a front panel mounted
can supply unbalanced loads. availability and the option to add new UPS graphic display providing UPS information,
• High inverter short circuit current to clear without interruption to site operations. measurements, status updates and alarms in
faults which occur between phase and multiple languages, with waveform displays
neutral on load side (up to three times including voltage/current and providing a
nominal current). kWh reading that can be used to measure IT
Output transformer housed within a cabinet loads and calculate a Data Centre PUE (Power
which allows for a significant reduction in Usage Effectiveness) ratio.
the footprint and provides space savings.
DIMENSIONS
MHT 65 UL MHT 160 UL MHT 160 UL MHT 300 UL MHT 300 UL TCE
MHT 80 UL MHT 200 UL MHT 200 UL MHT 400 UL MHT 400 UL TCE
MHT 100 UL MHT 250 UL MHT 250 UL MHT 500 UL MHT 500 UL TCE
MHT 125 UL
75 inches
75 inches
1900 mm
1900 mm
75 inches
1900 mm
75 inches
1900 mm
75 inches
1900 mm
s s
31.5 he 39.3 he s he
s
he
s
inc m 7 inc m he nc
in
800 ches .5 100 inches .5 55 inch inc m 7 i mm inc m
33 50 m 0m 33 50 m es .5 59.0 inch . 3 75 inch .37 m
mm 8 m 8 1400 m 33 50 m 1500 m
es 39 000 1900 m
es
39 000
m 8 m 1 m 1
The information in this document is subject to change without notice. Riello UPS assumes no responsibility for any errors that may appear in this document.
Number of phases 3+N
Nominal voltage 480 Vac three-phase + N
Static stability ± 1%
Dynamic stability from ± 5% to ± 1% in 20 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequency stability on battery 0.05%
Frequency 60 Hz
Overload 110% for 60 minutes; 125% for 10 minutes; 150% for 1 minute
INFO FOR INSTALLATION
Weight (lbs [kg]) 2138 [970] 2247 [1110] 4190 [1900] 4741 [2150] 4741 [2150]
Weight with TCE and Maintenance
2524 [1145] 2799 [1270] 4410 [2000] * 4961 [2250] * 4961 [2250] *
bypass (lbs [kg])
Dimensions (WxDxH) (inches [mm]) 39 x 33.5 x 75 [1000 x 850 x 1900] 59 x 39.5 x 75 [1500 x 1000 x 1900]
Dimensions with TCE and manual
55 x 33.5 x 75 [1400 x 850 x 1900] 75 x 39.5 x 75 [1900 x 1000 x 1900] *
bypass (WxDxH) (inches [mm])
Remote signals dry contacts (configurable)
Remote controls ESD and bypass (configurable)
Communications Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 °C / +40 °C (32 to 104 °F)
Relative humidity <95% non-condensing
Color Black
Noise level at 1 m (ECO Mode) 68 dBA 72 dBA
IP rating IP20
Smart Active efficiency up to 98.5%
UL Standard 1778: 5th edition;
UL 60950-1 1: Information Technology Equipment
UL Standard 1778: 5th edition;
- Safety - Part 1: General Requirements; National
National Electrical Code (NFPA-70); NEMA; CSA C22.2; ASME;
Standards Electrical Code (NFPA-70); FCC Part 15 Subpart J
FCC section 15 subsection J class A;
class A – Radio Frequency; IEC 62040-3; UL 924 and
IEC 62040-3;
OUST category – Emergency Lighting and power
equipment
Classification in accordance with
(Voltage Frequency Independent) VFI - SS - 111
IEC 62040-3
Transport Pallet Jack