Professional Documents
Culture Documents
Sentry G3
Sentry G3
TYPE
Sentry
Series INDUSTRY TRANSPORT EMERGENCY
UPS
3:3 SENTRY G3
10/20/30 kVA
HIGHLIGHTS
• Double-conversion True
Online UPS
• Wide Input Voltage &
Riello Sentry G3 Series UPS systems are display that shows the input and
Frequency Range
based on innovative and modem design output voltages, battery readings and
• Custom Diagnostics LCD with more improved and continuous UPS operating status information.
Display performance. Sentry Series UPS works on
online double conversion technology, Riello Sentry G3 Series has a practical,
• Low Noise Level
resulting in the highest levels of modem design and includes several
• Simplifie installation reliability and maximum protection for performance advantages over
critical loads such as servers, voice data, traditional online UPS models in terms
• Generator Compatible of technology and performance. Sentry
storage systems and network
• Interface slot with optional applications. The front display panel has Series UPS are one of the best UPS
boards been entirely redesigned, adding an LCD systems available in the market today.
MODEL SENTRY G3: 10 KVA SENTRY G3: 20 KVA SENTRY G3: 30 KVA
POWER 10000 VA / 8000 W 20000 VA / 16000 W 30000 VA / 24000 W
INPUT
190 Vac (Ph-Ph) / 110 Vac (Ph-N) + 3% at 50% load
Low Line Loss
305 Vac (Ph-Ph) / 176 Vac (Ph-N) + 3% at 100% load
The information in this document is subject to change without notice. Riello UPS assumes no responsibility for any errors that may appear in this document
AC Voltage Regulation ± 1%
Frequency Range 46Hz ~ 54Hz @ 50Hz system
(Synchronized Range) 56Hz ~ 64Hz @ 60Hz system
Frequency Range (Battery Mode) 50Hz + 0.1Hz or 60Hz + 0.1Hz
100% ~ 110%: 30 min - 10 min
Overload 110% ~ 130%: 10 min - 1 min
≥ 130%: 1 min - 1 s
Current Crest Ratio 3 : 1 max
Harmonic Distortion ≤2% @ 100% linear load; ≤5% @ 100% non-linear load
Line <---> Battery 0 ms
Inverter <---> Bypass 0 ms (When phase lock fails, < 4 ms interruption occurs from inverter to bupass)
Transfer Time
Eco <---> Inverter < 10 ms, during power failure
Eco <---> Inverter 0 ms, Voltage / Frequency out of range
PHYSICAL
Dimensions (DxWxH) (mm) 592 x 250 x 826 592 x 250 x 826 815 x 250 x 826
Outline
Net weight (kg) 38 40
MANAGEMENT
Optional SNMP Power management from SNMP manager and web browser