Professional Documents
Culture Documents
Edited PDF
Edited PDF
PDF Watermark Remover DEMO : Purchase from www.PDFWatermarkRemover.com to remove the waterma
for fault analysis at fundamental frequencies and not Analytical computations can be performed for the
suitable for finding system behaviour at harmonic purpose of determination of system impedance when the
frequency. There are a number of harmonic size of system is not too large. Succession of resonances
producing components in power systems like caused by cable or transmission line capacitance, results
capacitor banks for compensating KVARs, collector in variation of impedance. When the capacitance of the
cables, Line capacitance, transformer reactance, system is high there is great chance for resonances to
FACTS devices and power electronics devices for occur on low frequencies sometimes at power
power system control. Harmonic measurements and frequencies. It can happen due to capacitor banks and
simulations are performed for the determination of collector cables.
harmonic levels of voltage and current distortions. At power frequency, power systems are primarily
inductive. At distribution levels capacitive effects are
II. SYSTEM’S HARMONIC-IMPEDANCE normally neglected. There is direct relation between
System's Harmonic Impedance is an inductive reactance and frequency.
important thing in system response under harmonic Short circuit reactance Xsc, based on transformer
frequency and is used in modeling of systems under impedance only is:
harmonic conditions. It offers great difficulty in 𝑋𝑆𝐶 ≅ 𝑋𝑡 (3)
analyzing full power system in harmonic study. So Where
the dimensions of the system are therefore reduced to (𝑘𝑉)2
𝑋𝑡 = × %𝑍 (4)
minimum possible scale using the equivalent 𝑀𝑉𝐴
impedance representing the behavior of the Fig. 3 shows impedance frequency response
component to harmonic distortions. Impedance does of an inductive system without capacitors. For the
not remain constant and varies over time and from purpose of Harmonic analysis, capacitance can't be
one point to other in the power system. This change neglected. System impedance is dramatically
of impedance depends upon various factors such as changed due to shunt capacitance caused due to
cable length, short circuit power of the system, VAR collector cable and capacitor banks used for VAR
compensation and load level in the system. When the compensation.
measurement of the harmonic impedance is needed, a The Capacitive reactance is given as:
1
powerful harmonic current source and high pre- 𝑋𝑐 = (5)
2𝜋𝑓𝐶
existing harmonic voltage at the node where
impedance is to be measured, is presented in the Where C is the capacitance.
system. The line to neutral capacitive reactance can
Pre-existing harmonic or inter harmonic be determined by:
voltage Vh causes an inter-harmonic current to flow
in load Z as shown below in Fig. 1. 𝐾𝑉 2
As shown in the fig. below, the harmonic impedance 𝑋𝑐 = (6)
𝑀𝑉𝐴𝑅
Zh is given by:
Impedance (Ohms)
80
Zh 70
60
50
40
Vh2 Vh1 30
20
10 Frequency
PDF Watermark Remover DEMO : Purchase from www.PDFWatermarkRemover.com to remove the waterma
The resonant for a parallel combination of an inductive
and capacitive element is:
1
𝑓𝑟𝑒𝑠𝑜𝑛𝑎𝑛𝑐𝑒 = (7)
2𝜋√𝐿𝐶
Where L is the inductance and C is the capacitance of
the system. At high voltage levels caused due to harmonic
distortions, resistance of the network on the whole
becomes small as compared with capacitance and
inductance. So impedance changes abruptly and situation
becomes harsh. Due to harmonic voltage and current
amplification, system power components can be damaged.
A number of resonance frequencies can occur depending
upon grid configuration.
Advance analyses of harmonics are very important
due to small distortions in the resonance frequency. There
exist two types of resonances called parallel resonance
and series resonance. In paper we will concentrate only on
Parallel Resonance. Fig. 4: Cable capacitance in the inductive system and equivalent circuit
In parallel resonance, impedance becomes high and
resistance becomes zero in case of ideal resonance.
Impedance becomes infinitely high due to which voltage
rises to extremely high level. The parallel resonance in both the cases shown in Fig.5 is
Any source of harmonic current can cause parallel occurring in the same region, 400 Hz and 575 Hz respectively
resonance and that source of harmonic current can be for 50 km and 25 km cable lengths. This indicates that
modeled as a parallel connection of inductive and transformer’s rating as well as its physical location are the
capacitive components. There are several possibilities in important factors and have significant effect in determining
the power system when parallel resonance is caused due the resonance frequency.
to capacitor banks for VAR compensation, Collector Table 1: Data for different parameters in Fig.3, used for plots
cables in the grid, Transmission line reactance and
transformer reactance Case/Pl T1 T2 X1 X2 L1 L2
PDF Watermark Remover DEMO : Purchase from www.PDFWatermarkRemover.com to remove the waterma
1 1
1000 𝐶15𝑀𝑉𝐴 = 2
× = 39𝑢𝐹
C=20uF (2𝜋 × 500) 2.6 × 10−3
800 C=10uF All three plots in Fig. 2.8, demonstrate good
Impedance Ohm
Without Capacitance
agreement with afore calculated respective values of resonant
600
frequencies which substantiate the correctness of simulation
400
process.
Fig. 9 depicts the impact of three different parallel
200 resistances in the same case of parallel resonance in system
response characteristics. As little as ten percent resister
0 loading can have a noteworthy and valuable impact on peak
0 500 1000 1500
Frequency Hz impedance. The most troublesome resonant conditions evolve
1000 when capacitors are installed on substation buses where the
Without Capacitance transformer dominates the system impedance and has a high
800 C=10uF X/R ratio. The relative resistance is low and corresponding
Impedance Ohms
C=20uF
600
parallel resonant impedance peak is very sharp and high. This
is a common cause of capacitor failure, transformer failure or
400 the failure of other load equipment. It is a misunderstanding
200
that resistive load damp harmonics as in the absence of
resonance, load will have little impact on the harmonic
0
0 500 1000 1500
currents and the resulting voltage distortion. Most of the
Frequency Hz current will flow back in the power source. Nevertheless it is
appropriate to say the resistive loads damp the resonance
Fig.5. Frequency response of circuit shown in Fig.3, Case 1 and 2, Table 1 hence considerably reducing the harmonic distortion. Motor
Fig. 6 shows the frequency response of circuit shown in Fig 4. loads are primarily inductive and provide little damping, rather
The graphs correspond to Case 4, Case 5 and Case 6 in the they may cause an increase in the problem by shifting the
data Table 1. Unlike first three cases the transformer used resonant frequency closer to a significant harmonic. However
from 33 kV to 11 kV is a 10 MVA transformer, which some small fractional horsepower motors may help in
indicates a smaller value of inductive reactance. damping because their X/R ratio is lower than large three
Consequently the inductance in the circuit shown in Fig 4 has phase motors.
shifted to the new position determined by the length of the
cable. This is repeated for a 15MVA transformer in three
following cases.
PDF Watermark Remover DEMO : Purchase from www.PDFWatermarkRemover.com to remove the waterma
1000 Every small power plant has its own resonance
Without Capacitance frequency that is dependent on the grid topology, associated
800
Impedance Ohms
C=10uF
C=20uF
600
400
200
0 Cable
0 500 1000 1500
Frequency Hz
1000
Without Capacitance
800
Impedance Ohms
C=10uF
C=20uF
600
0 T-line Xl
0 500 1000 1500
Frequency Hz
PDF Watermark Remover DEMO : Purchase from www.PDFWatermarkRemover.com to remove the waterma
Table 2. Shadiwal to Grid data
Name of Plant Shadiwal Hydel Power Now let us see impedance-frequency responses of our system.
Station
Impedance
Capacity of Plant 13.5 MW 15000
Impedance (ohms)
10000
Per phase
reactance of step 8%
5000
up Transformer
Length of Line 10 Km
Spacing between Horizontal 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
conductors D12=2.4384m Frequency (Hz)
D23=2.4384m
Fig. 10: Frequency Response
D13=4.8768m
Total Line 377 Ohm 1000
Impedance
Reactance
800
Total Line 12 mH
Impedance (ohms)
Inductance 600
Capacitive 200
reactance
0
Total Line 0.1 µF 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Frequency (Hz)
Capacitance
KVAR of 400 KVAR Fig. 11: Zoom View of frequency response
Capacitor Banks
In the above response, system resonates near 3400Hz.
Per phase 0.073 µF
capacitance of IV. CONCLUSIONS
banks Addition of a distributed generation source into a system
Collector cable 500 mm²(1000 MCM) may cause parallel resonance and harmonics in the system
Size
which affects the power system badly. Sources of theses
No. of per phase 3
collector cables distortions in voltage and current levels may be
Collector cable’s 0.1 µF transformer reactance, line reactance, capacitor banks,
capacitance collector cables etc. The number of resonances is likely
equal to the number of physical and equivalent capacitors
Table 3. Data for components in Fig.8
(cables, capacitor banks etc). The effect of capacitive
Case T1 T2 X2 L1 L2 elements on resonance appears to be decoupled. Each
X1
/Plot 11/132 132/11 𝛀 mH mH
𝛀 capacitive element contributes to a resonance. Such is a
kv kV 𝑽𝟐𝑳 𝑽𝟐𝑳
5 6 � � � � 𝑿𝟏 𝑿𝟐 case of Shadiwal Hydel power station. In the context, the
No. MVA MVA 𝑴𝑽𝑨 𝑴𝑽𝑨
/𝟐𝝅𝒇 /𝟐𝝅𝒇 effect of connecting Shadiwal Hydel power station to the
X% X% × 𝟖% × 𝟖%
nearest grid (Gujrat old grid) is surveyed and results for the
level of parallel resonance are analysed.
1 8 8 278 232 887 740
PDF Watermark Remover DEMO : Purchase from www.PDFWatermarkRemover.com to remove the waterma
V. REFERENCES
PDF Watermark Remover DEMO : Purchase from www.PDFWatermarkRemover.com to remove the waterma