Consider a line-to-line (LL) fault between phases b and c on an unloaded Y connected generator
as shown in Figure
Ia0 = 0
Ia1 = – Ia2
Since Va1 = Va2 and Ia1 = –Ia2, positive- and negative-sequence networks must be connected in
parallel. Since Ia0 = 0, zero-sequence network will not be present. Accordingly, the connection
diagram for line-to-line fault is shown in Figure