You are on page 1of 70

Over 2000 Standard and Special Filters

GEA Air Filters


The Primary Choice in Highest Air Quality | Data & Facts

GEA Heat Exchangers / HVAC Systems


Table of Contents GEA Air Filters

Filter Mats, Rolls, Special-Dimension Elements and


Roll-Band Filters ............................................................................... 4
Filter Mats CTM ......................................................................................................... 4
FIBROIDELASTIC ..................................................................................................... 5
FIBROIDELASTOV ................................................................................................... 6
VENUFA 290 ............................................................................................................. 7
MY-STOP 500 ........................................................................................................... 8
ACELAN .................................................................................................................... 9
PERFEKT ................................................................................................................ 10
FARBGLAS 2" ......................................................................................................... 11
FIBROBAND ........................................................................................................... 12
Filter Band 402/411/412 .......................................................................................... 13

Filter Plates ...................................................................................... 14


GAL ......................................................................................................................... 14
HL 12,5 .................................................................................................................... 15
VISCINOL A30 ........................................................................................................ 16

Filter Cells ........................................................................................ 17


FILTERGLAS .......................................................................................................... 17
ULTRANGLAS ........................................................................................................ 18
Z-50/Z-100 ............................................................................................................... 19
FIBERGLAS ............................................................................................................ 20

Bag Filter ......................................................................................... 21


MULTISACK Overview ............................................................................................ 21
MULTISACK K35/K50 ............................................................................................. 22
MULTISACK K55/K65 ............................................................................................. 23
MULTISACK K85/K95 ............................................................................................. 24
MULTISACK G55/G65 ............................................................................................ 25
MULTISACK G85/G95 ............................................................................................ 26

Filter Elements ................................................................................ 27


MULTIFORM Overview ........................................................................................... 27
MULTIFORM MF65/MF85/MF90 ............................................................................ 28
MULTIFORM MF95/MF98/MF99 ............................................................................ 29
MULTIFORM MF100 ............................................................................................... 30
MULTITHERM Overview ......................................................................................... 31
MULTITHERM MT60/MT90 .................................................................................... 32
MULTIPLAN type code ............................................................................................ 34
MULTIPLAN I (MP65, 85, 95) ................................................................................. 35
MULTIPLAN II (MP55, 65, 85, 95) .......................................................................... 36
MULTI 2004 ............................................................................................................. 37
MULTICOL .............................................................................................................. 38

2 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Table of Contents

EPA/HEPA Filters ............................................................................ 40


Overview .................................................................................................................. 40
Description of Product Type Code ........................................................................... 41
E11 Panel Filter ....................................................................................................... 43
E11 V-Shape ............................................................................................................ 44
H13 with Aluminium Separators ............................................................................... 45
H13 Panel Filter ....................................................................................................... 45
H14 .......................................................................................................................... 48

Activated Carbon Filter .................................................................. 49


Activated Carbon, Loose .......................................................................................... 49
Activated Carbon Plate Element AK-20 ................................................................... 49
Activated Carbon Cartridge 705/706/707 ................................................................. 50
Activated Carbon Cartridge 708/709 ........................................................................ 51
CKG holding frame .................................................................................................. 52

Round Air Filters ............................................................................. 53


Overview .................................................................................................................. 53
DAH ......................................................................................................................... 54
DBH/DBA/DBV ......................................................................................................... 55
DAC/DBC ................................................................................................................. 58

Glove-Box Filters ............................................................................ 61


DKA/DKB ................................................................................................................. 61
DKC/DKD ................................................................................................................. 62

Filter Frames for Wall or Ceiling Installation ................................ 63


MULTI 2004 Holding Frame ..................................................................................... 63
CDD Wall Frame ...................................................................................................... 64
CGF Ceiling Air Outlets ............................................................................................ 65
CKC Wall Frame ...................................................................................................... 66
ELA Filter Casing ..................................................................................................... 67
EBE Casing .............................................................................................................. 68

Space for Notes ............................................................................... 69

Copyright note
Disclosing, copying, distributing or taking any action in reliance on the contents of this
document is strictly prohibited without express prior consent. Violations entail liability
for any damages or other liability arising. All rights in relation to patents, utility patents
or design patents are reserved.

PR-2009-0099-GB • Subject to modifications • Status 07/2011 3


Filter Mats, Rolls, Special-Dimension Elements and Roll-Band Filters GEA Air Filters
Filter Mats CTM

CTM filter mats consist of polyester fibres with pronounced labyrinth structure and
with progressive depth structure.
Application example:
pre-filter for small air handling systems with high dust
concentration and for coarse dust filtration in standard air handling units
Special features:
elastic, without wetting agent and regenerable
Areas of application:
standard ventilation and air handling units, climate control
facilities, cabinet air handling units, cooling of switch boxes, heat exchangers,
recirculating air units, unit heaters, cooling of large machines and switchgear as well
as paint spray compartments

Pressure drop diagram:


Pressure drop [Pa]

Air volume flow [m³/hm²]

Technical data:
CTM CTM-50 CTM-60 CTM-90
Filter class [EN 779] G2 G3 G4
Installation depth/thickness [mm] 5 10 20
Rated air volume flow [m³/hm²] 5.400 5.400 5.400
Initial pressure drop [Pa] 11 18 50
Maximum allowed pressure
[Pa] 250 250 250
drop
Mean degree of filtration [%] 72.0 81.4 91.7
Dust holding capacity [g/m²] 425 590 518
Fire behaviour [DIN 53438] F1/K1 F1/K1 F1/K1
Max. operating temperature [°C] 80 80 80
Max. rel. air humidity [%] 100 100 100

Form of delivery/
order numbers: CTM Size Order number
Special-dimension elements
CTM-50 0 to 40 m², maximum width 2 m X-CTM-50
CTM-60 0 to 40 m², maximum width 2 m X-CTM-60
CTM-90 0 to 40 m², maximum width 2 m X-CTM-90
Rolls
CTM-50 2 x 20 m, packaging unit 1 40 61 031
CTM-60 2 x 20 m, packaging unit 1 40 72 531
CTM-90 2 x 20 m, packaging unit 1 40 72 831

4 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Mats, Rolls, Special-Dimension Elements and Roll-Band Filters
FIBROIDELASTIC

FIBROIDELASTIC filter mats consist of latex-bonded, randomly structured natural


mixed fibres with uniform depth structure and great intrinsic stiffness, the mats are are
elastic, not provided with a wetting agent, and repeatedly regenerable
Application example:
primarily used with high dust concentration and filtration of
especially coarse dust
Special features:
very efficient thanks to extremely low initial pressure drop, with high air volume flow as
well; very high dust holding capacity
Areas of application:
climate control facilities and air handling units in the cement industry or similar areas,
intake and combustion air for fans, compressors,
internal-combustion motors and pneumatic conveyor systems

Pressure drop diagram:


Pressure drop [Pa]

Air volume flow [m³/hm²]

Technical data:
FIBROIDELASTIC TIC-20 TIC-30 TIC-40
Filter class [EN 779] G2 G2 G3
Installation depth/thickness [mm] 20 30 40
Rated air volume flow [m³/hm²] 10.000 10.000 10.000
Initial pressure drop [Pa] 65 75 95
Maximum allowed pressure
[Pa] 250 250 250
drop
Mean degree of filtration [%] 73.1 77.1 84.6
Dust holding capacity [g/m²] 920 933 1064
Fire behaviour [DIN 53438] F1/K1 F1/K1 F1/K1
Max. operating temperature [°C] 60 60 60
Max. rel. air humidity [%] 100 100 100

Form of delivery/
order numbers: FIBROIDELASTIC Size Order number
Special-dimension elements
TIC-20 0 to 2 m², maximum width 1 m X-TIC-20
TIC-30 0 to 2 m², maximum width 1 m X-TIC-30
TIC-40 0 to 2 m², maximum width 1 m X-TIC-40
Plate
TIC-20 1 x 2 m, packaging unit 1 16 08 481
TIC-30 1 x 2 m, packaging unit 1 16 08 881
TIC-40 1 x 2 m, packaging unit 1 16 09 281

PR-2009-0099-GB • Subject to modifications • Status 07/2011 5


Filter Mats, Rolls, Special-Dimension Elements and Roll-Band Filters GEA Air Filters
FIBROIDELASTOV 40

FIBROIDELASTOV 40 filter mats consist of robust fleece made of randomly struc-


tured polyester fibres with progressive depth structure, the filter layer, not provided with
a wetting agent, is elastic and regenerable.
Application example:
reliable filtration of coarse dust in climate control and air handling systems
Special features:
very efficient thanks to extremely low initial pressure drop, with high air volume flow as
well; very high dust holding capacity
Areas of application:
general purpose climate control facilities and air handling units, protection against con-
tamination of large machines and switchgear, air intake and combustion air for fans,
compressors, internal-combustion motors

Pressure drop diagram:


200
TOV-40
Pressure drop [Pa]

160

120

80

40

0
0 2500 5000 7500 10000
Air volume flow [m³/hm²]

Technical data:
FIBROIDELASTOV TOV-40
Filter class [EN 779] G4
Installation depth/thickness [mm] 40
Rated air volume flow [m³/hm²] 2.500-10.000
Initial pressure drop [Pa] 26-185
Maximum allowed pressure
[Pa] 250
drop
Mean degree of filtration [%] 93.0
Dust holding capacity [g/m²] 477
Fire behaviour [DIN 53438] F1/K1
Max. operating temperature [°C] 70
Max. rel. air humidity [%] 100

Form of delivery/
order numbers: FIBROIDELASTOV Size Order number

Special-dimension elements
TOV-40 0 to 2 m², maximum width 1 m X-TOV-40

Plate
TOV-40 1 x 1.5 m, packaging unit 5 16 08 021

6 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Mats, Rolls, Special-Dimension Elements and Roll-Band Filters
VENUFA 290

VENUFA 290 filter mats consist of polyester fibres with progressive depth structure
Application example:
filtration of dust particles in air handling systems
Special feature:
progressively constructed, without wetting agent and regenerable; meets F1/K1 fire
protection class; maximum continuous operating temperature 80 °C
Areas of application:
climate control and cabinet air handling units, decentral HVAC units, pre-fan and pre-
heat exchanger units

Pressure drop diagram: Pressure drop [Pa]

Air volume flow [m³/hm²]

Technical data:
VENUFA 290 VEN-290
Filter class [EN 779] G3
Installation depth/thickness [mm] 20
Rated air volume flow [m³/hm²] 5.400
Initial pressure drop [Pa] 31
Maximum allowed pressure
[Pa] 250
drop
Mean degree of filtration [%] 87.7
Dust holding capacity [g/m²] 572
Fire behaviour [DIN 53438] F1/K1
Max. operating temperature [°C] 80
Max. rel. air humidity [%] 100

Form of delivery/
order numbers: VENUFA 290 Size Order number
Special-dimension elements
VEN-290 0 to 40 m², maximum width 2 m X-VEN-290
Rolls
VEN-290 2 x 20 m, packaging unit 1 40 72 631

PR-2009-0099-GB • Subject to modifications • Status 07/2011 7


Filter Mats, Rolls, Special-Dimension Elements and Roll-Band Filters GEA Air Filters
MY-STOP 500

MY-STOP 500 filter mats consist of polyester fibres that have been spun to produce a
very robust fleece with progressive structure, the especially smoothed pure-air side
prevents migration of fibres and assures great dust-storage capacity
Application example:
reliable filtration of coarse dust in climate control and air handling units
Special features:
elastic, without wetting agent and regenerable, with progressive structure
Areas of application:
standard ventilation and air handling units, supply air units, units for cooling large
machines and switchgear, first filter stage for filtration of coarse dust, pre-filter for paint
spray compartments and painting installations

Pressure drop diagram:


Pressure drop [Pa]

Air volume flow [m³/hm²]

Technical data:
MY-STOP 500 MY-500
Filter class [EN 779] G4
Installation depth/thickness [mm] 20
Rated air volume flow [m³/hm²] 5.400
Initial pressure drop [Pa] 40
Maximum allowed pressure
[Pa] 250
drop
Mean degree of filtration [%] 94.4
Dust holding capacity [g/m²] 700
Fire behaviour [DIN 53438] F1/K1
Max. operating temperature [°C] 80
Max. rel. air humidity [%] 100

Form of delivery/
order numbers: MY-STOP 500 Size Order number
Special-dimension elements
MY-500 0 to 40 m², maximum width 2 m X-MY-500
Rolls
MY-500 2 x 20 m, packaging unit 1 40 72 731

8 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Mats, Rolls, Special-Dimension Elements and Roll-Band Filters
ACELAN

ACELAN filter mats consist of thermally bonded polyester fibres, the elastic medium is
not provided with a wetting agent, is progressive, and is constructed with compression
on the pure-air side.
Application example:
filtration of fine dust in climate control and air handling systems
Special features:
without wetting agent and with progressive structure, meets standards for
filter class F5
Areas of application:
filtration of supply air of sensitive switchgear, water treatment facilities, pre-filter for
paint spray compartments and painting installations, standard climate control and air
handling units

Pressure drop diagram:


Pressure drop [Pa]

Air volume flow [m³/hm²]

Technical data:
ACELAN ACELAN
Filter class [EN 779] F5
Installation depth/thickness [mm] 30
Rated air volume flow [m³/hm²] 5.040
Initial pressure drop [Pa] 106
Maximum allowed pressure
[Pa] 450
drop
Mean degree of filtration [%] 96.6
Mean filter efficiency [%] 43.5
Dust holding capacity [g/m²] 514
Fire behaviour [DIN 53438] F1/K1
Max. operating temperature [°C] 80
Max. rel. air humidity [%] 100

Form of delivery/
order numbers: ACELAN Size Order number
Special-dimension elements
ACELAN 0 to 20 m², maximum width 2 m X-ACELAN
Rolls
ACELAN 2 x 10 m, packaging unit 1 40 07 621

PR-2009-0099-GB • Subject to modifications • Status 07/2011 9


Filter Mats, Rolls, Special-Dimension Elements and Roll-Band Filters GEA Air Filters
PERFEKT

PERFEKT-300 filter mats consist of superfine, thermally bonded polyester fibres not
provided with a wetting agent, with progressive structure, and with compression on the
pure-air side.
PERFEKT-600 filter mats are wetted with a bond-active agent, and their pure-air side
is reinforced with a lattice structured fabric.
Application example:
for air handling units with very high standards in air purity
Special feature:
meets standards of filter class F5 Areas of applications: standard climate control and
air handling systems, supply air for paint spray compartments and paint installations

PERFEKT-600 filter mats are certified by Eurovent


AIR FILTERS
CLASS F5-F9

Pressure drop diagram:


70

60
PF-600
Pressure drop [Pa]

50

40

30 PF-300
20

10

0
0 500 1000 1500 2000

Air volume flow [m³/hm²]


Technical data:
PERFEKT PERFEKT-300 PERFEKT-600
Filter class [EN 779] F5 F5
Installation depth/thickness [mm] 15 20
Rated air volume flow [m³/hm²] 900 900
Initial pressure drop [Pa] 20 27
Maximum allowed pressure
[Pa] 450 450
drop
Mean degree of filtration [%] 96.4 97.9
Mean filter efficiency [%] 53.3 56.6
Dust holding capacity [g/m²] 342 387
Fire behaviour [DIN 53438] F1/K1 F1/K1
Max. operating temperature [°C] 80 80
Max. rel. air humidity [%] 100 100

Form of delivery/
order numbers: PERFEKT Size Order number
Special-dimension elements
PERFEKT-300 0 to 40 m², maximum width 2 m X-PF-300
PERFEKT-600 0 to 40 m², maximum width 2 m X-PF-600
Rolls
PERFEKT-300 2 x 20 m, packaging unit 1 40 72 931
PERFEKT-600 2 x 20 m, packaging unit 1 40 73 131

10 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Mats, Rolls, Special-Dimension Elements and Roll-Band Filters
FARBGLAS 2"

FARBGLAS 2" filter mats consists of a spun glass-fibre fabric with compression on
the pure-air side, the glass-fibre medium has no wetting agent and is odourless, non-
inflammable, and insensitive to moisture in the air
Application example:
filtration of paint mist in paint spray compartments and paint facilities
Special features:
progressively constructed, maximum continuous operating temperature 120 °C
Special features:
standard climate control and air handling systems, paint spray compartments and paint
installations, HVAC equipment

Pressure drop diagram:


Pressure drop [Pa]

Air volume flow [m³/hm²]

Technical data:
FARBGLAS 2" FAGL-2
Installation depth/thickness [mm] 50
Rated air volume flow [m³/hm²] 2.500-6.300
Initial pressure drop [Pa] 7-40
Maximum allowed pressure
[Pa] 80
drop
Mean degree of filtration [%] 97.0 *
Dust holding capacity [g/m²] –
Fire behaviour [DIN 53438] F1/K1
Max. operating temperature [°C] 120
Max. rel. air humidity [%] 100

* Mean degree of filtration with respect to paint mist

Form of delivery/
order numbers: FARBGLAS 2" Size Order number
Special-dimension elements
FARBGLAS 2" 0 to 40 m², maximum width 2 m X-FAGL-2
Rolls
FARBGLAS 2" 2 x 20 m, packaging unit 1 40 60 831

PR-2009-0099-GB • Subject to modifications • Status 07/2011 11


Filter Mats, Rolls, Special-Dimension Elements and Roll-Band Filters GEA Air Filters
FIBROBAND

FIBROBAND filter bands consist of fine, randomly structured polyester fibres, the fil-
ter layer is constructed on a stiff, tear-resistant polyester gauze which is mounted on a
cardboard spool with insertion sleeve for the DELBAG system
Application example:
filtration of coarse and fine dust in large air-flow volumes, in particular in roll-band
filter systems
Special features:
cardboard spool with an insertion sleeve; to be used in filter-band Delbag systems
Areas of application:
climate control facilities and air handling units with great air-flow volumes

Pressure drop diagram:


Pressure drop [Pa]

Air volume flow [m³/hm²]

Technical data:
FIBROBAND FIBROBAND
Filter class [EN 779] G3
Installation depth/thickness [mm] 10
Rated air volume flow [m³/hm²] 5.700
Initial pressure drop [Pa] 40
Maximum allowed pressure
[Pa] 250
drop
Mean degree of filtration [%] 88.1
Dust holding capacity [g/m²] 398
Fire behaviour [DIN 53438] F1/K1
Max. operating temperature [°C] 80
Max. rel. air humidity [%] 100

Form of delivery/
order numbers: FIBROBAND Size Order number

Cardboard spool with insertion sleeve for DELBAG system, packaging unit 1
Size 1 0,81 m x 20 m, weight/unit 6,2 kg 40 09 021
Size 2 1,11 m x 20 m , weight/unit 8,3 kg 40 09 121
Size 3 1,41 m x 20 m , weight/unit 10,4 kg 40 09 221
Size 4 1,71 m x 20 m, weight/unit 12,5 kg 40 09 321
Size 5 2,01 m x 20 m , weight/unit 14,6 kg 40 09 521

12 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Mats, Rolls, Special-Dimension Elements and Roll-Band Filters
Filter Band 402/411/412

402/411/412 filter bands consist of glass fibres with progressive structure. The filter
bands are wetted with an antibacterial and water-proof dust-trapping agent which en-
ables to achieve very high dust-holding capacity. The filter bands are suitable for three
different mounting systems:
– 402 for CEAG/AAF system
– 411 for SCHIRP system
– 412 for DELBAG system
Application example:
filtration of coarse and fine dust in large air-flow volumes, in particular in roll-band filter
systems
Special features:
When placing your order please consider 3 different mounting systems!
– 402 steel spool with side window
– 411 cardboard spool
– 412 cardboard spool with insertion sleeve
Areas of application:
climate control facilities and air handling units with great air-flow volumes
Technical data: Filter bands 402 411 412
Filter class [EN 779] G4 G4 G4
Installation depth/thickness [mm] 50 50 50
Rated air volume flow [m³/hm²] 10.800 10.800 10.800
Initial pressure drop [Pa] 40 50 50
Maximum allowed pressure
[Pa] 150-180 150-180 150-180
drop
Mean degree of filtration [%] 91.0 91.0 91.0
Fire behaviour [DIN 53438] F1/K1 F1/K1 F1/K1
Max. operating temperature [°C] 65 65 65
Max. rel. air humidity [%] 100 100 100

Form of delivery/
Filter bands Width [mm] Weight [kg] Order number
order numbers:
402, steel spool with side window, roll à 20 m, packaging unit 1
402-3 832 11.0 40 52 031
402-4 1.137 12.4 40 52 131
402-5 1.442 16.8 40 52 231
402-6 1.747 21.7 40 52 331
402-7 2.052 27.6 40 52 431

402, cardboard spool, roll à 20 m, packaging unit 1


411-3 832 8.3 40 51 031
411-4 1.137 9.9 40 51 131
411-5 1.442 12.0 40 51 231
411-6 1.747 13.8 40 51 331
411-7 2.052 19.0 40 51 431

412, steel spool with insertion sleeve, roll à 21 m, packaging unit 1


412-1 810 10.0 40 51 531
412-2 1.110 14.8 40 51 631
412-3 1.410 18.5 40 51 731
412-4 1.710 21.0 40 51 831
412-5 2.010 26.5 40 51 931

PR-2009-0099-GB • Subject to modifications • Status 07/2011 13


Filter Plates GEA Air Filters
GAL

GAL filter plates – several layers of aluminium or stainless-steel woven wire mesh are
installed between metal support plates made of expanded metal mesh on two sides,
and are framed by a sturdy U-shaped profile frame made of aluminium or stainless
steel, the filter cells are regenerable.
Application example:
pre-filter elements for filtration of highly concentrated dust and oil and emulsion mist
Special features:
high maximum operating temperature (400 °C); high dust-holding capacity
Areas of application:
steel and metallurgical industry in highly dust-laden and harsh conditions, power sta-
tions, off-shore facilities, air treatment facilities in arid and tropical regions, filtration of
mist in cooling and lubrication processes with metal cutting and non-cutting tools,
engineering, tools and vehicle industries, rolling mills

Pressure drop diagram:


Pressure drop [Pa]

Air volume flow [m³/hm²]

Technical data:
GAL GAL-A GAL-N
Filter class [EN 779] G3 G3
Installation depth/thickness [mm] 48 48
Rated air volume flow [m³/hm²] 6.850 10.400
Initial pressure drop [Pa] 84 86
Maximum allowed pressure
[Pa] 500 500
drop
Mean degree of filtration [%] 87.0 86.0
Dust holding capacity [g/m²] 400 400
Max. operating temperature [°C] 400 400
Casing material Aluminium Stainless steel

Form of delivery/
order numbers: Air volume flow Approx. weight
GAL Size W/H/D [mm] Order number
[m³/h] [kg]
Filter plate, packaging unit 1
GAL aluminium 287/287/48 600 1.3 00 02 592
GAL aluminium 287/592/48 1.200 1.5 00 02 591
GAL aluminium 592/592/48 2.400 2.9 60 04 481
GAL stainless
287/592/48 1.800 3.1 00 39 401
steel
GAL stainless
592/592/48 3.600 5.6 60 04 581
steel

14 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Plates
HL 12,5

HL 12,5 filter plates consist of several layers of bonded expanded metal mesh, which
is effective for separation of coarse dust owing to the labyrinth structure of the plates,
the filter plates are wetted with a dust-trapping agent (VISCINOL)
and are regenerable.
Application example:
filtration of coarse dust in climate control and air handling units
Special features:
high dust-holding capacity resulting in extended service life;
use with 2 or 3 plates
Areas of application:
steel and metallurgical industry, roll mills, power stations, engineering, tools and vehi-
cle industries, machine-room ventilation, filtration of mist in cooling and lubrication
processes with metal cutting and non-cutting tools, filtration of wax mist in car-making
industry and automated welding facilities, spark protection

Pressure drop diagram:

3 plates
Pressure drop [Pa]

double
plate

Air volume flow [m³/hm²]

Technical data:
HL 12,5 Double plate Triple-plate
Filter class [EN 779] G3 G4
Installation depth/thickness [mm] 2/12.5 3/12.5
Rated air volume flow [m³/hm²] 7.200 7.200
Initial pressure drop [Pa] 70 100
Maximum allowed pressure
[Pa] 500 500
drop
Mean degree of filtration [%] 86.0 91.0
Dust holding capacity [g/m²] 450 494
Max. operating temperature [°C] 45 * 45 *
Max. rel. air humidity [%] 100 100

* depending on wetting agent

Form of delivery/
order numbers: HL 12,5 Size W/H [mm] Approx. weight [kg] Order number
1 plate, packaging unit 1
2.5 60 01 021
Sendzimir galvanised surface
494/494 with key hole 2.5 60 02 281
Aluminium galvanised surface
0.8 60 01 521
2.5 60 01 121
Sendzimir galvanised surface
494/494 with handle 2.5 00 00 098
Aluminium galvanised surface
0.8 60 01 681
Aluminium 494/988 with key hole 2.0 60 01 881

PR-2009-0099-GB • Subject to modifications • Status 07/2011 15


Filter Plates GEA Air Filters
VISCINOL A30

The filter plates HL 12,5 and high efficiency round air filters HL are wetted with the
VISCINOL dust-trapping agent; depending on the application area - different
VISCINOL types are available; in dust-trapping agent is supplied in containers,
20 liters each
Application example:
wetting metal filter elements
Special features:
mixture of higher hydrocarbons
Areas of application:
filter plates HL 12,5 and round air filter of type DBH and DAH

Chemical composition Mixture of higher hydrocarbons, with addition of active and colouring agents,
silicone-based defoamer

Special warning Given that the conventional precaution measures during handling of mineral oil prod-
ucts are adhered to and instruction on personal protection equipment and toxicological
information is taken into account - no special warnings are so far known.

First-aid measures after skin Rinse with fresh water and soap at once. If skin irritation persists - search medical help,
contact and after eye contact rinse with much fresh water and search medical help.

Suitable extinguishing Foam, extinguishing powder, carbon dioxide


agents

Particularly high risk Combustion products NOx, CO, S02, soot and other organic substances. Do not inhale
smoke fumes.

Measures on environmental Prevent from entering into the sewage system, surface and ground water. Prevent from
protection entering into soil. Prevent area-like expansion. In case of leakage - inform the relevant
authority.

Form Liquid

Colour Red

Density at 15 °C 899-910 kg/m³

Viscosity at 40 °C 64-72 mm²/s

Primary irritation effect Not classified as irritating, continuous contact can cause irritation

Conditions to be avoided Higher temperatures (beginning decomposition)

Substances to be avoided Strong oxidizing agents

Instructions on disposal Consider regulations on waste management. Only mixing with old oil is allowed
(2/sentence 1 of the German waste oil legislation).

Labelling according to EC not subject to mandatory labelling


standards

Form of delivery/
VISCINOL Temperature range [°C] Approx. weight [kg] Order number
order numbers:
Container – minimum purchase quantity 20 l
VISCINOL A-30 20 liter -15 to +45 0.9 20 00 365

16 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Cells
FILTERGLAS

FILTERGLAS cells consist of tightly intermeshed glass fibres with special closure
fleece on the pure-air side, on two sides, the filter cell is framed with large-perforation
metal support plates in a moisture-resistant carton frame enclosure with a crimp fold.
Application example:
filtration of coarse dust in climate control and air handling systems
Special features:
special closure fleece that prevents migration of glass fibres
Areas of application:
standard climate control facilities and air handling units, pharmaceutical industry,
pre-filters for paint finishing line and paint spray compartment

Pressure drop diagram:


Curve applies to size 494 mm x 494 mm
Pressure drop [Pa]

Volume flow [m³/h]

Technical data:
FILTERGLAS FILTERGLAS
Filter class [EN779] G4
Installation depth/thickness [mm] 14
Rated air volume flow [m³/h] 1.000
Initial pressure drop [Pa] 140
Maximum allowed pressure
[Pa] 500
drop
Mean degree of filtration [%] 96.0
Max. operating temperature [°C] 80
Max. rel. air humidity [%] 100

Form of delivery/
order numbers: FILTERGLAS Size W/H [mm] Weight/unit [kg] Order number
Filter cell, packaging unit 25
FILTERGLAS 480/480 0.3 40 03 821

PR-2009-0099-GB • Subject to modifications • Status 07/2011 17


Filter Cells GEA Air Filters
ULTRANGLAS

ULTRANGLAS/ULTRANGLAS-H filter cells consist of tightly intermeshed glass


fibres. ULTRANGLAS is framed on two sides in a moisture-resistant carton frame with
large perforation in the metal support plates. ULTRANGLAS / -H is framed on all sides
in expanded aluminium mesh and is designed for operating temperatures up to 300°C.
Application example:
filtration of coarse dust in climate control and air handling units
Special feature:
ULTRANGLAS-H meets F1/K1 fire protection class; maximum continuous operating
temperature of 300 °C
Areas of application:
standard climate control facilities and air handling units, industrial drying facilities,
pre-filters for paint finishing lines and paint spray compartments

Pressure drop diagram:


Pressure drop [Pa]

Volume flow [m³/h]

Technical data:
ULTRANGLAS U-GLAS U-GLAS-H
Filter class [EN 779] G4 G4
Installation depth/thickness [mm] 48 14
Rated air volume flow [m³/h] 1.500 1.500
Initial pressure drop [Pa] 130 170
Maximum allowed pressure
[Pa] 500 500
drop
Mean degree of filtration [%] 93.0 93.0
Fire behaviour [DIN 53438] – F1/K1
Max. operating temperature [°C] 80 300
Max. rel. air humidity [%] 100 100

* depending on wetting agent

Form of delivery/
order numbers: ULTRANGLAS Size W/H [mm] Packaging unit Weight/unit [kg] Order number
Filter plate
U-GLAS 490/490 10 0.7 40 04 221
U-GLAS-H 480/480 30 0.3 60 35 921

18 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Cells
Z-50/Z-100

Z-50/Z-100 air-filter cells consist of pleated synthetic fleece in a sturdy, water-repel-


lent, impregnated carton frame with supporting lattices on the dust and pure-air sides;
the filter medium is folded in V shape and enables great air-flow rates with low pressure
drop and compact installation sizes; the filter medium is not regenerable; installation
depths amount to 47 mm with Z-50 and 92 mm with Z-100.
Application example:
filtration of coarse dust in climate control and air handling units
Special features:
pleating of the filter material results in enlargement of the active filter surface and thus
increases air-flow rate and dust-holding capacity; high efficiency thanks to low initial
pressure difference even with large air volume flows; filter cells can be completely
incinerated.
Areas of application:
standard climate control facilities and air handling units, pre-filters for laminar flow
units, pre-filters for high value HVAC systems, automobile industry and paint
finishing lines
Pressure drop diagram:
Pressure drop [Pa]

Air volume flow [m³/hm²]


Technical data:
Filter cells Z-50-G4 Z-50-F5 Z-100-G4 Z-100-F5
Filter class [EN 779] G4 F5 G4 F5
Installation depth/thickness [mm] 47 47 92 92
Rated air volume flow [m³/hm²] 7.200 5.100 7.200 5.100
Initial pressure drop [Pa] 42 55 31 47
Maximum allowed pressure
[Pa] 250 450 250 450
drop
Mean degree of filtration [%] 94.0 98.0 93.0 98.0
Average filtration efficiency [%] – > 40.0 – > 40.0
Max. operating temperature [°C] 70 70 70 70
Max. rel. air humidity [%] 100 100 100 100

Form of delivery/
Z-50/Z-100 Size W/H [mm] Weight/unit [kg] Order-Nr G4 Order-Nr F5
order numbers:
Filter cell packaging unit: 12 6
394/495/47 0.5 40 65 131 22 85 301
394/622/47 0.6 40 65 531 22 85 302
Z-50 495/495/47 0.7 40 65 231 22 85 303
495/622/47 0.8 40 65 631 22 85 304
592/592/47 0.9 40 65 331 22 85 305
394/495/92 0.7 00 39 061 22 85 306
394/622/92 0.8 40 66 031 22 85 307
Z-100 495/495/92 0.8 40 65 831 22 85 308
495/622/92 1.0 40 66 131 22 85 309
592/592/92 1.2 00 39 980 22 85 310

PR-2009-0099-GB • Subject to modifications • Status 07/2011 19


Filter Cells GEA Air Filters
FIBERGLAS

FILTERGLAS cells consist of tightly intermeshed glass fibres with special closure
fleece on the pure-air side, on two sides, the filter cell is framed with large-perforation
metal support plates in a moisture-resistant carton frame enclosure with a crimp fold

Pressure drop diagram:


200 Curve applies to size 480 mm x 480 mm
180
160
Pressure drop [Pa]

140
120
100
80
FIBERGLAS
60
40
20
0
0 100 200 300 400 500
Volume flow [m³/h]

Technical data:
FIBERGLAS
Filter class [EN 779] F5
Installation depth/thickness [mm] 14
Rated air volume flow [m³/h] 500
Initial pressure drop [Pa] 180
Maximum allowed pressure
[Pa] 450
drop
Mean degree of filtration [%] 99.0
Average filtration efficiency [%] 55.4
Max. operating temperature [°C] 80
Max. rel. air humidity [%] 100

Form of delivery/
order numbers: FIBERGLAS Size W/H [mm] Weight/unit [kg] Order number
Filter cell, packaging unit 25
FIBERGLAS 480/480 0.4 40 03 021

20 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Bag Filter
MULTISACK Overview

MULTISACK synthetic (S) and glass (G) bag filters are composed of several filter
bags. The individual bags, made of synthetic fibre or micro-fibreglass fleece, have
been shaped so as to provide wedge-shaped filter bags. The spacers in the individual
filter bags ensure complete utilization of the full bag depth and, in turn, of the entire filter
surface. The ready-to-install filter bags are secured to sturdy U-shaped profile frames
(25 mm) by clamp fittings. The frame is made of galvanized sheet steel.
Width, height and depth are specified like in the drawing!

Technical data:
MULTISACK K35 K50 K55 K65 K85 K95 G55 G65 G85 G95
Filter class * [EN 779] G4 F5 F5 F6 F7 F8 F5 F6 F7 F9
Installation depth [mm] 360 500 600 600 600 600 600 600 600 600
Number of filter bags [quantity] 4 6 6 8 8 8 6 8 8 8
Rated air volume flow [m³/h] 3.400 3.400 3.400 3.400 3.400 3.400 3.400 3.400 3.400 3.400
Initial pressure drop [Pa] 25 43 50 88 100 150 50 50 100 155
Max. pressure drop [Pa] 250 450 450 450 450 450 450 450 450 450
Mean deg. of filtration [%] 90.0 92.7 96.1 99.2 99.3 99.8 96.8 98.4 99.2 99.8
Average efficiency [%] – 46.1 51.9 71.9 84.9 92.3 50.4 62.8 88.4 95.4
Max. operating
[°C] 80 80 80 80 80 80 80 80 80 80
temperature
Max. rel. air humidity [%] 100 100 100 100 100 100 100 100 100 100

* Classification is valid at air-flow volume of 3400 m3/h for size 592/592 mm

Product Type Code:


Example: MULTISACK K6 5 6 V / 0600 / 08 / 05 / EX
size/rated volume flow

Number of filter bags

Frame thickness
Type/medium

Pattern code/
description

Frame type

Bag length

opt. model
MULTISACK Product description

K35, K50, K55, K65, K85, K95 Synthetic fibre fleece


G55, G65, G85, G95 Micro-fibreglass fleece

1 Size W/H [mm] 592/287 Rated volume flow [m³/h] 1.700-2.100


2 287/287 850-1.000
3 287/592 1.700-2.100
5 490/592 2.800-3.550
6 592/592 3.400-4.250
other special sizes on request

K Plastic
V Galvanized sheet steel
0195; 0360; 0380; 0500; 0534; 0600 Standard size [mm]
individual size on request

Number of bags according to filter class – refer to the table above „Technical Data“

05 Standard size [mm]


00 20 mm in galvanized frame

N Neutral
EX EX-model

PR-2009-0099-GB • Subject to modifications • Status 07/2011 21


Bag Filter GEA Air Filters
MULTISACK K35/K50

MULTISACK K35/K50 bag filters consist of synthetic fibre fleece


Application example:
filtration of coarse, fine and superfine dust
Special features:
The spacers ensure complete utilization of the full bag depth; sealing of spacer seams;
as compared to rated air-flow volume - operating air-flow volume can be increased
by 25%
Areas of application:
all HVAC and air handling installations with a filtration function

Installation instructions:
Pressure drop diagram valid for size 592 mm x 592 mm
Pressure drop [Pa]

Volume flow [m³/h]

Form of delivery:
Bag filter MULTISACK K35/K50

Model with a galvanized frame – surcharge for plastic frame on request

Number Bag Sur- Weig Pack- Energy Bag Sur- Weig Pack- Energy Bag Sur- Weig Pack- Energy
Multi- Size
of bags length face ht age unit efficiency length face ht age unit efficiency length face ht age unit efficiency
sack W/H [mm]
[quantity] [mm] [m²] [kg] [qty] class [mm] [m²] [kg] [qty] class [mm] [m²] [kg] [qty] class

Bag filter K35

0.5 1.0 20 0.9 1.0 10 1.5 1.1 8


K35-1 592/287 46 195 – 360 – 600 –
0.7 1.2 18 1.3 1.2 10 2.2 1.3 8

0.2 0.6 40 0.5 0.6 20 0.7 0.7 16 –


K35-2 287/287 23 195 – 360 – 600
0.3 0.7 36 0.7 0.7 20 1.1 0.8 16

0.5 0.9 20 0.9 1.0 10 1.5 1.1 8 –


K35-3 287/592 23 195 – 360 – 600
0.7 1.0 18 1.3 1.1 10 2.2 1.2 8

0.7 1.2 10 1.3 1.3 2.2 1.4 4 –


K35-5 490/592 35 195 – 360 55 – 600
1.2 1.3 9 2.2 1.6 3.8 1.7 4

1.0 1.5 10 1.8 1.5 3.0 1.6 4 –


K35-6 592/592 46 195 – 360 55 – 600
1.5 1.6 9 2.7 1.8 4.4 1.9 4

Multisack Size W/H [mm] Bags [quantity] Bag length [mm] Surface [m²] Weight [kg] Units [quantity] Energy efficiency class
Bag filter K50
K50-1 592/287 6 500 1.8 1.5 8 –
K50-2 287/287 3 500 0.9 0.9 16 –
K50-3 287/592 3 500 1.8 1.4 8 –
K50-5 490/592 5 500 3.0 2.1 4 –
K50-6 592/592 6 500 3.6 2.5 4 –

22 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Bag Filter
MULTISACK K55/K65

MULTISACK K55/K65 bag filters consist of synthetic fibre fleece


Application example: filtration of coarse, fine and superfine dust
Special feature:
Spacers ensure complete utilization of the filter bag depth; spacer seams are sealed;
compared to rated air-flow volume - operating air-flow volume can be
increased by 25%;
Filters with fire protection are optional;
Filters with antiseptic features are optional as well;
FireTex and SepTex filters meet standards for fire
protection class B as of DIN EN 13 501-1 2007

Range of application: AIR FILTERS


CLASS F5-F9

all HVAC units with a filtration function

Pressure drop diagram valid for size 592 mm x 592 mm Installation instructions:
200
Pressure drop [Pa]

150

100
K-65

50
K-55

0
0 850 1700 2250 3400 4250
Volume flow [m³/h]

Form of delivery:

Bag filter MULTISACK K55/K65

Model with a galvanized frame – surcharge for plastic frame on request

Number of Filter Weight Packaging Energy Filter Weight Packaging Energy


Multi- Size W/H Bag length Bag length
bags surface approx. unit efficiency surface approx. unit efficiency
sack [mm] [mm] [mm]
[quantity] [m²] [kg] [quantity] class [m²] [kg] [quantity] class
Bag filter K55
K55-1 592/287 6 360 1.3 1.3 8 – 600 2.2 1.4 8 –
K55-2 287/287 3 360 0.7 0.7 16 – 600 1.1 0.8 16 –
K55-3 287/592 3 360 1.3 1.2 8 – 600 2.2 1.3 8 –
K55-5 490/592 5 360 2.2 1.9 8 – 600 3.8 2.0 8 –
K55-6 592/592 6 360 2.7 2.3 8 – 600 4.4 2.4 8 –

Number Bag Sur- Weig Pack- Energy Bag Sur- Weig Pack- Energy Bag Sur- Weig Pack- Energy
Multi- Size W/H
of bags length face ht age unit efficiency length face ht age unit efficiency length face ht age unit efficiency
sack [mm]
[quantity] [mm] [m²] [kg] [qty] class [mm] [m²] [kg] [qty] class [mm] [m²] [kg] [qty] class
Bag filter K65
1.5 1.6 1.9 1.6 8 2.2 1.6 8
K65-1 592/287 68 380 88 – 534 – 600 –
1.9 1.7 2.6 1.7 8 3.0 1.7 8
0.7 0.8 0.9 0.8 16 1.1 0.9 16
K65-2 287/287 34 380 1616 – 534 – 600 –
0.9 0.9 1.3 0.9 16 1.5 1.0 16
1.5 1.5 1.9 1.5 8 2.2 1.5 8
K65-3 287/592 34 380 88 – 534 – 600 –
1.9 1.6 2.6 1.6 8 3.0 1.6 8
2.4 2.2 3.3 2.2 8 3.8 2.2 8
K65-5 490/592 56 380 88 – 534 – 600 –
2.9 2.3 3.9 2.3 8 4.4 2.3 8
2.9 2.7 3.9 2.7 8 4.4 2.8 8
K65-6 592/592 68 380 88 – 534 – 600 –
3.9 2.8 5.2 2.8 8 6.0 2.9 8

PR-2009-0099-GB • Subject to modifications • Status 07/2011 23


Bag Filter GEA Air Filters
MULTISACK K85/K95

MULTISACK K85/K95 bag filters consist of synthetic fibre fleece


Application example: filtration of coarse, fine and superfine dust
Special feature:
Spacers ensure complete utilization of the filter bag depth; spacer seams are sealed;
compared to rated air-flow volume - operating air-flow volume can be
increased by 25%;
Filters with fire protection are optional;
Filters with antiseptic features are optional as well;
FireTex and SepTex filters meet standards for fire
protection class B as of DIN EN 13 501-1 2007
Range of application:
all air handling units with a filtration function
AIR FILTERS
CLASS F5-F9

Pressure drop diagram valid for size 592 mm x 592 mm Installation instructions:
Pressure drop [Pa]

Volume flow [m³/h]

Form of delivery:

Bag filter MULTISACK K85/K95

Model with a galvanized frame – surcharge for plastic frame on request

Bag Sur- Weig Pack- Energy Bag Sur- Weig Energy Bag Sur- Weig Energy
Multi- Size W/H Bags Pack- Pack-
length face ht age unit efficiency length face ht efficiency length face ht efficiency
sack [mm] [quantity] age [qty] age [qty]
[mm] [m²] [kg] [qty] class [mm] [m²] [kg] class [mm] [m²] [kg] class
Bag filter K85
1.5 1.6 8 1.9 1.5 8 2.2 1.6 8
K85-1 592/287 68 380 B 534 B 600 B
1.9 1.7 8 2.6 1.6 8 3.0 1.7 8
0.7 0.8 16 0.9 0.8 16 1.1 0.9 16
K85-2 287/287 34 380 B 534 B 600 B
0.9 0.9 16 1.3 0.9 16 1.5 1.0 16
1.5 1.5 8 1.9 1.4 8 2.2 1.5 8
K85-3 287/592 34 380 B 534 B 600 B
1.9 1.6 8 2.6 1.5 8 3.0 1.6 8
2.4 2.2 8 3.3 2.1 8 3.8 2.1 8
K85-5 490/592 56 380 B 534 B 600 B
2.9 2.3 8 3.9 2.2 8 4.4 2.2 8
2.9 2.7 8 3.9 2.6 8 4.4 2.7 8
K85-6 592/592 68 380 B 534 B 600 B
3.9 2.8 8 5.2 2.7 8 6.0 2.8 8

Number Weight Packaging Weight Packag-


Multi- Size W/H Bag length Filter sur- Energy Bag length Filter sur- Energy efficiency
of bags approx. unit approx. ing unit
sack [mm] [mm] face [m²] efficiency class [mm] face [m²] class
[quantity] [kg] [quantity] [kg] [quantity]
Bag filter K95
K95-1 592/287 8 534 2.6 1.6 8 C 600 3.0 1.7 8 C
K95-2 287/287 4 534 1.3 0.9 16 C 600 1.5 1.0 16 C
K95-3 287/592 4 534 2.6 1.5 8 C 600 3.0 1.6 8 C
K95-5 490/592 6 534 3.9 2.1 8 C 600 4.4 2.2 8 C
K95-6 592/592 8 534 5.2 2.7 8 C 600 6.0 2.8 8 C

24 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Bag Filter
MULTISACK G55/G65

MULTISACK G55/G65 bag filters consist of micro-fibreglass fleece


Application example: filtration of fine and superfine dust
Special features:
The spacers ensure complete utilization of the full bag depth;
sealing of spacer seams; additional pure-air side gauze
prevents migration of fibreglass particles; compared to rated
air-flow volume - operating air-flow volume can be increase
by 25%; as an option this filter model is available
as EX protection type
AIR FILTERS
CLASS F5-F9

Areas of application:
all HVAC and air handling installations with a filtration function

Pressure drop diagram valid for size 592 mm x 592 mm Installation instructions:
Pressure drop [Pa]

Volume flow [m³/h]

Form of delivery:

Bag filter MULTISACK G55/G65

Model with a galvanized frame – surcharge for plastic frame on request

Number Bag Sur- Weig Pack- Energy Bag Sur- Weig Pack- Energy Bag Sur- Weig Pack- Energy
Multi- Size W/H
of bags length face ht age unit efficiency length face ht age efficiency length face ht age unit efficiency
sack [mm]
[quantity] [mm] [m²] [kg] [qty] class [mm] [m²] [kg] unit [qty] class [mm] [m²] [kg] [qty] class
Bag filter G55
G55-1 592/287 6 380 1.5 1.2 9 B 534 1.9 1.3 8 B 600 2.2 1.3 8 B
G55-2 287/287 3 380 0.7 0.6 18 B 534 0.9 0.7 16 B 600 1.1 0.8 16 B
G55-3 287/592 3 380 1.5 1.1 9 B 534 1.9 1.2 8 B 600 2.2 1.3 8 B
G55-5 490/592 5 380 2.4 1.7 9 B 534 3.3 1.8 8 B 600 3.8 1.9 8 B
G55-6 592/592 6 380 2.9 2.0 9 B 534 3.9 2.1 8 B 600 4.4 2.2 8 B

Number Bag Sur- Weig Pack- Energy Bag Sur- Weig Pack- Energy Bag Sur- Weig Pack- Energy
Multi- Size W/H
of bags length face ht age unit efficiency length face ht age unit efficiency length face ht age unit efficiency
sack [mm]
[quantity] [mm] [m²] [kg] [qty] class [mm] [m²] [kg] [qty] class [mm] [m²] [kg] [qty] class
Bag filter G65
1.9 1.5 8 2.6 1.5 8 3.0 1.5 8
G65-1 592/287 810 380 A 534 A 600 A
2.4 1.7 8 3.2 1.7 6 3.8 1.7 8
0.9 0.8 16 1.3 0.8 16 1.5 0.9 16
G65-2 287/287 45 380 A 534 A 600 A
1.1 0.9 16 1.6 0.9 12 1.9 1.0 16
1.9 1.4 8 2.6 1.4 8 3.0 1.5 8
G65-3 287/592 45 380 A 534 A 600 A
2.4 1.6 8 3.2 1.6 6 3.8 1.7 8
2.9 2.0 8 3.9 2.0 8 4.4 2.1 8
G65-5 490/592 68 380 A 534 A 600 A
3.9 2.4 8 5.2 2.4 8 6.0 2.5 8
3.9 2.5 8 5.2 2.5 8 6.0 2.6 8
G65-6 592/592 810 380 A 534 A 600 A
4.8 2.9 8 6.5 2.9 6 7.5 3.0 8

PR-2009-0099-GB • Subject to modifications • Status 07/2011 25


Bag Filter GEA Air Filters
MULTISACK G85/G95

MULTISACK G85/G95 bag filters consist of micro-fibreglass fleece


Application example: filtration of fine and superfine dust
Special features: The spacers ensure complete utilization of the
full bag depth; sealing of spacer seams; additional pure-air side
gauze prevents migration of fibreglass particles; compared to
rated air-flow volume - operating air-flow volume can be increased
by 25%; as an option this filter model is available as EX protection type
Areas of application:
all HVAC and air handling installations with a filtration function

AIR FILTERS
CLASS F5-F9

Pressure drop diagram valid for size 592 mm x 592 mm Installation instructions:
Pressure drop [Pa]

Volume flow [m³/h]


Form of delivery:

MULTISACK bag filter G85/G95

Model with a galvanized frame – surcharge for plastic frame on request

Number Bag Sur- Weig Pack- Energy Bag Sur- Weig Pack- Energy Bag Sur- Weig Pack- Energy
Multi- Size W/H
of bags length face ht age unit efficiency length face ht age efficiency length face ht age unit efficiency
sack [mm]
[quantity] [mm] [m²] [kg] [qty] class [mm] [m²] [kg] unit [qty] class [mm] [m²] [kg] [qty] class
Bag filter G85
1.9 1.5 8 2.6 1.5 8 3.0 1.5 8
G85-1 592/287 810 380 A 534 A 600 A
2.4 1.6 8 3.2 1.6 6 3.8 1.7 6
0.9 0.8 16 1.3 0.8 16 1.5 0.8 16
G85-2 287/287 45 380 A 534 A 600 A
1.1 0.9 16 1.6 0.9 12 1.9 0.9 12
1.9 1.4 8 2.6 1.4 8 3.0 1.4 8
G85-3 287/592 45 380 A 534 A 600 A
2.4 1.6 8 3.2 1.6 6 3.8 1.6 6
2.9 1,9 8 3.9 1.9 8 4.4 2.0 8
G85-5 490/592 68 380 A 534 A 600 A
3.9 2.3 8 5.2 2.3 8 6.0 2.4 8
3.9 2.4 8 5.2 2.4 8 6.0 2.5 8
G85-6 592/592 810 380 A 534 A 600 A
4.8 2.8 8 6.5 2.8 6 7.5 2.9 6

Number of
Multi- Size W/H Bag length Surface Weight Package Energy Bag length Surface Weight Package Energy
bags [quan-
sack [mm] [mm] [m²] [kg] unit [qty] efficiency class [mm] [m²] [kg] unit [qty] efficiency class
tity]
Bag filter G95
1.9 1.4 8 2.6 1.5
G95-1 592/287 810 534 A 600 8 A
2.4 1.6 6 3.2 1.7
0.9 1.4 16 1.3 1.5 16
G95-2 287/287 45 534 A 600 A
1.1 1.7 12 1.6 1.7 12
1.9 2.9 8 2.6 3.0 8
G95-3 287/592 45 534 A 600 A
2.4 3.6 6 3.2 3.7 6
2.9 4.4 8 3.9 4.5 8
G95-5 490/592 68 534 A 600 A
3,9 5.7 8 5.2 5.8 8
3.9 5.9 8 5.2 6.0 8
G95-6 592/592 810 534 A 600 A
4.8 7.2 6 6.5 7.3 6

26 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Elements
MULTIFORM Overview

MULTIFORM filter elements are made of micro-fibreglass fleece which is pleated to


form a stable package of folds; the number and the height of the folds are optimally
designed to match operating conditions; peripheral but merged synthetic strips keep
individual pleats at a distance along the entire pleat depth and ensure greater stability
and complete utilisation of the entire filter surface; the individual filter plates are
arranged in a V-shape (in 4 compartments) inside a synthetic frame made of ABS, so
as to assure a stable form of the filter plates, and are glued to assure air-tightness.

Technical data:
Filter element MF-65 MF-85 MF-90 MF-95 MF-98 MF-99 MF-100
[EN 779] F6 F7 F8 F9 – – –
Filter class
[EN 1822] – – – – E10 E11 E12
Installation depth/
[mm] 298 298 298 298 298 298 298
thickness
Initial pressure drop [Pa] 100 110 125 150 185 185 290
Maximum allowed
[Pa] 450 450 450 450 650 650 650
pressure drop
Mean deg. of filtration [%]
as of DIN EN 779 > 98.0 > 98.0 > 98.0 > 98.0 – – –
as of DIN EN 1822 – – – – > 85.0 > 95.0 > 99.5
Average efficiency [%] 72.6 85.9 93.5 96.2 – – –
Max. operating
[°C] 70 70 70 70 70 70 70
temperature
Max. rel. air humidity [%] 100 100 100 100 100 100 100

Product Type Code:


Example: MF 95 - 6

Size code (rated size)


Product description

Type

MF MULTIFORM

65 F6
85 F7
90 F8
95 F9
98 E10
99 E11
100 E12

Rated size Air volume flow


3 592 x 287 mm 2.125 m³/h
5 592 x 490 mm 3.500 m³/h
6 592 x 592 mm 4.250 m³/h

PR-2009-0099-GB • Subject to modifications • Status 07/2011 27


Filter Elements GEA Air Filters
MULTIFORM MF65/MF85/MF90

Filter Elements MULTIFORM MF65, MF85 and MF90


Application example:
all applications requiring maximum operating safety and highest standards in air purity;
for filtration of fine and superfine dust, bacteria, mould etc. in HVAC systems and air
handling units of all types, as well as a pre-filter for HEPA filters
Special features:
self-supporting, shape-steady design with high mechanical stability; great air volume
flow with small installation depth; large filter surface; can be completely incinerated
Areas of application:
standard climate control facilities and air handling units, photographic, electrical and
food product industry, high value assembly rooms and switchgear facilities, chemical,
pharmaceutical industry and hospitals, pre-filters for clean-room facilities,
air intake filter for power stations
MF65/Eco and MF85/Eco are avaialble in 3-V form on request

AIR FILTERS
CLASS F5-F9
MULTIFORM MF65, MF85 and MF90 filter elements are certified by the Eurovent

Pressure drop diagram:


Curve applies to size
592 mm x 592 mm
Pressure drop [Pa]

Volume flow [m³/h]

Form of delivery: Filter Elements MULTIFORM MF65, MF85 and MF90


Design without sealing – sealing and handle guard on request

Air volume flow Filter surface Weight approx.


Type Size W/H [mm] Filter class
[m³/h] [m²] [kg]

MF65-3 592/287 2.125 7.0 3.5


MF65-5 592/490 3.500 F6 13.0 4.5
MF65-6 592/592 4.250 16.0 5.5

MF85-3 592/287 2.125 8.0 3.5


MF85-5 592/490 3.500 F7 15.0 4.5
MF85-6 592/592 4.250 18.0 5.5

MF90-3 592/287 2.125 8.0 3.5


MF90-5 592/490 3.500 F8 15.0 4.5
MF90-6 592/592 4.250 18.0 5.5

28 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Elements
MULTIFORM MF95/MF98/MF99

Filter Elements MULTIFORM MF95, MF98 and MF99


Application example:
all applications requiring maximum operating safety and highest standards in air purity;
for filtration of fine and superfine dust, bacteria, mould etc. in HVAC systems and air
handling units of all types, as well as a pre-filter for HEPA filters
Special features:
self-supporting, shape-steady design with high mechanical stability; great air volume
flow with small installation depth; large filter surface; can be completely incinerated
Areas of application:
standard climate control facilities and air handling units, photographic, electrical and
food product industry, high value assembly rooms and switchgear facilities, chemical,
pharmaceutical industry and hospitals, pre-filters for clean-room facilities,
air intake filter for power stations

AIR FILTERS
Filter Elements MULTIFORM MF95 are certified by the Eurovent
CLASS F5-F9

Pressure drop diagram:


250 Curve applies to size
99
592 mm x 592 mm
200
98
Pressure drop [Pa]

150
95

100

50

0
0 850 2550 4250
Volume flow [m³/h]

Form of delivery: Filter Elements MULTIFORM MF95, MF98 and MF99


Design without sealing – sealing and handle guard on request

Air volume flow Filter surface Weight approx.


Type Size W/H [mm] Filter class
[m³/h] [m²] [kg]

MF95-3 592/287 2.125 8.0 3.5


MF95-5 592/490 3.500 F9 15.0 4.5
MF95-6 592/592 4.250 18.0 5.5

MF98-3 592/287 2.125 8.0 3.5


E10
MF98-6 592/592 4.250 18.0 5.5
MF99-3 592/287 1.700 8.0 3.5
E11
MF99-6 592/592 3.400 18.0 5.5

PR-2009-0099-GB • Subject to modifications • Status 07/2011 29


Filter Elements GEA Air Filters
MULTIFORM MF100

Filter Elements MULTIFORM MF100


Application example:
all applications requiring maximum operating safety and highest standards in air purity;
for filtration of fine and superfine dust, bacteria, mould etc. in HVAC systems and air
handling units of all types, as well as a pre-filter for EPA/HEPA filters
Special features:
self-supporting, shape-steady design with high mechanical stability; great air volume
flow with small installation depth; large filter surface; can be completely incinerated
Areas of application:
standard climate control facilities and air handling units, photographic, electrical and
food product industry, high value assembly rooms and switchgear facilities, chemical,
pharmaceutical industry and hospitals, pre-filters for clean-room facilities, air intake fil-
ter for power stations

Pressure drop diagram:


400 Curve applies to size
100
350 592 mm x 592 mm
300
Pressure drop [Pa]

250
200
150
100
50
0
0 850 2550 4250
Volume flow [m³/h]

Form of delivery: Filter Elements MULTIFORM MF100


Standard design with aluminium handle guard on the pure-air side, design without sealing – seal-
ing on request

Air volume flow Filter surface Weight approx.


Type Size W/H [mm] Filter class
[m³/h] [m²] [kg]

MF100-3 592/287 1.700 12.0 5.5


E12
MF100-6 592/592 3.400 26.0 9.0

30 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Elements
MULTITHERM Overview

MULTITHERM filter elements are made of deeply-folded, paper-like micro-fibre


fleece; the position of the folds is stabilised through:
– Wave-shaped aluminium separators (models: F, T, H, E, S with Al-separators)
NOTE!
Installation of MULTITHERM filter elements can only be done with
vertically arranged separators and horizontal air flow.

– Filter-material strips to separate the folds (aluminium-free C and D-design)


– Separators are designed for an air flow on both sides
The filter package is inserted dry without casting in a riveted filter frame (except F
model) made of sendzimir-galvanised sheet steel or stainless steel with grip protection
on both sides; with F model (without brackets) a one-sided peripheral flange is
mounted where all materials satisfy stipulations pertaining to the absence of silicone,
and are temperature resistant up to 250°C; for units with critical air-flow conditions - a
modified model (TP) can be supplied

Technical data:
Filter element MULTITHERM MT-60 MT-90
Filter class [EN 779] F6 F8
Installation depth/thickness [mm] 40/55/78/90/150/292 40/55/78/90/150/292
Glass-fibre peripheral belt seal [mm] +7 +7
Maximum allowed pressure
[Pa] 450 450
drop
Mean degree of filtration [%] > 98.0 > 98.0
Mean filtration efficiency [%] > 60.0 > 90.0
Max. operating temperature [°C] 250 250
Max. rel. air humidity [%] 100 100

Product type code:


Example: MT 90 S - 1800 / V 2

Rated volume flow rate


Product description

Installation depth

Frame type

Seal
Type

MT MULTITHERM

60 F6
90 F8

C depth 40 mm
D depth 55 mm
S depth 78 mm
E depth 90 mm
G depth 150 mm (flange)
H depth 150 mm
F depth 292 mm (flange)
T depth 292 mm

Rated volume flow rate – refer to table „form of delivery/order number“ on the next page

V steel, galvanized

1 on dust-air side – standard


2 on pure-air side

NOTE!
The standard size of a filter box with a flange design makes up 560 mm.

PR-2009-0099-GB • Subject to modifications • Status 07/2011 31


Filter Elements GEA Air Filters
MULTITHERM MT60/MT90

Filter elements MULTITHERM MT60 und MT90


Application example:
supply and recirculating air units for filtration of fine and superfine dust
(filter classes F 6/F 8) at high temperatures
Special features:
great air volume flow with small installation depth; temperature-resistant up to 250 °C,
easy separation of a filter element from a frame by using brackets, satisfies stipulations
pertaining to the absence of silicone
Application area:
surface technology, drying equipment, automobile industry

MULTITHERM MT60 and MT90 filter elements are certified by the Eurovent
AIR FILTERS
CLASS F5-F9

Pressure drop diagram:


Curve applies to size
610 mm x 610 mm
Pressure drop [Pa]

Volume flow [m³/h]

Form of delivery: Filter elements MULTITHERM MT60 and MT90


Volume flow pressure Filter Filter surface Weight approx.
Type Size W/H/D [mm]
difference [m³/h/Pa] class [m²] [kg]
Installation depth 40 mm and 55 mm, aluminium-free compact design

MT60-C 490/490/40 1.500/125 F6 4.0 1.5

610/610/55 1.800/85 8.0 3.5


MT60-D 915/457/55 2.000/85 F6 9.0 4.5
915/610/55 2.700/85 12.0 5.5

MT90-C 490/490/40 1.500/125 F8 4.0 1.5

610/610/55 1.800/110 8.0 3.5


MT90-D 915/457/55 2.000/110 F8 9.0 4.5
915/610/55 2.700/110 12.0 5.5

Installation depth 78 mm and 292 mm, design with aluminium separators

610/610/78 1.800/40 4.0 5.0


MT60-S 915/457/78 2.000/40 F6 4.0 5.0
915/610/78 2.700/40 5.2 6.0

287/592/292 1.700/110 4.5 4.5


MT60-F F6
592/592/292 3.400/110 9.0 7.0

305/610/292 2.125/120 6.0 6.0


MT60-T F6
610/610/292 4.250/120 12.0 9.5

610/610/78 1.800/40 4.0 5.0


MT90-S 915/457/78 2.000/40 F8 4.5 5.5
915/610/78 2.700/40 6.0 6.5

287/592/292 1.700/110 4.5 4.5


MT90-F F8
592/592/292 3.400/110 9.0 7.0

305/610/292 2.125/120 6.0 6.0


MT90-T F8
610/610/292 4.250/120 12.0 9.5

32 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Elements
MULTITHERM MT60/MT90

MULTIPLAN filter elements – medium uses special paper-like fleece made of super-
fine micro-glass fibres, which are processed to form a stable package of folds; number
and height of folds is designed to match the optimal rated operating points; here the
individual folds are separated down to the greatest depth of the folds by continuous
synthetic threads (hot melt) that are bonded together, which provides great stability as
a result of the compact fold structure; as standard version the filter element is provided
with a peripheral seal on the intake (dusty)-air side and the filter frame is made of MDF
(Multiplan I) or plastic (Multiplan II)

Technical data:
Filter Elements MULTIPLAN I

MP-65 MP-85 MP-95

Filter class [EN 779] F6 F7 F9

Mean degree of filtration [%] 98 >98 >99

Mean filtration efficiency [%] >60 >80 >95

Installation depth [mm] 78/150/292 78/150/292 78/150/292

Rated air volume flow * [m³/h] 3000 3000 3000

Initial pressure drop [Pa] 150 170 190

Maximum allowed
[Pa] 450 450 450
pressure drop

Max. operating
[°C] 80 80 80
temperature

Max. rel. air humidity [%] 100 100 100

* applies to size 610/610

Filter Elements MULTIPLAN II

MP-55 MP-65 MP-85 MP-95

Filter class [EN 779] F5 F6 F7 F9

Mean filtration [%] 98 98 >98 >99

Mean efficiency [%] >50 >60 >80 >95

Installation depth [mm] 48/96 48/96 48/96 48/96


Rated air volume flow * [m³/h] 1900/3400 1900/3400 1900/3400 1900/3400

Initial pressure drop [Pa] 50/80 60/90 80/110 130/140

Max. pressure drop [Pa] 450 450 450 450

Max. oper temperature [°C] 70 70 70 70

Max. rel. air humidity [%] 100 100 100 100

* applies to size 592/592

Filter Elements MULTIPLAN II + flange

MP-55 MP-65 MP-85 MP-95

Filter class [EN 779] F5 F6 F7 F9

Mean filtration [%] 98 98 >98 >99

Mean efficiency [%] >50 >60 >80 >95

Installation depth [mm] 78/100 78/100 78/100 78/100

Rated air volume flow * [m³/h] 2400/3400 2400/3400 2400/3400 2400/3400

Initial pressure drop [Pa] 80 90 110 140

Maximum allowed
[Pa] 450 450 450 450
pressure drop

Max. operating
[°C] 70 70 70 70
temperature

Max. rel. air humidity [%] 100 100 100 100

* applies to size 592/592

PR-2009-0099-GB • Subject to modifications • Status 07/2011 33


Filter Elements GEA Air Filters
MULTIPLAN type code

Type code Multiplan I and II:


Example: MP 95 S - 3000 / M G 1 B 2 N

Rated volume flow rate


Product description

Installation depth

Seal position
Seal design
Frame type
Filter class

Option

Option

Option
MP MULTIPLAN

55 F5
65 F6
85 F7
95 F9

L Depth 48 mm
S Depth 78 mm
E Depth 90 mm
J Depth 96 mm
H Depth 150 mm
T Depth 292 mm
SF Depth 78 mm (flange)
JF Depth 100 mm (flange)

Rated volume flow rate – refer to table „form of delivery/order number“ on the next page

M MDF

K Synthetic

V Galvanized steel

G Polyurethane, foamed
F Flat profile
0 Without

1 Seal on the dust-air side – standard


2 Seal on pure-air side
3 Seal on both sides

B Contact protection (not for K-frame)

1 Handle guard on dust-air side


2 Handle guard on pure-air side

3 Handle guard on both sides

N Neutral

34 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Elements
MULTIPLAN I (MP65, 85, 95)

Filter elements MULTIPLAN I (MP65, 85, 95)


Application example:
mainly as pre-filter for HEPA filters which allows to significantly prolong service life of
HEPA filters; filter classes F6/F7/F9
Special features:
high volume flows with small installation depth; great mechanical stability through
established fold design; metal-free separation of folds
Areas of application:
microelectronics, production of semiconductors, health care, chemical, pharmaceutical
industries, microbiology

Filter elements MULTIPLAN I (MP65, 85, 95) are certified by Eurovent


AIR FILTERS
CLASS F5-F9

Pressure drop diagrams:


Curve applies to size
610 mm x 610 mm
Pressure drop [Pa]

Volume flow [m³/h]

Form of delivery:
Filter elements MULTIPLAN I (MP65, MP85 and MP95)
Standard configuration with PUR seal; galvanized frame and other dimensions are available on request

W/H/D + seal
Volume flow [m³/h] Filter surface [m²] Approx. weight [kg] Packaging unit [pieces]
[mm]

305/610/78 1.500 5.0 3.3 1

610/610/78 3.000 10.8 6.0 2

305/610/150 1.500 5.0 5.5 2

610/610/150 3.000 10.8 7.0 1

305/610/292 1.500 5.0 9.6 2

610/610/292 3.000 10.8 14.0 1

PR-2009-0099-GB • Subject to modifications • Status 07/2011 35


Filter Elements GEA Air Filters
MULTIPLAN II (MP55, 65, 85, 95)

Filter elements MULTIPLAN II (MP55, 65, 85, 95)


Application example:
mainly as pre-filter for HEPA filters which allows to significantly prolong service life of
HEPA filters; filter classes F5/F6/F7/F9
Special features:
high volume flows with small installation depth; great mechanical stability through
established fold design; metal-free separation of folds
Areas of application:
microelectronics, production of semiconductors, health care, chemical, pharmaceutical
industries, microbiology

AIR FILTERS
CLASS F5-F9

Pressure drop diagram:


for MULTIPLAN II and Multiplan II + flange

Curve applies to size


592 mm x 592 mm
Pressure drop [Pa]

Volume flow [m³/h]

Form of delivery:
Filter elements MULTIPLAN II
(MP55, MP65, MP85 and MP95) Filter elements MULTIPLAN II + flange
Standard configuration without seal; plastic (MP55, MP65, MP85 and MP95)
Standard configuration without seal;
frame and other dimensions are available on
other dimensions are available on request
request
Volume flow Filter surface Approx. W/H/D Volume flow Filter surface Approx.
W/H/D [mm] Packaging unit Packaging unit
[m³/h] [m²] weight [kg] [mm] [m³/h] [m²] weight [kg]

287/287/48 475 1.3 0.4 2 287/287/78 600 1.5 0.6 2

287/592/48 950 2.7 0.8 4 287/592/78 1200 3.6 1.1 1

305/610/48 1000 2.9 0.8 4 490/592/78 2000 6.7 1.8 1

490/592/48 1570 4.6 1.2 2 592/592/78 2400 8.3 2.1 1

592/592/48 1900 5.6 1.4 2 287/287/100 850 1.7 0.7 1

610/610/48 2000 6.0 1.4 2 287/592/100 1700 3.9 1.3 2

287/287/96 850 2.3 0.8 1 490/592/100 2800 7.1 2.1 1

287/592/96 1700 4.7 1.6 2 592/592/100 3400 8.8 2.4 1

305/610/96 1750 5.2 1.6 2

490/592/96 2800 8.2 2.3 1

592/592/96 3400 10.0 2.7 1

610/610/96 3500 10.7 2.8 1

36 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Elements
MULTI 2004

MULTI 2004 filter elements consist of a frame and filter inserts; steel frame is corro-
sion-resistant as a result of an RAL 9011 surface finish; in the system frame, the filter
inserts are inserted with a magnetic-strip seal, in V shape. Safety grille on the pure-air
side prevents the elements from breaking through, the pleated filter packs are glued
airtight in a polyester-coated and moisture-resistant carton frame; for filtration of emul-
sion mist and dust - micro glass-fibre paper is used and for absorbtion of odour-inten-
sive pollutants - activated-carbon foam.
Application example:
special inserts are used for filtration of emulsion mist, filtration of gaseous,
odour-intensive pollutants in high value HVAC units
Special features:
reusable filter frame; filter medium can be replaced without tools easily and fast; low
recycling and disposal costs (filter inserts can be fully incinerated); low shipping
volume and weight in case of repeat orders for filter inserts and their disposal
Areas of application:
standard climate control facilities and air handling units, pre-filter for clean-room
facilities, chemical, pharmaceutical and health-care industry, electronic and
automobile industry, filtration of emulsion mist and other mist types caused by
inflammable liquids, adsorption of odour and toxic pollutants

MULTI 2004 filter elements are certified by the Eurovent


AIR FILTERS
CLASS F5-F9

Pressure drop diagram:


Curve applies to size 592 mm x 592
mm
Pressure drop [Pa]

Volume flow [m³/h]

Technical data,
form of delivery/ Filter Elements
MULTI 2004 MULTI 2004 MULTI 2004 MULTI 2004 MULTI 2004
order numbers: MF65 MF85 MF95 AKK AKS

Filter class [EN 779] F6 F7 F9 – –

Install. depth/thickness [mm] 301 301 301 301 301

Rated air volume flow [m³/h] 4.250 4.250 4.250 – –

Max. volume flow


[m³/h] – – – 2.125 2.125
activated-carbon elem.

Initial pressure drop [Pa] 130 140 200 35 35

Maximum pressure drop [Pa] 450 450 450 – –

Mean degree of filtration [%] 98.0 98.0 >99.0 – –

Mean filtration efficiency [%] >60 >80 95 – –

Max. operating
[°C] 80 80 80 40 40
temperature

Max. rel. air humidity [%] 100 100 100 70 70

Order number 30 00 211 30 00 213 30 00 214 30 00 215 30 01 246

PR-2009-0099-GB • Subject to modifications • Status 07/2011 37


Filter Elements GEA Air Filters
MULTICOL

MULTICOL filter elements – in these filters wave-shaped aluminium separators are


used for stabilisation instead of synthetic threads, package of folds in galvanized steel
frame; as an option flange is available on the dust-air side (EF model) or on the dust
and pure-air side (DF model)
Application example:
filtration of supply or extract air in climate control and air handling unit
Areas of application: in areas with very irregular air flows
involving unusual turbulences and high dust concentration;
as an option - also available in EX protection

AIR FILTERS
CLASS F5-F9

Pressure drop diagram:


Curve applies to size
592 mm x 592 mm
Pressure drop [Pa]

Volume flow [m³/h]

Technical data:
MULTICOL DF60/EF60 DF90/EF90
Filter class [EN 779] F6 F8

Installation depth [mm] 292 292

Rated air volume flow [m³/h] 3.400 3.400

Initial pressure drop [Pa] 100 140

Maximum allowed pressure


[Pa] 450 450
drop

Filter surface [m²] 10 10

Mean degree of filtration [%] 98 98

Mean filtration efficiency [%] 66 91


Max. operating temperature [°C] 80 80

38 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Elements
MULTICOL

MULTICOL type code:


Example: MC EF 90 F - 3 / V 2 A BV N

Product description

Burst protection
Design type
Flange type

Filter class

Option

Option

Option
Frame
Size
MC MULTICOL

DF Double flange
EF Single flange

60 F6
90 F8

F Installation depth 292


G Installation depth 150

1 592/287
3 287/592
5 490/592
6 592/592

V Galvanized

0 Without flange profile seal


1 Flange profile seal on dust-air side
2 Flange profile seal on pure-air side (standard with DF)
3 Flange profile seal on both sides

A Standard model (592/592 = 10 m²)


B Extended surface model (592/592 = 13 m²)
C Reduced surface model (592/592 = 8 m²)

BV Burst protection galvanized steel


BA Burst protection Al expanded metal

N Neutral

PR-2009-0099-GB • Subject to modifications • Status 07/2011 39


EPA/HEPA Filters GEA Air Filters
Overview

GEA Delbag high efficiency submicron particulate air (EPA/HEPA) filters consist of
special, paper-like fleece made of superfine micro-glass fibres that have different filtra-
tion and air-flow capacity depending on the filter class. The filter fleece is processed to
form a stable package of folds; number and height of folds is designed for extended
service life and to match the optimal rated operating points; here the individual folds
are separated down to the greatest depth by continuous synthetic threads (hot melt)
that are bonded together, which provides great stability and even thread run as a result
of the compact fold structure. The packages of folds are cast airtight in robust frames;
the filter frames are available as MDF, plywood, aluminium and stainless steel.

Technical data:
EPA/HEPA Filters E11 H13 H14 H14
Filter class [EN 1822] E11 H13 H14 H14
Initial pressure drop [Pa] 125 250 125 250
Maximum allowed pressure
[Pa] 750 750 600 600
drop
Mean degree of filtration [%] > 95.0 > 99.95 > 99.995 > 99.995
Max. operating temperature [°C] 80 80 80 80
Max. rel. air humidity [%] 100 100 100 100

40 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters EPA/HEPA Filters
Description of Product Type Code

Description of product type code

Type code
Pleated package of folds Example: M13F H 1200 / M G 1
E11 - H13

Rated volume flow rate


Product description

Installation depth

Seal position
Seal design
Frame type
M 11 F Filter class E11
M 13 F Filter class H13

C Installation depth46 mm
D Installation depth54 mm
A Installation depth69 mm
S Installation depth78 mm
H Installation depth150 mm
T Installation depth292 mm

Rated volume flow rate – refer to tables „form of delivery/order numbers“ on the next pages

A Aluminium
N Stainless steel
M MDF

G Polyurethane
F Flat profile
U Test groove seal

1 Dust air side – standard


2 Pure-air side

Type code
Aaluminium separators Example: M13A T 1200 / S G 1 EX
E11 - H13
Rated volume

Seal position
Seal design
description

Frame type
Installation

flow rate

Optional
Product

design
depth

M 11 A Filter class E11


M 13 A Filter class H13

H Installation depth150 mm
T Installation depth292 mm

Rated volume flow rate – refer to tables „form of delivery/order numbers“ on the next pages

S Plywood
N Stainless steel

G Polyurethane
F Flat profile
U Test groove seal

1 dust air side – standard


2 pure-air side

N neutral
EX EX model

PR-2009-0099-GB • Subject to modifications • Status 07/2011 41


EPA/HEPA Filters GEA Air Filters
Description of Product Type Code

Type code
Pleated package of folds Example: A14F A 600 / A G 1 BR 2
H14 - H15

Grille position
Rated volume

Seal position
Seal design
description

Frame type
Installation

protection
flow rate
Product

Type of
depth

grille
A 14 F Filter class H14
U 15 F Filter class U15

A Installation depth69 mm
S Installation depth78 mm
E Installation depth90 mm
B Installation depth117 mm

Rated volume flow rate – refer to tables „form of delivery/order numbers“ on the next pages

Frame
A Aluminium

G Polyurethane
F Flat profile
U Test groove seal

1 dust air side – standard


2 pure-air side

Protection grille
BR painted steel
BA Aluminium

1 dust air side – standard


2 pure-air side
Type code
V-shape package of folds Example: M13V T 35 0 0 / S G 1 EX
H13 - H14
optional design
Rated volume

Seal position
Seal design
description

Frame type
Installation

flow rate
Product

depth

Filter class E11


M 11 F
Filter class H13 Filter class
M 13 F M 13 VA 14 V
H13 Filter class H14

T Installation depth292 mm

Rated volume flow rate – refer to tables „form of delivery/order numbers“ on the next pages

S Plywood
N Stainless steel

G Polyurethane
F Flat profile
U Test groove seal

1 dust air side – standard


2 pure-air side

N neutral
EX EX model

42 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters EPA/HEPA Filters
E11 Panel Filter

GEA Delbag E11 HEPA filters consists of fold packages that are cast in a frame with
polyurethane to ensure air tightness
Application example:
designed as final filters with great capacity in filtration of all aerosol types in a multiple
filter chain to be used in climate control and air handling units; for cleaning supply and
extract air in industrial processes; for filtration of health endangering dust, viruses and
bacteria
Special features:
great mechanical stability through established fold design; high volume flows with
small installation depth, metal-free separation of folds
Areas of application:
health-care industry, chemical, pharmaceutical production, food product industry,
electronics, production of semiconductors, nuclear technology

Pressure drop diagram:


150

125
Pressure drop [Pa]

100

75

50

25

0
0 20 40 60 80 100
Volume flow [%]

Form of delivery:
GEA Delbag E11 HEPA filters

Design with a MDF frame and PU semicircular seal – others seals and handle guard on request

Type M11FS Type M11FH Type M11FT


installation depth 78 mm installation depth 150 mm installation depth 292 mm
Size W/H Volume flow Filter sur- Approx. Volume flow Filter sur- Weight [kg] Size W/H Volume flow Filter sur- Approx.
[mm] [m³/h] face [m²] weight [kg] [m³/h] face [m²] [kg] [mm] [m³/h] face [m²] weight [kg]

260 2.2 2.0 260 2.2 3.6 420 3.6 7.5


305/305 305/305
300 2.9 2.1 300 2.8 3.8 520 4.7 8.0

550 4.7 3.3 550 4.7 5.4 930 7.8 11.5


305/610 305/610
640 6.2 3.4 710 6.0 5.9 1.160 10.0 12.5

640 5.4 3.5 640 5.4 5.7 1.450 12.5 15.0


457/457 457/610
740 7.1 3.6 820 6.8 6.2 1.820 15.9 16.0

1.060 8.7 4.8 1.060 8.7 7.6 2.000 16.5 18.0


575/575 610/610
1.230 11.6 4.9 1.350 11.0 8.4 2.510 21.5 20.0

1.200 10.0 5.2 1.200 10.0 8.2


610/610
1.400 13.2 5.3 1.530 12.5 9.1

1.060 8.7 4.8 1.060 8.7 7.6 2.000 16.5 18.0


762/610 610/610
1.230 11.6 4.9 1.350 11.0 8.4 2.510 21.5 20.0

1.850 15.0 7.1 1.850 15.0 11.0


915/610
2.150 20.2 7.2 2.350 19.2 12.5

2.250 20.5 9.1 2.500 20.5 13.5


1220/610
2.900 27.2 9.2 3.180 26.0 15.5

PR-2009-0099-GB • Subject to modifications • Status 07/2011 43


EPA/HEPA Filters GEA Air Filters
E11 V-Shape

GEA Delbag E11 HEPA filters in V-shape are cast so as to be airtight in a U-shaped
profile, they have a V-shaped arrangement.
Application example:
designed as final filters with great capacity in filtration of all aerosol types in a multiple
filter chain to be used in climate control and air handling units; for cleaning supply and
extract air in industrial processes; for filtration of health endangering dust, viruses and
bacteria
Special features:
great mechanical stability through established fold design; high volume flows with
small installation depth, metal-free separation of folds
Areas of application:
health-care industry, chemical, pharmaceutical production, food product industry,
electronics, production of semiconductors, nuclear technology

Pressure drop diagram:


200
Pressure drop [Pa]

150

100

50

0
0 20 40 60 80 100
Volume flow [%]

Form of delivery:
GEA Delbag E11 HEPA filter in V-shape
Design with a galvanized frame and PU semicircular seal – other seals on request

Type M11VT
Size W/H [mm] Volume flow [m³/h] Filter surface [m²] Approx. weight [kg]

730 7.5 5.0


305/305
830 9.0 5.5

1.600 18.0 8.0


305/610
1.800 22.0 8.5

3.500 36.0 15.0


610/610
4.000 40.0 15.5

NOTE!
A handle guard is not possible for E11 HEPA filters in V-shape!

44 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters EPA/HEPA Filters
H13 with Aluminium Separators

GEA Delbag H13 HEPA filters with aluminium separators – here wave-shaped alu-
minium separators are used for stabilisation instead of synthetic threads; the packages
of folds are cast in a wooden frame with polyurethane so as to be airtight
Application example:
designed as final filters with great capacity in filtration of all aerosol types in a multiple
filter chain to be used in climate control and air handling units; for cleaning supply and
extract air in industrial processes; for filtration of health endangering dust, viruses and
bacteria
Areas of application:
health-care industry, chemical, pharmaceutical production, food product industry,
electronics, production of semiconductors, nuclear technology

This filter is also optionally available for high temperature applications up to 250°C

Pressure drop diagram:


250

200
Pressure drop [Pa]

150

100

50

0
0 20 40 60 80 100
Volume flow [%]

Form of delivery:
GEA Delbag H13 HEPA filters with aluminium separators

Model with a standard seal – other seals and handle guard on request

Type M13AH installation depth 150 mm Type M13AT installation depth 292 mm
Size W/H/D + seal Volume flow Filter surface Weight Size W/H/D + seal Volume flow Filter surface Weight
[mm] [m³/h] [m²] [kg] [mm] [m³/h] [m²] [kg]

415 3.9 6.0


305/305/150 + 8 320 2.0 3.7 305/305/292 + 8
525 5.5 6.5

930 8.0 9.5


305/610/150 + 8 530 4.0 4.3 305/610/292 + 8
1.160 12.0 10.0

610/610/150 + 8 1.530 13.5 10.0 595/595/292 + 8 1.900 15.9 14.5

2.000 16.9 15.0


762/610/150 + 8 1.930 17.0 12.5 610/610/292 + 8
2.510 24.9 16.0

762/610/292 + 8 2.540 21.4 19.3

PR-2009-0099-GB • Subject to modifications • Status 07/2011 45


EPA/HEPA Filters GEA Air Filters
H13 Panel Filter

GEA Delbag H13 HEPA filters consist of fold packages that are cast in a frame with
polyurethane to ensure air tightness
Application example:
designed as final filters with great capacity in filtration of all aerosol types in a multiple
filter chain to be used in climate control and air handling units; for cleaning supply and
extract air in industrial processes; for filtration of health endangering dust, viruses and
bacteria
Special features:
great mechanical stability through established fold design; high volume flows with
small installation depth, metal-free separation of folds
Areas of application:
health-care industry, chemical, pharmaceutical production, food product industry, elec-
tronics, production of semiconductors, nuclear technology

Pressure drop diagram:


250

200
Pressure drop [Pa]

150

100

50

0
0 20 40 60 80 100
Volume flow [%]

Form of delivery:
GEA Delbag H13 HEPA filters

Design with a MDF frame and PU semicircular seal – others seals and handle guard on request

Type M13FS Type M13FH Type M13FT


installation depth 78 mm installation depth 150 mm installation depth 292 mm
Size W/H Volume flow Filter sur- Weight Volume flow Filter sur- Weight Size W/H Volume flow Filter sur- Weight
[mm] [m³/h] face [m²] [kg] [m³/h] face [m²] [kg] [mm] [m³/h] face [m²] [kg]

260 2.2 2.0 260 2.2 3.6 420 3.6 7.5


305/305 305/305
300 2.9 2.1 300 2.8 3.8 520 4.7 8.0

550 4.7 3.3 550 4.7 5.4 930 7.8 11.5


305/610 305/610
640 6.2 3.4 710 6.0 5.9 1.160 10.0 12.5

640 5.4 3.5 640 5.4 5.7 1.450 12.5 15.0


457/457 457/610
740 7.1 3.6 820 6.8 6.2 1.820 15.9 16.0

1.060 8.7 4.8 1.060 8.7 7.6 2.000 16.5 18.0


575/575 610/610
1.230 11.6 4.9 1.350 11.0 8.4 2.510 21.5 20.0

1.200 10.0 5.2 1.200 10.0 8.2


610/610 610/610 3.000 29.5 23.5
1.400 13.2 5.3 1.530 12.5 9.1

1.850 15.0 7.1 1.850 15.0 11.0


915/610
2.150 20.2 7.2 2.350 19.2 12.5

2.250 20.5 9.1 2.500 20.5 13.5


1220/610
2.900 27.2 9.2 3.180 26.0 15.5

46 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters EPA/HEPA Filters
H13 Panel Filter

GEA Delbag H13 HEPA filters in V-shape are cast so as to be airtight in a U-shaped
profile, they have a V-shaped arrangement.
Application example:
designed as final filters with great capacity in filtration of all aerosol types in a multiple
filter chain to be used in climate control and air handling units; for cleaning supply and
extract air in industrial processes; for filtration of health endangering dust, viruses and
bacteria
Special features:
great mechanical stability through
established fold design; high volume
flows with small installation depth,
metal-free separation of folds,
an an option available in EX protection
Areas of application:
health-care industry, chemical, pharmaceutical production,
food product industry, electronics, production of semiconductors, nuclear technology

Pressure drop diagram:


250

200
Pressure drop [Pa]

150

100

50

0
0 20 40 60 80 100
Volume flow [%]

Form of delivery:
GEA Delbag H13 HEPA filters in V-shape
Design with a galvanized frame and PU semicircular seal – other seals and handle guard on request

Type M13VT
Volume flow Filter surface Approx. weight
Size W/H [mm]
[m³/h] [m²] [kg]

730 7.5 5.0


305/305
830 9.0 5.5

1.600 18.0 8.0


305/610
1.800 22.0 8.5

3.500 36.0 15.0


610/610
4.000 40.0 15.5

PR-2009-0099-GB • Subject to modifications • Status 07/2011 47


EPA/HEPA Filters GEA Air Filters
H14

GEA Delbag H14 HEPA filters - here packages of folds are cast airtight in aluminium
frames and are provided with handle guard on the pure-air side
Application example:
for systems with very high standards in air purity; in supply air ceilings and walls of fully-
equipped clean rooms with turbulence-free (laminar flow) replacement ventilation, for
work benches and workroom cabins
Special features:
great mechanical stability, metal-free separation of folds, pure-air side laminator on
downstream air flow
Areas of application:
electronics or microelectronics, production of semiconductors, health care, chemical,
pharmaceutical industries, microbiology

Pressure drop diagram:


200
Pressure drop [Pa]

150

100

50

0
0 20 40 60 80 100

Volume flow [%]

Form of delivery:

GEA Delbag H14 HEPA filters

Type A14VT installation depth 292 mm


Type A14FA installation depth 69 mm *
design with a galvanized frame and PU
Model with a standard seal –
semicircular seal –
other seals and handle guard on request
other seals and handle guard on request

Volume flow Filter surface Approx. weight Volume flow Filter surface Approx. weight
Size W/H/ [mm]
[m³/h] [m²] [kg] [m³/h] [m²] [kg]

305/305 150 2.6 1.6 – – –

305/610 300 5.3 2.9 1.200 22.0 8.0

457/457 340 5.9 3.0 – – –

610/610 600 10.6 4.7 3.000 40.0 15.5

610/915 900 15.9 6.7

610/1.220 1.200 21.2 8.7

* Other sizes are available on request

48 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Activated Carbon Filter
Activated Carbon, Loose

Activated carbon, loose

Technical data/
form of delivery/ Weight Density Impregna- Minimum Order
Grain size Insert e.g.
[kg/bag] [g/l] tion contact time number
order numbers:
AKOLIT-A1 25 490 no 0.1–0.2 s 00 01 294
Odours
AKOLIT-A2 25 490 no Hydrocarbons 0.1–0.2 s 00 01 581
Solvents
AKOLIT-A3 25 460 no 0.1–0.2 s 00 01 793

Sulphuric acid, hydro-


chloric acid, sulphur
AKOLIT-C1 25 640 yes 0.2 s 00 03 572
dioxide, hydrogen
fluoride

AKOLIT-CG1 25 560 yes 0.25 s 20 02 410


Radioactive gas types
AKOLIT-CG1.5 8.0 520 yes 0.25 s 20 01 606

Grain size 1 = Rods with diameter 1 mm


2 = Rods with diameter 2 mm
3 = Rods with diameter 3 mm

Plate element AK-20 consists of MDF-frame with a V-shaped arranged and


airtight cast activated carbon plate
Application example:
if saturated - activated carbon filter must be replaced
Areas of application:
EBE duct filter

Technical data:
Plate element AK-20 AK-20
[mm]
dimensions W/H/D + seal 305/610/292 + 8 610/610/292 + 8
Flow rate [m³/h] 625 1.250
Pressure drop [Pa] 50 50
Contact time [s] 0.15 0.15
Layer thickness [mm] 20 20
Activated carbon volume [l] 25 50
Weight [kg] approx. 22 approx. 37

Form of delivery/
order numbers: AK-20 Size Order number
305/610/292 + 8 20 01 202
Akolit-A1 packaging unit 1
610/610/292 + 8 60 22 581

PR-2009-0099-GB • Subject to modifications • Status 07/2011 49


Activated Carbon Filter GEA Air Filters
Activated Carbon Cartridge 705/706/707

Activated-carbon cartridges 705/706/707 consist of perforated, concentric synthetic


cylinders; the interstices of the cartridge are filled with activated carbon; expansion
adjustment ring in each cartridge ensures that the cartridges can be used in any
arrangement and that no air leakages occur allowing in such a way dust air to escape;
carbon content can be replaced; mounting is performed as plug or screw connection
Application example: adsorption of toxic gas pollutants
Special features: different activated carbon types; regeneration is possible
Areas of application: odours, hydrocarbons, solvents

Pressure drop diagram:


1600
Pressure drop [Pa]

1200
707

800

400
705/706

0
0 25 50 75 100 125

Volume flow [m³/h]

Technical data:
Activated carbon
705 706 707
cartridges
Activated carbon type AKOLIT-A AKOLIT-A AKOLIT-A
Diameter/height [mm] 119/291 119/291 119/291
Max. operating
[°C] 40 40 40
temperature
Max. rel. air humidity [%] 70 70 70
Activated carbon volume [i] 1.7 1.7 2.0
Layer thickness [mm] 22 22 31
Flange diameter [mm] 67.1 67.1 38.0
Connection type Screw connection Plug connection Screw connection

Form of delivery/
order numbers: Activated Activated carbon Packaging unit Empty weight
Order number
carbon cartridge type [pieces] [kg]
705 Akolit-A2 25 0.2 60 50 331
706 Akolit-A2 25 0.2 60 50 431
707 Akolit-A2 25 0.2 00 37 109

Intake capacity and degree of filtration of activated carbon filters depend on gas composition and
concentration as well as contact period of gas molecules with activated carbon.
Maximum allowed air humidity 70 %, max. temperature 40 °C, minimum contact period depend-
ing on application 0,05 s to 1,0 s, pre-filtration is necessary, required filter class F7 (DIN EN 779).
Activated carbon cartridges 706 and 707 are also regenerable. In this case a used activated car-
bon cartridge is opened, cleared, cleaned, recharged with unused activated carbon, closed and
is available in regenerated form. Used activated carbon is then recycled by an authorized and
certified waste management company.

50 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Activated Carbon Filter
Activated Carbon Cartridge 708/709

Activated-carbon cartridges 708/709 consist of perforated steel sheet or stainless


steel; the interstices of the cartridge are filled with activated carbon; expansion adjust-
ment ring in each cartridge ensures that the cartridges can be used in any arrangement
and that no air leakages occur allowing in such a way dust air to escape; carbon con-
tent can be replaced; connection is performed via 3-point bayonet
Application example:
adsorption of toxic gas pollutants
Special features:
different activated carbon types; regeneration is possible
Areas of application:
odours, hydrocarbons, solvents

Pressure drop diagram:


Contact
period [s]
Pressure drop [Pa]

Volume flow [m³/h]


Grain size 3,0 mm
Technical data:
Activated carbon cartridge 708 709
Activated carbon type AKOLIT-A AKOLIT-A
Insert CKG holding frame
Diameter/height [mm] 140/450 140/600
Max. operating temperature [°C] 40 40
Max. rel. air humidity [%] 70 70
Activated carbon volume [i] 4.0 5.3
Layer thickness [mm] 26 26
Connection type 3-point bayonet 3-point bayonet

Form of delivery/ Activated


Packaging unit Empty weight
order numbers: carbon Activated carbon type Order number
[pieces] [kg]
cartridge
AKOLIT-A3 galvanized steel 8 1.6 00 03 499
708
AKOLIT-A3 stainless steel 8 1.6 20 01 418
AKOLIT-A3 galvanized steel 8 2.0 10 37 410
709
AKOLIT-A3 stainless steel 8 2.0 10 37 415

Intake capacity and degree of filtration of activated carbon filters depend on gas composition and
concentration as well as contact period of gas molecules with activated carbon.
Maximum allowed air humidity 70 %, max. temperature 40 °C, minimum contact period depend-
ing on application 0,05 s to 1,0 s, pre-filtration is necessary, required filter class F7 (DIN EN 779).
Activated carbon cartridges 708 and 709 are also regenerable. In this case a used activated car-
bon cartridge is opened, cleared, cleaned, recharged with unused activated carbon, closed and
is available in regenerated form. Used activated carbon is then recycled by an authorized and
certified waste management company.

PR-2009-0099-GB • Subject to modifications • Status 07/2011 51


Activated Carbon Filter GEA Air Filters
CKG holding frame

CKG holding frame – individual, exchangeable activated carbon bayonet-fitted type


708/709 cartridges are used in frames made of galvanised or stainless steel
Special features:
the cartridges can be individually replaced and have a 3-point
bayonet-type connection
Areas of application:
frames are used in duct air filters EBE with 472 + 620 mm
installation depth (on request), or as wall frames

NOTE!
Large cartridges are only available for CKG-2 and CKG-3 frames!

Technical data/ * only for 708


order numbers: CKG holding frame CKG-2-N-708-03 CKG-3-N-708-03 CKG-6-N-708-03

Casing size [mm] 304/304/70 304/609/70 609/609/70 *

Number of cartridges [quantity] 4 8 16


Activated carbon volume [l] 16.9 32.0 64.0

Packaging unit [quantity] 1 1 1

Order number

Galvanized steel frame 10 39 837 10 39 323 10 39 321

Stainless steel frame 10 39 321 10 32 720 10 32 719

52 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Round Air Filters
Overview

These round filters are used to purify the intake air for internal-combustion engines and
for fans. Various structural designs, sizes, and filter media are available, depending on
the purpose of use. Weather-protection hoods are available for outdoor applications.

Explanation of specifications for all round air filters


Description Filter medium Wetting
DAH High performance (HL) wetted
DAC FIBROIDELASTIC-30 unwetted
DBH High performance (HL) wetted
DBA FIBROIDELASTOV-20 / ACELAN unwetted
DBC FIBROIDELASTIC-30 unwetted
DBV FIBROIDELASTOV-40 unwetted

Pressure drops for types DAH, DBC, DBH, DBV, DAC

DBA type
Pressure drop [Pa]

Pressure drop [Pa]

Volume flow [m³/h] Volume flow [m³/h]

DAH type
1 0 85 170 250 340 420
Size

2 0 145 290 440 580 730

3 0 260 520 780 1040 1300

DBC, DBH, DBV types


1 0 200 400 600 800 1000

2 0 400 800 1200 1600 2000


Size

3 0 700 1400 2100 2800 3500

4 0 1000 2000 3000 4000 5000

5 0 1400 2800 4200 5600 7000

DAC type
1 0 45 90 130 180 220
Size

2 0 100 200 300 400 500

3 0 200 400 600 800 1000

PR-2009-0099-GB • Subject to modifications • Status 07/2011 53


Round Air Filters GEA Air Filters
DAH

DAH round air filters and weather-protection hoods are manufactured of painted steel
(RAL 5001); metal filter cartridges (HL high performance model) are used as a filter
medium; round air filters DA for clamping are supplied with a slotted fitting with clamps
Application example:
for cleaning intake air of internal-combustion motors, fans and compressors
Special feature:
slotted fitting with a clamp
Areas of application:
industrial facilities requiring process air treatment, heavy industry, cement industry,
sewage treatment plants, water treatments plants

Pressure drop diagram:


Volume flow [m³/h]

Weather protection
hood (optional)

Pressure drop [Pa]

Round air filter DAH

Technical data,
form of delivery, DAH1-70 DAH1-100 DAH1-120
order numbers: Round air filter DAH
Filter class [EN 779] G2 G2 G2

Diameter/height [mm] 130/140 180/155 180/230

Rated air volume flow [m³/h] 250 440 780

Initial pressure drop [Pa] 100 100 100

Flange diameter [mm] 70 100 120


Weight [kg] 0.9 1.6 2.3

Multi-stage model no no no

Wetting yes yes yes

Packaging unit [quantity] 1

Order number 20 00 333 20 00 339 20 00 340

DAH weather protection hood


Diameter/height [mm] 180/145 225/160 225/235

Weight [kg] 0.6 1.0 1.3

Packaging unit [quantity] 1

Order number 20 00 631 20 00 204 20 00 632

Wetting agent VISCINOL A 30 – 15 to + 45 °C 20 liter container


Net weight [kg/l] 0.9

Order number 20 00 365

54 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Round Air Filters
DBH/DBA/DBV

DBH/DBA/DBV round air filter – the cartridge can be exchanged, and can be used
again after being cleaned and wetted; the filter medium can be exchanged and can be
used again after cleaning (except for F5).

Technical data:
Round air filter, multi-stage design,
Size 1 Size 2 Size 3 Size 4 Size 5
with and without wetting
Diameter/height [mm] 240/255 360/305 360/505 500/505 500/705
DBH HL wetted Filter class (DIN EN 779) G2
Cartridge height h [mm] 150 200 200 200 200
Number of cartridges [qty] 1 1 2 2 3
Filter weight [kg] 8.5 15.5 24.5 40.5 51.0
Weight per cartridge set [kg] 3.0 4.0 8.0 11.0 17.0
DBV FIBROIDELASTOV-40 Filter class (DIN EN 779) G4
Filter layer size [mm] 150/670 200/1,050 200/1,050 200/1,500 300/1,500
Number of cartridges/filter layer [qty] 1 1 2 2 2
Filter weight [kg] 8.0 12.0 19.0 26.0 36.0
Weight [kg] 0.7 1.2 1.2 2.4 2.4
DBA 2-stage FIBROIDELASTOV-20/ACELAN Filter class (DIN EN 779) F5
Filter layer size [mm] 150/670 200/1,050 200/1,050 200/1,500 300/1,500
Number of cartridges/filter layer [qty] 1 1 2 2 2
Filter weight [kg] 8.7 13.2 20.2 28.4 38.4
Weight per package [kg] 1.4 2.4 2.4 4.8 4.8
Nominal width:

Flange for DB Nominal width NW


Number of
DIN 2641 for PN 6 125 200 250 350 400
Diameter D [mm] 240 320 375 490 540
Bolt circuit diameter k [mm] 200 280 335 445 495
Number of bolt holes n 8 8 12 12 16
Hole diameter d [mm] 18 18 18 23 23
Reduced thickness b [mm] 8 8 8 12 12
DIN 2642 for PN 10 100 150 200 250 300
Loose flange
Diameter D [mm] 220 285 340 395 445
Bolt circuit diameter k [mm] 180 240 295 350 400
Number of bolt holes n 8 8 8 12 12
Hole diameter d [mm] 18 23 23 23 23
Reduced thickness b [mm] 8 8 8 8 12

PR-2009-0099-GB • Subject to modifications • Status 07/2011 55


Round Air Filters GEA Air Filters
DBH/DBA/DBV

Product type code:


Order sample: DBH 1 - 100 / 2642

Flange DIN
Flange NW
Type

Size
DBH Round air filter DBH (G2) High performance HL
DBA Round air filter DBA (F5) FIBROIDELASTOV-20/ACELAN
DBV Round air filter DBV (G4) FIBROIDELASTOV-40

Diameter/height
1 240/255
2 360/305
3 360/505
4 500/505
5 500/705

Flange nominal width according to table


„Nominal width“ on page 55

DIN 2641 for PN 6


PIN 2642 for PN 10

Form of delivery/
order numbers: Round air filter DBH (G2) High per- DBA (F5) DBV (G4)
colour RAL 5001 formance HL FIBROIDELASTOV-20/ACELAN FIBROIDELASTOV-40

1-100/2642 20 02 007 20 15 021 20 01 469

1-125/2641 20 01 145 20 00 627 20 15 024

2-150/2642 20 00 723 20 00 580 20 02 912

2-200/2641 20 00 581 20 00 628 20 01 531

3-200/2642 20 15 028 20 15 022 20 01 144

3-250/2641 20 15 029 20 00 958 20 15 025


4-250/2642 20 15 030 20 01 072 20 03 548

4-350/2641 20 01 541 20 00 629 20 15 026

5-300/2642 20 04 659 20 15 023 20 00 671

5-400/2641 20 15 031 20 02 261 20 01 880

Packaging unit 1 1 1

Order numbers,
accessories DBH: Spare cartridges Size 1 Size 2 Size 3 Size 4 Size 5

DBH high performance HL filter class (DIN EN 779) G2


Quantity/size 1 1 2 2 3
Diameter/height [mm] 240/150 360/200 360/200 500/200 500/200

Weight per unit [kg] 3.0 4.0 4.0 5.5 5.5

Order number 20 00 501 20 00 500 20 00 502

Wetting agent VISCINOL A 30; – 15 to + 45 °C 20 liter container


Net weight [kg/l] 0.9

Order number 20 00 365

56 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Round Air Filters
DBH/DBA/DBV

Order numbers,
accessories DBA: Spare Size 1 Size 2 Size 3 Size 4 Size 5

DBA FIBROIDELASTOV-20/ACELAN Filter class (DIN EN 779) F5


Width/length [mm] 150/670 200/1.050 200/1.050 200/1.050 300/1.050

Weight per unit [kg] 0.7 1.2 1.2 2.4 2.4

Packaging unit [qty] 10

Quantity/size 1 1 2 2 2

DB, FIBROIDELASTOV-20
20 00 208 20 00 205 20 00 206 20 00 207
order number

DB, ACELAN order


20 00 213 20 00 214 20 00 215 20 00 216
number

Order numbers,
accessories DBV: Spare Size 1 Size 2 Size 3 Size 4 Size 5

DBA FIBROIDELASTOV-40 Filter class (DIN EN 779) G4


Width/length [mm] 150/670 200/1.050 200/1.050 200/1.050 300/1.050

Weight per unit [kg] 0.7 1.2 1.2 2.4 2.4

Packaging unit [qty] 10 1

Quantity/size 1 1 2 2 2

Order number 20 00 209 20 00 210 20 00 211 20 00 212

Order numbers,
weather protection hood Weather protection hood DBH/
Size 1 Size 2 Size 3 Size 4 Size 5
DBH/DBA/DBV: DBA/DBL, colour RAL 5001
Quantity/size 1 1 2 2 3

Diameter/height [mm] 310/295 430/350 430/550 575/560 575/760


Weight per unit [kg] 3.0 4.0 7.0 9.0 14.0

Packaging unit [qty] 1

Order number 20 00 635 20 00 636 20 00 636 20 00 638 20 00 639

PR-2009-0099-GB • Subject to modifications • Status 07/2011 57


Round Air Filters GEA Air Filters
DAC/DBC

DAC/DBC round air filters are made of immersion painted steel (RAL 5001); ring
packs (FIBROIDELASTIC-30) are used as a filter medium; round air filters DA for
clamping are supplied with a slotted fitting with clamps
Application example:
for cleaning intake air of internal-combustion motors, fans and compressors
Special feature:
slotted fitting with a clamp
Areas of application:
industrial facilities requiring process air treatment, heavy industry, cement industry,
sewage treatment plants, water treatments plants
Pressure drop diagram:
Structure of round air filter
DAC
Fastening nuts
Volume flow [m³/h]

Disk

Weather protec-
tion hood
(optional)

Cover

Pressure drop [Pa]


Filter ring
FIBROIDELASTIC

Cartridge core

Connection
fitting

Technical data/
form of delivery/ DAC1-52 DAC2-80 DAC3-110
order numbers DAC: Round air filter DAC, single stage model, without wetting
Filter class [EN 779] G2 G2 G2
Diameter/height [mm] 180/120 180/180 180/250
Rated air volume flow [m³/h] 130 300 600
Initial pressure drop [Pa] 100 100 100
Flange diameter d [mm] 52 80 110
Ring pack height h [mm] 60 120 190
Filter weight [kg] 1.8 2.0 2.3
Packaging unit [quantity] 1
Order number 20 00 494 20 00 491 20 00 634

Weather protection hood DAC


Diameter/height [mm] 225/125 225/185 225/255
Weight [kg] 0.7 1.0 1.5
Packaging unit [quantity] 1
Order number 20 00 633 20 00 204 20 00 632

Filter ring FIBROIDELASTIC-30


Diameter/height [mm] 180/60 180/120 180/190
Weight [kg/l] 0.15 0.3 0.4
Packaging unit [quantity] 240 120 60
Order number 20 00 103 20 00 104 20 00 105

58 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Round Air Filters
DAC/DBC

Technical data DBC: DBC, FIBROIDELASTIC-30 Filter class (DIN EN 779) G2

Ring pack height [mm] 150 200 400 400 600

Filter weight [kg] 6.0 8.0 12.0 17.0 21.0

Weight per package [kg] 0.4 0.8 1.6 2.2 3.3

Flange for DB Nominal width NW


Nominal width:
DIN 2641 for PN 6 125 200 250 350 400
Number of holes n
Diameter D [mm] 240 320 375 490 540

Bolt circuit diameter k [mm] 200 280 335 445 495

Number of bolt holes n 8 8 12 12 16

Hole diameter d [mm] 18 18 18 23 23

Reduced thickness b [mm] 8 8 8 12 12

DIN 2642 for PN 10 100 150 200 250 300

Loose flange Diameter D [mm] 220 285 340 395 445

Bolt circuit diameter k [mm] 180 240 295 350 400

Number of bolt holes n 8 8 8 12 12

Hole diameter d [mm] 18 23 23 23 23

Reduced thickness b [mm] 8 8 8 8 12

Product type code DBC:


Order sample: DBC 1 - 100 / 2642

Flange DIN
Flange NW
Type

Size
DBC Round air filter DBC (G2) FIBROIDELASTIC-30

Diameter/height
1 240/255
2 360/305
3 360/505
4 500/505
5 500/705

Flange nominal width according to table


„Nominal width“ see above

DIN 2641 for PN 6


DIN 2642 for PN 10

PR-2009-0099-GB • Subject to modifications • Status 07/2011 59


Round Air Filters GEA Air Filters
DAC/DBC

Form of delivery/ Round air filter colour RAL 5001 DBC (G2) FIBROIDELASTIC-30
order numbers DBC:
DBC 1-100/2642 20 15 021

DBC 1-125/2641 20 00 627

DBC 2-150/2642 20 00 580

DBC 2-200/2641 20 00 628

DBC 3-200/2642 20 15 022

DBC 3-250/2641 20 00 958

DBC 4-250/2642 20 01 072

DBC 4-350/2641 20 00 629

DBC 5-300/2642 20 15 023

DBC 5-4 20 02 261

Packaging unit 1

Order numbers,
accessories DBC: Spare filter ring DBC Size 1 Size 2 Size 3 Size 4 Size 5

DB, FIBROIDELASTIC-30 Filter class (DIN EN 779) G2


Quantity/size 1 1 1 1 1

Diameter/height [mm] 240/150 360/200 360/400 500/400 500/600

Weight per unit [kg] 0.4 0.8 1.6 2.2 3.3


Packaging unit [qty] 45 20 20 15 8

Order number 20 00 106 20 00 107 20 00 108 20 00 109 20 00 110

60 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Glove-Box Filters
DKA/DKB

DKA/DKB glove-box filters are high-efficiency submicron particulate air filters


(HEPA) in encapsulated form (model types DKA and DKB); the filters can be installed
on the air-intake or the air-outlet sides, maximum pressure load for the cartridge casing
makes up 5.000 Pa
Application example:
filtration of dust and gas pollutants from industrial process and atmospheric air
Special features:
filtration meeting highest standards (HEPA); filters can be installed on the air-intake or
the air-outlet sides; encapsulated form
Areas of application:
disinfecting and sterilisation equipment, insulating boxes, glove boxes, laboratory and
photo laboratory equipment, ventilation of drink water containers, fermentation and
yeast processing plants

Glove box filter DKA DKB

M 62x2,5 M 62x2,5
Ø 53 Ø 53

22

22
172

194
150 22
Ø 140
Ø 140

Technical data/
form of delivery/
order numbers: Glove-Box Filters DKA DKB
Filter class (HEPA) [EN 1822] H13 H13

Diameter/height [mm] 140/172 140/194

Rated air volume flow [m³/h] 25 25

Initial pressure drop [Pa] 115 140

Maximum allowed pressure


[Pa] 1000 1000
drop

Filtration efficiency [%] > 99.95 > 99.95

Max. operating temperature [°C] 60 60

Max. rel. air humidity [%] 100 100

Connection fitting [quantity] 1 2

Connection M62x2,5 M62x2,5

Order number 20 00 711 20 00 712

PR-2009-0099-GB • Subject to modifications • Status 07/2011 61


Glove-Box Filters GEA Air Filters
DKC/DKD

DKC/DKD glove-box filters are high-efficiency submicron particulate air filters


(HEPA) in encapsulated form; the filters can be installed on the air-intake or the air-
outlet sides, maximum pressure load for the cartridge casing makes up 5.000 Pa,
these filters can combined with gas sorption filters using activated-carbon cartridges
that can be installed only vertically
Application example:
filtration of dust and gas pollutants from industrial process and atmospheric air
Special features:
filtration that meets highest standards (HEPA); filters can be installed on the air-intake
or the air-outlet sides; encapsulated form, combination with activated-carbon filters
Areas of application:
disinfecting and sterilisation equipment, insulating boxes, glove boxes, laboratory and
photo laboratory equipment, ventilation of drink water containers, fermentation and
yeast processing plants

Glove box filter DKC DKD

Technical data/
form of delivery/
order numbers: Glove-Box Filters DKC DKD

Filter class (HEPA) [EN 1822] H13 and activated carbon H13 and activated carbon

Diameter/height [mm] 140/257 140/279

Rated air volume flow [m³/h] 25 25

Initial pressure drop [Pa] 815 840

Maximum allowed pressure


[Pa] 1700 1700
drop

Filtration efficiency [%] > 99.95 > 99.95

Max. operating temperature [°C] 40 40

Max. rel. air humidity [%] 70 70

Connection fitting [quantity] 1 2

Connection M62x2.5 M62x2.5

Order number AKOLIT-A1 20 02 396 20 01 931


Activated carbon type AKOLIT-CG 20 04 289 20 01 930

62 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Frames for Wall or Ceiling Installation
MULTI 2004 Holding Frame

MULTI 2004 holding frame with air filter element – the filter medium is made of spe-
cial, open-pored synthetic foam which is processed with powdered activated carbon or
activated ball carbon in an abrasion-proof manner
Areas of application:
as CDD wall frames or EBE duct air filters

Pressure drop diagram:


Diagram applies to size 592 mm x 592 mm
Pressure drop [Pa]

Volume flow [m³/h]


Technical data/
form of delivery/
order numbers: MULTI 2004 holding frame; colour RAL 9011 (anthracite)
Nominal size W/H/D [mm] 287/592/301 490/592/301 592/592/301

Number of filter inserts [quantity] 4 6 8

Rated air volume flow [m³/h] 2.125 3.500 4.250

Max volume flow with


activated carbon [m³/h] 1,070 1,750 2,125
elements

Activated carbon volume [l] 15 23 30

Max. operating
[°C] 40 40 40
temperature

Layer thickness/
Order numbers, [mm] 304 304 304
installation depth
accessories:
Weight/each [kg] 4.2 5.1 6.0

Order number 30 00 406 30 00 405 30 00 210

Fixing slide with horizontal model


Order number 30 00 907 30 00 907 –

PR-2009-0099-GB • Subject to modifications • Status 07/2011 63


Filter Frames for Wall or Ceiling Installation GEA Air Filters
CDD Wall Frame

CDD wall frames are made of galvanized or stainless steel; 4 spring clamps hold the
air filters to the frame; the frames can be bolted together to form a filter wall

Technical data/
order numbers: Filter frame for wall or ceiling installation CDD/CDD-VA
Unit size [mm] 304/304 304/609 507/609 609/609

Filter class (depending on


G2 to F9
complement items installed)

Filter size [mm] 287/287 287/592 490/592 592/592

Installation depth [mm] 72 72 72 72


Weight/each [kg] 1.5 1.6 2.1 2.2

CDD order number


Range of terminals 20-25 [mm] 10 08 381 62 06 744 62 07 144 62 07 544

Range of terminals 45-50 [mm] 21 00 004 21 00 010 10 48 535 10 44 360


CDD-VA order number
Range of terminals 20-25 [mm] 10 14 432 62 06 844 62 07 244 62 07 644

Range of terminals 45-50 [mm] 21 00 001 21 00 007 21 00 013 20 47 925

64 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Frames for Wall or Ceiling Installation
CGF Ceiling Air Outlets

CGF ceiling air outlets are made of powder-coated sheet steel (colour RAL 9010) and
are equipped with the following:
– shut-off flap is installed in the intake-air fitting at the side, closes airtight
(as per DIN 1946, Part 4)
– the flap is operated manually or electrically (actuator 230 V or 24V selectable)
– check device for filter airtight fit of recommended HEPA filter element
with a U-shaped profile seal
– integrated pressure-gauge connection for monitoring pressure drop
– fitting for oil-mist passage
– sealing of filters using four non-slip clamping elements
– connection of different air distributing outlets by using central or 4-point locks
Application example: CGF ceiling air outlets with integrated HEPA filters operate as
last filter stage in efficient filtration of particle-shaped air pollutants of all types, includ-
ing microorganisms
Special feature: compact shape; high-quality and high-value model; high operating
safety; using different air distributors is possible; can be integrated in DDC-controlled
building management system (in model with an actuator)
Areas of application: AHU systems in hospitals according to DIN 1946 Part 4 for Indoor
Class I, operating rooms Type B and auxiliary room in operating area, intensive care
units and emergency room, clean rooms, pharmaceutical industry, genetic technology,
microbiology, food product industry, production of semiconductors

Hose or pipe
connection
C L1
Ø20
Connection for
20 checking
airtight fit DN
H
h
155

B T 50
K K
L2
Connection for
pressure drop Air diffuser Manual actuator for
measurement shut off flap

Technical data/
Ceiling Air Outlet CGF 318-1 / 1 CGF 470-1 / 1 CGF 587-1 / 1 CGF 623-1 / 1
order numbers:
Filter size W/H/D + seal [mm] 305/305/78+ 7 457/457/78+ 7 575/575/78+ 7 610/610/78+ 7
For filter class E10 to H14
Weight [kg] 6.4 10.7 15.5 16.4
Installation depth [mm] 345 380 435 435
Packaging unit [unit] 1 1 1 1
Order number
with shut off flap 10 13 596 10 13 691 10 31 377 10 13 692
without shut off flap 10 17 639 10 18 526 10 31 378 10 13 694

Air diffuser with central mounting W/H 350/350 500/500 623/623 650/650
Order numbers,
Twist outlet 358 steel RAL 9010 00 05 414 10 09 824 10 13 618 10 09 825
accessories:
Ventilation grille aluminium, discharge on 4 sides 10 13 597 10 09 822 10 13 619 10 09 823
Ventilation grille steel RAL 9010,
10 13 611 10 13 609 10 13 620 10 13 610
discharge on 4 sides
Packaging unit 1 1 1 1

PR-2009-0099-GB • Subject to modifications • Status 07/2011 65


Filter Frames for Wall or Ceiling Installation GEA Air Filters
CKC Wall Frame

CKC wall frame is especially developed for holding HEPA filters; five different filter
sizes are available; filter media of different installation depth can be used
(78, 150, 292 mm); profile frame is gastight welded and is either made of galvanised
steel or stainless steel 1.4301 (material can be selected); four supporting brackets with
a centring function enable fast and safe sealing of a HEPA filter on the sealing surface;
all frames are equipped with a monitoring device for checking seat tightness of HEPA
filter
Application example:
climate control and air handling units with highest standards in air purity
Special features:
easy assembly of a complete wall frame system; different frame sizes in Euro grid size;
combination of complete-size and half-size units is possible; easy mounting and disas-
sembly of HEPA filter elements; high operating safety
Areas of application:
pharmaceutical industry and health care, chemical and clean room technology

Technical data:
CKC Wall Frame Size 2 Size 3 Size 6

Thickness/depth/length [mm] 355 355 355

Width/height [mm] 303/303 303/608 608/608

Accessories: Steel angle mounting frame, assembly set

66 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Filter Frames for Wall or Ceiling Installation
ELA Filter Casing

ELA filter casing type has a stable and light construction made of steel sheet and sup-
plied as galvanized model; individual modules are assembled through clinch connec-
tions to casing sizes of 385 x 690 mm to 1.910 x 690 mm; undrilled run-around flange
(40 mm) enables flexible adjustment to upstream and/or downstream duct compo-
nents; filters are fixed in an integrated CDD frame; the casing is designed for intake
and pressure-side operation (max. 1.000 Pa); an easily removable service door on side
enables filter replacement in airflow direction from left or right (can be selected); doors
are fixed by four star bolts; the modular design enables casing combinations up to
three vertical levels
Application example:
for all types of climate control and air handling units that are designed for installation
of pleated filters of series MULTISACK and filter elements of series MULTIFORM; filter
media of classes G3 - F9
Special features:
modular construction; stable light design with galvanised sheet steel; filter replacement
in air flow direction can be selected on left or right side (from size 2/2 filter change on
both sides is necessary); run-around, undrilled flange frame; casing is designed for
intake and pressure-side operation (max. 1.000 Pa)
Areas of application:
standard HVAC applications with a filtration function in all air handling units

Star formed screws

Untreated
air Clean air

Technical data:
ELA Filter Casing ELA 05/10 ELA 10/10

Width/height [mm] 385/690 690/690

Thickness/depth/length [mm] 700 700

Filter size [mm] 287/592 592/592

Accessories: Pressure drop measuring devices

PR-2009-0099-GB • Subject to modifications • Status 07/2011 67


Filter Frames for Wall or Ceiling Installation GEA Air Filters
EBE Casing

EBE casing type has a stable and light construction made of galvanised steel sheet
or stainless steel (1.4571 or 1.4301); because of modular design - a combination with
different unit sizes and use of different filter media with different filter sizes is possible;
use of filter media of classes G2 - H13 is also possible; several filter stages can be
combined straight through; four threaded rods with clamping nuts are used to secure
HEPA filters, filter elements and activated carbon filters; an additional holding frame is
required for MULTIFORM filter elements and activated carbon cartridges; MULTISACK
bag filters are secured with an integrated CDD frame; easy open and close functions
of airtight service cover with a star grip
Application example:
for all HVAC and air handling applications
Special features:
airtight design thanks to soldered or welded profile connections; suction and pressure-
side operation (max. 2000 Pa); wide-range accessories: pressure drop measuring
devices, connection fittings, contact grille etc.; combination of duct air filters of full-size
and half-size units for different unit sizes; assembly of vertical casing units or securing
of transition fittings is done through prefabricated bolt connection (rivet nuts of size
M8); drilled flange frame (M8) enables easy and quick vertical connection
Areas of application:
cleaning of supply air for protection of corrosion-risk electronic components, control
centres and data processing units, air filtration in industrial processes, air cleaning for
protection of valuable items in libraries and museums; ventilation of drinking water
processing plants and containers, filtration of exhaust air to comply with emission
standards, safety filter in de-dusting facilities, combined filter for filtration of coarse, fine
dust and odour pollutants, e.g. kitchen exhaust, multi-stage adsorption filter
Star formed screws

Untreated
air Clean air

Air flow cross section


Untreated
air Clean air
Connection flange
frame,
35 mm run-around

Technical data:
EBE filter casing EBE 05/10 EBE 10/10

Width/height [mm] 445/750 750/750

Thickness/depth/length [mm] 700 700

Filter size [mm] 305/610 610/610

Accessories: Protection grille weather flap

68 PR-2009-0099-GB • Subject to modifications • Status 07/2011


GEA Air Filters Space for Notes

PR-2009-0099-GB • Subject to modifications • Status 07/2011 69


w w w.gea -air treatment .com

You might also like