Professional Documents
Culture Documents
Abstract—The interrupting rating and short-circuit current IR is defined in the 2011 NEC Article 100 as “the highest
rating of equipment is an key consideration for the installation of current at rated voltage that a device is identified to interrupt
equipment in electrical distribution systems. To emphasize this under standard test conditions.” Therefore, IR simply is the
consideration, the 2005 National Electrical Code (NEC®) added highest current that an overcurrent protective device is rated to
short-circuit current rating marking requirements for various
safely clear. According to NEC 110.9, the IR of the
types of equipment, that previously was not required to be
marked with the equipment short-circuit current rating. The overcurrent protective device must be no less than the current
marked short-circuit current rating of equipment is determined available at the equipment’s line terminals.
by the product standards as part of the listing and labeling The NEC requires the marking of the interrupting rating of
process of the equipment or an approved method, such as UL fuses per NEC 240.60(C) and circuit breakers per 240.83(C)
508A for industrial control panels. UL 508A Supplement SB is [see figure 1].
an analytical (non-tested) method of determining the short-circuit
current rating of industrial control panels. This method basically
determines the “weak-link” of all power circuit components in
the industrial control panel and the lowest rated component then
determines the assembly rating. Additional changes to the 2011
NEC have occurred to ensure equipment has short-circuit
current ratings sufficient for the fault current where the
equipment is installed.
I. INTRODUCTION
Overcurrent protective device interrupting rating (IR) and Figure 1. The NEC requires marking of the interrupting
equipment short-circuit current rating (SCCR) are key rating on a current-limiting fuse per NEC 240.60(C).
considerations for the safety of commercial and industrial
electrical systems. If inadequate overcurrent protective device III. SHORT-CIRCUIT CURRENT RATING
IR or equipment SCCR is present, a serious potential safety The 2011 NEC Article 100 defines SCCR as “the
hazard exists. As a result, the NEC and Occupational Safety prospective symmetrical fault current at a nominal voltage to
and Health Administration (OSHA) have added requirements which an apparatus or system is able to be connected without
that draw attention to this issue that are resulting in changes to sustaining damage exceeding defined acceptance criteria.”
equipment design and specification. Therefore, SCCR simply is the highest current that equipment
This paper focuses on the equipment SCCR marking is rated to safely withstand.
requirements, how equipment SCCR is determined, and the NEC 110.10 requires that the equipment SCCR “be
proper equipment installation requirements according to the selected and coordinated to permit the circuit protective devices
NEC. The NEC identifies the overcurrent protective device IR to clear a fault, and to do so without extensive damage to the
and equipment SCCR marking requirements. More electrical equipment of the circuit.” Notice that NEC 110.10
importantly, it also addresses the installation requirements for indicates that a specific circuit protective device (fuse or circuit
the proper application of overcurrent protective device IR and breaker) might be required to provide proper protection.
equipment SCCR. NEC 110.10 also says the protective device must protect
the equipment from extensive damage. Therefore, damage can
II. INTERRUPTING RATING
occur to equipment after a fault, but it can’t result in a shock or
It’s important to understand the difference between the IR fire hazard outside of the enclosure.
of overcurrent protective devices (such as fuses and circuit The acceptable damage criteria for SCCR testing and
breakers) versus equipment SCCR (such as devices, evaluation in product standards is another topic for an in-depth
appliances, apparatus and machinery). discussion not covered in this article. Typically, acceptable
damage might render the assembly or a component in the V. HOW TO DETERMINE IR & SCCR
assembly as useless. The main objective of the product Product standards are used to determine the IR of
standard SCCR acceptable damage level, however, is to overcurrent protection devices and SCCR for components and
prevent a shock hazard or a fire outside the enclosure. assemblies.
If a violation of NEC 110.9 or 110.10 occurs, and the fault The interrupting rating for overcurrent devices is
current exceeds the IR of the overcurrent protective device or determined in accordance with UL 489 for circuit breakers and
the SCCR of equipment, a catastrophic and violent failure of UL 248 for fuses.
the overcurrent protective device or equipment can occur. The SCCR for industrial control equipment is determined in
OSHA 1910.303(b)(4) and 1910.303(b)(5) contain similar accordance with UL 508; for power conversion equipment, the
language to NEC 110.9 and NEC 110.10, so both new and standard is UL 508C; for terminal blocks, the standard is UL
existing overcurrent protective devices and equipment must 1059; for power distribution blocks, the standard is UL 1953;
have adequate IR and SCCR. and for switches, the standards are UL 508 (motor controllers)
or UL 98 (branch circuit disconnects). The SCCR of a
IV. SCCR MARKING REQUIREMENTS component often is dependent on a specific type of
In the past, equipment such as HVAC, industrial control overcurrent device.
panels and industrial machinery was considered “utilization For assemblies, the SCCR can be determined by the testing
equipment” and was overlooked regarding proper SCCR and and listing process in accordance with the product standard.
the ability to withstand fault currents. To correct this issue, the For instance, panelboards are tested and listed in accordance
2005 NEC added new requirements for marking equipment with UL 67; switchboards in accordance with UL 891; and
SCCR to correlate with the product standards. motor control centers in accordance with UL 845.
The 2005 NEC added SCCR marking requirements for For industrial control panels, two alternatives are available
motor controllers in NEC 430.8; HVAC equipment in to determine an assembly SCCR: testing or analysis method.
440.4(B); industrial control panels in 409.110; and industrial UL 508A, Supplement SB identifies an approved process that
machinery in 670.3(A). can be used to determine the SCCR for industrial control
In addition, 409.110(3) and 670.3(A) also contained fine panels by analyzing the components in the industrial control
print notes (changed to information notes in the 2011 NEC) panel. If desired as an alternative, testing of industrial control
that UL 508A, Supplement SB was an approved method for panels can be performed to determine the SCCR of industrial
determining equipment SCCR for industrial control panels and control panels. However, this often is cost prohibitive unless
industrial machinery (see figure 2). large usage of the same industrial control panel is expected.
For heating and cooling systems (HVAC equipment), UL
1995, the UL Standard for Safety for Heating and Cooling
Equipment, recently was updated to require HVAC equipment
to be marked with an SCCR, effective July 30, 2012. This can
be determined by testing or by analysis in accordance with the
requirements added to UL 1995 which are similar to that of
UL 508A, Supplement SB.
VI. UL 508A SUPPLEMENT SB
Three main considerations are used to determine the
SCCR of an industrial control panel according to UL
508A, Supplement SB (analysis method):
1. Power circuit components
2. Current-limiting devices in the feeder circuit
3. Overcurrent protective devices.
For power circuit components, the SCCR is determined by (taken from UL 248) is less than the branch circuit component
either the product markings or the instruction sheets (see SCCR, then the branch circuit component SCCR can be raised
figure 3). If there are no product markings, a default value can to that value (50 kA, 100 kA or 200 kA) (see figure 5).
be used as indicated in UL 508A, Supplement SB. For motor
controllers, high SCCR can be used when tested in accordance
with UL 508 and procedure described.